... ... @@ -1,1 +1,1 @@
1 -XWiki.Bob
1 +XWiki.Ben
Content
... ... @@ -182,7 +182,7 @@
182 182  
183 183  MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
184 184  
185 -**1)V-BOX setting**
185 +**1)PLC Settings**
186 186  
187 187  |**Item**|**Settings**|**Note**
188 188  |Protocol|Allen-Bradlley DF1 Advanced|
... ... @@ -420,7 +420,7 @@
420 420  The above are all the steps for establishing Ethernet communication between Wecon V-box with CompactLogix L1769 PLC.
421 421  
422 422  
423 -= **Allen-Bradley Ethernet DF1** =
423 +== **Allen-Bradley Ethernet DF1** ==
424 424  
425 425  [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Allen-Bradley%20Ethernet%20DF1.zip]]
426 426  
... ... @@ -436,7 +436,7 @@
436 436  
437 437  Supported Series: Siemens S7-300 series PLC
438 438  
439 -**1)V-BOX setting**
439 +**1)PLC Setting**
440 440  
441 441  |**Items**|**Settings**|**Note**
442 442  |Protocol|Simens S7-300 Ethernet|
... ... @@ -498,7 +498,7 @@
498 498  
499 499  Supported Series: Siemens S7-400, S7-1200 and S7-1500
500 500  
501 -**1)V-BOX setting**
501 +**1)PLC Setting**
502 502  
503 503  |=**Items**|=**Settings**|=**Note**
504 504  |Protocol|Siemens S7-XXX|
... ... @@ -704,101 +704,6 @@
704 704  [[image:image-20220825100845-4.png]]
705 705  
706 706  
707 -== **FX3U Ethernet Protocol** ==
708 -
709 -Supported Modules: FX3U-ENET-ADP, FX3U-ENET-L
710 -
711 -**1)V-BOX Settings**
712 -
713 -|Items|Settings|Note
714 -|Protocol|Mitsubishi FX3U|
715 -|Connection|Ethernet|
716 -|Port No.|5009|Must be the same as the PLC setting
717 -|PLC station No.|0|
718 -
719 -**2)Address List**
720 -
721 -|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
722 -|(% colspan="1" rowspan="7" %)Bit|X|X|X OOO|0~~377|
723 -|Y|Y|Y OOO|0~~377|
724 -|M|M|M DDDD|0~~7679|
725 -|SM|SM|SM DDDD|8000~~8511|
726 -|S|S|S DDDD|0~~4095|
727 -|TS|TS|TS DDD|0~~511|
728 -|CS|CS|CS DDD|0~~255|
729 -|(% colspan="1" rowspan="9" %)Word|CN|CN|CN DDD|0~~199|
730 -|TN|TN|TN DDD|0~~511|
731 -|D|D|D DDDD|0~~7999|
732 -|SD|SD|SD DDDD|8000~~8511|
733 -|R|R|R DDDDD|0~~32767|
734 -
735 -**3)Ethernet Module Settings**
736 -
737 -FX3U-ENET-L module configuration
738 -Set up the FX3U-ENET-L Ethernet module settings as follows.
739 -Select the module location, which in this document is Module 0.
740 -
741 -[[image:image-20221116105850-1.png]]
742 -
743 -Select "Operational setting" to enter the following screen.
744 -
745 -The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default.
746 -
747 -[[image:image-20221116105947-1.png]]
748 -
749 -Select "Open setting" to enter the setting interface, the settings are as follows.
750 -
751 -The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the
752 -
753 -Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module.
754 -
755 -[[image:image-20221116110802-1.png]]
756 -
757 -Click on "transter setup" - "PC side I/F setting", see the following figure.
758 -
759 -After setting, the first download must use the programming cable, as shown in the figure; after that, can
760 -
761 -use the IP set in the "Ethernet board" to communicate directly with the network cable.
