Changes for page 1 Communication

Last modified by Hunter on 2024/07/01 10:54

From version 235.1
edited by Hunter
on 2023/05/06 14:31
Change comment: There is no comment for this version
To version 241.1
edited by Hunter
on 2023/05/19 18:15
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -663,9 +663,102 @@
663 663  **✎Note: **As the wiring diagram indicated, this protocol requires the DB9 serial port pin 4. But pin 4 is undefined for all V-Box, so it need the user to solder a Pull-up resistor to make the pin 4 working. As for how to solder the resistor on the motherboard, please contact with Wecon technical support for the details.
664 664  {{/info}}
665 665  
666 -= Create communication with **EMERSON PLC** =
666 += Create communication with EMERSON PLC =
667 667  
668 +== **RTU Slave Protocol** ==
668 668  
670 +Supported series: EC10 series
671 +
672 +**1)V-BOX setting**
673 +
674 +|**Items**|**Settings**|**Note**
675 +|Protocol|Emerson 984 RTU Slave MODBUS|
676 +|Connection|RS485|
677 +|Baud rate|19200|
678 +|Data bit|8|
679 +|Parity|EVEN|
680 +|Stop bit|1|
681 +|Device station No.|1|Need to be same as the PLC setting
682 +
683 +(% class="wikigeneratedid" %)
684 +**2)PLC Setting**
685 +
686 +(% class="wikigeneratedid" %)
687 +Remember to use the Control Star to enable the Modbus RTU communication for port 1 in system block before dowload into PLC.
688 +
689 +(% style="text-align:center" %)
690 +[[image:ControlStarSystemBlock.png]]
691 +
692 +(% style="text-align:center" %)
693 +[[image:ControlStarCommunicate.png]]
694 +
695 +(% style="text-align:center" %)
696 +[[image:ControlStarModbus.png]]
697 +
698 +(% class="wikigeneratedid" %)
699 +**3)Address List**
700 +
701 +|**Type**|**Device registers**|**Format**|**Range**|**Note**
702 +|(% colspan="1" rowspan="12" %)Bit|Y|YOOO|0~~377|
703 +|X|XOOO|0~~377|
704 +|M0|M0DDDD|0~~2047|
705 +|M1|M1DDDDD|2048~~10239|
706 +|SM0|SM0DDD|0~~255|
707 +|SM1|SM1DDD|256~~511|
708 +|S0|S0DDDD|0~~1023|
709 +|S1|S1DDDD|1024~~4095|
710 +|T0|T0DDD|0~~255|
711 +|T1|T1DDD|256~~511|
712 +|C0|C0DDD|0~~255|
713 +|C1|C1DDD|256~~306|
714 +|(% colspan="1" rowspan="7" %)Word|D|DDDDD|0~~7999|
715 +|Z|ZDD|0~~15|
716 +|TW0|TW0DDD|0~~255|
717 +|TW1|TW1DDD|256~~511|
718 +|SD0|SD0DDD|0~~255|
719 +|SD1|SD1DDD|256~~511|
720 +|CW|CWDDD|0~~306|
721 +|(% colspan="1" rowspan="2" %)Double Word|CW0|CW0DDD|200~~255|
722 +|CW1|CW1DDDDD|256~~99999|
723 +
724 +**4) Cable Wiring**
725 +
726 +(% style="text-align:center" %)
727 +[[image:Emerson.png]]
728 +
729 += Create communication with HollySys PLC =
730 +
731 +== **LK Modbus RTU** ==
732 +
733 +Supported Series: HollySys LK series PLC
734 +
735 +**1)V-BOX setting**
736 +
737 +|**Items**|**Settings**|**Note**
738 +|Protocol|HollySys LK Modbus RTU|
739 +|Connection|RS485|
740 +|Baud rate|38400|
741 +|Data bit|8|
742 +|Parity|None|
743 +|Stop bit|1|
744 +|Device station No.|1|
745 +
746 +**2)Address List**
747 +
748 +|=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note**
749 +|Bit|QX|QXDDDDD.dd|0~~65535.15|
750 +|Bit|IX|IXDDDDD.dd|0~~65535.15|
751 +|Bit|MX|MXDDDDD.dd|0~~65535.15|
752 +|Word|QW|QWDDDDD|0~~99999|
753 +|Word|IW|IWDDDDD|0~~99999|
754 +|Word|MW|MWDDDDD|0~~99999|
755 +|Word|MD|MDDDDDD|0~~99999|
756 +
757 +**3)Cable Wiring**
758 +
759 +(% style="text-align:center" %)
760 +[[image:Hollysys485-2.png]]
761 +
669 669  = Create communication with **Siemens PLC** =
670 670  
671 671  == **S7-200 Smart Ethernet Protocol** ==
ControlStarCommunicate.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +26.0 KB
Content
ControlStarModbus.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +24.9 KB
Content
ControlStarSystemBlock.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +46.3 KB
Content
Emerson.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +13.7 KB
Content
Hollysys485-2.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +13.5 KB
Content
Hollysys485box.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +13.4 KB
Content