Changes for page 1 Communication

Last modified by Hunter on 2024/07/01 10:54

From version 191.1
edited by Bob
on 2022/12/01 11:02
Change comment: There is no comment for this version
To version 205.1
edited by Bob
on 2023/02/02 11:23
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -178,6 +178,102 @@
178 178  
179 179  = Create communication with **Rockwell PLC** =
180 180  
181 +== **DF1 Advanced Protocol** ==
182 +
183 +MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
184 +
185 +**1) V-Box Settings**
186 +
187 +|=Item|=Recommended |=Note
188 +|=Protocol|Allen Bradley DF1 Advanced|
189 +|=Connection|RS232|
190 +|=Baud rate|19200|
191 +|=Stop bits|1|
192 +|=Data bits|8|
193 +|=Parity|None|
194 +|=PLC Station No.|1|
195 +|=HMI Station No.|0|
196 +
197 +**2) Address List**
198 +
199 +|=**Type**|=**Device registers**|=**Format**|=**Range**|=Note
200 +|(% colspan="1" rowspan="7" %)Bit|I1|I1ddd.dd|0.0~~255.15|Only able to communicate with file number I1
201 +|O0|O0ddd.dd|0.0~~255.15|Only able to communicate with file number O0
202 +|S2|S2ddd.dd|0.0~~255.15|Only able to communicate with file number S2
203 +|B3|B3ddd.dd|0.0~~255.15|Only able to communicate with file number B3
204 +|BN|BNddddd.dd|0.0~~99255.15|(((
205 +Bit data file B0~~B99
206 +
207 +First two digits is for file number
208 +
209 +For example, BN13001.00 represents file number B13, address 001, the 0th bit.
210 +)))
211 +|N7|N7ddd.dd|0.0~~255.15|Only able to communicate with file number N7
212 +|NN|NNddddd.dd|0.0~~99255.15|(((
213 +Integer data file bit format N0~~N99
214 +
215 +First two digits is for file number
216 +
217 +For example, NN13001.00 represents file number N13, address 001, the 0th bit.
218 +)))
219 +|(% rowspan="11" %)Word|S2|S2ddd|0~~255|Only able to communicate with file number S2
220 +|T4S|T4Sddd|0~~255|Only able to communicate with file number T4 (Timer Preset Value)
221 +|T4P|T4Pddd|0~~255|Only able to communicate with file number T4 (Timer Accumulator Value)
222 +|TNS|TNSddddd|0~~99255|(((
223 +Timer Preset Value
224 +
225 +First two digits is for file number
226 +
227 +For example, TNS99255 represents file number T99, address 255.
228 +)))
229 +|TNP|TNPddddd|0~~99255|(((
230 +Timer Accumulator Value
231 +
232 +First two digits is for file number
233 +
234 +For example, TNP99255 represents file number T99, address 255.
235 +)))
236 +|C5S|C5Sddd|0~~255|Only able to communicate with file number C5 (Counter Preset Value)
237 +|C5P|C5Pddd|0~~255|Only able to communicate with file number C5 (Counter Accumulator Value)
238 +|CNS|CNSddddd|0~~99255|(((
239 +Counter Preset Value
240 +
241 +First two digits is for file number
242 +
243 +For example, CNS99255 represents file number C99, address 255.
244 +)))
245 +|CNP|CNPddddd|0~~99255|(((
246 +Counter Accumulator Value
247 +
248 +First two digits is for file number
249 +
250 +For example, CNP99255 represents file number C99, address 255.
251 +)))
252 +|N7|N7ddd|0~~255|Only able to communicate with file number N7
253 +|NN|NNddd|0~~99255|(((
254 +Integer data file
255 +
256 +First two digits is for file number
257 +
258 +For example, NN99255 represents file number N99, address 255.
259 +)))
260 +|(% colspan="1" rowspan="3" %)Double Word|F8|F8ddd|0~~255|(((
261 +Only able to communicate with file number N7
262 +)))
263 +|FN|FNddddd|0~~99255|(((
264 +Floating point data file
265 +
266 +First two digits is for file number
267 +
268 +For example, FN99255 represents file number F99, address 255.