762 -
763 -[[image:image-20221116110832-2.png||height="423" width="708"]]
764 -
765 -Read and write data from the Ethernet module
766 -
767 -[[image:image-20221116110907-3.png]]
768 -
769 -Set "Transter setup" to COM communication, and read or write operation as shown below
770 -
771 -[[image:image-20221116110917-4.png]]
772 -
773 -**4)PLC Settings (GX Works 2)**
774 -
775 -Create a blank FX5U project
776 -
777 -Find Current Connection in the navigation
778 -
779 -[[image:image-20221116111427-1.png||height="421" width="705"]]
780 -
781 -Select Connection Channel List
782 -
783 -Select Ethernet board communication
784 -
785 -[[image:image-20221116111451-2.png||height="421" width="705"]]
786 -
787 -Select Ethernet Module
788 -Set the IP address of the PLC
789 -
790 -[[image:image-20221116111509-3.png||height="666" width="699"]]
791 -
792 -Read or write PLC data, in this document is read
793 -
794 -[[image:image-20221116111651-4.png||height="416" width="697"]]
795 -
796 -[[image:image-20221116111727-5.png||height="416" width="697"]]
797 -
798 -**4)Configure the communication protocol**
799 -
800 -[[image:image-20221119101946-2.png||height="395" width="695"]]
801 -
802 802  == **FX5U Serial Protocol** ==
803 803  
804 804  Mitsubishi FX5U series PLC
... ... @@ -953,10 +953,11 @@
953 953  
954 954  [[image:image-20220825112403-1.png||alt="图片-20220825112403-1.png"]]
955 955  
956 -**5)Cable Wiring**
861 +**5)电缆布线**
957 957  
958 958  [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
959 959  
865 +
960 960  == **L02 Serial Protocol** ==
961 961  
962 962  Mitsubishi L02 series CPU built-in serial port.
... ... @@ -1090,9 +1090,6 @@
1090 1090  
1091 1091  [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1092 1092  
1093 -(% class="wikigeneratedid" %)
1094 -== **Q12H ** ==
1095 -
1096 1096  == **QJ71E71 Ethernet Protocol** ==
1097 1097  
1098 1098  Mitsubishi QJ71E71 Ethernet communication module;
... ... @@ -1141,13 +1141,10 @@
1141 1141  
1142 1142  * Click [Ethernet/CC IE/MELSECNET];
1143 1143  * Please select [Ethernet] as network type;
1144 -* Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order);
1047 +* Set station I/O number according to situation (For example, 0000 means that the module is connected to PLC CPU in first order);
1145 1145  * Select [Online] as Mode;
1146 -* [[image:image-20221119171343-2.png||height="341" width="587"]]
1147 1147  * Click [Operation setting] to set IP;
1148 1148  * Select [Binary Code] as [Communication Data Code];
1149 -* [[image:image-20221119171436-3.png||height="354" width="588"]]
1150 -* Click [Open setting]
1151 1151  * Set protocol: TCP;
1152 1152  * Set [unpassive] in [Open system];
1153 1153  * Set [receive] in [Fixed buffer];
... ... @@ -1154,16 +1154,14 @@
1154 1154  * Set [procedure Exist] in [Fixed buffer communication];
1155 1155  * Disable [Pairing open];
1156 1156  * Set [No confirm] in [Existence confirmation];
1157 -* Host station port number: 5009;
1057 +* Host station port number: 1025;
1158 1158  * Save settings;
1159 -* [[image:image-20221119171611-4.png||height="354" width="588"]]
1160 1160  * Download project into PLC and restart it
1161 1161  
1162 1162  **4)Configure the communication protocol**
1163 1163  
1164 -[[image:image-20221119171832-5.png||height="354" width="625"]]
1063 +[[image:image-20220825143728-1.png]]
1165 1165  
1166 -
1167 1167  **5)Cable Wiring**
1168 1168  
1169 1169  [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png"]]
