1 -{{info}}
2 -✎Note: Communication Connection Description
3 -
4 -* Modbus TCP: Maximum 16 devices
5 -* Modbus RTU: Maximum 32 devices
6 -* Ethernet Protocol: Maximum 16 devices
7 -{{/info}}
8 -
9 -= Create communication with WECON PLC =
10 -
11 -== **LX3V Serial Protocol** ==
12 -
13 -Supported series: Wecon LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
14 -
15 -**1)V-BOX setting**
16 -
17 -|**Item**|**Settings**|**Note**
18 -|Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
19 -|Connection|RS422/RS485|
20 -|Baud rate|9600|
21 -|Data bit|7|
22 -|Parity|EVEN|
23 -|Stop bit|1|
24 -|PLC station No.|1|
25 -
26 -**2)Address List**
27 -
28 -
29 -|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
30 -|(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
31 -|Y|Y|Y o|0~~303237|
32 -|M|M|M d|0~~99999|
33 -|T|T|T d|0~~99999|
34 -|C|C|C d|0~~99999|
35 -|S|S|S d|0~~99999|
36 -|(% rowspan="8" %)Word|X|X|Xo|0~~303237|
37 -|Y|Y|Y o|0~~303237|
38 -|M|M|M d|0~~99999|
39 -|T|T|T d|0~~99999|
40 -|C|C|C d|0~~199|
41 -|D|D|D d|0~~7999|
42 -|S|S|S d|0~~99999|
43 -|SD|SD|SD d|8000~~9999|
44 -
45 -**3)Configure the communication protocol**
46 -
47 -[[image:image-20220824152217-1.png||alt="图片-20220824152217-1.png"]]
48 -
49 -**4)Cable Wiring**
50 -
51 -* **RS422**
52 -
53 - [[image:image-20220824120614-5.png]]
54 -
55 -* **RS485**
56 -
57 - [[image:image-20220824120524-3.png]]
58 -
59 -== **LX5V Serial Protocol** ==
60 -
61 -This example introduces the establishment of serial port communication between V-BOX and LX5V. It is introduced through three parts: PLC software configuration, V-BOX software configuration, and hardware wiring.
62 -
63 -**Software configuration of PLC**
64 -
65 -**1)PLC programming software**
66 -
67 -[[image:image-20220824142722-1.png]]
68 -
69 -**2)New PLC project**
70 -
71 -Click New Project and select the PLC model.
72 -
73 -[[image:image-20220822172623-2.png]]
74 -
75 -**3)Set Serial port parameters**
76 -
77 -Follow the steps below to configure Serial port parameters
78 -
79 -Baud rate:115200
80 -
81 -Data bit:8
82 -
83 -Stop bit:1
84 -
85 -Parity:No verification
86 -
87 -[[image:image-20220822172657-3.png]]
88 -
89 -**4)Registers list**
90 -
91 -[[image:image-20220822172730-4.png]]
92 -
93 -**V-BOX software configuration**
94 -
95 -**1)V-BOX programming software**
96 -
97 - [[image:image-20220824104124-1.png]]
98 -
99 -**2)V-NET add device**
100 -
101 -Open V-NET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the access key, password and remark, to add the device.
102 -
103 -[[image:image-20220824104909-2.png]]
104 -
105 -**3)Set communication port parameters**
106 -
107 -Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
108 -
109 -Baud rate:115200
110 -
111 -Data bit:8
112 -
113 -Stop bit:1
114 -
115 -Parity:No verification
116 -
117 -[[image:image-20220824142130-1.png]]
118 -
119 -**hardware connection**
120 -
121 -**1)Hardware wiring diagram**
122 -
123 -[[image:image-20220824142546-2.png]]
124 -
125 -[[image:image-20220824142643-3.png]]
126 -
127 -The above are all the steps for establishing serial port communication between V-BOX with LX5V PLC.
128 -
129 -== **LX5V-N Ethernet protocol** ==
130 -
131 -This example introduces the establishment of Ethernet communication between V-BOX and LX5V-N. It is introduced through three parts: PLC software configuration, V-BOX software configuration, and hardware wiring.
132 -
133 -**Software configuration of PLC**
134 -
135 -**1)PLC programming software**
136 -
137 -[[image:image-20220824142722-1.png]]
138 -
139 -**2)New PLC project**
140 -
141 -Click New Project and select the PLC model.
142 -
143 -[[image:image-20220824143613-1.png]]
144 -
145 -**3)Set Ethernet port parameters**
146 -
147 -Follow the steps below to configure Ethernet parameters
148 -
149 -PLC IP address:192.168.39.200
150 -
151 -default gateway:192.168.39.1
152 -
153 -subnet mask:255.255.255.0
154 -
155 -[[image:image-20220824143744-2.png]]
156 -
157 -**4)Registers list**
158 -
159 -[[image:image-20220822172730-4.png]]
160 -
161 -(% id="cke_bm_22473S" style="display:none" %)** **(%%)**V-BOX software configuration**
162 -
163 -**1)V-BOX programming software**
164 -
165 - [[image:image-20220824104124-1.png]]
166 -
167 -**2)V-NET add device**
168 -
169 -Open V-NET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the access key, password and remark, to add the device.
170 -
171 -[[image:image-20220824104909-2.png]]
172 -
173 -**3)Set communication Protocol**
174 -
175 -Click Communication to configure the LX5V plc protocol and IP address.
176 -
177 -[[image:image-20220824144619-1.png]]
178 -
179 -**hardware connection**
180 -
181 -**1)Hardware wiring diagram**
182 -
183 -[[image:image-20220824151127-2.png]]
184 -
185 -The above are all the steps for establishing ethernet communication between V-BOX with LX5V PLC.
186 -
187 -= Create communication with Allen-Bradley(**Rockwell**)** PLC** =
188 -
189 -== **DF1 Advanced Protocol** ==
190 -
191 -MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
192 -
193 -**1) V-Box Settings**
194 -
195 -|=Item|=Recommended |=Note
196 -|=Protocol|Allen Bradley DF1 Advanced|
197 -|=Connection|RS232|
198 -|=Baud rate|19200|
199 -|=Stop bits|1|
200 -|=Data bits|8|
201 -|=Parity|None|
202 -|=PLC Station No.|1|
203 -|=HMI Station No.|0|
204 -
205 -**2) Address List**
206 -
207 -|=**Type**|=**Device registers**|=**Format**|=**Range**|=Note
208 -|(% colspan="1" rowspan="7" %)Bit|I1|I1ddd.dd|0.0~~255.15|Only able to communicate with file number I1
209 -|O0|O0ddd.dd|0.0~~255.15|Only able to communicate with file number O0
210 -|S2|S2ddd.dd|0.0~~255.15|Only able to communicate with file number S2
211 -|B3|B3ddd.dd|0.0~~255.15|Only able to communicate with file number B3
212 -|BN|BNddddd.dd|0.0~~99255.15|(((
213 -Bit data file B0~~B99
214 -
215 -First two digits is for file number
216 -
217 -For example, BN13001.00 represents file number B13, address 001, the 0th bit.
218 -)))
219 -|N7|N7ddd.dd|0.0~~255.15|Only able to communicate with file number N7
220 -|NN|NNddddd.dd|0.0~~99255.15|(((
221 -Integer data file bit format N0~~N99
222 -
223 -First two digits is for file number
224 -
225 -For example, NN13001.00 represents file number N13, address 001, the 0th bit.
226 -)))
227 -|(% rowspan="11" %)Word|S2|S2ddd|0~~255|Only able to communicate with file number S2
228 -|T4S|T4Sddd|0~~255|Only able to communicate with file number T4 (Timer Preset Value)
229 -|T4P|T4Pddd|0~~255|Only able to communicate with file number T4 (Timer Accumulator Value)
230 -|TNS|TNSddddd|0~~99255|(((
231 -Timer Preset Value
232 -
233 -First two digits is for file number
234 -
235 -For example, TNS99255 represents file number T99, address 255.
236 -)))
237 -|TNP|TNPddddd|0~~99255|(((
238 -Timer Accumulator Value
239 -
240 -First two digits is for file number
241 -
242 -For example, TNP99255 represents file number T99, address 255.
243 -)))
244 -|C5S|C5Sddd|0~~255|Only able to communicate with file number C5 (Counter Preset Value)
245 -|C5P|C5Pddd|0~~255|Only able to communicate with file number C5 (Counter Accumulator Value)
246 -|CNS|CNSddddd|0~~99255|(((
247 -Counter Preset Value
248 -
249 -First two digits is for file number
250 -
251 -For example, CNS99255 represents file number C99, address 255.
252 -)))
253 -|CNP|CNPddddd|0~~99255|(((
254 -Counter Accumulator Value
255 -
256 -First two digits is for file number
257 -
258 -For example, CNP99255 represents file number C99, address 255.
