... ... @@ -178,6 +178,102 @@
178 178  
179 179  = Create communication with **Rockwell PLC** =
180 180  
181 +== **DF1 Advanced Protocol** ==
182 +
183 +MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
184 +
185 +**1) V-Box Settings**
186 +
187 +|=Item|=Recommended |=Note
188 +|=Protocol|Allen Bradley DF1 Advanced|
189 +|=Connection|RS232|
190 +|=Baud rate|19200|
191 +|=Stop bits|1|
192 +|=Data bits|8|
193 +|=Parity|None|
194 +|=PLC Station No.|1|
195 +|=HMI Station No.|0|
196 +
197 +**2) Address List**
198 +
199 +|=**Type**|=**Device registers**|=**Format**|=**Range**|=Note
200 +|(% colspan="1" rowspan="7" %)Bit|I1|I1ddd.dd|0.0~~255.15|Only able to communicate with file number I1
201 +|O0|O0ddd.dd|0.0~~255.15|Only able to communicate with file number O0
202 +|S2|S2ddd.dd|0.0~~255.15|Only able to communicate with file number S2
203 +|B3|B3ddd.dd|0.0~~255.15|Only able to communicate with file number B3
204 +|BN|BNddddd.dd|0.0~~99255.15|(((
205 +Bit data file B0~~B99
206 +
207 +First two digits is for file number
208 +
209 +For example, BN13001.00 represents file number B13, address 001, the 0th bit.
210 +)))
211 +|N7|N7ddd.dd|0.0~~255.15|Only able to communicate with file number N7
212 +|NN|NNddddd.dd|0.0~~99255.15|(((
213 +Integer data file bit format N0~~N99
214 +
215 +First two digits is for file number
216 +
217 +For example, NN13001.00 represents file number N13, address 001, the 0th bit.
218 +)))
219 +|(% rowspan="11" %)Word|S2|S2ddd|0~~255|Only able to communicate with file number S2
220 +|T4S|T4Sddd|0~~255|Only able to communicate with file number T4 (Timer Preset Value)
221 +|T4P|T4Pddd|0~~255|Only able to communicate with file number T4 (Timer Accumulator Value)
222 +|TNS|TNSddddd|0~~99255|(((
223 +Timer Preset Value
224 +
225 +First two digits is for file number
226 +
227 +For example, TNS99255 represents file number T99, address 255.
228 +)))
229 +|TNP|TNPddddd|0~~99255|(((
230 +Timer Accumulator Value
231 +
232 +First two digits is for file number
233 +
234 +For example, TNP99255 represents file number T99, address 255.
235 +)))
236 +|C5S|C5Sddd|0~~255|Only able to communicate with file number C5 (Counter Preset Value)
237 +|C5P|C5Pddd|0~~255|Only able to communicate with file number C5 (Counter Accumulator Value)
238 +|CNS|CNSddddd|0~~99255|(((
239 +Counter Preset Value
240 +
241 +First two digits is for file number
242 +
243 +For example, CNS99255 represents file number C99, address 255.
244 +)))
245 +|CNP|CNPddddd|0~~99255|(((
246 +Counter Accumulator Value
247 +
248 +First two digits is for file number
249 +
250 +For example, CNP99255 represents file number C99, address 255.
251 +)))
252 +|N7|N7ddd|0~~255|Only able to communicate with file number N7
253 +|NN|NNddd|0~~99255|(((
254 +Integer data file
255 +
256 +First two digits is for file number
257 +
258 +For example, NN99255 represents file number N99, address 255.
259 +)))
260 +|(% colspan="1" rowspan="3" %)Double Word|F8|F8ddd|0~~255|(((
261 +Only able to communicate with file number N7
262 +)))
263 +|FN|FNddddd|0~~99255|(((
264 +Floating point data file
265 +
266 +First two digits is for file number
267 +
268 +For example, FN99255 represents file number F99, address 255.