... ... @@ -1340,6 +1340,9 @@
1340 1340  
1341 1341  [[image:image-20220831163441-4.png]]
1342 1342  
1241 +(% class="wikigeneratedid" %)
1242 +== ==
1243 +
1343 1343  == **XD serial protocol** ==
1344 1344  
1345 1345  **1)V-BOX Settings**
... ... @@ -1414,50 +1414,15 @@
1414 1414  
1415 1415  [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830160232-3.png?rev=1.1||alt="image-20220830160232-3.png"]]
1416 1416  
1318 += Create communication with Inovance** PLC**[[Edit>>url:https://docs.we-con.com.cn/bin/edit/PIStudio/12.PLC%20protocols/WebHome?section=37]] =
1417 1417  
1418 -= Create communication with **Schneider PLC** =
1320 +== **H3U serial protocol**[[Edit>>url:https://docs.we-con.com.cn/bin/edit/PIStudio/12.PLC%20protocols/WebHome?section=38]] ==
1419 1419  
1420 -== **Schneider MODBUS RTU** ==
1322 +**1)HMI Settings**
1421 1421  
1422 -**1)V-BOX Setting**
1423 -
1424 -|=**Parameters**|=**Recommended**|=**Notes**
1425 -|**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
1426 -|**Connection**|RS485|
1427 -|**Baud rate**|19200|
1428 -|**Data bit**|8|
1429 -|**Parity**|Even|
1430 -|**Stop bit**|1|
1431 -|**PLC station No.**|1|
1432 -
1433 -**2)Address List**
1434 -
1435 -|=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
1436 -|B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
1437 -|B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
1438 -|B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
1439 -|W|MW|DDDDDD|0 ~~ 999999|Output register
1440 -|DW|MD|DDDDDD|0 ~~ 999999|Output register
1441 -
1442 -**3)Configure the communication protocol**
1443 -
1444 -[[image:image-20220902104329-1.png]]
1445 -
1446 -**4)Cable Wiring**
1447 -
1448 -**RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
1449 -
1450 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220817154212-1.jpeg?width=554&height=315&rev=1.1||alt="image-20220817154212-1.jpeg" height="315" width="554"]]
1451 -
1452 -= Create communication with Inovance** PLC** =
1453 -
1454 -== **H3U serial protocol** ==
1455 -
1456 -**1)V-BOX Settings**
1457 -
1458 1458  |**Item**|**Settings**|**Note**
1459 1459  |Protocol|INOVANCE H3U PLC|
1460 -|Connection|RS422|
1326 +|Connection|RS22|
1461 1461  |Baud rate|9600|
1462 1462  |Data bit|7|
1463 1463  |Parity|EVEN|
... ... @@ -1487,25 +1487,25 @@
1487 1487  
1488 1488  **3)Configure the communication protocol**
1489 1489  
1490 -[[image:image-20220831164626-1.png]]
1356 +[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830170114-4.png?rev=1.1||alt="image-20220830170114-4.png"]]
1491 1491  
1358 +[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830170017-3.png?rev=1.1||alt="image-20220830170017-3.png"]]
1492 1492  
1493 -
1494 1494  **4)Cable Wiring**
1495 1495  
1496 1496  Figure
1497 1497  
1498 -[[image:image-20220831164646-2.png]][[image:image-20220831164700-3.png]]
1364 +[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830165930-1.png?rev=1.1||alt="image-20220830165930-1.png"]]
1499 1499  
1500 1500  Pin Definition Diagram
1501 1501  
1502 -[[image:image-20220831164731-4.png]]
1368 +[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830165947-2.png?rev=1.1||alt="image-20220830165947-2.png"]]
1503 1503  
1504 -= Create communication with Panasonic** PLC** =
1370 += Create communication with Panasonic** PLC**[[Edit>>url:https://docs.we-con.com.cn/bin/edit/PIStudio/12.PLC%20protocols/WebHome?section=39]] =
1505 1505  
1506 -== **FP serial protocol** ==