259 -)))
260 -|N7|N7ddd|0~~255|Only able to communicate with file number N7
261 -|NN|NNddd|0~~99255|(((
262 -Integer data file
263 -
264 -First two digits is for file number
265 -
266 -For example, NN99255 represents file number N99, address 255.
267 -)))
268 -|(% colspan="1" rowspan="3" %)Double Word|F8|F8ddd|0~~255|(((
269 -Only able to communicate with file number N7
270 -)))
271 -|FN|FNddddd|0~~99255|(((
272 -Floating point data file
273 -
274 -First two digits is for file number
275 -
276 -For example, FN99255 represents file number F99, address 255.
277 -)))
278 -|LN|LNddddd|0~~99255|Long
279 -
280 -**3) Cable Wiring**
281 -
282 -(% style="text-align:center" %)
283 -[[image:ABRS232.gif]]
284 -
285 -(% class="wikigeneratedid" id="HMicroLogixA0Protocol" %)
286 -(% id="cke_bm_5621S" style="display:none" %)** **
287 -
288 -== **MicroLogix Protocol** ==
289 -
290 -(% class="wikigeneratedid" %)
291 -MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
292 -
293 -**1)V-BOX setting**
294 -
295 -|**Item**|**Settings**|**Note**
296 -|Protocol|Allen-Bradley DF1 Advanced|
297 -|Connection|RS232|
298 -|Baud rate|19200|
299 -|Data bit|8|
300 -|Parity|None|
301 -|Stop bit|1|
302 -|PLC station No.|1|
303 -
304 -**2)Address List**
305 -
306 -|**Type**|**Device registers**|**Format**|**Range**|**Note**
307 -|(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
308 -|O|O d.d|0.0~~255.15|
309 -|B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
310 -|S|S d.d|0.0~~255.15|
311 -|N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
312 -|(% rowspan="9" %)Word|S|S d|0~~255|
313 -|TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
314 -|TP|TP nnhh|0~~ffff
315 -|CS|CS nnhh|0~~ffff
316 -|CP|CP nnhh|0~~ffff
317 -|N|N nnhh|0~~ffff
318 -|C|C nnhh|0~~ffff
319 -|T|T nnhh|0~~ffff
320 -|R|R nnhh|0~~ffff
321 -
322 -**3)Configure the communication protocol**[[image:image-20220824152928-1.png]]
323 -
324 -**4)Configure the communication protocol**
325 -
326 -[[image:image-20220824110724-1.png]]
327 -
328 -== **Micro850_FreeTag Protocol** ==
329 -
330 -(((
331 -(((
332 -This example introduces the establishment of Ethernet communication between Wecon V-box and CompactLogix L1769. It is introduced through three parts: PLC software configuration, V-box software configuration, and hardware wiring.
333 -)))
334 -)))
335 -
336 -(((
337 -(% class="wikigeneratedid" id="HSoftwareconfigurationofPLC" %)
338 -(((
339 -**Software configuration of PLC**
340 -)))
341 -
342 -(% class="wikigeneratedid" id="HPLCprogrammingsoftware" %)
343 -(((
344 -**1)PLC programming software**
345 -)))
346 -
347 -[[image:image-20220714162600-1.png]]
348 -
349 -(% class="wikigeneratedid" id="HNewPLCproject" %)
350 -(((
351 -**2)New PLC project**
352 -)))
353 -
354 -(((
355 -(((
356 -Click New Project and select the PLC model.
357 -)))
358 -)))
359 -
360 -(((
361 -[[image:image-20220714162617-2.png]]
362 -)))
363 -
364 -(((
365 -
366 -
367 -[[image:image-20220714162652-4.png]]
368 -)))
369 -
370 -(((
371 -(% class="wikigeneratedid" id="HSetEthernetparameters" %)
372 -(((
373 -**3)Set Ethernet parameters**
374 -)))
375 -
376 -(((
377 -(((
378 -(((
379 -Follow the steps below to configure Ethernet parameters
380 -)))
381 -)))
382 -)))
383 -
384 -(((
385 -(((
386 -(((
387 -PLC IP address:192.168.40.101
388 -)))
389 -)))
390 -)))
391 -
392 -(((
393 -(((
394 -(((
395 -default gateway:192.168.40.1
396 -)))
397 -)))
398 -)))
399 -
400 -(((
401 -(((
402 -(((
403 -subnet mask:255.255.255.0
404 -)))
405 -)))
406 -)))
407 -
408 -(((
409 -[[image:image-20220714162713-5.png]]
410 -)))
411 -
412 -(((
413 -
414 -)))
415 -
416 -(((
417 -(% class="wikigeneratedid" id="HV-boxsoftwareconfiguration" %)
418 -(((
419 -**V-box software configuration**
420 -)))
421 -
422 -(% class="wikigeneratedid" id="HV-boxprogrammingsoftware" %)
423 -(((
424 -**1)V-box programming software**
425 -)))
426 -
427 -(% class="wikigeneratedid" %)
428 -(((
429 - [[image:image-20220714162725-6.png]]
430 -)))
431 -
432 -(% class="wikigeneratedid" id="HConfiguredevicenetwork" %)
433 -(((
434 -**2)Configure device network**
435 -)))
436 -
437 -(((
438 -(((
439 -(((
440 -Click the Configuration Download button[[image:image-20220714115308-8.png||height="22" width="15"]], It is used to configure the device network, update the device time, obtain the device machine code, check the device network, etc.
441 -)))
442 -
443 -(((
444 -In the example below, the IP address of V-Box is configured as 192.168.40.66, and the networking method is 4G connection
445 -)))
446 -)))
447 -)))
448 -
449 -(((
450 -(((
451 -[[image:image-20220714162737-7.png]]
452 -
453 -
454 -)))
455 -)))
456 -)))
457 -)))
458 -
459 -(% class="wikigeneratedid" id="HV-netadddevice" %)
460 -(((
461 -**3)V-net add device**
462 -)))
463 -)))
464 -
465 -(((
466 -(((
467 -Open VNET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the device machine code/product code, device password, and device alias to add the device.   [[image:image-20220714162752-8.png]]
468 -)))
469 -
470 -
471 -)))
472 -
473 -(((
474 -(% class="wikigeneratedid" id="HSetcommunicationportparameters" %)
475 -(((
476 -**4)Set communication port parameters**
477 -)))
478 -
479 -(((
480 -In the device list on the left, find the Vbox that communicates with the L1769, click it and select configuration,communication port configuration in the main interface to add a communication protocol.
481 -)))
482 -
483 -[[image:image-20220714162805-9.png]]
484 -)))
485 -
486 -(((
487 -The communication port is selected as Ethernet, the device type is selected as Allen-Bradley, the protocol is Allen-BradleyMicro850_FreeTag EthemetIP, and the IP is the internal IP address of the L1769 PLC. The port number is 44818.
488 -)))
489 -
490 -[[image:image-20220824164346-1.png]]
491 -
492 -
493 -(((
494 -After adding the protocol Allen-BradleyMicro850_FreeTag, click[[image:image-20220714143838-2.png]]icon add label.[[image:image-20220714162827-11.png]]
495 -)))
496 -
497 -(% class="wikigeneratedid" id="HEngineeringproduction" %)
498 -(((
499 -**5)Engineering production**
500 -)))
501 -
502 -(% class="wikigeneratedid" %)
503 -(((
504 -(((
505 -According to your own needs, use the V-NET client software to edit the required data monitoring points.
506 -)))
507 -
508 -[[image:image-20220714162841-12.png]]
509 -
510 -
511 -(((
512 -**hardware connection**
513 -)))
514 -)))
515 -
516 -(((
517 -**1)Hardware wiring diagram**
518 -)))
519 -
520 -(((
521 -(((
522 -This example introduces Wecon V-box with Allen-Bradley L1769 PLC to establish communication through Ethernet. The connection diagram is as follows:
523 -)))
524 -
525 -[[image:image-20220714162856-13.png]]
526 -
527 -(((
528 -The above are all the steps for establishing Ethernet communication between Wecon V-box with CompactLogix L1769 PLC.
529 -
530 -
531 -== **Micro850_FreeTag Protocol(new)** ==
532 -
533 -This example introduces the establishment of Ethernet communication between Wecon V-box and 2080-LC50-48QWB,Micro850. It is introduced through three parts: PLC software configuration, V-box software configuration.
534 -
535 -(% class="wikigeneratedid" id="HSoftwareconfigurationofPLC" %)
536 -(((
537 -**Software configuration of PLC**
538 -)))
539 -
540 -(% class="wikigeneratedid" id="HPLCprogrammingsoftware" %)
541 -(((
542 -**1)PLC programming software:Connected Components Workbench™**
543 -
544 -(% style="text-align:center" %)
545 -[[image:software.png]]
546 -
547 -**2)New PLC project**
548 -
549 -Click New Project and select the PLC model.
