Content
... ... @@ -178,6 +178,102 @@
178 178  
179 179  = Create communication with **Rockwell PLC** =
180 180  
181 +== **DF1 Advanced Protocol** ==
182 +
183 +MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
184 +
185 +**1) V-Box Settings**
186 +
187 +|=Item|=Recommended |=Note
188 +|=Protocol|Allen Bradley DF1 Advanced|
189 +|=Connection|RS232|
190 +|=Baud rate|19200|
191 +|=Stop bits|1|
192 +|=Data bits|8|
193 +|=Parity|None|
194 +|=PLC Station No.|1|
195 +|=HMI Station No.|0|
196 +
197 +**2) Address List**
198 +
199 +|=**Type**|=**Device registers**|=**Format**|=**Range**|=Note
200 +|(% colspan="1" rowspan="7" %)Bit|I1|I1ddd.dd|0.0~~255.15|Only able to communicate with file number I1
201 +|O0|O0ddd.dd|0.0~~255.15|Only able to communicate with file number O0
202 +|S2|S2ddd.dd|0.0~~255.15|Only able to communicate with file number S2
203 +|B3|B3ddd.dd|0.0~~255.15|Only able to communicate with file number B3
204 +|BN|BNddddd.dd|0.0~~99255.15|(((
205 +Bit data file B0~~B99
206 +
207 +First two digits is for file number
208 +
209 +For example, BN13001.00 represents file number B13, address 001, the 0th bit.
210 +)))
211 +|N7|N7ddd.dd|0.0~~255.15|Only able to communicate with file number N7
212 +|NN|NNddddd.dd|0.0~~99255.15|(((
213 +Integer data file bit format N0~~N99
214 +
215 +First two digits is for file number
216 +
217 +For example, NN13001.00 represents file number N13, address 001, the 0th bit.
218 +)))
219 +|(% rowspan="11" %)Word|S2|S2ddd|0~~255|Only able to communicate with file number S2
220 +|T4S|T4Sddd|0~~255|Only able to communicate with file number T4 (Timer Preset Value)
221 +|T4P|T4Pddd|0~~255|Only able to communicate with file number T4 (Timer Accumulator Value)
222 +|TNS|TNSddddd|0~~99255|(((
223 +Timer Preset Value
224 +
225 +First two digits is for file number
226 +
227 +For example, TNS99255 represents file number T99, address 255.
228 +)))
229 +|TNP|TNPddddd|0~~99255|(((
230 +Timer Accumulator Value
231 +
232 +First two digits is for file number
233 +
234 +For example, TNP99255 represents file number T99, address 255.
235 +)))
236 +|C5S|C5Sddd|0~~255|Only able to communicate with file number C5 (Counter Preset Value)
237 +|C5P|C5Pddd|0~~255|Only able to communicate with file number C5 (Counter Accumulator Value)
238 +|CNS|CNSddddd|0~~99255|(((
239 +Counter Preset Value
240 +
241 +First two digits is for file number
242 +
243 +For example, CNS99255 represents file number C99, address 255.
244 +)))
245 +|CNP|CNPddddd|0~~99255|(((
246 +Counter Accumulator Value
247 +
248 +First two digits is for file number
249 +
250 +For example, CNP99255 represents file number C99, address 255.
251 +)))
252 +|N7|N7ddd|0~~255|Only able to communicate with file number N7
253 +|NN|NNddd|0~~99255|(((
254 +Integer data file
255 +
256 +First two digits is for file number
257 +
258 +For example, NN99255 represents file number N99, address 255.
259 +)))
260 +|(% colspan="1" rowspan="3" %)Double Word|F8|F8ddd|0~~255|(((
261 +Only able to communicate with file number N7
262 +)))
263 +|FN|FNddddd|0~~99255|(((
264 +Floating point data file
265 +
266 +First two digits is for file number
267 +
268 +For example, FN99255 represents file number F99, address 255.
269 +)))
270 +|LN|LNddddd|0~~99255|Long
271 +
272 +**3) Cable Wiring**
273 +
274 +(% style="text-align:center" %)
275 +[[image:ABRS232.gif]]
276 +
181 181  == (% id="cke_bm_5621S" style="display:none" %)** **(%%)**MicroLogix Protocol** ==
182 182  
183 183  MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
... ... @@ -185,7 +185,7 @@
185 185  **1)V-BOX setting**
186 186  
187 187  |**Item**|**Settings**|**Note**
188 -|Protocol|Allen-Bradlley DF1 Advanced|
284 +|Protocol|Allen-Bradley DF1 Advanced|
189 189  |Connection|RS232|
190 190  |Baud rate|19200|
191 191  |Data bit|8|
AB.gif
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +7.3 KB
Content
ABRS232.gif
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +7.3 KB
Content