... ... @@ -178,102 +178,6 @@
178 178  
179 179  = Create communication with **Rockwell PLC** =
180 180  
181 -== **DF1 Advanced Protocol** ==
182 -
183 -MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
184 -
185 -**1) V-Box Settings**
186 -
187 -|=Item|=Recommended |=Note
188 -|=Protocol|Allen Bradley DF1 Advanced|
189 -|=Connection|RS232|
190 -|=Baud rate|19200|
191 -|=Stop bits|1|
192 -|=Data bits|8|
193 -|=Parity|None|
194 -|=PLC Station No.|1|
195 -|=HMI Station No.|0|
196 -
197 -**2) Address List**
198 -
199 -|=**Type**|=**Device registers**|=**Format**|=**Range**|=Note
200 -|(% colspan="1" rowspan="7" %)Bit|I1|I1ddd.dd|0.0~~255.15|Only able to communicate with file number I1
201 -|O0|O0ddd.dd|0.0~~255.15|Only able to communicate with file number O0
202 -|S2|S2ddd.dd|0.0~~255.15|Only able to communicate with file number S2
203 -|B3|B3ddd.dd|0.0~~255.15|Only able to communicate with file number B3
204 -|BN|BNddddd.dd|0.0~~99255.15|(((
205 -Bit data file B0~~B99
206 -
207 -First two digits is for file number
208 -
209 -For example, BN13001.00 represents file number B13, address 001, the 0th bit.
210 -)))
211 -|N7|N7ddd.dd|0.0~~255.15|Only able to communicate with file number N7
212 -|NN|NNddddd.dd|0.0~~99255.15|(((
213 -Integer data file bit format N0~~N99
214 -
215 -First two digits is for file number
216 -
217 -For example, NN13001.00 represents file number N13, address 001, the 0th bit.
218 -)))
219 -|(% rowspan="11" %)Word|S2|S2ddd|0~~255|Only able to communicate with file number S2
220 -|T4S|T4Sddd|0~~255|Only able to communicate with file number T4 (Timer Preset Value)
221 -|T4P|T4Pddd|0~~255|Only able to communicate with file number T4 (Timer Accumulator Value)
222 -|TNS|TNSddddd|0~~99255|(((
223 -Timer Preset Value
224 -
225 -First two digits is for file number
226 -
227 -For example, TNS99255 represents file number T99, address 255.
228 -)))
229 -|TNP|TNPddddd|0~~99255|(((
230 -Timer Accumulator Value
231 -
232 -First two digits is for file number
233 -
234 -For example, TNP99255 represents file number T99, address 255.
235 -)))
236 -|C5S|C5Sddd|0~~255|Only able to communicate with file number C5 (Counter Preset Value)
237 -|C5P|C5Pddd|0~~255|Only able to communicate with file number C5 (Counter Accumulator Value)
238 -|CNS|CNSddddd|0~~99255|(((
239 -Counter Preset Value
240 -
241 -First two digits is for file number
242 -
243 -For example, CNS99255 represents file number C99, address 255.
244 -)))
245 -|CNP|CNPddddd|0~~99255|(((
246 -Counter Accumulator Value
247 -
248 -First two digits is for file number
249 -
250 -For example, CNP99255 represents file number C99, address 255.
251 -)))
252 -|N7|N7ddd|0~~255|Only able to communicate with file number N7
253 -|NN|NNddd|0~~99255|(((
254 -Integer data file
255 -
256 -First two digits is for file number
257 -
258 -For example, NN99255 represents file number N99, address 255.
259 -)))
260 -|(% colspan="1" rowspan="3" %)Double Word|F8|F8ddd|0~~255|(((
261 -Only able to communicate with file number N7
262 -)))
263 -|FN|FNddddd|0~~99255|(((
264 -Floating point data file
265 -
266 -First two digits is for file number
267 -
268 -For example, FN99255 represents file number F99, address 255.