550 -
551 -(% style="text-align:center" %)
552 -[[image:project create.png]]
553 -
554 -**3)Set Ethernet parameters**
555 -
556 -Follow the steps below to configure Ethernet parameters
557 -
558 -PLC IP address:192.168.39.56
559 -
560 -default gateway:192.168.39.1
561 -
562 -subnet mask:255.255.255.0
563 -
564 -(% style="text-align:center" %)
565 -[[image:Ethernet.png]]
566 -
567 -**4)connect PLC**
568 -
569 -**When downloading the setting, need to change the status of the PLC to PRG**
570 -
571 -(% style="text-align:center" %)
572 -[[image:conne ab plc.png]]
573 -
574 -**V-box software configuration**
575 -
576 -**1)V-box programming software**
577 -
578 -(% style="text-align:center" %)
579 -[[image:v-net client vers.png]]
580 -
581 -**2)Set communication port parameters**
582 -
583 -In the device list on the left, find the Vbox that communicates with the L1769, click it and select configuration,communication port configuration in the main interface to add a communication protocol.
584 -
585 -(% style="text-align:center" %)
586 -[[image:V-NET_Client_t2Rg2wpSoY.png]]
587 -
588 -The communication port is selected as Ethernet, the device type is selected as Allen-Bradley, the protocol is Allen-BradleyMicro850_FreeTag EthemetIP, and the IP is the internal IP address of the L1769 PLC. The port number is 44818.
589 -
590 -(% style="text-align:center" %)
591 -[[image:V-NET_Client_communication.png]]
592 -
593 -Export variables from PLC, select CSV file, comma delimited.(% id="cke_bm_1950S" style="display:none" %)
594 -
595 -(% style="text-align:center" %)
596 -[[image:export1.png]]
597 -
598 -(% style="text-align:center" %)
599 -[[image:CCW.Shell_E5Cwj4tUL3.png]]
600 -
601 -After adding the protocol Allen-BradleyMicro850_FreeTag, click[[image:https://docs.we-con.com.cn/bin/download/V-BOX/V-Net/Training/1%20Communication/WebHome/image-20220714143838-2.png?rev=1.1||alt="image-20220714143838-2.png"]]icon add label.
602 -
603 -(% style="text-align:center" %)
604 -[[image:V-NET_Client_TNBuqy7T5r.png]]
605 -
606 -**3)Engineering production**
607 -
608 -According to your own needs, use the V-NET client software to edit the required data monitoring points.
609 -
610 -(% style="text-align:center" %)
611 -[[image:V-NET_Client_KOR0AHEA4M.png]]
612 -
613 -
614 -)))
615 -
616 -== **Ethernet DF1 Protocol** ==
617 -
618 -[[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Allen-Bradley%20Ethernet%20DF1.zip]]
619 -
620 -= Create communication with **Crouzet PLC** =
621 -
622 -== **CROUZET M3 (FBD)** ==
623 -
624 -Support Series: Crouzet Millenium 3 CD12/CB12
625 -
626 -**1)V-BOX setting**
627 -
628 -|=Item|=Recommended |=Note
629 -|=Protocol|CROUZET M3 (FBD)|
630 -|=Connection|RS232|
631 -|=Baud rate|115200|
632 -|=Stop bits|1|
633 -|=Data bits|7|
634 -|=Parity|EVEN|
635 -
636 -**2)Address List**
637 -
638 -|=**Type**|=**Device registers**|=**Format**|=**Range**|=Note
639 -|(% rowspan="4" %)Bit|I|I DD|1~~99|Input
640 -|SLIBit|SLIBit DD.dd|1.0~~24.15|Serial Link Input
641 -|SLOBit|SLOBit DD.dd|25.0~~48.15|Serial Link Output(Read only)
642 -|State|State D|1~~1|PLC state(Read only)
643 -|(% rowspan="5" %)Word|AI|AI DD|1~~99|Analog Input
644 -|SLIn|SLIn DD|1~~24|Serial Link Input
645 -|SLOut|SLOut DD|25~~48|Serial Link Output(Read only)
646 -|Time|Time D|1~~6|(((
647 -Time1: Second
648 -
649 -Time2: Minute
650 -
651 -Time3: Hour
652 -
653 -Time4: Day
654 -
655 -Time5: Month
656 -
657 -Time6: Year
658 -)))
659 -|Order|Order D|1~~1|(((
660 -Running command(Write only)
661 -
662 -~=2: Run mode; =1: Stop mode;
663 -)))
664 -
665 -**3)Cable Wiring**
666 -
667 -(% style="text-align:center" %)
668 -[[image:CrouzetRS232 VBox.png]]
669 -
670 -{{info}}
671 -**✎Note: **As the wiring diagram indicated, this protocol requires the DB9 serial port pin 4. But pin 4 is undefined for all V-Box, so it need the user to solder a Pull-up resistor to make the pin 4 working. As for how to solder the resistor on the motherboard, please contact with Wecon technical support for the details.
672 -{{/info}}
673 -
674 -= Create communication with EMERSON PLC =
675 -
676 -= **RTU Slave Protocol** =
677 -
678 -Supported series: EC10 series
679 -
680 -**1)V-BOX setting**
681 -
682 -|**Items**|**Settings**|**Note**
683 -|Protocol|Emerson 984 RTU Slave MODBUS|
684 -|Connection|RS485|
685 -|Baud rate|19200|
686 -|Data bit|8|
687 -|Parity|EVEN|
688 -|Stop bit|1|
689 -|Device station No.|1|Need to be same as the PLC setting
690 -
691 -(% class="wikigeneratedid" %)
692 -**2)PLC Setting**
693 -
694 -(% class="wikigeneratedid" %)
695 -Remember to use the Control Star to enable the Modbus RTU communication for port 1 in system block before dowload into PLC.
696 -
697 -(% style="text-align:center" %)
698 -[[image:ControlStarSystemBlock.png]]
699 -
700 -(% style="text-align:center" %)
701 -[[image:ControlStarCommunicate.png]]
702 -
703 -(% style="text-align:center" %)
704 -[[image:ControlStarModbus.png]]
705 -
706 -(% class="wikigeneratedid" %)
707 -**3)Address List**
708 -
709 -|**Type**|**Device registers**|**Format**|**Range**|**Note**
710 -|(% colspan="1" rowspan="12" %)Bit|Y|YOOO|0~~377|
711 -|X|XOOO|0~~377|
712 -|M0|M0DDDD|0~~2047|
713 -|M1|M1DDDDD|2048~~10239|
714 -|SM0|SM0DDD|0~~255|
715 -|SM1|SM1DDD|256~~511|
716 -|S0|S0DDDD|0~~1023|
717 -|S1|S1DDDD|1024~~4095|
718 -|T0|T0DDD|0~~255|
719 -|T1|T1DDD|256~~511|
720 -|C0|C0DDD|0~~255|
721 -|C1|C1DDD|256~~306|
722 -|(% colspan="1" rowspan="7" %)Word|D|DDDDD|0~~7999|
723 -|Z|ZDD|0~~15|
724 -|TW0|TW0DDD|0~~255|
725 -|TW1|TW1DDD|256~~511|
726 -|SD0|SD0DDD|0~~255|
727 -|SD1|SD1DDD|256~~511|
728 -|CW|CWDDD|0~~306|
729 -|(% colspan="1" rowspan="2" %)Double Word|CW0|CW0DDD|200~~255|
730 -|CW1|CW1DDDDD|256~~99999|
731 -
732 -**4) Cable Wiring**
733 -
734 -(% style="text-align:center" %)
735 -[[image:Emerson.png]]
736 -
737 -= Create communication with HollySys PLC =
738 -
739 -== **LK Modbus RTU** ==
740 -
741 -Supported Series: HollySys LK series PLC
742 -
743 -**1)V-BOX setting**
744 -
745 -|**Items**|**Settings**|**Note**
746 -|Protocol|HollySys LK Modbus RTU|
747 -|Connection|RS485|
748 -|Baud rate|38400|
749 -|Data bit|8|
750 -|Parity|None|
751 -|Stop bit|1|
752 -|Device station No.|1|
753 -
754 -**2)Address List**
755 -
756 -|=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note**
757 -|Bit|QX|QXDDDDD.dd|0~~65535.15|
758 -|Bit|IX|IXDDDDD.dd|0~~65535.15|
759 -|Bit|MX|MXDDDDD.dd|0~~65535.15|
760 -|Word|QW|QWDDDDD|0~~99999|
761 -|Word|IW|IWDDDDD|0~~99999|
762 -|Word|MW|MWDDDDD|0~~99999|
763 -|Word|MD|MDDDDDD|0~~99999|
764 -
765 -**3)Cable Wiring**
766 -
767 -(% style="text-align:center" %)
768 -[[image:Hollysys485-2.png]]
769 -
770 -== **LM Modbus RTU** ==
771 -
772 -(% class="wikigeneratedid" %)
773 -Supported Series: HollySys LM3109/LM3107 PLC
774 -
775 -(% class="wikigeneratedid" %)
776 -**1)V-BOX setting**
777 -
778 -|(% style="width:208px" %)**Items**|(% style="width:310px" %)**Settings**|(% style="width:365px" %)**Optional**|(% style="width:152px" %)**Note**
