... ... @@ -706,6 +706,44 @@
706 706  
707 707  == **LOGO Ethernet Protocol** ==
708 708  
709 +Supported Series: Siemens Logo 0BA0, 0BA1 series
710 +
711 +**V-BOX Settings**
712 +
713 +
714 +|**Items**|**Settings**|**Note**
715 +|Protocol|Siemens LOGO|
716 +|Connection|Ethernet|
717 +|Port No.|102|
718 +|PLC station No.|2|
719 +
720 +**Address List**
721 +
722 +
723 +|**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
724 +|1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
725 +|2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
726 +|3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
727 +|4|VW|Word|0-1468|DB1.DBX0.0|0x000000
728 +|5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
729 +|6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
730 +|7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
731 +|8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
732 +|9|AI|Word|1-16|DB1.DBX1032.0|0x002040
733 +|10|I|Bit|1-64|DB1.DBX1024.0|0x002000
734 +|11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
735 +|12|M|Bit|1-112|DB1.DBX1104.0|0x002280
736 +|13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
737 +|14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
738 +|15|V|Bit|0-14697|DB1.DBX0.0|0x000000
739 +
740 + **PLC Settings in LOGO Software:**
741 +
742 +Click [Tools]~-~-[Ethernet Connections],shown as below.
743 +
744 +(% style="text-align:center" %)
745 +[[image:12.PLC Protocol_html_8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]]
746 +