Changes for page 1 Communication

Last modified by Hunter on 2024/07/01 10:54

From version 246.1
edited by Hunter
on 2023/07/05 11:37
Change comment: There is no comment for this version
To version 251.1
edited by Theodore Xu
on 2023/07/10 11:34
Change comment: There is no comment for this version

Summary

Details

Page properties
Author
... ... @@ -1,1 +1,1 @@
1 -XWiki.Hunter
1 +XWiki.AiXia
Content
... ... @@ -759,6 +759,46 @@
759 759  (% style="text-align:center" %)
760 760  [[image:Hollysys485-2.png]]
761 761  
762 +== **LM Modbus RTU** ==
763 +
764 +(% class="wikigeneratedid" %)
765 +Supported Series: HollySys LM3109/LM3107 PLC
766 +
767 +(% class="wikigeneratedid" %)
768 +**1)V-BOX setting**
769 +
770 +|(% style="width:208px" %)**Items**|(% style="width:310px" %)**Settings**|(% style="width:365px" %)**Optional**|(% style="width:152px" %)**Note**
771 +|(% style="width:208px" %)Protocol|(% style="width:310px" %)HollySys LM Modbus RTU|(% style="width:365px" %)HollySys LM Modbus RTU|(% style="width:152px" %)
772 +|(% style="width:208px" %)Connection|(% style="width:310px" %)RS232|(% style="width:365px" %)RS485|(% style="width:152px" %)
773 +|(% style="width:208px" %)Baud rate|(% style="width:310px" %)38400|(% style="width:365px" %)38400|(% style="width:152px" %)
774 +|(% style="width:208px" %)Data bit|(% style="width:310px" %)8|(% style="width:365px" %)8|(% style="width:152px" %)
775 +|(% style="width:208px" %)Parity|(% style="width:310px" %)None|(% style="width:365px" %)None|(% style="width:152px" %)
776 +|(% style="width:208px" %)Stop bit|(% style="width:310px" %)1|(% style="width:365px" %)1|(% style="width:152px" %)
777 +|(% style="width:208px" %)Device station No.|(% style="width:310px" %)1|(% style="width:365px" %)1|(% style="width:152px" %)
778 +
779 +**2)Address List**
780 +
781 +|=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note**
782 +|Bit|QX|QXDDDDD.o|0~~99999.7|
783 +|Bit|IX|IXDDDDD.o|0~~99999.7|
784 +|Bit|MX|MXDDDDD.o|0~~99999.7|
785 +|Word|QW|QWDDDDD|0~~99999|
786 +|Word|IW|IWDDDDD|0~~99999|
787 +|Word|MW|MWDDDDD|0~~99999|
788 +|Word|MD|MDDDDDD|0~~99999|
789 +
790 +**Cable Wiring**
791 +
792 +RS232
793 +
794 +(% style="text-align:center" %)
795 +[[image:HollySysRS232.png]]
796 +
797 +RS485
798 +
799 +(% style="text-align:center" %)
800 +[[image:Hollysys LM Modbus RTU.gif]]
801 +
762 762  = Create communication with **Siemens PLC** =
763 763  
764 764  == **S7-200 Smart Ethernet Protocol** ==
... ... @@ -2167,6 +2167,37 @@
2167 2167  
2168 2168  [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2169 2169  
2210 += Create communication with INVT PLC =
2211 +
2212 +**1)V-BOX setting**
2213 +
2214 +|**Item**|**Settings**|**Note**
2215 +|Protocol|INVT_IVC2L|
2216 +|Connection|RS232|
2217 +|Baud rate|19200|
2218 +|Data bit|7|
2219 +|Parity|EVEN|
2220 +|Stop bit|1|
2221 +|PLC station No.|1
2222 +
2223 +**2)Address List**
2224 +
2225 +
2226 +|**Type**|**Device registers**|**Format**|**Range**|**Note**
2227 +|(% colspan="1" rowspan="7" %)Bit|X|XOOO|0~~377|
2228 +|Y|YOOO|0~~377|
2229 +|M|MDDDD|0~~1999|
2230 +|SM|SMDDD|0~~255|
2231 +|S|SDDD|0~~991|
2232 +|T|TDDD|0~~255|
2233 +|C|CDDD|0~~255|
2234 +|(% rowspan="5" %)Word|D|DDDDD|0~~7999|
2235 +|SD|SDDDD|0~~255|
2236 +|Z|ZDD|0~~15|
2237 +|T|TDDD|0~~255|
2238 +|C|CDDD|0~~199|
2239 +|Double word|C|CDDD|200~~255|
2240 +
2170 2170  = Create communication with **Modbus ** =
2171 2171  
2172 2172  == **MODBUS RTU Slave (All function)** ==
HollySysRS232.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +10.4 KB
Content
Hollysys LM Modbus RTU.gif
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +7.1 KB
Content