779 -|(% style="width:208px" %)Protocol|(% style="width:310px" %)HollySys LM Modbus RTU|(% style="width:365px" %)HollySys LM Modbus RTU|(% style="width:152px" %)
780 -|(% style="width:208px" %)Connection|(% style="width:310px" %)RS232|(% style="width:365px" %)RS485|(% style="width:152px" %)
781 -|(% style="width:208px" %)Baud rate|(% style="width:310px" %)38400|(% style="width:365px" %)38400|(% style="width:152px" %)
782 -|(% style="width:208px" %)Data bit|(% style="width:310px" %)8|(% style="width:365px" %)8|(% style="width:152px" %)
783 -|(% style="width:208px" %)Parity|(% style="width:310px" %)None|(% style="width:365px" %)None|(% style="width:152px" %)
784 -|(% style="width:208px" %)Stop bit|(% style="width:310px" %)1|(% style="width:365px" %)1|(% style="width:152px" %)
785 -|(% style="width:208px" %)Device station No.|(% style="width:310px" %)1|(% style="width:365px" %)1|(% style="width:152px" %)
786 -
787 -**2)Address List**
788 -
789 -|=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note**
790 -|Bit|QX|QXDDDDD.o|0~~99999.7|
791 -|Bit|IX|IXDDDDD.o|0~~99999.7|
792 -|Bit|MX|MXDDDDD.o|0~~99999.7|
793 -|Word|QW|QWDDDDD|0~~99999|
794 -|Word|IW|IWDDDDD|0~~99999|
795 -|Word|MW|MWDDDDD|0~~99999|
796 -|Word|MD|MDDDDDD|0~~99999|
797 -
798 -**Cable Wiring**
799 -
800 -RS232
801 -
802 -(% style="text-align:center" %)
803 -[[image:HollySysRS232.png]]
804 -
805 -RS485
806 -
807 -(% style="text-align:center" %)
808 -[[image:Hollysys LM Modbus RTU.gif]]
809 -
810 -= Create communication with **Siemens PLC** =
811 -
812 -== **S7-200 Smart Ethernet Protocol** ==
813 -
814 -[[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20S7-200%20Smart.zip]]
815 -
816 -
817 -== **S7-300 Ethernet Protocol** ==
818 -
819 -Supported Series: Siemens S7-300 series PLC
820 -
821 -**1)V-BOX setting**
822 -
823 -|**Items**|**Settings**|**Note**
824 -|Protocol|Simens S7-300 Ethernet|
825 -|Connection|Ethernet|
826 -|Port No.|102|
827 -|PLC station No.|2|Need to be same as the PLC setting
828 -
829 -**2)Address List**
830 -
831 -|**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
832 -|(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
833 -|Q|Q|Q ddddd.o|0.0~~99999.7|
834 -|M|M|M ddddd.o|0.0~~99999.7|
835 -|DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
836 -nn: block number;
837 -
838 -dddd: address;
839 -)))
840 -|(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
841 -|Q|QW|QW ddddd|0~~99999|
842 -|(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
843 -|MW|MW ddddd|0~~99999|(((
844 -MW0=MB(0~~1)
845 -
846 -MW2=MB(2~~3)
847 -
848 -Address value is a multiple of 2
849 -)))
850 -|MD|MD ddddd|0~~99999|(((
851 -MD0=MB(0~~3)
852 -
853 -MD4=MB(4~~7)
854 -
855 -Address value is a multiple of 4
856 -)))
857 -|(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
858 -nn: block number;
859 -
860 -dddd: address
861 -)))
862 -|DBxDBW|DBxDBW nndddd|0~~99999999
863 -|DBxDBD|DBxDBD nndddd|0~~99999999
864 -
865 -**3)Configure the communication protocol**
866 -
867 -[[image:image-20220824161345-1.png]]
868 -
869 -**4)Cable Wiring**
870 -
871 -[[image:image-20220824161450-2.png]]
872 -)))
873 -)))
874 -
875 -== **S7-1200 Ethernet Protocol** ==
876 -
877 -[[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]]
878 -
879 -== **S7-XXX Ethernet Protocol** ==
880 -
881 -Supported Series: Siemens S7-400, S7-1200 and S7-1500
882 -
883 -**1)V-BOX setting**
884 -
885 -|=**Items**|=**Settings**|=**Note**
886 -|Protocol|Siemens S7-XXX|
887 -|Connection|Ethernet|
888 -|Port No.|102|
889 -|Device No.|Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|
890 -|HMI No.|Rack (Default as 0)|
891 -
892 -Slot from TIA Portal is equal to Device No. of V-net
893 -
894 -Rack from TIA Portal is equal to HMI No. of V-net
895 -
896 -[[image:image-20220824162459-3.png]]
897 -
898 -[[image:image-20220824163305-2.png]]
899 -
900 -**2)Address List**
901 -
902 -|**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
903 -|(% rowspan="4" %)Bit|I|I|M d.o|(((
904 -d:0~-~-9999
905 -
906 -o:0-7
907 -)))|
908 -|Q|Q|Q d.o|(((
909 -d:0~-~-9999
910 -
911 -o:0-7
912 -)))|
913 -|M|M|M d.o|(((
914 -d:0~-~-9999
915 -
916 -o:0-7
917 -)))|
918 -|DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
919 -nn:0-9999,
920 -
921 -dddd:0-9999,
922 -
923 -o:0-7
924 -)))|(((
925 -nn:DB No.
926 -
927 -dddd:address value
928 -
929 -o: digit address
930 -)))
931 -|(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
932 -|M|MW|MW d|d:0-99999|(((
933 -MW0=MB(0~~1)
934 -
935 -MW2=MB(2~~3)
936 -
937 -Address value is a multiple of 2
938 -)))
939 -|M|MD|MD d|d:0-99999|(((
940 -MD0=MB(0~~3)
941 -
942 -MD4=MB(4~~7)
943 -
944 -Address value is a multiple of 4
945 -)))
946 -|I|IW|IW d|d:0-99999|
947 -|Q|QW|QW d|d:0-99999|
948 -|DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
949 -nn:0-9999
950 -
951 -dddd:0-9999
952 -)))|(((
953 -nn:DB No.
954 -
955 -dddd:address value
956 -)))
957 -|DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
958 -nn:0-9999
959 -
960 -dddd:0-9999
961 -)))|(((
962 -nn:DB No.
963 -
964 -dddd:address value
965 -
966 -Address value is a multiple of 2
967 -)))
968 -|DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
969 -nn:0-9999
970 -
971 -dddd:0-9999
972 -)))|(((
973 -nn:DB No.
974 -
975 -dddd:address value
976 -
977 -Address value is a multiple of 4
978 -)))
979 -
980 -**3)Configure the communication protocol**
981 -
982 -[[image:image-20220824163448-3.png]]
983 -
984 -**✎Note:**
985 -
986 -* The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three V-BOX.
987 -* V-BOX access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
988 -
989 -**4)Cable Wiring**
990 -
991 -[[image:image-20220824162342-2.png]]
992 -
993 -== **LOGO Ethernet Protocol** ==
994 -
995 -Supported Series: Siemens Logo 0BA0, 0BA1 series
996 -
997 -**V-BOX Settings**
998 -
999 -
1000 -|**Items**|**Settings**|**Note**
1001 -|Protocol|Siemens LOGO|
1002 -|Connection|Ethernet|
1003 -|Port No.|102|
1004 -|PLC station No.|2|
1005 -
1006 -**Address List**
1007 -
1008 -
1009 -|**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
1010 -|1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
1011 -|2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
1012 -|3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
1013 -|4|VW|Word|0-1468|DB1.DBX0.0|0x000000
1014 -|5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
1015 -|6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
1016 -|7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
1017 -|8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
1018 -|9|AI|Word|1-16|DB1.DBX1032.0|0x002040
1019 -|10|I|Bit|1-64|DB1.DBX1024.0|0x002000
1020 -|11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
1021 -|12|M|Bit|1-112|DB1.DBX1104.0|0x002280
1022 -|13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
1023 -|14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
1024 -|15|V|Bit|0-14697|DB1.DBX0.0|0x000000
1025 -
1026 -**PLC Settings in LOGO Software:**
1027 -
1028 -Click [Tools]~-~-[Ethernet Connections],shown as below.