1372 +== **FP serial protocol**[[Edit>>url:https://docs.we-con.com.cn/bin/edit/PIStudio/12.PLC%20protocols/WebHome?section=40]] ==
1507 1507  
1508 -**1)V-BOX Settings**
1374 +**1)HMI Settings**
1509 1509  
1510 1510  |**Item**|**Settings**|**Note**
1511 1511  |Protocol|Panasonic FP MFWTOCOL|
... ... @@ -1537,25 +1537,25 @@
1537 1537  
1538 1538  **3)Configure the communication protocol**
1539 1539  
1540 -[[image:image-20220831165238-4.png]]
1406 +[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830171050-1.png?rev=1.1||alt="image-20220830171050-1.png"]]
1541 1541  
1408 +[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830171126-2.png?rev=1.1||alt="image-20220830171126-2.png"]]
1542 1542  
1543 -
1544 1544  **4)Cable Wiring**
1545 1545  
1546 1546  Figure
1547 1547  
1548 -[[image:image-20220831165031-3.png]][[image:image-20220831165017-2.png]]
1414 +[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830171328-4.png?rev=1.1||alt="image-20220830171328-4.png"]]
1549 1549  
1550 1550  Pin Definition Diagram
1551 1551  
1552 -[[image:image-20220831165008-1.png]]
1418 +[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830171146-3.png?rev=1.1||alt="image-20220830171146-3.png"]]
1553 1553  
1554 -= Create communication with LS** PLC** =
1420 += Create communication with LS** PLC**[[Edit>>url:https://docs.we-con.com.cn/bin/edit/PIStudio/12.PLC%20protocols/WebHome?section=41]] =
1555 1555  
1556 -== **XBC serial protocol** ==
1422 +== **XBC serial protocol**[[Edit>>url:https://docs.we-con.com.cn/bin/edit/PIStudio/12.PLC%20protocols/WebHome?section=42]] ==
1557 1557  
1558 -**1)V-BOX Settings**
1424 +**1)HMI Settings**
1559 1559  
1560 1560  |**Item**|**Settings**|**Note**
1561 1561  |Protocol|LS XBC CNet|
... ... @@ -1593,23 +1593,25 @@
1593 1593  
1594 1594  **3)Configure the communication protocol**
1595 1595  
1596 -[[image:image-20220831170147-1.png]]
1462 +[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830174853-3.png?rev=1.1||alt="image-20220830174853-3.png"]]
1597 1597  
1464 +[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830174733-2.png?rev=1.1||alt="image-20220830174733-2.png"]]
1465 +
1598 1598  **4)Cable Wiring**
1599 1599  
1600 1600  Figure
1601 1601  
1602 -[[image:image-20220831170306-4.png]][[image:image-20220831170254-3.png]]
1470 +[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830174659-1.png?rev=1.1||alt="image-20220830174659-1.png"]]
1603 1603  
1604 1604  Pin Definition Diagram
1605 1605  
1606 -[[image:image-20220831170215-2.png]]
1474 +[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830173402-8.png?rev=1.1||alt="image-20220830173402-8.png"]]
1607 1607  
1608 -== **XGK FEnet Ethernet protocol** ==
1476 +== **XGK FEnet Ethernet protocol**[[Edit>>url:https://docs.we-con.com.cn/bin/edit/PIStudio/12.PLC%20protocols/WebHome?section=43]] ==
1609 1609  
1610 1610  Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
1611 1611  
1612 -**1)V-BOX Settings**
1480 +**HMI Settings**
1613 1613  
1614 1614  |**Items**|**Settings**|**Note**
1615 1615  |Protocol|LG XGK FEnet(Ethernet)|
... ... @@ -1616,7 +1616,7 @@
1616 1616  |Connection|Ethernet|
1617 1617  |Port No.|2004|
1618 1618  
1619 -**2)Address List**
1487 +**Address List**
1620 1620  
1621 1621  |**Type**|**Register**|**Range**|**Format**|**Note**
1622 1622  |(% rowspan="14" %)Word|P|0~~2047|P d|
... ... @@ -1640,18 +1640,186 @@
1640 1640  * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