269 -)))
270 -|LN|LNddddd|0~~99255|Long
271 -
272 -**3) Cable Wiring**
273 -
274 -(% style="text-align:center" %)
275 -[[image:ABRS232.gif]]
276 -
277 277  == (% id="cke_bm_5621S" style="display:none" %)** **(%%)**MicroLogix Protocol** ==
278 278  
279 279  MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
... ... @@ -281,7 +281,7 @@
281 281  **1)V-BOX setting**
282 282  
283 283  |**Item**|**Settings**|**Note**
284 -|Protocol|Allen-Bradley DF1 Advanced|
188 +|Protocol|Allen-Bradlley DF1 Advanced|
285 285  |Connection|RS232|
286 286  |Baud rate|19200|
287 287  |Data bit|8|
... ... @@ -704,8 +704,6 @@
704 704  
705 705  [[image:image-20220824162342-2.png]]
706 706  
707 -== **LOGO Ethernet Protocol** ==
708 -
709 709  = Create communication with **Mitsubishi PLC** =
710 710  
711 711  == **FX1S,1N,2N Serial Protocol** ==
... ... @@ -1273,7 +1273,7 @@
1273 1273  
1274 1274  == **DVP Ethernet Protocol** ==
1275 1275  
1276 -Supoort Series: DELTA DVP20/32/40/60ES200RE/200TE or any DVP models with built-in Ethernet port, DELTA DVPEN01-SL module
1178 +Supoort Series: DELTA DVP20/32/40/60ES200RE/200TE, DELTA DVPEN01-SL
1277 1277  
1278 1278  **1)V-BOX Settings**
1279 1279  
... ... @@ -1286,92 +1286,17 @@
1286 1286  
1287 1287  **2)Address List **
1288 1288  
1289 -|=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 217px;" %)**VBox registers**|=(% style="width: 168px;" %)**Format**|=(% style="width: 225px;" %)**Range**|=**Note**
1290 -|Bit|(% style="width:191px" %)X|(% style="width:217px" %)X|(% style="width:168px" %)X OOO|(% style="width:225px" %)0~~377|
1291 -|Bit|(% style="width:191px" %)Y|(% style="width:217px" %)Y|(% style="width:168px" %)Y OOO|(% style="width:225px" %)0~~377|
1292 -|Bit|(% style="width:191px" %)M0|(% style="width:217px" %)M0|(% style="width:168px" %)M0DDDD|(% style="width:225px" %)0~~1535|
1293 -|Bit|(% style="width:191px" %)M1|(% style="width:217px" %)M1|(% style="width:168px" %)M1DDDD|(% style="width:225px" %)1536~~4096|
1294 -|Bit|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDD|(% style="width:225px" %)0~~255|
1295 -|Bit|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~255|
1296 -|Bit|(% style="width:191px" %)S|(% style="width:217px" %)S|(% style="width:168px" %)SDDDD|(% style="width:225px" %)0~~1023|
1297 -|Word|(% style="width:191px" %)D0|(% style="width:217px" %)D0|(% style="width:168px" %)D0DDDD|(% style="width:225px" %)0~~4095|
1298 -|Word|(% style="width:191px" %)D1|(% style="width:217px" %)D1|(% style="width:168px" %)D1DDDD|(% style="width:225px" %)4096~~11999|
1299 -|Word|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDD|(% style="width:225px" %)0~~255|
1300 -|Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~199|
1301 -|Double Word|(% style="width:191px" %)HC|(% style="width:217px" %)HC|(% style="width:168px" %)HCDDD|(% style="width:225px" %)200~~255|
1191 +|=**Type**|=(% style="width: 215px;" %)**Device registers**|=(% style="width: 237px;" %)**VBox registers**|=(% style="width: 214px;" %)**Format**|=**Range**|=**Note**
1192 +|Bit|(% style="width:215px" %)X|(% style="width:237px" %)X|(% style="width:214px" %)X OOO|0~~377|
1193 +|Bit|(% style="width:215px" %)Y|(% style="width:237px" %)Y|(% style="width:214px" %)Y OOO|0~~377|
1194 +|Bit|(% style="width:215px" %)M0|(% style="width:237px" %)M0|(% style="width:214px" %)M0DDDD|0~~1535|
1195 +|Bit|(% style="width:215px" %)M1|(% style="width:237px" %)M1|(% style="width:214px" %)M1DDDD|1536~~4096|
1196 +| |(% style="width:215px" %) |(% style="width:237px" %) |(% style="width:214px" %) | |
1302 1302  
1303 -**3) PLC Setting:**
1304 -
1305 -~1. Create new project in Delta WPL Soft, and click Setting to open the communication settings:
1306 -
1307 -(% style="text-align:center" %)
1308 -[[image:DVPEthernetWPLSoft2.png]]
1309 -
1310 -2. Set up the communication type and PLC IP:
1311 -
1312 -(% style="text-align:center" %)
1313 -[[image:DVPEthernetSetup.png]]
1314 -
1315 -(% class="wikigeneratedid" %)
1316 -3. Click OK and save the settings. Then click Communication on toolbar, then click Transfer Setup to open new window:
1317 -
1318 -(% style="text-align:center" %)
1319 -[[image:DVPEthernetTransfer.png]]
1320 -
1321 -(% class="wikigeneratedid" %)
1322 -4. Select Communication Mode as PC => PLC to download or select PC <=PLC to upload:
1323 -
1324 -(% style="text-align:center" %)
1325 -[[image:DVPEthernetPLCtoPC.png]]
1326 -
1327 -5. Click Auto-Search Ethernet Module to find the PLC on the same LAN network:
1328 -
1329 -(% style="text-align:center" %)
1330 -[[image:DVPEthernetAutoSearch.png]]
1331 -
1332 -**4) V-BOX Setting:**
1333 -
1334 -Set the same IP address according to the setting from WPL Soft:
1335 -
1336 -(% style="text-align:center" %)
1337 -[[image:DVPEthernetVNETPortocol.png]]
