... ... @@ -1,15 +1,7 @@
1 -{{info}}
2 -✎Note: Communication Connection Description
1 += WECON =
3 3  
4 -* Modbus TCP: Maximum 16 devices
5 -* Modbus RTU: Maximum 32 devices
6 -* Ethernet Protocol: Maximum 16 devices
7 -{{/info}}
3 +== **LX3V Serial ** ==
8 8  
9 -= Create communication with WECON PLC =
10 -
11 -== **LX3V Serial Protocol** ==
12 -
13 13  Supported series: Wecon LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
14 14  
15 15  **1)V-BOX setting**
... ... @@ -56,7 +56,7 @@
56 56  
57 57   [[image:image-20220824120524-3.png]]
58 58  
59 -== **LX5V Serial Protocol** ==
51 +== **LX5V Serial ** ==
60 60  
61 61  This example introduces the establishment of serial port communication between V-BOX and LX5V. It is introduced through three parts: PLC software configuration, V-BOX software configuration, and hardware wiring.
62 62  
... ... @@ -126,7 +126,7 @@
126 126  
127 127  The above are all the steps for establishing serial port communication between V-BOX with LX5V PLC.
128 128  
129 -== **LX5V-N Ethernet protocol** ==
121 +== **LX5V-N Ethernet ** ==
130 130  
131 131  This example introduces the establishment of Ethernet communication between V-BOX and LX5V-N. It is introduced through three parts: PLC software configuration, V-BOX software configuration, and hardware wiring.
132 132  
... ... @@ -184,9 +184,9 @@
184 184  
185 185  The above are all the steps for establishing ethernet communication between V-BOX with LX5V PLC.
186 186  
187 -= Create communication with Allen-Bradley(**Rockwell**)** PLC** =
179 += Allen-Bradley(**Rockwell**) =
188 188  
189 -== **DF1 Advanced Protocol** ==
181 +== **DF1 Advanced  Serial** ==
190 190  
191 191  MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
192 192  
... ... @@ -285,7 +285,7 @@
285 285  (% class="wikigeneratedid" id="HMicroLogixA0Protocol" %)
286 286  (% id="cke_bm_5621S" style="display:none" %)** **
287 287  
288 -== **MicroLogix Protocol** ==
280 +== **MicroLogix Serial** ==
289 289  
290 290  (% class="wikigeneratedid" %)
291 291  MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
... ... @@ -325,7 +325,7 @@
325 325  
326 326  [[image:image-20220824110724-1.png]]
327 327  
328 -== **Micro850_FreeTag Protocol** ==
320 +== **Micro850_FreeTag Ethernet** ==
329 329  
330 330  (((
331 331  (((
... ... @@ -528,7 +528,7 @@
528 528  The above are all the steps for establishing Ethernet communication between Wecon V-box with CompactLogix L1769 PLC.
529 529  
530 530  
531 -== **Micro850_FreeTag Protocol(new)** ==
523 +== **Micro850_FreeTag Ethernet(new)** ==
532 532  
533 533  This example introduces the establishment of Ethernet communication between Wecon V-box and 2080-LC50-48QWB,Micro850. It is introduced through three parts: PLC software configuration, V-box software configuration.
534 534  
... ... @@ -671,9 +671,9 @@
671 671  **✎Note: **As the wiring diagram indicated, this protocol requires the DB9 serial port pin 4. But pin 4 is undefined for all V-Box, so it need the user to solder a Pull-up resistor to make the pin 4 working. As for how to solder the resistor on the motherboard, please contact with Wecon technical support for the details.
672 672  {{/info}}
673 673  
674 -= Create communication with EMERSON PLC =
666 += EMERSON =
675 675  
676 -= **RTU Slave Protocol** =
668 += **RTU Slave ** =
677 677  
678 678  Supported series: EC10 series
679 679  
... ... @@ -734,9 +734,9 @@
734 734  (% style="text-align:center" %)
735 735  [[image:Emerson.png]]
736 736  
737 -= Create communication with HollySys PLC =
729 += HollySys PLC =
738 738  
739 -== **LK Modbus RTU** ==
731 +== **LK Modbus RTU ** ==
740 740  
741 741  Supported Series: HollySys LK series PLC
742 742  
... ... @@ -807,15 +807,14 @@
807 807  (% style="text-align:center" %)
808 808  [[image:Hollysys LM Modbus RTU.gif]]
809 809  
810 -= Create communication with **Siemens PLC** =
802 += **Siemens ** =
811 811  
812 -== **S7-200 Smart Ethernet Protocol** ==
804 +== **S7-200 Smart Ethernet ** ==
813 813  
814 814  [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20S7-200%20Smart.zip]]
815 815  
808 +== **S7-300 Ethernet ** ==
816 816  
817 -== **S7-300 Ethernet Protocol** ==
818 -
819 819  Supported Series: Siemens S7-300 series PLC
820 820  
821 821  **1)V-BOX setting**
... ... @@ -872,11 +872,11 @@
872 872  )))
873 873  )))
874 874  
875 -== **S7-1200 Ethernet Protocol** ==
866 +== **S7-1200 Ethernet ** ==
876 876  
877 877  [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]]
878 878  
879 -== **S7-XXX Ethernet Protocol** ==
870 +== **S7-XXX Ethernet l** ==
880 880  
881 881  Supported Series: Siemens S7-400, S7-1200 and S7-1500
882 882  
... ... @@ -990,7 +990,7 @@
990 990  
991 991  [[image:image-20220824162342-2.png]]
992 992  
993 -== **LOGO Ethernet Protocol** ==
984 +== **LOGO Ethernet ** ==
994 994  
995 995  Supported Series: Siemens Logo 0BA0, 0BA1 series
996 996  
... ... @@ -1081,9 +1081,9 @@
1081 1081  ** Register VD: Use only registers that are multiples of 4, such as 0, 4, 8, etc.