269 +)))
270 +|LN|LNddddd|0~~99255|Long
271 +
272 +**3) Cable Wiring**
273 +
274 +(% style="text-align:center" %)
275 +[[image:ABRS232.gif]]
276 +
181 181  == (% id="cke_bm_5621S" style="display:none" %)** **(%%)**MicroLogix Protocol** ==
182 182  
183 183  MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
... ... @@ -185,7 +185,7 @@
185 185  **1)V-BOX setting**
186 186  
187 187  |**Item**|**Settings**|**Note**
188 -|Protocol|Allen-Bradlley DF1 Advanced|
284 +|Protocol|Allen-Bradley DF1 Advanced|
189 189  |Connection|RS232|
190 190  |Baud rate|19200|
191 191  |Data bit|8|
... ... @@ -608,6 +608,46 @@
608 608  
609 609  [[image:image-20220824162342-2.png]]
610 610  
707 +== **LOGO Ethernet Protocol** ==
708 +
709 +Supported Series: Siemens Logo 0BA0, 0BA1 series
710 +
711 +**V-BOX Settings**
712 +
713 +
714 +|**Items**|**Settings**|**Note**
715 +|Protocol|Siemens LOGO|
716 +|Connection|Ethernet|
717 +|Port No.|102|
718 +|PLC station No.|2|
719 +
720 +**Address List**
721 +
722 +
723 +|**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
724 +|1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
725 +|2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
726 +|3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
727 +|4|VW|Word|0-1468|DB1.DBX0.0|0x000000
728 +|5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
729 +|6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
730 +|7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
731 +|8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
732 +|9|AI|Word|1-16|DB1.DBX1032.0|0x002040
733 +|10|I|Bit|1-64|DB1.DBX1024.0|0x002000
734 +|11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
735 +|12|M|Bit|1-112|DB1.DBX1104.0|0x002280
736 +|13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
737 +|14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
738 +|15|V|Bit|0-14697|DB1.DBX0.0|0x000000
739 +
740 + **PLC Settings in LOGO Software:**
741 +
742 +Click [Tools]~-~-[Ethernet Connections],shown as below.
743 +
744 +(% style="text-align:center" %)
745 +[[image:12.PLC Protocol_html_8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]]
746 +
611 611  = Create communication with **Mitsubishi PLC** =
612 612  
613 613  == **FX1S,1N,2N Serial Protocol** ==
... ... @@ -1175,12 +1175,105 @@
1175 1175  
1176 1176  == **DVP Ethernet Protocol** ==
1177 1177  
1178 -[[Download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Delta%20DVP%20Ethernet.zip]]
1314 +Supoort Series: DELTA DVP20/32/40/60ES200RE/200TE or any DVP models with built-in Ethernet port, DELTA DVPEN01-SL module
1179 1179  
1316 +**1)V-BOX Settings**
1317 +
1318 +|=**Items**|=**Settings**|=**Note**
1319 +|Protocol|DELTA DVP MODBUS TCP|
1320 +|Connection|Ethernet|
1321 +|Port No.|502|
1322 +|Device No.|1|
1323 +|VBox Device No.|0|
1324 +
1325 +**2)Address List **
1326 +
1327 +|=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 217px;" %)**VBox registers**|=(% style="width: 168px;" %)**Format**|=(% style="width: 225px;" %)**Range**|=**Note**
1328 +|Bit|(% style="width:191px" %)X|(% style="width:217px" %)X|(% style="width:168px" %)X OOO|(% style="width:225px" %)0~~377|
1329 +|Bit|(% style="width:191px" %)Y|(% style="width:217px" %)Y|(% style="width:168px" %)Y OOO|(% style="width:225px" %)0~~377|
1330 +|Bit|(% style="width:191px" %)M0|(% style="width:217px" %)M0|(% style="width:168px" %)M0DDDD|(% style="width:225px" %)0~~1535|
1331 +|Bit|(% style="width:191px" %)M1|(% style="width:217px" %)M1|(% style="width:168px" %)M1DDDD|(% style="width:225px" %)1536~~4096|
1332 +|Bit|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDD|(% style="width:225px" %)0~~255|
1333 +|Bit|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~255|
1334 +|Bit|(% style="width:191px" %)S|(% style="width:217px" %)S|(% style="width:168px" %)SDDDD|(% style="width:225px" %)0~~1023|
1335 +|Word|(% style="width:191px" %)D0|(% style="width:217px" %)D0|(% style="width:168px" %)D0DDDD|(% style="width:225px" %)0~~4095|
1336 +|Word|(% style="width:191px" %)D1|(% style="width:217px" %)D1|(% style="width:168px" %)D1DDDD|(% style="width:225px" %)4096~~11999|
1337 +|Word|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDD|(% style="width:225px" %)0~~255|
1338 +|Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~199|
1339 +|Double Word|(% style="width:191px" %)HC|(% style="width:217px" %)HC|(% style="width:168px" %)HCDDD|(% style="width:225px" %)200~~255|
1340 +
1341 +**3) PLC Setting:**
1342 +
1343 +~1. Create new project in Delta WPL Soft, and click Setting to open the communication settings:
1344 +
1345 +(% style="text-align:center" %)
1346 +[[image:DVPEthernetWPLSoft2.png]]
1347 +
1348 +2. Set up the communication type and PLC IP:
1349 +
1350 +(% style="text-align:center" %)
1351 +[[image:DVPEthernetSetup.png]]
1352 +
1353 +(% class="wikigeneratedid" %)
1354 +3. Click OK and save the settings. Then click Communication on toolbar, then click Transfer Setup to open new window:
1355 +
1356 +(% style="text-align:center" %)