1029 -
1030 -(% style="text-align:center" %)
1031 -[[image:PIStudio.12\.PLC protocols.WebHome@12.PLC Protocol_html_8b9d2322edf89519.png]]
1032 -
1033 -Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
1034 -
1035 -(% style="text-align:center" %)
1036 -[[image:PIStudio.12\.PLC protocols.WebHome@image-20221228142937-4.png]]
1037 -
1038 -**TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
1039 -
1040 -(% style="text-align:center" %)
1041 -[[image:PIStudio.12\.PLC protocols.WebHome@image-20221228143047-5.png]]
1042 -
1043 - **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
1044 -
1045 -(% style="text-align:center" %)
1046 -[[image:PIStudio.12\.PLC protocols.WebHome@image-20221228143246-6.png]]
1047 -
1048 -**V-BOX Communication Settings**
1049 -
1050 -Set PLC IP in [IP Address] settings;
1051 -
1052 -(% style="text-align:center" %)
1053 -[[image:LldwDGntf4.png]]
1054 -
1055 -Enable V-BOX Ethernet in [Network];
1056 -
1057 -(% style="text-align:center" %)
1058 -[[image:WgvjfWbQif.png]]
1059 -
1060 -TSAP setting
1061 -
1062 -* The initialization script needs to set the source TSAP address and the target TSAP address, otherwise the communication will not be successful.
1063 -
1064 -{{code language="LUA"}}
1065 -function init.main()
1066 -addr_setword("@W_0#HSW1200",8192) -- Set the source TSAP address
1067 -addr_setword("@W_0#HSW1201",4096) -- Set the destination TSAP address
1068 -end
1069 -{{/code}}
1070 -
1071 -Note: The name of the test script is init, 8192 and 4096 are the data used for the test, there is no HSW address in the register option, but you can directly set the value of the corresponding address through the code.
1072 -
1073 -**✎Note:**
1074 -
1075 -* **Communication port configuration: **
1076 -** Continuous length needs to be set to 0.
1077 -** Integration interval needs to be set to 1. (no change may result in data errors)
1078 -** Set Port and Device Station NO.
1079 -** Other set as defaulted.
1080 -* **Notes on the use of registers:**
1081 -** Register VD: Use only registers that are multiples of 4, such as 0, 4, 8, etc.
1082 -** Register VW: Use only registers thay are multiples of 2, such as 0, 2, 4 etc. (Using an odd-length register may result in data errors, such as 2 3 4 )
1083 -
1084 -= Create communication with **Mitsubishi PLC** =
1085 -
1086 -== **FX1S,1N,2N Serial Protocol** ==
1087 -
1088 -Supported Series: Mitsubishi FX1S, FX1N, FX2N series
1089 -
1090 -**1)V-BOX Settings**
1091 -
1092 -|**Item**|**Settings**|**Note**
1093 -|Protocol|Mitsubishi FX1S/FX1N/FX2N|
1094 -|Connection|RS422/RS485/RS232|
1095 -|Baud rate|9600~~115200|
1096 -|Data bit|7/8|
1097 -|Parity|EVEN/Odd/None|
1098 -|Stop bit|1/2|
1099 -|PLC station No.|1~~255|
1100 -
1101 -**2)Address List**
1102 -
1103 -|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1104 -|(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1105 -|Y|Y|Y o|0~~303237|
1106 -|M|M|M d|0~~99999|
1107 -|T|T|T d|0~~99999|
1108 -|C|C|C d|0~~99999|
1109 -|S|S|S d|0~~99999|
1110 -|SM|SM|SM d|8000~~9999|
1111 -|(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1112 -|Y|Y|Y o|0~~303237|
1113 -|M|M|M d|0~~99999|
1114 -|T|T|T d|0~~99999|
1115 -|C|C|C d|0~~199|
1116 -|D|D|D d|0~~7999|
1117 -|S|S|S d|0~~99999|
1118 -|SD|SD|SD d|8000~~9999|
1119 -
1120 -**3)Configure the communication protocol**
1121 -
1122 -[[image:image-20220825102844-3.png]]
1123 -
1124 -**4)Cable Wiring**
1125 -
1126 -* **RS422**
1127 -
1128 -[[image:image-20220825103350-4.png]]
1129 -
1130 -[[image:image-20220825100845-4.png]]
1131 -
1132 -
1133 -== **FX3U,3G,3GA Serial Protocol** ==
1134 -
1135 -Supported Series: Mitsubishi FX3U, FX3G, FX3GA series
1136 -
1137 -**1)V-BOX Settings**
1138 -
1139 -|**Item**|**Settings**|**Note**
1140 -|Protocol|Mitsubishi FX3U/3G/3GA|
1141 -|Connection|RS422/RS485/RS232|
1142 -|Baud rate|9600~~115200|
1143 -|Data bit|7/8|
1144 -|Parity|EVEN/Odd/None|
1145 -|Stop bit|1/2|
1146 -|PLC station No.|1~~255|
1147 -
1148 -**2)Address List**
1149 -
1150 -|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1151 -|(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1152 -|Y|Y|Y o|0~~303237|
1153 -|M|M|M d|0~~99999|
1154 -|T|T|T d|0~~99999|
1155 -|C|C|C d|0~~99999|
1156 -|S|S|S d|0~~99999|
1157 -|SM|SM|SM d|8000~~9999|
1158 -|(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1159 -|Y|Y|Y o|0~~303237|
1160 -|M|M|M d|0~~99999|
1161 -|T|T|T d|0~~99999|
1162 -|C|C|C d|0~~199|
1163 -|D|D|D d|0~~7999|
1164 -|S|S|S d|0~~99999|
1165 -|SD|SD|SD d|8000~~9999|
1166 -
1167 -**3)Configure the communication protocol**
1168 -
1169 -[[image:image-20220825102649-2.png]]
1170 -
1171 -**4)Cable Wiring**
1172 -
1173 -* **RS422**
1174 -
1175 -[[image:image-20220825103421-5.png]]
1176 -
1177 -[[image:image-20220825100845-4.png]]
1178 -
1179 -
1180 -== **FX3U Ethernet Protocol** ==
1181 -
1182 -Supported Modules: FX3U-ENET-ADP, FX3U-ENET-L
1183 -
1184 -**1)V-BOX Settings**
1185 -
1186 -|Items|Settings|Note
1187 -|Protocol|Mitsubishi FX3U|
1188 -|Connection|Ethernet|
1189 -|Port No.|5009|Must be the same as the PLC setting
1190 -|PLC station No.|0|
1191 -
1192 -**2)Address List**
1193 -
1194 -|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1195 -|(% colspan="1" rowspan="7" %)Bit|X|X|X OOO|0~~377|
1196 -|Y|Y|Y OOO|0~~377|
1197 -|M|M|M DDDD|0~~7679|
1198 -|SM|SM|SM DDDD|8000~~8511|
1199 -|S|S|S DDDD|0~~4095|
1200 -|TS|TS|TS DDD|0~~511|
1201 -|CS|CS|CS DDD|0~~255|
1202 -|(% colspan="1" rowspan="9" %)Word|CN|CN|CN DDD|0~~199|
1203 -|TN|TN|TN DDD|0~~511|
1204 -|D|D|D DDDD|0~~7999|
1205 -|SD|SD|SD DDDD|8000~~8511|
1206 -|R|R|R DDDDD|0~~32767|
1207 -
1208 -**3)Ethernet Module Settings**
1209 -
1210 -FX3U-ENET-L module configuration
1211 -Set up the FX3U-ENET-L Ethernet module settings as follows.
1212 -Select the module location, which in this document is Module 0.
1213 -
1214 -[[image:image-20221116105850-1.png]]
1215 -
1216 -Select "Operational setting" to enter the following screen.
1217 -
1218 -The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default.
1219 -
1220 -[[image:image-20221116105947-1.png]]
1221 -
1222 -Select "Open setting" to enter the setting interface, the settings are as follows.
1223 -
1224 -The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the
1225 -
1226 -Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module.
1227 -
1228 -[[image:image-20221116110802-1.png]]
1229 -
1230 -Click on "transter setup" - "PC side I/F setting", see the following figure.
1231 -
1232 -After setting, the first download must use the programming cable, as shown in the figure; after that, can
1233 -
1234 -use the IP set in the "Ethernet board" to communicate directly with the network cable.