1082 1082  ** Register VW: Use only registers thay are multiples of 2, such as 0, 2, 4 etc. (Using an odd-length register may result in data errors, such as 2 3 4 )
1083 1083  
1084 -= Create communication with **Mitsubishi PLC** =
1075 += **Mitsubishi ** =
1085 1085  
1086 -== **FX1S,1N,2N Serial Protocol** ==
1077 +== **FX1S,1N,2N Serial ** ==
1087 1087  
1088 1088  Supported Series: Mitsubishi FX1S, FX1N, FX2N series
1089 1089  
... ... @@ -1130,7 +1130,7 @@
1130 1130  [[image:image-20220825100845-4.png]]
1131 1131  
1132 1132  
1133 -== **FX3U,3G,3GA Serial Protocol** ==
1124 +== **FX3U,3G,3GA Serial ** ==
1134 1134  
1135 1135  Supported Series: Mitsubishi FX3U, FX3G, FX3GA series
1136 1136  
... ... @@ -1177,7 +1177,7 @@
1177 1177  [[image:image-20220825100845-4.png]]
1178 1178  
1179 1179  
1180 -== **FX3U Ethernet Protocol** ==
1171 +== **FX3U Ethernet ** ==
1181 1181  
1182 1182  Supported Modules: FX3U-ENET-ADP, FX3U-ENET-L
1183 1183  
... ... @@ -1272,7 +1272,7 @@
1272 1272  
1273 1273  [[image:image-20221119101946-2.png||height="395" width="695"]]
1274 1274  
1275 -== **FX5U Serial Protocol** ==
1266 +== **FX5U Serial ** ==
1276 1276  
1277 1277  Mitsubishi FX5U series PLC
1278 1278  
... ... @@ -1354,7 +1354,7 @@
1354 1354  
1355 1355  [[image:image-20220825105533-3.png]]
1356 1356  
1357 -== **FX5U Ethernet Protocol** ==
1348 +== **FX5U Ethernet ** ==
1358 1358  
1359 1359  Mitsubishi FX5U series PLC
1360 1360  
... ... @@ -1430,7 +1430,7 @@
1430 1430  
1431 1431  [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1432 1432  
1433 -== **L02 Serial Protocol** ==
1424 +== **L02 Serial ** ==
1434 1434  
1435 1435  Mitsubishi L02 series CPU built-in serial port.
1436 1436  
... ... @@ -1490,7 +1490,7 @@
1490 1490  
1491 1491  [[image:image-20220825160820-4.png]]
1492 1492  
1493 -== **L02 Ethernet Protocol** ==
1484 +== **L02 Ethernet ** ==
1494 1494  
1495 1495  Mitsubishi L series CPU built-in Ethernet port.
1496 1496  
... ... @@ -1563,13 +1563,13 @@
1563 1563  
1564 1564  [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1565 1565  
1566 -== **Q12H Serial Protocol** ==
1557 +== **Q12H Serial ** ==
1567 1567  
1568 1568  This Demo shows V-BOX communicate with Q12H PLC by Q02H serial Protocol
1569 1569  
1570 1570  [[**Download link**>>https://ftp.we-con.com.cn/Download/WIKI/PI%20HMI/Demo/Communication/V-Box%20connect%20PLC%20Q12H.rar]]
1571 1571  
1572 -== **QJ71E71 Ethernet Protocol** ==
1563 +== **QJ71E71 Ethernet ** ==
1573 1573  
1574 1574  Mitsubishi QJ71E71 Ethernet communication module;
1575 1575  
... ... @@ -1644,9 +1644,9 @@
1644 1644  
1645 1645  [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png"]]
1646 1646  
1647 -= Create communication with **Delta PLC** =
1638 += **Delta** =
1648 1648  
1649 -== **DVP Ethernet Protocol** ==
1640 +== **DVP Ethernet** ==
1650 1650  
1651 1651  Supoort Series: DELTA DVP20/32/40/60ES200RE/200TE or any DVP models with built-in Ethernet port, DELTA DVPEN01-SL module
1652 1652  
... ... @@ -1711,7 +1711,7 @@
1711 1711  (% style="text-align:center" %)
1712 1712  [[image:DVPEthernetVNETPortocol.png]]
1713 1713  
1714 -== **DVP serial protocol** ==
1705 +== **DVP serial** ==
1715 1715  
1716 1716  Supoort Series: DELTA DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX
1717 1717  
... ... @@ -1747,7 +1747,7 @@
1747 1747  (% style="text-align:center" %)
1748 1748  [[image:Delta DVP PROTOCOLSerial232.png]]
1749 1749  
1750 -== **AS Ethernet Protocol** ==
1741 +== **AS Ethernet** ==
1751 1751  
1752 1752  **1)V-BOX Settings**
1753 1753  
... ... @@ -1792,19 +1792,18 @@
1792 1792  
1793 1793  [[image:image-20220831155157-3.png]]
1794 1794  
1795 -= Create communication with **Omron PLC** =
1786 += **Omron** =
1796 1796  