269 +)))
270 +|LN|LNddddd|0~~99255|Long
271 +
272 +**3) Cable Wiring**
273 +
274 +(% style="text-align:center" %)
275 +[[image:ABRS232.gif]]
276 +
181 181  == (% id="cke_bm_5621S" style="display:none" %)** **(%%)**MicroLogix Protocol** ==
182 182  
183 183  MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
... ... @@ -185,7 +185,7 @@
185 185  **1)V-BOX setting**
186 186  
187 187  |**Item**|**Settings**|**Note**
188 -|Protocol|Allen-Bradlley DF1 Advanced|
284 +|Protocol|Allen-Bradley DF1 Advanced|
189 189  |Connection|RS232|
190 190  |Baud rate|19200|
191 191  |Data bit|8|
... ... @@ -608,6 +608,86 @@
608 608  
609 609  [[image:image-20220824162342-2.png]]
610 610  
707 +== **LOGO Ethernet Protocol** ==
708 +
709 +Supported Series: Siemens Logo 0BA0, 0BA1 series
710 +
711 +**V-BOX Settings**
712 +
713 +
714 +|**Items**|**Settings**|**Note**
715 +|Protocol|Siemens LOGO|
716 +|Connection|Ethernet|
717 +|Port No.|102|
718 +|PLC station No.|2|
719 +
720 +**Address List**
721 +
722 +
723 +|**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
724 +|1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
725 +|2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
726 +|3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
727 +|4|VW|Word|0-1468|DB1.DBX0.0|0x000000
728 +|5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
729 +|6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
730 +|7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
731 +|8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
732 +|9|AI|Word|1-16|DB1.DBX1032.0|0x002040
733 +|10|I|Bit|1-64|DB1.DBX1024.0|0x002000
734 +|11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
735 +|12|M|Bit|1-112|DB1.DBX1104.0|0x002280
736 +|13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
737 +|14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
738 +|15|V|Bit|0-14697|DB1.DBX0.0|0x000000
739 +
740 +**PLC Settings in LOGO Software:**
741 +
742 +Click [Tools]~-~-[Ethernet Connections],shown as below.
743 +
744 +(% style="text-align:center" %)
745 +[[image:PIStudio.12\.PLC protocols.WebHome@12.PLC Protocol_html_8b9d2322edf89519.png]]
746 +
747 +Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
748 +
749 +(% style="text-align:center" %)
750 +[[image:PIStudio.12\.PLC protocols.WebHome@image-20221228142937-4.png]]
751 +
752 +**TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
753 +
754 +(% style="text-align:center" %)
755 +[[image:PIStudio.12\.PLC protocols.WebHome@image-20221228143047-5.png]]
756 +
757 + **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
758 +
759 +(% style="text-align:center" %)
760 +[[image:PIStudio.12\.PLC protocols.WebHome@image-20221228143246-6.png]]
761 +
762 +**V-BOX Communication Settings**
763 +
764 +Set PLC IP in [IP Address] settings;
765 +
766 +(% style="text-align:center" %)
767 +[[image:LldwDGntf4.png]]
768 +
769 +Enable V-BOX Ethernet in [Network];
770 +
771 +(% style="text-align:center" %)
772 +[[image:WgvjfWbQif.png]]
773 +
774 +TSAP setting
775 +
776 +* The initialization script needs to set the source TSAP address and the target TSAP address, otherwise the communication will not be successful.
777 +
778 +{{code language="LUA"}}
779 +function init.main()
780 +    addr_setword("@W_0#HSW1200",8192) -- Set the source TSAP address
781 +
782 +    addr_setword("@W_0#HSW1201",4096) -- Set the destination TSAP address
783 +
784 +end
785 +{{/code}}
786 +
611 611  = Create communication with **Mitsubishi PLC** =
612 612  
613 613  == **FX1S,1N,2N Serial Protocol** ==
... ... @@ -1090,8 +1090,12 @@
1090 1090  
1091 1091  [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1092 1092  
1093 -== **Q12H port Protocal** ==
1269 +== **Q12H Serial Protocol** ==
1094 1094  
1271 +This Demo shows V-BOX communicate with Q12H PLC by Q02H serial Protocol
1272 +
1273 +[[**Download link**>>https://ftp.we-con.com.cn/Download/WIKI/PI%20HMI/Demo/Communication/V-Box%20connect%20PLC%20Q12H.rar]]
1274 +
1095 1095  == **QJ71E71 Ethernet Protocol** ==
1096 1096  
1097 1097  Mitsubishi QJ71E71 Ethernet communication module;
... ... @@ -1171,12 +1171,105 @@
1171 1171  
1172 1172  == **DVP Ethernet Protocol** ==
1173 1173  