1235 -
1236 -[[image:image-20221116110832-2.png||height="423" width="708"]]
1237 -
1238 -Read and write data from the Ethernet module
1239 -
1240 -[[image:image-20221116110907-3.png]]
1241 -
1242 -Set "Transter setup" to COM communication, and read or write operation as shown below
1243 -
1244 -[[image:image-20221116110917-4.png]]
1245 -
1246 -**4)PLC Settings (GX Works 2)**
1247 -
1248 -Create a blank FX5U project
1249 -
1250 -Find Current Connection in the navigation
1251 -
1252 -[[image:image-20221116111427-1.png||height="421" width="705"]]
1253 -
1254 -Select Connection Channel List
1255 -
1256 -Select Ethernet board communication
1257 -
1258 -[[image:image-20221116111451-2.png||height="421" width="705"]]
1259 -
1260 -Select Ethernet Module
1261 -Set the IP address of the PLC
1262 -
1263 -[[image:image-20221116111509-3.png||height="666" width="699"]]
1264 -
1265 -Read or write PLC data, in this document is read
1266 -
1267 -[[image:image-20221116111651-4.png||height="416" width="697"]]
1268 -
1269 -[[image:image-20221116111727-5.png||height="416" width="697"]]
1270 -
1271 -**4)Configure the communication protocol**
1272 -
1273 -[[image:image-20221119101946-2.png||height="395" width="695"]]
1274 -
1275 -== **FX5U Serial Protocol** ==
1276 -
1277 -Mitsubishi FX5U series PLC
1278 -
1279 -**1)V-BOX Settings**
1280 -
1281 -|**Item**|**Settings**|**Note**
1282 -|Protocol|Mitsubishi FX5U|
1283 -|Connection|RS422/RS485|
1284 -|Baud rate|9600|
1285 -|Data bit|7|
1286 -|Parity|Odd|
1287 -|Stop bit|1|
1288 -|PLC station No.|1~~255|Need to be the same as PLC settings
1289 -
1290 -**2)Address List**
1291 -
1292 -|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1293 -|(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1294 -|Y|Y|Y o|0~~303237|
1295 -|M|M|M d|0~~99999|
1296 -|B|B|B h|0~~7FFF|
1297 -|F|F|F d|0~~32767|
1298 -|SB|SB|SB h|0~~7FFF|
1299 -|TS|TS|TS d|0~~1023|
1300 -|TC|TC|TC d|0~~1023|
1301 -|STS|STS|STS d|0~~1023|
1302 -|STC|STC|STS d|0~~1023|
1303 -|CS|CS|CS d|0~~1023|
1304 -|CC|CC|CC d|0~~1023|
1305 -|SM|SM|SM d|0~~9999|
1306 -|L|L|L d|0~~32767|
1307 -|S|S|S d|0~~4095|
1308 -|(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1309 -|TN|TN|TN d|0~~1023|
1310 -|STN|STN|STN d|0~~1023|
1311 -|CN|CN|CN d|0~~1023|
1312 -|R|R|R d|0~~32767|
1313 -|SW|SW|SW h|0~~7FFF|
1314 -|Z|Z|Z d|0~~23|
1315 -|D|D|D d|0~~7999|
1316 -|SD|SD|SD d|0~~11999|
1317 -
1318 -**3)PLC Settings (GX Works 3)**
1319 -
1320 -Create a blank FX5U project
1321 -
1322 -Find the 485 serial port module in the system navigation bar and double click to enter the settings.
1323 -
1324 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5c9cb13fac1e6c93.png?width=200&height=462&rev=1.1||alt="12.PLC Protocol_html_5c9cb13fac1e6c93.png" height="462" width="200"]]
1325 -
1326 -Select protocol in the setting item, and set parameters.
1327 -
1328 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_de942589ca070228.png?width=600&height=324&rev=1.1||alt="12.PLC Protocol_html_de942589ca070228.png" height="324" width="600"]]
1329 -
1330 -Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
1331 -
1332 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_387ec7d00b5feb59.png?width=600&height=323&rev=1.1||alt="12.PLC Protocol_html_387ec7d00b5feb59.png" height="323" width="600"]]
1333 -
1334 -Click the [Apply] button to finish the setting.
1335 -
1336 -Click download and select the items as below, then click [execute] to download the configuration to PLC.
1337 -
1338 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_cdef1c5ec8cc2105.png?width=600&height=434&rev=1.1||alt="12.PLC Protocol_html_cdef1c5ec8cc2105.png" height="434" width="600"]]
1339 -
1340 - As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
1341 -
1342 -Done.
1343 -
1344 -**4)Configure the communication protocol**
1345 -
1346 -[[image:image-20220825104904-1.png]]
1347 -
1348 -**5)Cable Wiring**
1349 -
1350 -
1351 -* **RS422**
1352 -
1353 -[[image:image-20220825105105-2.png]]
1354 -
1355 -[[image:image-20220825105533-3.png]]
1356 -
1357 -== **FX5U Ethernet Protocol** ==
1358 -
1359 -Mitsubishi FX5U series PLC
1360 -
1361 -**1)V-BOX Settings**
1362 -
1363 -|**Items**|**Settings**|**Note**
1364 -|Protocol|Mitsubishi FX5U|
1365 -|Connection|Ethernet|
1366 -|Port No.|5002|Must be the same as the PLC setting
1367 -|PLC station No.|0|
1368 -
1369 -**2)Address List**
1370 -
1371 -|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1372 -|(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1373 -|Y|Y|Y o|0~~303237|
1374 -|M|M|M d|0~~99999|
1375 -|B|B|B h|0~~7FFF|
1376 -|F|F|F d|0~~32767|
1377 -|SB|SB|SB h|0~~7FFF|
1378 -|TS|TS|TS d|0~~1023|
1379 -|TC|TC|TC d|0~~1023|
1380 -|STS|STS|STS d|0~~1023|
1381 -|STC|STC|STS d|0~~1023|
1382 -|CS|CS|CS d|0~~1023|
1383 -|CC|CC|CC d|0~~1023|
1384 -|SM|SM|SM d|0~~9999|
1385 -|L|L|L d|0~~32767|
1386 -|S|S|S d|0~~4095|
1387 -|(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1388 -|TN|TN|TN d|0~~1023|
1389 -|STN|STN|STN d|0~~1023|
1390 -|CN|CN|CN d|0~~1023|
1391 -|R|R|R d|0~~32767|
1392 -|SW|SW|SW h|0~~7FFF|
1393 -|Z|Z|Z d|0~~23|
1394 -|D|D|D d|0~~7999|
1395 -|SD|SD|SD d|0~~11999|
1396 -
1397 -**3)PLC Settings (GX Works 3)**
1398 -
1399 -Find the [Ethernet port] in the navigation area.
1400 -
1401 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_8e8f85ace087346c.png?width=300&height=593&rev=1.1||alt="12.PLC Protocol_html_8e8f85ace087346c.png" height="593" width="300"]]
1402 -
1403 -Select [Own Node Settings] in the [Setting Item List];
1404 -
1405 -Set [IP Address], [Subnet Mask], [Default Gateway];
1406 -
1407 -Click [Detailed Settings] into [Ethernet Configuration (Built-in Ethernet Port)] windows;
1408 -
1409 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5d98495052c8c10e.png?width=600&height=339&rev=1.1||alt="12.PLC Protocol_html_5d98495052c8c10e.png" height="339" width="600"]]
1410 -
1411 -Select [SLMP Connection Module] and add into host station as below picture shows;
1412 -
1413 -Set Port number as 5002 (this is necessary settings);
1414 -
1415 -Click [Close with Reflecting the Setting] to save and close window;
1416 -
1417 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_14b489fdc6c6589d.png?width=600&height=350&rev=1.1||alt="12.PLC Protocol_html_14b489fdc6c6589d.png" height="350" width="600"]]
1418 -
1419 -Click [Apply] to completed Etherenet settings;
1420 -
1421 -Switch to the [On line data operation] interface as below, check the item and click [Execute] to download.
1422 -
1423 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_c93025a968a8a9e7.png?width=600&height=434&rev=1.1||alt="12.PLC Protocol_html_c93025a968a8a9e7.png" height="434" width="600"]]
1424 -
1425 -**4)Configure the communication protocol**
1426 -
1427 -[[image:image-20220825112403-1.png||alt="图片-20220825112403-1.png"]]
1428 -
1429 -**5)Cable Wiring**
1430 -
1431 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1432 -
1433 -== **L02 Serial Protocol** ==
1434 -
1435 -Mitsubishi L02 series CPU built-in serial port.
