Changes for page 1 Communication

Last modified by Hunter on 2024/07/01 10:54

From version 223.1
edited by Hunter
on 2023/03/23 14:57
Change comment: There is no comment for this version
To version 224.2
edited by Hunter
on 2023/03/23 17:20
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -2050,8 +2050,15 @@
2050 2050  |(% style="width:107px" %)0x14|(% style="width:100px" %)20|Ib|float|2|(% style="width:318px" %)Phase Current data, Unit A
2051 2051  |(% style="width:107px" %)0x16|(% style="width:100px" %)22|Ic|float|2|(% style="width:318px" %)Phase Current data, Unit A
2052 2052  
2053 -
2053 +{{info}}
2054 +**✎Note: **We usually use the Data Type 4 for read the Modbus registers(Function Code 03)
2055 +{{/info}}
2054 2054  
2057 +For example, here we want to read the Phase Voltage Ua (Modbus offset 0006), so the tag configured like the following screenshot:
2058 +
2059 +(% style="text-align:center" %)
2060 +[[image:VNETModbusTagSettings.png]]
2061 +
2055 2055  == **MODBUS RTU Master** ==
2056 2056  
2057 2057  Select the protocol "Modbus RTU Master",
VNETModbusTagSettings.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +35.7 KB
Content