1641 1641  * All bit registers are in the form of bits in word, and the range is the same as the word register;
1642 1642  
1643 -**3)Communication Settings**
1511 +**Communication settings in HMI**
1644 1644  
1645 -[[image:image-20220831171127-1.png]]
1513 +Enable HMI Ethernet in [Project Settings];
1646 1646  
1647 -**4)Cable Wiring**
1515 +[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_43b671f18153910d.png?width=405&height=107&rev=1.1||alt="12.PLC Protocol_html_43b671f18153910d.png" height="107" width="405"]]
1648 1648  
1517 +Set PLC IP in [Device IP] settings;
1518 +
1519 +[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_a2a19b5003ad4090.png?width=554&height=189&rev=1.1||alt="12.PLC Protocol_html_a2a19b5003ad4090.png" height="189" width="554"]]
1520 +
1521 +**Cable Wiring**
1522 +
1649 1649  [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1650 1650  
1651 -= Create communication with **Modbus ** =
1525 += Create communication with **SHIMADEN PLC**[[Edit>>url:https://docs.we-con.com.cn/bin/edit/PIStudio/12.PLC%20protocols/WebHome?section=44]] =
1652 1652  
1653 -== **MODBUS RTU Slave (All function)** ==
1527 +== **FP23 series protocol**[[Edit>>url:https://docs.we-con.com.cn/bin/edit/PIStudio/12.PLC%20protocols/WebHome?section=45]] ==
1654 1654  
1529 +Supported series: SHIMADEN FP23 series
1530 +
1531 +**HMI Setting**
1532 +
1533 +|**Items**|**Settings**|**Note**
1534 +|Protocol|SHIMADEN FP23 series|
1535 +|Connection|RS485 (9600, 1, 7, EVEN)|
1536 +|Port No.|None|
1537 +|PLC station No.|0|
1538 +
1539 +**Address List**
1540 +
1541 +|**Device address**|**HMI register**|**Address range**|**Type**
1542 +|0040-0043(HEX)|FP040|100064-200067|Read only
1543 +|0100-010B(HEX)|FP100|100256-200267|Read only
1544 +|0110-0142(HEX)|FP110|100272-200322|Read only
1545 +|0182-0252(HEX)|FP182|100386-200594|Write only
1546 +|0280-0281(HEX)|FP280|100640-200641|Read only
1547 +|0300-030B(HEX)|FP300|100768-200779|Read and write
1548 +|0380-039F(HEX)|FP380|100896-200927|Read and write
1549 +|0400-04D7(HEX)|FP400|101024-201239|Read and write
1550 +|0500-05B0(HEX)|FP500|101280-201456|Read and write
1551 +|0600-0670(HEX)|FP600|101536-201814|Read and write
1552 +|0720-0738(HEX)|FP720|101824-201848|Read and write
1553 +|0800-083F(HEX)|FP800|102048-202111|Read and write
1554 +|0900-0952(HEX)|FP900|102304-202386|Read and write
1555 +| |Ctrl|0-2|
1556 +
1557 +**✎Note:**
1558 +
1559 +* The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
1560 +* The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in FP23;
1561 +* The Ctrl register is used to store the control group number and BCC check mode.
1562 +
1563 +**Ctrl Register Description**
1564 +
1565 +* The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
1566 +* Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
1567 +* Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
1568 +* Ctrl3 reserved
1569 +
1570 +**✎Note:**
1571 +
1572 +After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
1573 +
1574 +**Cable Wiring**
1575 +
1576 +[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5e9a81a14106da9e.png?width=392&height=223&rev=1.1||alt="12.PLC Protocol_html_5e9a81a14106da9e.png" height="223" width="392"]]
1577 +
1578 +[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_1897d92be6948d58.png?width=393&height=223&rev=1.1||alt="12.PLC Protocol_html_1897d92be6948d58.png" height="223" width="393"]]
1579 +
1580 +**✎Note:** COM3 only available in PI8000/PI9000 series.