1436 -
1437 -**1)V-BOX Settings**
1438 -
1439 -|**Item**|**Settings**|**Note**
1440 -|Protocol|Mitsubishi L02|
1441 -|Connection|RS422|
1442 -|Baud rate|115200|
1443 -|Data bit|8|
1444 -|Parity|Odd|
1445 -|Stop bit|1|
1446 -|PLC station No.|1~~255|Need to be the same as PLC settings
1447 -
1448 -**2)Address List**
1449 -
1450 -|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1451 -|Bit|X|X|X h|0~~FFFF|
1452 -|Bit|Y|Y|Y h|0~~FFFF|
1453 -|Bit|M|M|M d|0~~9999|
1454 -|Bit|L|L|L d|0~~9999|
1455 -|Bit|F|F|F d|0~~9999|
1456 -|Bit|B|B|B h|0~~FFFF|
1457 -|Bit|V|V|V d|0~~2047|
1458 -|Bit|TC|TC|TC d|0~~9999|
1459 -|Bit|SS|SS|SS d|0~~9999|
1460 -|Bit|SC|SC|SC d|0~~9999|
1461 -|Bit|CS|CS|CS d|0~~9999|
1462 -|Bit|CC|CC|CC d|0~~9999|
1463 -|Bit|SB|SB|SB h|0~~FFFF|
1464 -|Bit|SM|SM|SM d|0~~2047|
1465 -|Bit|STS|STS|STS d|0~~1023|
1466 -|Bit|S|S|S d|0~~9999|
1467 -|Bit|DX|DX|DX h|0~~FFFF|
1468 -|Bit|DY|DY|DY h|0~~FFFF|
1469 -|Bit|TS|TS|TS d|0~~9999|
1470 -|Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1471 -|Word|W|W|W h|0~~FFFF|
1472 -|Word|TN|TN|TN d|0~~99999|
1473 -|Word|SN|SN|SN d|0~~99999|
1474 -|Word|CN|CN|CN d|0~~99999|
1475 -|Word|R|R|R d|0~~99999|
1476 -|Word|SW|SW|SW h|0~~FFFF|
1477 -|Word|Z|Z|Z d|0~~99999|
1478 -|Word|ZR|ZR|ZR h|0~~FFFF|
1479 -|Word|D|D|D d|0~~99999|
1480 -
1481 -**3)Communication Settings**
1482 -
1483 -[[image:image-20220825160648-3.png]]
1484 -
1485 -**4)Cable Wiring**
1486 -
1487 -* **RS422**
1488 -
1489 -[[image:image-20220825161612-8.png]]
1490 -
1491 -[[image:image-20220825160820-4.png]]
1492 -
1493 -== **L02 Ethernet Protocol** ==
1494 -
1495 -Mitsubishi L series CPU built-in Ethernet port.
1496 -
1497 -**1)V-BOX Settings**
1498 -
1499 -|**Items**|**Settings**|**Note**
1500 -|Protocol|MIT L02 CPU MELSEC|
1501 -|Connection|Ethernet|
1502 -|Port No.|1025|Must be the same as the PLC setting
1503 -|PLC station No.|0|Must be the same as the PLC setting
1504 -
1505 -**2)Address List**
1506 -
1507 -|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1508 -|Bit|X|X|X h|0~~FFFF|
1509 -|Bit|Y|Y|Y h|0~~FFFF|
1510 -|Bit|M|M|M d|0~~9999|
1511 -|Bit|L|L|L d|0~~9999|
1512 -|Bit|F|F|F d|0~~9999|
1513 -|Bit|B|B|B h|0~~FFFF|
1514 -|Bit|V|V|V d|0~~2047|
1515 -|Bit|TC|TC|TC d|0~~9999|
1516 -|Bit|SS|SS|SS d|0~~9999|
1517 -|Bit|SC|SC|SC d|0~~9999|
1518 -|Bit|CS|CS|CS d|0~~9999|
1519 -|Bit|CC|CC|CC d|0~~9999|
1520 -|Bit|SB|SB|SB h|0~~FFFF|
1521 -|Bit|SM|SM|SM d|0~~2047|
1522 -|Bit|STS|STS|STS d|0~~1023|
1523 -|Bit|S|S|S d|0~~9999|
1524 -|Bit|DX|DX|DX h|0~~FFFF|
1525 -|Bit|DY|DY|DY h|0~~FFFF|
1526 -|Bit|TS|TS|TS d|0~~9999|
1527 -|Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1528 -|Word|W|W|W h|0~~FFFF|
1529 -|Word|TN|TN|TN d|0~~99999|
1530 -|Word|SN|SN|SN d|0~~99999|
1531 -|Word|CN|CN|CN d|0~~99999|
1532 -|Word|R|R|R d|0~~99999|
1533 -|Word|SW|SW|SW h|0~~FFFF|
1534 -|Word|Z|Z|Z d|0~~99999|
1535 -|Word|ZR|ZR|ZR h|0~~FFFF|
1536 -|Word|D|D|D d|0~~99999|
1537 -
1538 -**3)PLC Settings (GX Works2 )**
1539 -
1540 -Create a project
1541 -
1542 -Set PLC IP, subnet mask and gateway;
1543 -
1544 -Select [Binary Code] as communication data code;
1545 -
1546 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_776e17505f3fc6c0.png?width=600&height=524&rev=1.1||alt="12.PLC Protocol_html_776e17505f3fc6c0.png" height="524" width="600"]]
1547 -
1548 -Set PLC port number, for example 1025
1549 -
1550 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_8d0d1a22d388f70b.png?width=600&height=524&rev=1.1||alt="12.PLC Protocol_html_8d0d1a22d388f70b.png" height="524" width="600"]]
1551 -
1552 -Save settings;
1553 -
1554 -Download project into PLC device;
1555 -
1556 -Restart PLC device;
1557 -
1558 -**4)Configure the communication protocol**
1559 -
1560 -[[image:image-20220825142659-1.png]]
1561 -
1562 -**5)Cable Wiring**
1563 -
1564 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1565 -
1566 -== **Q12H Serial Protocol** ==
1567 -
1568 -This Demo shows V-BOX communicate with Q12H PLC by Q02H serial Protocol
1569 -
1570 -[[**Download link**>>https://ftp.we-con.com.cn/Download/WIKI/PI%20HMI/Demo/Communication/V-Box%20connect%20PLC%20Q12H.rar]]
1571 -
1572 -== **QJ71E71 Ethernet Protocol** ==
1573 -
1574 -Mitsubishi QJ71E71 Ethernet communication module;
1575 -
1576 -**1)V-BOX Settings**
1577 -
1578 -|**Items**|**Settings**|**Note**
1579 -|Protocol|MIT QJ71E71 MELSEC|
1580 -|Connection|Ethernet|
1581 -|Port No.|1025|Must be the same as the PLC setting
1582 -|PLC station No.|0|Must be the same as the PLC setting
1583 -
1584 -**2)Address List**
1585 -
1586 -|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1587 -|(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1588 -|Y|Y|Y h|0~~1FFF|
1589 -|M|M|M d|0~~99999|
1590 -|L|L|L d|0~~8191|
1591 -|F|F|F d|0~~2047|
1592 -|B|B|B h|0~~1FFF|
1593 -|V|V|V d|0~~2047|
1594 -|TS|TS|TS d|0~~2047|
1595 -|TC|TC|TC d|0~~2047|
1596 -|SS|SS|SS d|0~~2047|
1597 -|SC|SC|SC d|0~~2047|
1598 -|CS|CS|CS d|0~~1023|
1599 -|CC|CC|CC d|0~~1023|
1600 -|SB|SB|SB h|0~~7FF|
1601 -|S|S|S d|0~~8191|
1602 -|DX|DX|DX h|0~~1FFF|
1603 -|DY|DY|DY h|0~~1FFF|
1604 -|SM|SM|SM d|8000~~9999|
1605 -|(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1606 -|D|D|D d|0~~12287|
1607 -|W|W|W h|0~~1FFF|
1608 -|TN|TN|TN d|0~~2047|
1609 -|SN|SN|SN d|0~~2047|
1610 -|CN|CN|CN d|0~~1023|
1611 -|R|R|R d|0~~32767|
1612 -|SW|SW|SW h|0~~7FF|
1613 -|Z|Z|Z d|0~~15|
1614 -|ZR|ZR|ZR h|0~~FE7FF|
1615 -
1616 -**3)PLC Settings(GX Works2)**
1617 -
1618 -* Click [Ethernet/CC IE/MELSECNET];
1619 -* Please select [Ethernet] as network type;
1620 -* Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order);
1621 -* Select [Online] as Mode;
1622 -* [[image:image-20221119171343-2.png||height="341" width="587"]]
1623 -* Click [Operation setting] to set IP;
1624 -* Select [Binary Code] as [Communication Data Code];
1625 -* [[image:image-20221119171436-3.png||height="354" width="588"]]
1626 -* Click [Open setting]
1627 -* Set protocol: TCP;
1628 -* Set [unpassive] in [Open system];
1629 -* Set [receive] in [Fixed buffer];
1630 -* Set [procedure Exist] in [Fixed buffer communication];
1631 -* Disable [Pairing open];
1632 -* Set [No confirm] in [Existence confirmation];
1633 -* Host station port number: 5009;
1634 -* Save settings;
1635 -* [[image:image-20221119171611-4.png||height="354" width="588"]]
1636 -* Download project into PLC and restart it
1637 -
1638 -**4)Configure the communication protocol**
1639 -
1640 -[[image:image-20221119171832-5.png||height="354" width="625"]]
1641 -
1642 -
1643 -**5)Cable Wiring**
1644 -
1645 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png"]]
1646 -
1647 -= Create communication with **Delta PLC** =
1648 -
1649 -== **DVP Ethernet Protocol** ==
1650 -
1651 -Supoort Series: DELTA DVP20/32/40/60ES200RE/200TE or any DVP models with built-in Ethernet port, DELTA DVPEN01-SL module
1652 -
1653 -**1)V-BOX Settings**
1654 -
1655 -|=**Items**|=**Settings**|=**Note**
1656 -|Protocol|DELTA DVP MODBUS TCP|
1657 -|Connection|Ethernet|
1658 -|Port No.|502|
1659 -|Device No.|1|
1660 -|VBox Device No.|0|
