707 +== **FX3U Ethernet Protocol** ==
708 +
709 + Mitsubishi FX3U series PLC
710 +
711 +**HMI Settings**
712 +
713 +|Items|Settings|Note
714 +|Protocol|Mitsubishi FX3U|
715 +|Connection|Ethernet|
716 +|Port No.|5009|Must be the same as the PLC setting
717 +|PLC station No.|0|
718 +
719 +**Address List**
720 +
721 +|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
722 +|(% colspan="1" rowspan="7" %)Bit|X|X|X OOO|0~~377|
723 +|Y|Y|Y OOO|0~~377|
724 +|M|M|M DDDD|0~~7679|
725 +|SM|SM|SM DDDD|8000~~8511|
726 +|S|S|S DDDD|0~~4095|
727 +|TS|TS|TS DDD|0~~511|
728 +|CS|CS|CS DDD|0~~255|
729 +|(% colspan="1" rowspan="9" %)Word|CN|CN|CN DDD|0~~199|
730 +|TN|TN|TN DDD|0~~511|
731 +|D|D|D DDDD|0~~7999|
732 +|SD|SD|SD DDDD|8000~~8511|
733 +|R|R|R DDDDD|0~~32767|
734 +
735 +**Ethernet Module Settings**
736 +
737 +FX3U-ENET-L module configuration
738 +Set up the FX3U-ENET-L Ethernet module settings as follows.
739 +Select the module location, which in this document is Module 0.
740 +
741 +
742 +[[image:image-20221116105850-1.png]]
743 +
744 +Select "Operational setting" to enter the following screen.
745 +
746 +The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default.
747 +
748 +
749 +
750 +Select "Open setting" to enter the setting interface, the settings are as follows.
751 +
752 +The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the
753 +
754 +Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module.
755 +
756 +
757 +
758 +Click on "transter setup" - "PC side I/F setting", see the following figure.
759 +
760 +After setting, the first download must use the programming cable, as shown in the figure; after that, can
761 +
762 +use the IP set in the "Ethernet board" to communicate directly with the network cable.
763 +
764 +
765 +
766 +Read and write data from the Ethernet module
767 +
768 +
769 +
770 +Set "Transter setup" to COM communication, and read or write operation as shown below
771 +
772 +
773 +
774 +**PLC Settings (GX Works 2)**
775 +
776 +Create a blank FX5U project
777 +
778 +Find Current Connection in the navigation
779 +
780 +
781 +
782 +Select Connection Channel List
783 +
784 +Select Ethernet board communication
785 +
786 +
787 +
788 +Select Ethernet Module
789 +Set the IP address of the PLC
790 +
791 +
792 +
793 +Read or write PLC data, in this document is read
794 +
795 +
796 +
797 +**V-BOX Communication Setting**
798 +
799 +
800 +
801 +
707 707  == **FX5U Serial Protocol** ==
708 708  
709 709  Mitsubishi FX5U series PLC
... ... @@ -858,11 +858,10 @@
858 858  
859 859  [[image:image-20220825112403-1.png||alt="图片-20220825112403-1.png"]]
860 860  
861 -**5)电缆布线**
956 +**5)Cable Wiring**
862 862  
863 863  [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
864 864  
865 -
866 866  == **L02 Serial Protocol** ==
867 867  
868 868  Mitsubishi L02 series CPU built-in serial port.
image-20221116105850-1.png