1797 -== **CP1 Series Protocol ** ==
1788 +== **CP1 Series** ==
1798 1798  
1799 -[[下载链接>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CP1%20Series.zip]]
1790 +[[Download>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CP1%20Series.zip]]
1800 1800  
1801 -== **CP2M Series Protocol** ==
1792 +== **CP2M Series** ==
1802 1802  
1803 -[[下载链接>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CJ2M.zip]]
1794 +[[Download>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CJ2M.zip]]
1804 1804  
1796 +== **EC55 Series ** ==
1805 1805  
1806 -== **EC55 Series Protocol** ==
1807 -
1808 1808  Supported device: EC55 temperature instrument
1809 1809  
1810 1810  **1)V-BOX Settings**
... ... @@ -1864,9 +1864,9 @@
1864 1864  * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
1865 1865  * [[image:image-20220831161356-1.png]]Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
1866 1866  
1867 -= Create communication with Xinje** PLC** =
1857 += Xinje =
1868 1868  
1869 -== **XC serial protocol** ==
1859 +== **XC serial** ==
1870 1870  
1871 1871  **1)V-BOX Settings**
1872 1872  
... ... @@ -1908,7 +1908,7 @@
1908 1908  
1909 1909  [[image:image-20220831163441-4.png]]
1910 1910  
1911 -== **XD serial protocol** ==
1901 +== **XD serial** ==
1912 1912  
1913 1913  **1)V-BOX Settings**
1914 1914  
... ... @@ -1982,7 +1982,7 @@
1982 1982  
1983 1983  [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830160232-3.png?rev=1.1||alt="image-20220830160232-3.png"]]
1984 1984  
1985 -= Create communication with **Schneider PLC** =
1975 += **Schneider** =
1986 1986  
1987 1987  == **Schneider MODBUS RTU** ==
1988 1988  
... ... @@ -2016,7 +2016,7 @@
2016 2016  
2017 2017  [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220817154212-1.jpeg?width=554&height=315&rev=1.1||alt="image-20220817154212-1.jpeg" height="315" width="554"]]
2018 2018  
2019 -= Create communication with Inovance** PLC** =
2009 += Inovance =
2020 2020  
2021 2021  == **H3U serial protocol** ==
2022 2022  
... ... @@ -2068,9 +2068,9 @@
2068 2068  
2069 2069  [[image:image-20220831164731-4.png]]
2070 2070  
2071 -= Create communication with Panasonic** PLC** =
2061 += Panasonic =
2072 2072  
2073 -== **FP serial protocol** ==
2063 +== **FP serial** ==
2074 2074  
2075 2075  **1)V-BOX Settings**
2076 2076  
... ... @@ -2118,9 +2118,9 @@
2118 2118  
2119 2119  [[image:image-20220831165008-1.png]]
2120 2120  
2121 -= Create communication with LS** PLC** =
2111 += LS =
2122 2122  
2123 -== **XBC serial protocol** ==
2113 +== **XBC serial** ==
2124 2124  
2125 2125  **1)V-BOX Settings**
2126 2126  
... ... @@ -2172,7 +2172,7 @@
2172 2172  
2173 2173  [[image:image-20220831170215-2.png]]
2174 2174  
2175 -== **XGK FEnet Ethernet protocol** ==
2165 +== **XGK FEnet Ethernet** ==
2176 2176  
2177 2177  Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
2178 2178  
... ... @@ -2215,7 +2215,7 @@
2215 2215  
2216 2216  [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2217 2217  
2218 -= Create communication with INVT PLC =
2208 += INVT =
2219 2219  
2220 2220  **1)V-BOX setting**
2221 2221  
... ... @@ -2283,7 +2283,7 @@
2283 2283  (% style="text-align:center" %)
2284 2284  [[image:wire.png]]
2285 2285  
2286 -= Create communication with **Modbus ** =
2276 += **Modbus ** =
2287 2287  
2288 2288  == **MODBUS RTU Slave (All function)** ==
2289 2289  
... ... @@ -2294,7 +2294,7 @@
2294 2294  (% style="text-align:center" %)
2295 2295  [[image:1624342015914-382.png||height="486" width="800" class="img-thumbnail"]]
2296 2296  
2297 -== **Communicate with Modbus Meter** ==
2287 +== **Modbus Meter** ==
2298 2298  
2299 2299  The following example is using the Linfee meter LNF96EY to demonstrate how to set up the Modbus communication.