665 665  
666 666  = Create communication with EMERSON PLC =
667 667  
668 -== **RTU Slave Protocol** ==
669 669  
670 -Supported series: EC10 series
671 -
672 -**1)V-BOX setting**
673 -
674 -|**Items**|**Settings**|**Note**
675 -|Protocol|Emerson 984 RTU Slave MODBUS|
676 -|Connection|RS485|
677 -|Baud rate|19200|
678 -|Data bit|8|
679 -|Parity|EVEN|
680 -|Stop bit|1|
681 -|Device station No.|1|Need to be same as the PLC setting
682 -
683 -(% class="wikigeneratedid" %)
684 -**2)PLC Setting**
685 -
686 -(% class="wikigeneratedid" %)
687 -Remember to use the Control Star to enable the Modbus RTU communication for port 1 in system block before dowload into PLC.
688 -
689 -(% style="text-align:center" %)
690 -[[image:ControlStarSystemBlock.png]]
691 -
692 -(% style="text-align:center" %)
693 -[[image:ControlStarCommunicate.png]]
694 -
695 -(% style="text-align:center" %)
696 -[[image:ControlStarModbus.png]]
697 -
698 -(% class="wikigeneratedid" %)
699 -**3)Address List**
700 -
701 -|**Type**|**Device registers**|**Format**|**Range**|**Note**
702 -|(% colspan="1" rowspan="12" %)Bit|Y|YOOO|0~~377|
703 -|X|XOOO|0~~377|
704 -|M0|M0DDDD|0~~2047|
705 -|M1|M1DDDDD|2048~~10239|
706 -|SM0|SM0DDD|0~~255|
707 -|SM1|SM1DDD|256~~511|
708 -|S0|S0DDDD|0~~1023|
709 -|S1|S1DDDD|1024~~4095|
710 -|T0|T0DDD|0~~255|
711 -|T1|T1DDD|256~~511|
712 -|C0|C0DDD|0~~255|
713 -|C1|C1DDD|256~~306|
714 -|(% colspan="1" rowspan="7" %)Word|D|DDDDD|0~~7999|
715 -|Z|ZDD|0~~15|
716 -|TW0|TW0DDD|0~~255|
717 -|TW1|TW1DDD|256~~511|
718 -|SD0|SD0DDD|0~~255|
719 -|SD1|SD1DDD|256~~511|
720 -|CW|CWDDD|0~~306|
721 -|(% colspan="1" rowspan="2" %)Double Word|CW0|CW0DDD|200~~255|
722 -|CW1|CW1DDDDD|256~~99999|
723 -
724 -**4) Cable Wiring**
725 -
726 -(% style="text-align:center" %)
727 -[[image:Emerson.png]]
728 -
729 -= Create communication with HollySys PLC =
730 -
731 -== **LK Modbus RTU** ==
732 -
733 -**1)V-BOX setting**
734 -
735 -|**Items**|**Settings**|**Note**
736 -|Protocol|HollySys LK Modbus RTU|
737 -|Connection|RS485|
738 -|Baud rate|38400|
739 -|Data bit|8|
740 -|Parity|None|
741 -|Stop bit|1|
742 -|Device station No.|1|
743 -
744 -**2)Address List**
745 -
746 -|=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note**
747 -|Bit|QX|QXDDDDD.dd|0~~65535.15|
748 -|Bit|IX|IXDDDDD.dd|0~~65535.15|
749 -|Bit|MX|MXDDDDD.dd|0~~65535.15|
750 -|Word|QW|QWDDDDD|0~~99999|
751 -|Word|IW|IWDDDDD|0~~99999|
752 -|Word|MW|MWDDDDD|0~~99999|
753 -|Word|MD|MDDDDDD|0~~99999|
754 -
755 -**3)Cable Wiring**
756 -
757 -(% style="text-align:center" %)
758 -[[image:Hollysys485-2.png]]
759 -
760 760  = Create communication with **Siemens PLC** =
761 761  
762 762  == **S7-200 Smart Ethernet Protocol** ==
ControlStarCommunicate.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Hunter
Size
... ... @@ -1,1 +1,0 @@
1 -26.0 KB
Content
ControlStarModbus.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Hunter
Size
... ... @@ -1,1 +1,0 @@
1 -24.9 KB
Content
ControlStarSystemBlock.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Hunter
Size
... ... @@ -1,1 +1,0 @@
1 -46.3 KB
Content
Emerson.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Hunter
Size
... ... @@ -1,1 +1,0 @@
1 -13.7 KB
Content
Hollysys485-2.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Hunter
Size
... ... @@ -1,1 +1,0 @@
1 -13.5 KB
Content
Hollysys485box.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Hunter
Size
... ... @@ -1,1 +1,0 @@
1 -13.4 KB
Content