1357 +[[image:DVPEthernetTransfer.png]]
1358 +
1359 +(% class="wikigeneratedid" %)
1360 +4. Select Communication Mode as PC => PLC to download or select PC <=PLC to upload:
1361 +
1362 +(% style="text-align:center" %)
1363 +[[image:DVPEthernetPLCtoPC.png]]
1364 +
1365 +5. Click Auto-Search Ethernet Module to find the PLC on the same LAN network:
1366 +
1367 +(% style="text-align:center" %)
1368 +[[image:DVPEthernetAutoSearch.png]]
1369 +
1370 +**4) V-BOX Setting:**
1371 +
1372 +Set the same IP address according to the setting from WPL Soft:
1373 +
1374 +(% style="text-align:center" %)
1375 +[[image:DVPEthernetVNETPortocol.png]]
1376 +
1180 1180  == **DVP serial protocol** ==
1181 1181  
1182 -[[Download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Delta%20DVP%20Ethernet.zip]]
1379 +Supoort Series: DELTA DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX
1183 1183  
1381 +**1)V-BOX Settings**
1382 +
1383 +|=**Items**|=**Settings**|=**Note**
1384 +|Protocol|DELTA DVP PROTOCOL|
1385 +|Connection|RS232|
1386 +|Baud Rate|9600|
1387 +|Stop Bit|1|
1388 +|Data Bit|7|
1389 +|Parity|EVEN|
1390 +|Device No.|1|
1391 +
1392 +(% class="wikigeneratedid" %)
1393 +**2)Address List**
1394 +
1395 +|=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 217px;" %)**VBox registers**|=(% style="width: 168px;" %)**Format**|=(% style="width: 225px;" %)**Range**|=**Note**
1396 +|Bit|(% style="width:191px" %)X|(% style="width:217px" %)X|(% style="width:168px" %)X OOOOOO|(% style="width:225px" %)0~~303237|
1397 +|Bit|(% style="width:191px" %)Y|(% style="width:217px" %)Y|(% style="width:168px" %)Y OOOOOO|(% style="width:225px" %)0~~303237|
1398 +|Bit|(% style="width:191px" %)M|(% style="width:217px" %)M|(% style="width:168px" %)MDDDDD|(% style="width:225px" %)0~~99999|
1399 +|Bit|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDDDD|(% style="width:225px" %)0~~99999|
1400 +|Bit|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDDDD|(% style="width:225px" %)0~~99999|
1401 +|Bit|(% style="width:191px" %)S|(% style="width:217px" %)S|(% style="width:168px" %)SDDDDD|(% style="width:225px" %)0~~99999|
1402 +|Word|(% style="width:191px" %)D|(% style="width:217px" %)D|(% style="width:168px" %)D DDDDD|(% style="width:225px" %)0~~99999|
1403 +|Word|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDDDD|(% style="width:225px" %)0~~99999|
1404 +|Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~199|
1405 +|Double Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDDDD|(% style="width:225px" %)200~~99999|
1406 +
1407 +(% class="wikigeneratedid" %)
1408 +**3)Wiring Diagram**
1409 +
1410 +(% style="text-align:center" %)
1411 +[[image:Delta DVP PROTOCOLSerial232.png]]
1412 +
1184 1184  == **AS Ethernet Protocol** ==
1185 1185  
1186 1186  **1)V-BOX Settings**
... ... @@ -1214,7 +1214,6 @@
1214 1214  
1215 1215  **3)Configure the communication protocol**
1216 1216  
1217 -
1218 1218  [[image:image-20220831160010-4.png]]
1219 1219  
1220 1220  **4)Cable Wiring**
... ... @@ -1673,8 +1673,8 @@
1673 1673  **address list**
1674 1674  
1675 1675  (% class="table-bordered" %)
1676 -|**type**|**register**|**Function code and description**
1677 -|(% rowspan="11" %)|(% rowspan="3" %)3|04 (Read Input Registers: Read the current binary value in one or more input registers)
1904 +|=(% scope="row" %)**Type**|=**Data Type**|=**Function code and description**
1905 +|(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (Read Input Registers: Read the current binary value in one or more input registers)
1678 1678  |06 (write single register: write a binary value to a holding register)
1679 1679  |10 (write values to multiple addresses )
1680 1680  |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
... ... @@ -1713,7 +1713,7 @@
1713 1713  
1714 1714  **2)Address List**
1715 1715  
1716 -|**Type**|**Register**|**Function code & Description**
1944 +|=**Type**|=**Data Type**|=**Function code & Description**
1717 1717  |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
1718 1718  |06 (write single register: write a binary value to a holding register)
1719 1719  |10 (write values to multiple addresses )
AB.gif
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +7.3 KB
Content
ABRS232.gif
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +7.3 KB
Content
DVPEthernetAutoSearch.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +43.6 KB
Content
DVPEthernetPLCtoPC.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +8.9 KB
Content
DVPEthernetSetup.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +19.9 KB
Content
DVPEthernetTransfer.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +59.9 KB
Content
DVPEthernetVNETPortocol.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +21.4 KB
Content
DVPEthernetWPLSoft.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +97.5 KB
Content
DVPEthernetWPLSoft2.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +45.2 KB
Content
Delta DVP PROTOCOLSerial232.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +10.7 KB
Content