1581 +
1582 +== **SR90 protocol**[[Edit>>url:https://docs.we-con.com.cn/bin/edit/PIStudio/12.PLC%20protocols/WebHome?section=46]] ==
1583 +
1584 +Supported series: SHIMADEN SR90 series
1585 +
1586 +**HMI Setting**
1587 +
1588 +|**Items**|**Settings**|**Note**
1589 +|Protocol|SHIMADEN SR90 protocol|
1590 +|Connection|RS485 (1200, 1, 7, EVEN)|
1591 +|Port No.|None|
1592 +|PLC station No.|0|
1593 +
1594 +**Address List**
1595 +
1596 +|**Device address**|**HMI register**|**Address range**|**Type**
1597 +|0040-0043 (HEX)|SR040|100064-100067|Read only
1598 +|0100-010A(HEX)|SR0100|100256-100266|Read only
1599 +|0182-018C(HEX)|SR0182|100386-100396|Write only
1600 +|0300-04FE(HEX)|SR0300|100768-101278|Write/read
1601 +|0500-050B(HEX)|SR0500|101280-101291|Write/read
1602 +|0590-0611(HEX)|SR0590|101424-101553|Write/read
1603 +|0701-0709(HEX)|SR0701|101793-101801|Write/read
1604 +| |Ctrl|0-2|~-~-
1605 +
1606 +**✎Note:**
1607 +
1608 +* The upper 2 bits of the address of HMIs are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
1609 +* The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in SR90;
1610 +* The Ctrl register is used to store the control group number and BCC check mode. See how to use it below;
1611 +
1612 +**Ctrl Register Description**
1613 +
1614 +* The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
1615 +* Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
1616 +* Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
1617 +* Ctrl3 reserved
1618 +
1619 +**✎Note:**
1620 +
1621 +After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
1622 +
1623 +**Cable Wiring**
1624 +
1625 +[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5e9a81a14106da9e.png?width=392&height=223&rev=1.1||alt="12.PLC Protocol_html_5e9a81a14106da9e.png" height="223" width="392"]]
1626 +
1627 +[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_1897d92be6948d58.png?width=393&height=223&rev=1.1||alt="12.PLC Protocol_html_1897d92be6948d58.png" height="223" width="393"]]
1628 +
1629 +**✎Note:** COM3 only available in PI8000/PI9000 series.
1630 +
1631 +== **MR13 series(standard protocol)**[[Edit>>url:https://docs.we-con.com.cn/bin/edit/PIStudio/12.PLC%20protocols/WebHome?section=47]] ==
1632 +
1633 +Supported series: SHIMADEN MR13 series
1634 +
1635 +**HMI Setting**
1636 +
1637 +|**Items**|**Settings**|**Note**
1638 +|Protocol|SHIMADEN standard protocol|
1639 +|Connection|RS485 (1200, 1, 7, EVEN)|
1640 +|Port No.|None|
1641 +|PLC station No.|0|
1642 +
1643 +**Address List**
1644 +
1645 +|**Device address**|**HMI register**|**Address range**|**Type**
1646 +|0100-010B(HEX)|MR100|100256-300267|Read only
1647 +|0111-0126(HEX)|MR111|100273-300294|Read only
1648 +|0184-0192(HEX)|MR184|100388-300402|Write only
1649 +|0280-0282(HEX)|MR280|100640-300642|Read only
1650 +|0300-030B(HEX)|MR300|100768-300779|Read/write
1651 +|0314-0317(HEX)|MR314|100788-300791|Read/write
1652 +|031A(HEX)|MR31A|100794-300794|Read/write
1653 +|0320-0321(HEX)|MR320|100800-300801|Read/write
1654 +|0400-0504(HEX)|MR400|101024-301284|Read/write
1655 +|0506(HEX)|MR506|101286-301286|Read/write
1656 +|0510-0514(HEX)|MR510|101296-301300|Read/write
1657 +|0516-0524(HEX)|MR516|101302-301316|Read/write
1658 +|0526(HEX)|MR526|101318-301318|Read/write
1659 +|0580-08C3(HEX)|MR580|101408-302243|Read/write
1660 +|~-~-|Ctrl|0-2|~-~-
1661 +
1662 +**✎Note:**
1663 +
1664 +* The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
1665 +* The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in MR13;
1666 +* The Ctrl register is used to store the control group number and BCC check mode.