1174 -[[下载链接>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Delta%20DVP%20Ethernet.zip]]
1354 +Supoort Series: DELTA DVP20/32/40/60ES200RE/200TE or any DVP models with built-in Ethernet port, DELTA DVPEN01-SL module
1175 1175  
1356 +**1)V-BOX Settings**
1357 +
1358 +|=**Items**|=**Settings**|=**Note**
1359 +|Protocol|DELTA DVP MODBUS TCP|
1360 +|Connection|Ethernet|
1361 +|Port No.|502|
1362 +|Device No.|1|
1363 +|VBox Device No.|0|
1364 +
1365 +**2)Address List **
1366 +
1367 +|=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 217px;" %)**VBox registers**|=(% style="width: 168px;" %)**Format**|=(% style="width: 225px;" %)**Range**|=**Note**
1368 +|Bit|(% style="width:191px" %)X|(% style="width:217px" %)X|(% style="width:168px" %)X OOO|(% style="width:225px" %)0~~377|
1369 +|Bit|(% style="width:191px" %)Y|(% style="width:217px" %)Y|(% style="width:168px" %)Y OOO|(% style="width:225px" %)0~~377|
1370 +|Bit|(% style="width:191px" %)M0|(% style="width:217px" %)M0|(% style="width:168px" %)M0DDDD|(% style="width:225px" %)0~~1535|
1371 +|Bit|(% style="width:191px" %)M1|(% style="width:217px" %)M1|(% style="width:168px" %)M1DDDD|(% style="width:225px" %)1536~~4096|
1372 +|Bit|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDD|(% style="width:225px" %)0~~255|
1373 +|Bit|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~255|
1374 +|Bit|(% style="width:191px" %)S|(% style="width:217px" %)S|(% style="width:168px" %)SDDDD|(% style="width:225px" %)0~~1023|
1375 +|Word|(% style="width:191px" %)D0|(% style="width:217px" %)D0|(% style="width:168px" %)D0DDDD|(% style="width:225px" %)0~~4095|
1376 +|Word|(% style="width:191px" %)D1|(% style="width:217px" %)D1|(% style="width:168px" %)D1DDDD|(% style="width:225px" %)4096~~11999|
1377 +|Word|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDD|(% style="width:225px" %)0~~255|
1378 +|Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~199|
1379 +|Double Word|(% style="width:191px" %)HC|(% style="width:217px" %)HC|(% style="width:168px" %)HCDDD|(% style="width:225px" %)200~~255|
1380 +
1381 +**3) PLC Setting:**
1382 +
1383 +~1. Create new project in Delta WPL Soft, and click Setting to open the communication settings:
1384 +
1385 +(% style="text-align:center" %)
1386 +[[image:DVPEthernetWPLSoft2.png]]
1387 +
1388 +2. Set up the communication type and PLC IP:
1389 +
1390 +(% style="text-align:center" %)
1391 +[[image:DVPEthernetSetup.png]]
1392 +
1393 +(% class="wikigeneratedid" %)
1394 +3. Click OK and save the settings. Then click Communication on toolbar, then click Transfer Setup to open new window:
1395 +
1396 +(% style="text-align:center" %)
1397 +[[image:DVPEthernetTransfer.png]]
1398 +
1399 +(% class="wikigeneratedid" %)
1400 +4. Select Communication Mode as PC => PLC to download or select PC <=PLC to upload:
1401 +
1402 +(% style="text-align:center" %)
1403 +[[image:DVPEthernetPLCtoPC.png]]
1404 +
1405 +5. Click Auto-Search Ethernet Module to find the PLC on the same LAN network:
1406 +
1407 +(% style="text-align:center" %)
1408 +[[image:DVPEthernetAutoSearch.png]]
1409 +
1410 +**4) V-BOX Setting:**
1411 +
1412 +Set the same IP address according to the setting from WPL Soft:
1413 +
1414 +(% style="text-align:center" %)
1415 +[[image:DVPEthernetVNETPortocol.png]]
1416 +
1176 1176  == **DVP serial protocol** ==
1177 1177  
1178 -[[下载链接>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Delta%20DVP%20Ethernet.zip]]
1419 +Supoort Series: DELTA DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX
1179 1179  
1421 +**1)V-BOX Settings**
1422 +
1423 +|=**Items**|=**Settings**|=**Note**
1424 +|Protocol|DELTA DVP PROTOCOL|
1425 +|Connection|RS232|
1426 +|Baud Rate|9600|
1427 +|Stop Bit|1|
1428 +|Data Bit|7|
1429 +|Parity|EVEN|
1430 +|Device No.|1|
1431 +
1432 +(% class="wikigeneratedid" %)
1433 +**2)Address List**
1434 +
1435 +|=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 217px;" %)**VBox registers**|=(% style="width: 168px;" %)**Format**|=(% style="width: 225px;" %)**Range**|=**Note**
1436 +|Bit|(% style="width:191px" %)X|(% style="width:217px" %)X|(% style="width:168px" %)X OOOOOO|(% style="width:225px" %)0~~303237|
