... ... @@ -1,3 +1,11 @@
1 +{{info}}
2 +✎Note: Communication Connection Description
3 +
4 +* Modbus TCP:Maximum 16 devices
5 +* Modbus RTU:Maximum 32 devices
6 +* Ethernet protocol:Maximum 16 devices
7 +{{/info}}
8 +
1 1  = Create communication with WECON PLC =
2 2  
3 3  == **LX3V Serial Protocol** ==
... ... @@ -759,6 +759,46 @@
759 759  (% style="text-align:center" %)
760 760  [[image:Hollysys485-2.png]]
761 761  
770 +== **LM Modbus RTU** ==
771 +
772 +(% class="wikigeneratedid" %)
773 +Supported Series: HollySys LM3109/LM3107 PLC
774 +
775 +(% class="wikigeneratedid" %)
776 +**1)V-BOX setting**
777 +
778 +|(% style="width:208px" %)**Items**|(% style="width:310px" %)**Settings**|(% style="width:365px" %)**Optional**|(% style="width:152px" %)**Note**
779 +|(% style="width:208px" %)Protocol|(% style="width:310px" %)HollySys LM Modbus RTU|(% style="width:365px" %)HollySys LM Modbus RTU|(% style="width:152px" %)
780 +|(% style="width:208px" %)Connection|(% style="width:310px" %)RS232|(% style="width:365px" %)RS485|(% style="width:152px" %)
781 +|(% style="width:208px" %)Baud rate|(% style="width:310px" %)38400|(% style="width:365px" %)38400|(% style="width:152px" %)
782 +|(% style="width:208px" %)Data bit|(% style="width:310px" %)8|(% style="width:365px" %)8|(% style="width:152px" %)
783 +|(% style="width:208px" %)Parity|(% style="width:310px" %)None|(% style="width:365px" %)None|(% style="width:152px" %)
784 +|(% style="width:208px" %)Stop bit|(% style="width:310px" %)1|(% style="width:365px" %)1|(% style="width:152px" %)
785 +|(% style="width:208px" %)Device station No.|(% style="width:310px" %)1|(% style="width:365px" %)1|(% style="width:152px" %)
786 +
787 +**2)Address List**
788 +
789 +|=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note**
790 +|Bit|QX|QXDDDDD.o|0~~99999.7|
791 +|Bit|IX|IXDDDDD.o|0~~99999.7|
792 +|Bit|MX|MXDDDDD.o|0~~99999.7|
793 +|Word|QW|QWDDDDD|0~~99999|
794 +|Word|IW|IWDDDDD|0~~99999|
795 +|Word|MW|MWDDDDD|0~~99999|
796 +|Word|MD|MDDDDDD|0~~99999|
797 +
798 +**Cable Wiring**
799 +
800 +RS232
801 +
802 +(% style="text-align:center" %)
803 +[[image:HollySysRS232.png]]
804 +
805 +RS485
806 +
807 +(% style="text-align:center" %)
808 +[[image:Hollysys LM Modbus RTU.gif]]
809 +
762 762  = Create communication with **Siemens PLC** =
763 763  
764 764  == **S7-200 Smart Ethernet Protocol** ==
... ... @@ -2167,6 +2167,74 @@
2167 2167  
2168 2168  [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2169 2169  
2218 += Create communication with INVT PLC =
2219 +
2220 +**1)V-BOX setting**
2221 +
2222 +|**Item**|**Settings**|**Note**
2223 +|Protocol|INVT_IVC2L|
2224 +|Connection|RS232|
2225 +|Baud rate|19200|
2226 +|Data bit|8|
2227 +|Parity|EVEN|
2228 +|Stop bit|1|
2229 +|PLC station No.|1
2230 +
2231 +**2)Address List**
2232 +
2233 +
2234 +|**Type**|**Device registers**|**Format**|**Range**|**Note**
2235 +|(% colspan="1" rowspan="7" %)Bit|X|XOOO|0~~377|
2236 +|Y|YOOO|0~~377|
2237 +|M|MDDDD|0~~1999|
2238 +|SM|SMDDD|0~~255|
2239 +|S|SDDD|0~~991|
2240 +|T|TDDD|0~~255|
2241 +|C|CDDD|0~~255|
2242 +|(% rowspan="5" %)Word|D|DDDDD|0~~7999|
2243 +|SD|SDDDD|0~~255|
2244 +|Z|ZDD|0~~15|
2245 +|T|TDDD|0~~255|
2246 +|C|CDDD|0~~199|
2247 +|Double word|C|CDDD|200~~255|
2248 +
2249 +**3)Communication Settings**
2250 +
2251 +(% style="text-align:center" %)
2252 +[[image:盒子创建英威腾.png]]
2253 +
2254 +**4)PLC software**
2255 +
2256 +(% style="text-align:center" %)
2257 +[[image:英威腾软件.png]]
2258 +
2259 +**5)PLC setting **
2260 +
2261 +Open the INVI plc software, create a new project or open a project that has already been created
2262 +
2263 +(% style="text-align:center" %)
2264 +[[image:英威腾创建1.png]]
2265 +
2266 +Configure serial port parameters.
2267 +
2268 +(% style="text-align:center" %)
2269 +[[image:英威腾创建2.png]]
2270 +
2271 +PC connect PLC
2272 +
2273 +(% style="text-align:center" %)
2274 +[[image:英威腾创建3.png]]
2275 +
2276 +Download
2277 +
2278 +(% style="text-align:center" %)
2279 +[[image:英威腾下载.png]]
2280 +
2281 +**6)Cable Wiring**
2282 +
2283 +(% style="text-align:center" %)
2284 +[[image:wire.png]]
2285 +
2170 2170  = Create communication with **Modbus ** =
2171 2171  
2172 2172  == **MODBUS RTU Slave (All function)** ==
HollySysRS232.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +10.4 KB
Content
Hollysys LM Modbus RTU.gif
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +7.1 KB
Content
plc 软件.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.AiXia
Size
... ... @@ -1,0 +1,1 @@
1 +106.8 KB
Content
wire.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.AiXia
Size
... ... @@ -1,0 +1,1 @@
1 +137.2 KB
Content
企业微信截图_16889606174191.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.AiXia
Size
... ... @@ -1,0 +1,1 @@
1 +20.7 KB
Content
盒子创建英威腾.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.AiXia
Size
... ... @@ -1,0 +1,1 @@
1 +86.5 KB
Content
英威腾下载.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.AiXia
Size
... ... @@ -1,0 +1,1 @@
1 +49.0 KB
Content
英威腾创建1.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.AiXia
Size
... ... @@ -1,0 +1,1 @@
1 +36.7 KB
Content
英威腾创建2.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.AiXia
Size
... ... @@ -1,0 +1,1 @@
1 +115.7 KB
Content
英威腾创建3.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.AiXia
Size
... ... @@ -1,0 +1,1 @@
1 +76.6 KB
Content
英威腾软件.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.AiXia
Size
... ... @@ -1,0 +1,1 @@
1 +52.6 KB
Content