1667 +
1668 +**Ctrl Register Description**
1669 +
1670 +* The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
1671 +* Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR, STX_ETX_CR LF and @_:_CR .
1672 +* Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
1673 +* Ctrl3 reserved
1674 +
1675 +**✎Note:**
1676 +
1677 +After reloading project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
1678 +
1679 +**Cable Wiring**
1680 +
1681 +[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5e9a81a14106da9e.png?width=392&height=223&rev=1.1||alt="12.PLC Protocol_html_5e9a81a14106da9e.png" height="223" width="392"]]
1682 +
1683 +[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_1897d92be6948d58.png?width=393&height=223&rev=1.1||alt="12.PLC Protocol_html_1897d92be6948d58.png" height="223" width="393"]]
1684 +
1685 +**✎Note:** COM3 only available in PI8000/PI9000 series.
1686 +
1687 += Create communication with **Modbus RTU** =
1688 +
1689 +== **V-BOX as Slave** ==
1690 +
1655 1655  Select the protocol "Modbus RTU Slave (All Fuction)",
1656 1656  
1657 1657  Then set baud rate, port, stop bits, data bits, parity.
... ... @@ -1659,7 +1659,7 @@
1659 1659  (% style="text-align:center" %)
1660 1660  [[image:1624342015914-382.png||height="486" width="800" class="img-thumbnail"]]
1661 1661  
1662 -== **MODBUS RTU Master** ==
1698 +== **V-BOX as Master** ==
1663 1663  
1664 1664  Select the protocol "Modbus RTU Master",
1665 1665  
... ... @@ -1695,61 +1695,6 @@
1695 1695  |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1696 1696  |0F (Write multiple bits)
1697 1697  
1698 -== **MODBUS TCP Slave (All function)** ==
1699 -
1700 -Supported series: MODBUS TCP controller
1701 -
1702 -V-B0X works as MODBUS TCP MASTER connecting with TCP SLAVE
1703 -
1704 -**1)V-BOX Setting**
1705 -
1706 -|**Items**|**Settings**|**Note**
1707 -|Protocol|MODBUS TCP Slave (All function)|
1708 -|Connection|Ethernet|
1709 -|Port No.|502|
1710 -|PLC station No.|1
1711 -
1712 -**2)Address List**
1713 -
1714 -|**Type**|**Register**|**Function code & Description**
1715 -|(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
1716 -|06 (write single register: write a binary value to a holding register)
1717 -|10 (write values to multiple addresses )
1718 -|(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1719 -|06 (write single register: write a binary value to a holding register)
1720 -|10 (write values to multiple addresses )
1721 -|(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1722 -|06 (write single register: write a binary value to a holding register)
1723 -|10 (write values to multiple addresses )
1724 -|(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1725 -|10 (write values to multiple addresses )
1726 -|(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1727 -|05 (Force a single coil to force the on/off state of a logic coil)
1728 -|0F (Write multiple bits, ie write continuously)
1729 -|(% rowspan="3" %)1|02 (Read the input state)
1730 -|05 (Force a single coil to force the on/off state of a logic coil)
1731 -|0F (Write multiple bits)
1732 -|(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1733 -|05 (Force a single coil to force the on/off state of a logic coil)
1734 -|0F (Write multiple bits)
1735 -|(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1736 -|0F (Write multiple bits)
1737 -
1738 -**3)Communication Settings**
1739 -
1740 -Configure V-BOX Ethernet IP in Networking Settings
1741 -
1742 -[[image:image-20220902111833-3.png]]
1743 -
1744 -
1745 -Configure PLC Ethernet IP in Communication;
1746 -
1747 -[[image:image-20220902111121-1.png]]
1748 -
1749 -**4)Cable Wiring**
1750 -
1751 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1752 -
1753 1753  == **communicate with VB inverter** ==
1754 1754  
1755 1755  [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20VB%20inverter.zip]]
image-20220831164626-1.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -56.1 KB
