... ... @@ -520,7 +520,7 @@
520 520  The above are all the steps for establishing Ethernet communication between Wecon V-box with CompactLogix L1769 PLC.
521 521  
522 522  
523 -= **Micro850_FreeTag Protocol(new)** =
523 +== **Micro850_FreeTag Protocol(new)** ==
524 524  
525 525  This example introduces the establishment of Ethernet communication between Wecon V-box and 2080-LC50-48QWB,Micro850. It is introduced through three parts: PLC software configuration, V-box software configuration.
526 526  
... ... @@ -582,7 +582,7 @@
582 582  (% style="text-align:center" %)
583 583  [[image:V-NET_Client_communication.png]]
584 584  
585 -Export variables from PLC, select CSV file, comma delimited. After adding the protocol Allen-BradleyMicro850_FreeTag, click[[image:https://docs.we-con.com.cn/bin/download/V-BOX/V-Net/Training/1%20Communication/WebHome/image-20220714143838-2.png?rev=1.1||alt="image-20220714143838-2.png"]]icon add label.
585 +Export variables from PLC, select CSV file, comma delimited.(% id="cke_bm_1950S" style="display:none" %)
586 586  
587 587  (% style="text-align:center" %)
588 588  [[image:export1.png]]
... ... @@ -590,8 +590,10 @@
590 590  (% style="text-align:center" %)
591 591  [[image:CCW.Shell_E5Cwj4tUL3.png]]
592 592  
593 +After adding the protocol Allen-BradleyMicro850_FreeTag, click[[image:https://docs.we-con.com.cn/bin/download/V-BOX/V-Net/Training/1%20Communication/WebHome/image-20220714143838-2.png?rev=1.1||alt="image-20220714143838-2.png"]]icon add label.
594 +
593 593  (% style="text-align:center" %)
594 -[[image:V-NET_Client_iKKKhcgxm1.png]]
596 +[[image:V-NET_Client_TNBuqy7T5r.png]]
595 595  
596 596  **3)Engineering production**
597 597  
... ... @@ -661,6 +661,100 @@
661 661  **✎Note: **As the wiring diagram indicated, this protocol requires the DB9 serial port pin 4. But pin 4 is undefined for all V-Box, so it need the user to solder a Pull-up resistor to make the pin 4 working. As for how to solder the resistor on the motherboard, please contact with Wecon technical support for the details.
662 662  {{/info}}
663 663  
666 += Create communication with EMERSON PLC =
667 +
668 +== **RTU Slave Protocol** ==
669 +
670 +Supported series: EC10 series
671 +
672 +**1)V-BOX setting**
673 +
674 +|**Items**|**Settings**|**Note**
675 +|Protocol|Emerson 984 RTU Slave MODBUS|
676 +|Connection|RS485|
677 +|Baud rate|19200|
678 +|Data bit|8|
679 +|Parity|EVEN|
680 +|Stop bit|1|
681 +|Device station No.|1|Need to be same as the PLC setting
682 +
683 +(% class="wikigeneratedid" %)
684 +**2)PLC Setting**
685 +
686 +(% class="wikigeneratedid" %)
687 +Remember to use the Control Star to enable the Modbus RTU communication for port 1 in system block before dowload into PLC.
688 +
689 +(% style="text-align:center" %)
690 +[[image:ControlStarSystemBlock.png]]
691 +
692 +(% style="text-align:center" %)
693 +[[image:ControlStarCommunicate.png]]
694 +
695 +(% style="text-align:center" %)
696 +[[image:ControlStarModbus.png]]
697 +
698 +(% class="wikigeneratedid" %)
699 +**3)Address List**
700 +
701 +|**Type**|**Device registers**|**Format**|**Range**|**Note**
702 +|(% colspan="1" rowspan="12" %)Bit|Y|YOOO|0~~377|
703 +|X|XOOO|0~~377|
704 +|M0|M0DDDD|0~~2047|
705 +|M1|M1DDDDD|2048~~10239|
706 +|SM0|SM0DDD|0~~255|
707 +|SM1|SM1DDD|256~~511|
708 +|S0|S0DDDD|0~~1023|
709 +|S1|S1DDDD|1024~~4095|
710 +|T0|T0DDD|0~~255|
711 +|T1|T1DDD|256~~511|
712 +|C0|C0DDD|0~~255|
713 +|C1|C1DDD|256~~306|
714 +|(% colspan="1" rowspan="7" %)Word|D|DDDDD|0~~7999|
715 +|Z|ZDD|0~~15|
716 +|TW0|TW0DDD|0~~255|
717 +|TW1|TW1DDD|256~~511|
718 +|SD0|SD0DDD|0~~255|
719 +|SD1|SD1DDD|256~~511|
720 +|CW|CWDDD|0~~306|
721 +|(% colspan="1" rowspan="2" %)Double Word|CW0|CW0DDD|200~~255|
722 +|CW1|CW1DDDDD|256~~99999|
723 +
724 +**4) Cable Wiring**
725 +
726 +(% style="text-align:center" %)
727 +[[image:Emerson.png]]
728 +
729 += Create communication with HollySys PLC =
730 +
731 +== **LK Modbus RTU** ==
732 +
733 +**1)V-BOX setting**
734 +
735 +|**Items**|**Settings**|**Note**
736 +|Protocol|HollySys LK Modbus RTU|
737 +|Connection|RS485|
738 +|Baud rate|38400|
739 +|Data bit|8|
740 +|Parity|None|
741 +|Stop bit|1|
742 +|Device station No.|1|
743 +
744 +**2)Address List**
745 +
746 +|=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note**
747 +|Bit|QX|QXDDDDD.dd|0~~65535.15|
748 +|Bit|IX|IXDDDDD.dd|0~~65535.15|
749 +|Bit|MX|MXDDDDD.dd|0~~65535.15|
750 +|Word|QW|QWDDDDD|0~~99999|
751 +|Word|IW|IWDDDDD|0~~99999|
752 +|Word|MW|MWDDDDD|0~~99999|
753 +|Word|MD|MDDDDDD|0~~99999|
754 +
755 +**3)Cable Wiring**
756 +
757 +(% style="text-align:center" %)
758 +[[image:Hollysys485-2.png]]
759 +
664 664  = Create communication with **Siemens PLC** =
665 665  
666 666  == **S7-200 Smart Ethernet Protocol** ==
ControlStarCommunicate.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +26.0 KB
Content
ControlStarModbus.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +24.9 KB
Content
ControlStarSystemBlock.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +46.3 KB
Content
Emerson.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +13.7 KB
Content
Hollysys485-2.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +13.5 KB
Content
Hollysys485box.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +13.4 KB