... ... @@ -2026,9 +2026,32 @@
2026 2026  [[image:VNETCommunicationtabmeter.png]]
2027 2027  
2028 2028  (% class="wikigeneratedid" %)
2029 -4. Create new real-time monitoring tag.
2029 +4. Create new real-time monitoring tag accroding to Modbus manual
2030 2030  
2031 +(% class="wikigeneratedid" %)
2032 +Enter the address we want to read from the meter. The following table is intercept part of the manual for Linfee Modbus manual.
2031 2031  
2034 +(% class="wikigeneratedid" %)
2035 +**0x03/0x04 command data register address**:
2036 +
2037 +(% style="width:1079.22px" %)
2038 +|(% style="display:none" %) |=(% colspan="2" rowspan="1" style="width: 165px;" %)Address(% style="display:none" %) |=Description|=Data Format|=Data Length(Word)|=Remark
2039 +|(%%)(% style="display:none" %) (%%) |(% style="width:107px" %)HEX|(%%)(% style="display:none" %) (%%) |(% style="width:100px" %)DEC|(%%)(% style="display:none" %) (%%) | | | |
2040 +|(% style="width:107px" %)0x00|(% style="width:100px" %)0|Reserved| | |
2041 +|(% style="width:107px" %)0x02|(% style="width:100px" %)2|Reserved| | |
2042 +|(% style="width:107px" %)0x04|(% style="width:100px" %)4|Reserved| | |
2043 +|(% style="width:107px" %)0x06|(% style="width:100px" %)6|Ua|float|2|Phase Voltage data, Unit V
2044 +|(% style="width:107px" %)0x08|(% style="width:100px" %)8|Ub|float|2|Phase Voltage data, Unit V
2045 +|(% style="width:107px" %)0x0A|(% style="width:100px" %)10|Uc|float|2|Phase Voltage data, Unit V
2046 +|(% style="width:107px" %)0x0C|(% style="width:100px" %)12|Uab|float|2|Line Voltage data, Unit V
2047 +|(% style="width:107px" %)0x0E|(% style="width:100px" %)14|Ubc|float|2|Line Voltage data, Unit V
2048 +|(% style="width:107px" %)0x10|(% style="width:100px" %)16|Uca|float|2|Line Voltage data, Unit V
2049 +|(% style="width:107px" %)0x12|(% style="width:100px" %)18|Ia|float|2|Phase Current data, Unit A
2050 +|(% style="width:107px" %)0x14|(% style="width:100px" %)20|Ib|float|2|Phase Current data, Unit A
2051 +|(% style="width:107px" %)0x16|(% style="width:100px" %)22|Ic|float|2|Phase Current data, Unit A
2052 +
2053 +
2054 +
2032 2032  == **MODBUS RTU Master** ==
2033 2033  
2034 2034  Select the protocol "Modbus RTU Master",