Content
image-20220831164646-2.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -28.4 KB
Content
image-20220831164700-3.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -66.6 KB
Content
image-20220831164731-4.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -12.3 KB
Content
image-20220831165008-1.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -13.3 KB
Content
image-20220831165017-2.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -36.2 KB
Content
image-20220831165031-3.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -28.3 KB
Content
image-20220831165238-4.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -57.4 KB
Content
image-20220831170147-1.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -57.1 KB
Content
image-20220831170215-2.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -14.3 KB
Content
image-20220831170254-3.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -43.5 KB
Content
image-20220831170306-4.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -28.5 KB
Content
image-20220831171127-1.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -60.1 KB
Content
image-20220902104329-1.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -58.7 KB
Content
image-20220902111121-1.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -60.9 KB
Content
image-20220902111754-2.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -57.6 KB
Content
image-20220902111833-3.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -56.1 KB
Content
image-20221116105850-1.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Bob
Size
... ... @@ -1,1 +1,0 @@
1 -18.9 KB
Content
image-20221116105947-1.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Bob
Size
... ... @@ -1,1 +1,0 @@
1 -18.7 KB
Content
image-20221116110802-1.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Bob
Size
... ... @@ -1,1 +1,0 @@
1 -16.4 KB
Content
image-20221116110832-2.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Bob
Size
... ... @@ -1,1 +1,0 @@
1 -42.2 KB
Content
image-20221116110907-3.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Bob
Size
... ... @@ -1,1 +1,0 @@
1 -17.8 KB
Content
image-20221116110917-4.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Bob
Size
... ... @@ -1,1 +1,0 @@
1 -23.2 KB
Content
image-20221116111427-1.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Bob
Size
... ... @@ -1,1 +1,0 @@
1 -63.4 KB
Content
image-20221116111451-2.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Bob
Size
... ... @@ -1,1 +1,0 @@
1 -225.5 KB
Content
image-20221116111509-3.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Bob
Size
... ... @@ -1,1 +1,0 @@
1 -34.1 KB
Content
image-20221116111651-4.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Bob
Size
... ... @@ -1,1 +1,0 @@
1 -74.3 KB
Content
image-20221116111727-5.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Bob
Size
... ... @@ -1,1 +1,0 @@
1 -106.2 KB
Content
image-20221116114106-1.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Bob
Size
... ... @@ -1,1 +1,0 @@
1 -99.5 KB
Content
image-20221119101759-1.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Bob
Size
... ... @@ -1,1 +1,0 @@
1 -62.1 KB
Content
image-20221119101946-2.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Bob
Size
... ... @@ -1,1 +1,0 @@
1 -68.7 KB
Content
image-20221119171318-1.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Bob
Size
... ... @@ -1,1 +1,0 @@
1 -90.3 KB
Content
image-20221119171343-2.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Bob
Size
... ... @@ -1,1 +1,0 @@
1 -90.3 KB
Content
image-20221119171436-3.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Bob
Size
... ... @@ -1,1 +1,0 @@
1 -43.4 KB
Content
image-20221119171611-4.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Bob
Size
... ... @@ -1,1 +1,0 @@
1 -23.1 KB
Content
image-20221119171832-5.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Bob
Size
... ... @@ -1,1 +1,0 @@
1 -69.6 KB
Content