1338 -
1339 1339  == **DVP serial protocol** ==
1340 1340  
1341 -Supoort Series: DELTA DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX
1200 +[[Download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Delta%20DVP%20Ethernet.zip]]
1342 1342  
1343 -**1)V-BOX Settings**
1344 -
1345 -|=**Items**|=**Settings**|=**Note**
1346 -|Protocol|DELTA DVP PROTOCOL|
1347 -|Connection|RS232|
1348 -|Baud Rate|9600|
1349 -|Stop Bit|1|
1350 -|Data Bit|7|
1351 -|Parity|EVEN|
1352 -|Device No.|1|
1353 -
1354 -(% class="wikigeneratedid" %)
1355 -**2)Address List**
1356 -
1357 -|=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 217px;" %)**VBox registers**|=(% style="width: 168px;" %)**Format**|=(% style="width: 225px;" %)**Range**|=**Note**
1358 -|Bit|(% style="width:191px" %)X|(% style="width:217px" %)X|(% style="width:168px" %)X OOOOOO|(% style="width:225px" %)0~~303237|
1359 -|Bit|(% style="width:191px" %)Y|(% style="width:217px" %)Y|(% style="width:168px" %)Y OOOOOO|(% style="width:225px" %)0~~303237|
1360 -|Bit|(% style="width:191px" %)M|(% style="width:217px" %)M|(% style="width:168px" %)MDDDDD|(% style="width:225px" %)0~~99999|
1361 -|Bit|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDDDD|(% style="width:225px" %)0~~99999|
1362 -|Bit|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDDDD|(% style="width:225px" %)0~~99999|
1363 -|Bit|(% style="width:191px" %)S|(% style="width:217px" %)S|(% style="width:168px" %)SDDDDD|(% style="width:225px" %)0~~99999|
1364 -|Word|(% style="width:191px" %)D|(% style="width:217px" %)D|(% style="width:168px" %)D DDDDD|(% style="width:225px" %)0~~99999|
1365 -|Word|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDDDD|(% style="width:225px" %)0~~99999|
1366 -|Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~199|
1367 -|Double Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDDDD|(% style="width:225px" %)200~~99999|
1368 -
1369 -(% class="wikigeneratedid" %)
1370 -**3)Wiring Diagram**
1371 -
1372 -(% style="text-align:center" %)
1373 -[[image:Delta DVP PROTOCOLSerial232.png]]
1374 -
1375 1375  == **AS Ethernet Protocol** ==
1376 1376  
1377 1377  **1)V-BOX Settings**
... ... @@ -1405,6 +1405,7 @@
1405 1405  
1406 1406  **3)Configure the communication protocol**
1407 1407  
1235 +
1408 1408  [[image:image-20220831160010-4.png]]
1409 1409  
1410 1410  **4)Cable Wiring**
... ... @@ -1863,8 +1863,8 @@
1863 1863  **address list**
1864 1864  
1865 1865  (% class="table-bordered" %)
1866 -|=(% scope="row" %)**Type**|=**Data Type**|=**Function code and description**
1867 -|(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (Read Input Registers: Read the current binary value in one or more input registers)
1694 +|**type**|**register**|**Function code and description**
1695 +|(% rowspan="11" %)|(% rowspan="3" %)3|04 (Read Input Registers: Read the current binary value in one or more input registers)
1868 1868  |06 (write single register: write a binary value to a holding register)
1869 1869  |10 (write values to multiple addresses )
1870 1870  |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
... ... @@ -1903,7 +1903,7 @@
1903 1903  
1904 1904  **2)Address List**
1905 1905  
1906 -|=**Type**|=**Data Type**|=**Function code & Description**
1734 +|**Type**|**Register**|**Function code & Description**
1907 1907  |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
1908 1908  |06 (write single register: write a binary value to a holding register)
1909 1909  |10 (write values to multiple addresses )
AB.gif
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Hunter
Size
... ... @@ -1,1 +1,0 @@
1 -7.3 KB
Content
ABRS232.gif
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Hunter
Size
... ... @@ -1,1 +1,0 @@
1 -7.3 KB
Content
DVPEthernetAutoSearch.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Hunter
Size
... ... @@ -1,1 +1,0 @@
1 -43.6 KB
Content
DVPEthernetPLCtoPC.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Hunter
Size
... ... @@ -1,1 +1,0 @@
1 -8.9 KB
Content
DVPEthernetSetup.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Hunter
Size
... ... @@ -1,1 +1,0 @@
1 -19.9 KB
Content
DVPEthernetTransfer.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Hunter
Size
... ... @@ -1,1 +1,0 @@
1 -59.9 KB
Content
DVPEthernetVNETPortocol.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Hunter
Size
... ... @@ -1,1 +1,0 @@
1 -21.4 KB
Content
DVPEthernetWPLSoft.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Hunter
Size
... ... @@ -1,1 +1,0 @@
1 -97.5 KB
Content
DVPEthernetWPLSoft2.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Hunter
Size
... ... @@ -1,1 +1,0 @@
1 -45.2 KB
Content
Delta DVP PROTOCOLSerial232.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Hunter
Size
... ... @@ -1,1 +1,0 @@
1 -10.7 KB
Content