1437 +|Bit|(% style="width:191px" %)Y|(% style="width:217px" %)Y|(% style="width:168px" %)Y OOOOOO|(% style="width:225px" %)0~~303237|
1438 +|Bit|(% style="width:191px" %)M|(% style="width:217px" %)M|(% style="width:168px" %)MDDDDD|(% style="width:225px" %)0~~99999|
1439 +|Bit|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDDDD|(% style="width:225px" %)0~~99999|
1440 +|Bit|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDDDD|(% style="width:225px" %)0~~99999|
1441 +|Bit|(% style="width:191px" %)S|(% style="width:217px" %)S|(% style="width:168px" %)SDDDDD|(% style="width:225px" %)0~~99999|
1442 +|Word|(% style="width:191px" %)D|(% style="width:217px" %)D|(% style="width:168px" %)D DDDDD|(% style="width:225px" %)0~~99999|
1443 +|Word|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDDDD|(% style="width:225px" %)0~~99999|
1444 +|Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~199|
1445 +|Double Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDDDD|(% style="width:225px" %)200~~99999|
1446 +
1447 +(% class="wikigeneratedid" %)
1448 +**3)Wiring Diagram**
1449 +
1450 +(% style="text-align:center" %)
1451 +[[image:Delta DVP PROTOCOLSerial232.png]]
1452 +
1180 1180  == **AS Ethernet Protocol** ==
1181 1181  
1182 1182  **1)V-BOX Settings**
... ... @@ -1210,7 +1210,6 @@
1210 1210  
1211 1211  **3)Configure the communication protocol**
1212 1212  
1213 -
1214 1214  [[image:image-20220831160010-4.png]]
1215 1215  
1216 1216  **4)Cable Wiring**
... ... @@ -1343,7 +1343,7 @@
1343 1343  
1344 1344  **1)V-BOX Settings**
1345 1345  
1346 -Supported Series: Delta Xinjie XD/XE Series PLC
1618 +Supported Series: Xinjie XD/XE Series PLC
1347 1347  
1348 1348  |**Item**|**Settings**|**Note**
1349 1349  |Protocol|XINJE XD/XC MODBUS|
... ... @@ -1413,7 +1413,6 @@
1413 1413  
1414 1414  [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830160232-3.png?rev=1.1||alt="image-20220830160232-3.png"]]
1415 1415  
1416 -
1417 1417  = Create communication with **Schneider PLC** =
1418 1418  
1419 1419  == **Schneider MODBUS RTU** ==
... ... @@ -1670,8 +1670,8 @@
1670 1670  **address list**
1671 1671  
1672 1672  (% class="table-bordered" %)
1673 -|**type**|**register**|**Function code and description**
1674 -|(% rowspan="11" %)|(% rowspan="3" %)3|04 (Read Input Registers: Read the current binary value in one or more input registers)
1944 +|=(% scope="row" %)**Type**|=**Data Type**|=**Function code and description**
1945 +|(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (Read Input Registers: Read the current binary value in one or more input registers)
1675 1675  |06 (write single register: write a binary value to a holding register)
1676 1676  |10 (write values to multiple addresses )
1677 1677  |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
... ... @@ -1710,7 +1710,7 @@
1710 1710  
1711 1711  **2)Address List**
1712 1712  
1713 -|**Type**|**Register**|**Function code & Description**
1984 +|=**Type**|=**Data Type**|=**Function code & Description**
1714 1714  |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
1715 1715  |06 (write single register: write a binary value to a holding register)
1716 1716  |10 (write values to multiple addresses )
0Il1q9GZgk.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Bob
Size
... ... @@ -1,0 +1,1 @@
1 +24.6 KB
Content
AB.gif
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +7.3 KB
Content
ABRS232.gif
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +7.3 KB
Content
DVPEthernetAutoSearch.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +43.6 KB
Content
DVPEthernetPLCtoPC.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +8.9 KB
Content
DVPEthernetSetup.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +19.9 KB
Content
DVPEthernetTransfer.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +59.9 KB
Content
DVPEthernetVNETPortocol.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +21.4 KB
Content
DVPEthernetWPLSoft.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +97.5 KB
Content
DVPEthernetWPLSoft2.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +45.2 KB
Content
Delta DVP PROTOCOLSerial232.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter