1 -= **1 General communication with PLC** =
1 += **Modbus RTU** =
2 2  
3 -== **Modbus RTU** ==
4 -
5 5  === **V-BOX as master** ===
6 6  
7 7  Select the protocol “(% class="mark" %)Modbus RTU Slave(All Fuction)”,
... ... @@ -47,19 +47,217 @@
47 47  |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
48 48  |0F (Write multiple bits)
49 49  
50 -== **WECON LX3V PLC** ==
48 += **WECON PLC** =
51 51  
52 -Select the protocol (% class="mark" %)"WECON LX3V"
50 +== **V-BOX 和维控 LX3V 串行通信** ==
53 53  
54 -(% class="mark" %)then set BaudRate,Port,Stop Bit,Data Bit,Parity same with PLC.
52 +Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
55 55  
56 -(% class="mark" %)WECON PLC RS422 port,default communication parameters is 9600,1,7,ZEVEN
54 +**HMI Settings**
57 57  
56 +|**Item**|**Settings**|**Note**
57 +|Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
58 +|Connection|RS422/RS485|
59 +|Baud rate|9600|
60 +|Data bit|7|
61 +|Parity|EVEN|
62 +|Stop bit|1|
63 +|PLC station No.|1|
64 +
65 +**Address List**
66 +
67 +|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
68 +|(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
69 +|Y|Y|Y o|0~~303237|
70 +|M|M|M d|0~~99999|
71 +|T|T|T d|0~~99999|
72 +|C|C|C d|0~~99999|
73 +|S|S|S d|0~~99999|
74 +|(% rowspan="8" %)Word|X|X|Xo|0~~303237|
75 +|Y|Y|Y o|0~~303237|
76 +|M|M|M d|0~~99999|
77 +|T|T|T d|0~~99999|
78 +|C|C|C d|0~~199|
79 +|D|D|D d|0~~7999|
80 +|S|S|S d|0~~99999|
81 +|SD|SD|SD d|8000~~9999|
82 +
83 +**Cable Wiring**
84 +
85 +* **RS485**
86 +
87 + [[image:image-20220822172124-1.png]]
88 +
89 +* **RS422**
90 +
91 + [[image:image-20220822172228-2.png]]
92 +
93 +
94 +**✎Note:**
95 +
96 +* HMI COM3 is available in PI8000 series and COM3 is in COM2(hardware PIN 7 and PIN 8) .
97 +* If PLC <= 20 points,such as LX3V-1208/LX3V-0806 PLC,PLC RS485A and RS485B mean PLC COM2 RS485+ and RS485- .PLC COM2 can support modbus. Please refer to PLC COM2 setting manual.
98 +
99 +[[https:~~/~~/drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing>>url:https://drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing]]
100 +
101 +
102 +== **V-BOX and Wecon LX5V serial communication** ==
103 +
104 +This example introduces the establishment of serial port communication between Wecon HMI and LX5V. It is introduced through three parts: PLC software configuration, HMI software configuration, and hardware wiring.
105 +
106 +**Software configuration of PLC**
107 +
108 +**1)PLC programming software**
109 +
110 +[[image:image-20220810164710-1.png]]
111 +
112 +
113 +**2)New PLC project**
114 +
115 +Click New Project and select the PLC model.
116 +
117 +[[image:image-20220810172412-1.png]]
118 +
119 +
120 +**3)Set Serial port parameters**
121 +
122 +Follow the steps below to configure Serial port parameters
123 +
124 +Baud rate:115200
125 +
126 +Data bit:8
127 +
128 +Stop bit:1
129 +
130 +Parity:No verification
131 +
132 +[[image:image-20220810165759-3.png]]
133 +
134 +
135 +**4)Registers list**
136 +
137 +[[image:image-20220811102219-3.png]]
138 +
139 +
140 +**HMI software configuration**
141 +
142 +**1)HMI programming software**
143 +
144 + [[image:image-20220810171237-4.png]]
145 +
146 +**2)New HMI project**
147 +
148 +Click New Project and select the HMI model.
149 +
150 +[[image:image-20220810172010-5.png]]
151 +
152 +
153 +**3)Set communication port parameters**
154 +
155 +Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
156 +
157 +Baud rate:115200
158 +
159 +Data bit:8
160 +
161 +Stop bit:1
162 +
163 +Parity:No verification
164 +
165 +[[image:image-20220811104012-1.png]]
166 +
167 +
168 +**hardware connection**
169 +
170 +**1)Hardware wiring diagram**
171 +
172 +This example introduces WeconHMI with LX5V PLC to establish communication through serial port. The connection diagram is as follows:
173 +
174 +
175 +
176 +[[image:image-20220811103005-4.png]]
177 +
178 +[[image:image-20220811103227-7.png]]
179 +
180 +The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC.
181 +
182 +== **V-BOX and Wecon LX5V-N Ethernet communication** ==
183 +
184 + This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V. It is introduced through three parts: PLC software configuration, HMI software configuration, and hardware wiring.
185 +
186 +**Software configuration of PLC**
187 +
188 +**1)PLC programming software**
189 +
190 +[[image:image-20220810164710-1.png]]
191 +
192 +**2)New PLC project**
193 +
194 +Click New Project and select the PLC model.
195 +
196 +[[image:image-20220811115454-1.png]]
197 +
198 +**3)Set Ethernet port parameters**
199 +
200 +Follow the steps below to configure Ethernet parameters
201 +
202 +PLC IP address:192.168.39.200
203 +
204 +default gateway:192.168.39.1
205 +
206 +subnet mask:255.255.255.0
207 +
208 +[[image:image-20220811140530-2.png]]
209 +
210 +**4)Registers list**
211 +
212 +[[image:image-20220811102219-3.png]]
213 +
214 +**HMI software configuration**
215 +
216 +**1)HMI programming software**
217 +
218 + [[image:image-20220810171237-4.png]]
219 +
220 +**2)New HMI project**
221 +
222 +Click New Project and select the HMI model.
223 +
224 +[[image:image-20220810172010-5.png]]
225 +
226 +**3)Set communication port parameters**
227 +
228 +Click the project setting button on the left to configure the IP address of the HMI machine to ensure that the HMI and PLC IP remain in a local area network.
229 +
230 +HMI IP address:192.168.39.201
231 +
232 +default gateway:192.168.39.1
233 +
234 +subnet mask:255.255.255.0
235 +
236 +[[image:image-20220811170753-2.png]]
237 +
238 +Next, click Communication Settings to configure the IP of the HMI communication object.
239 +
240 +[[image:image-20220811163047-1.png]]
241 +
242 +**hardware connection**
243 +
244 +**1)Hardware wiring diagram**
245 +
246 +This example introduces WeconHMI with LX5V-N PLC to establish communication through ethernet. The connection diagram is as follows:
247 +
248 +[[image:image-20220811170248-1.png]]
249 +
250 +The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC.
251 +
58 58  (% style="text-align:center" %)
59 59  [[image:1624348978863-771.png||queryString="width=812&height=494" height="487" width="800" class="img-thumbnail"]]
60 60  
61 -== **2 Communication with Allen-Bradley CompactLogix L1769** ==
255 += **Rockwell PLC** =
62 62  
257 +== **Communication with AB CompactLogix L1769** ==
258 +
63 63  (((
64 64  (((
65 65  This example introduces the establishment of Ethernet communication between Wecon V-box and Allen-Bradley L1769. It is introduced through three parts: PLC software configuration, V-box software configuration, and hardware wiring.
... ... @@ -199,7 +199,7 @@
199 199  
200 200  (((
201 201  (((
202 -Open VNET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the device machine code/product code, device password, and device alias to add the device.   ​​​​​​​[[image:image-20220714162752-8.png]]
398 +Open VNET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the device machine code/product code, device password, and device alias to add the device.   [[image:image-20220714162752-8.png]]
203 203  )))
204 204  
205 205  
... ... @@ -226,7 +226,7 @@
226 226  
227 227  
228 228  (((
229 -After adding the protocol Allen-BradleyMicro850_FreeTag, click[[image:image-20220714143838-2.png]]icon add label.​​​​​​​[[image:image-20220714162827-11.png]]
425 +After adding the protocol Allen-BradleyMicro850_FreeTag, click[[image:image-20220714143838-2.png]]icon add label.[[image:image-20220714162827-11.png]]
230 230  )))
231 231  
232 232  (% class="wikigeneratedid" id="HEngineeringproduction" %)
... ... @@ -261,6 +261,14 @@
261 261  
262 262  (((
263 263  The above are all the steps for establishing Ethernet communication between Wecon V-box with Allen-Bradley L1769 PLC.
460 +
461 +
462 +== **Allen-Bradley Ethernet DF1** ==
463 +
464 +[[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Allen-Bradley%20Ethernet%20DF1.zip]]
465 +
466 +
467 += **Siemens PLC** =
264 264  )))
265 265  )))
266 266  
... ... @@ -268,14 +268,12 @@
268 268  
269 269  [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]]
270 270  
271 -== **Allen-Bradley Ethernet DF1** ==
272 -
273 -[[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Allen-Bradley%20Ethernet%20DF1.zip]]
274 -
275 275  == **Communication with S7-200 Smart** ==
276 276  
277 277  [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20S7-200%20Smart.zip]]
278 278  
479 += **Delta PLC** =
480 +
279 279  == **Delta DVP Ethernet** ==
280 280  
281 281  [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Delta%20DVP%20Ethernet.zip]]
image-20220820164423-1.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Ben
Size
... ... @@ -1,0 +1,1 @@
1 +18.4 KB
Content
image-20220822172124-1.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Ben
Size
... ... @@ -1,0 +1,1 @@
1 +38.7 KB
Content
image-20220822172228-2.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Ben
Size
... ... @@ -1,0 +1,1 @@
1 +48.8 KB
Content