1661 -
1662 -**2)Address List **
1663 -
1664 -|=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 217px;" %)**VBox registers**|=(% style="width: 168px;" %)**Format**|=(% style="width: 225px;" %)**Range**|=**Note**
1665 -|Bit|(% style="width:191px" %)X|(% style="width:217px" %)X|(% style="width:168px" %)X OOO|(% style="width:225px" %)0~~377|
1666 -|Bit|(% style="width:191px" %)Y|(% style="width:217px" %)Y|(% style="width:168px" %)Y OOO|(% style="width:225px" %)0~~377|
1667 -|Bit|(% style="width:191px" %)M0|(% style="width:217px" %)M0|(% style="width:168px" %)M0DDDD|(% style="width:225px" %)0~~1535|
1668 -|Bit|(% style="width:191px" %)M1|(% style="width:217px" %)M1|(% style="width:168px" %)M1DDDD|(% style="width:225px" %)1536~~4096|
1669 -|Bit|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDD|(% style="width:225px" %)0~~255|
1670 -|Bit|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~255|
1671 -|Bit|(% style="width:191px" %)S|(% style="width:217px" %)S|(% style="width:168px" %)SDDDD|(% style="width:225px" %)0~~1023|
1672 -|Word|(% style="width:191px" %)D0|(% style="width:217px" %)D0|(% style="width:168px" %)D0DDDD|(% style="width:225px" %)0~~4095|
1673 -|Word|(% style="width:191px" %)D1|(% style="width:217px" %)D1|(% style="width:168px" %)D1DDDD|(% style="width:225px" %)4096~~11999|
1674 -|Word|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDD|(% style="width:225px" %)0~~255|
1675 -|Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~199|
1676 -|Double Word|(% style="width:191px" %)HC|(% style="width:217px" %)HC|(% style="width:168px" %)HCDDD|(% style="width:225px" %)200~~255|
1677 -
1678 -**3) PLC Setting:**
1679 -
1680 -~1. Create new project in Delta WPL Soft, and click Setting to open the communication settings:
1681 -
1682 -(% style="text-align:center" %)
1683 -[[image:DVPEthernetWPLSoft2.png]]
1684 -
1685 -2. Set up the communication type and PLC IP:
1686 -
1687 -(% style="text-align:center" %)
1688 -[[image:DVPEthernetSetup.png]]
1689 -
1690 -(% class="wikigeneratedid" %)
1691 -3. Click OK and save the settings. Then click Communication on toolbar, then click Transfer Setup to open new window:
1692 -
1693 -(% style="text-align:center" %)
1694 -[[image:DVPEthernetTransfer.png]]
1695 -
1696 -(% class="wikigeneratedid" %)
1697 -4. Select Communication Mode as PC => PLC to download or select PC <=PLC to upload:
1698 -
1699 -(% style="text-align:center" %)
1700 -[[image:DVPEthernetPLCtoPC.png]]
1701 -
1702 -5. Click Auto-Search Ethernet Module to find the PLC on the same LAN network:
1703 -
1704 -(% style="text-align:center" %)
1705 -[[image:DVPEthernetAutoSearch.png]]
1706 -
1707 -**4) V-BOX Setting:**
1708 -
1709 -Set the same IP address according to the setting from WPL Soft:
1710 -
1711 -(% style="text-align:center" %)
1712 -[[image:DVPEthernetVNETPortocol.png]]
1713 -
1714 -== **DVP serial protocol** ==
1715 -
1716 -Supoort Series: DELTA DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX
1717 -
1718 -**1)V-BOX Settings**
1719 -
1720 -|=**Items**|=**Settings**|=**Note**
1721 -|Protocol|DELTA DVP PROTOCOL|
1722 -|Connection|RS232|
1723 -|Baud Rate|9600|
1724 -|Stop Bit|1|
1725 -|Data Bit|7|
1726 -|Parity|EVEN|
1727 -|Device No.|1|
1728 -
1729 -(% class="wikigeneratedid" %)
1730 -**2)Address List**
1731 -
1732 -|=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 217px;" %)**VBox registers**|=(% style="width: 168px;" %)**Format**|=(% style="width: 225px;" %)**Range**|=**Note**
1733 -|Bit|(% style="width:191px" %)X|(% style="width:217px" %)X|(% style="width:168px" %)X OOOOOO|(% style="width:225px" %)0~~303237|
1734 -|Bit|(% style="width:191px" %)Y|(% style="width:217px" %)Y|(% style="width:168px" %)Y OOOOOO|(% style="width:225px" %)0~~303237|
1735 -|Bit|(% style="width:191px" %)M|(% style="width:217px" %)M|(% style="width:168px" %)MDDDDD|(% style="width:225px" %)0~~99999|
1736 -|Bit|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDDDD|(% style="width:225px" %)0~~99999|
1737 -|Bit|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDDDD|(% style="width:225px" %)0~~99999|
1738 -|Bit|(% style="width:191px" %)S|(% style="width:217px" %)S|(% style="width:168px" %)SDDDDD|(% style="width:225px" %)0~~99999|
1739 -|Word|(% style="width:191px" %)D|(% style="width:217px" %)D|(% style="width:168px" %)D DDDDD|(% style="width:225px" %)0~~99999|
1740 -|Word|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDDDD|(% style="width:225px" %)0~~99999|
1741 -|Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~199|
1742 -|Double Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDDDD|(% style="width:225px" %)200~~99999|
1743 -
1744 -(% class="wikigeneratedid" %)
1745 -**3)Wiring Diagram**
1746 -
1747 -(% style="text-align:center" %)
1748 -[[image:Delta DVP PROTOCOLSerial232.png]]
1749 -
1750 -== **AS Ethernet Protocol** ==
1751 -
1752 -**1)V-BOX Settings**
1753 -
1754 -|=**Items**|=**Settings**|=**Note**
1755 -|Protocol|DELTA AS300 MODBUS TCP|
1756 -|Connection|Ethernet|
1757 -|Port No.|502|
1758 -|Device No.|1|
1759 -|HMI No.|0|
1760 -
1761 -**2)Address List**
1762 -
1763 -|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1764 -|Bit|X|X|X d|0~~63|
1765 -|Bit|Y|Y|Y d|0~~63|
1766 -|Bit|D|D|D d|0~~29999|
1767 -|Bit|M|M|M d|0~~8191|
1768 -|Bit|SM|SM|SM d|0~~4095|
1769 -|Bit|S|S|S h|0~~2047|
1770 -|Bit|T|T|T d|0~~511|
1771 -|Bit|C|C|C d|0~~511|
1772 -|Bit|HC|HC|HC d|0~~255|
1773 -|Word|X|X|X h|0~~63|
1774 -|Word|Y|Y|Y d|0~~63|
1775 -|Word|SR|SR|SR d|0~~2047|
1776 -|Word|D|D|D d|0~~29999|
1777 -|Word|T|T|T d|0~~511|
1778 -|Word|C|C|C h|0~~511|
1779 -|Word|E|E|E d|0~~9|
1780 -
1781 -**3)Configure the communication protocol**
1782 -
1783 -[[image:image-20220831160010-4.png]]
1784 -
1785 -**4)Cable Wiring**
1786 -
1787 -Figure
1788 -
1789 -[[image:image-20220831155101-1.png]][[image:image-20220831160055-5.png]]
1790 -
1791 -Pin Definition Diagram
1792 -
1793 -[[image:image-20220831155157-3.png]]
1794 -
1795 -= Create communication with **Omron PLC** =
1796 -
1797 -== **CP1 Series Protocol ** ==
1798 -
1799 -[[下载链接>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CP1%20Series.zip]]
1800 -
1801 -== **CP2M Series Protocol** ==
1802 -
1803 -[[下载链接>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CJ2M.zip]]
1804 -
1805 -
1806 -== **EC55 Series Protocol** ==
1807 -
1808 -Supported device: EC55 temperature instrument
1809 -
1810 -**1)V-BOX Settings**
1811 -
1812 -|**Items**|**Settings**|**Note**
1813 -|Protocol|Omron EC55|
1814 -|Connection|RS485 (9600, 2, 7, EVEN)|
1815 -|Port No.|None|
1816 -|PLC station No.|0|
1817 -
1818 -**2)Address List**
1819 -
1820 -|**Type**|**Register**|**Device range**|**HMI range**|**Function**
1821 -|(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
1822 -|C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
1823 -|C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
1824 -|(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
1825 -|81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
1826 -|83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
1827 -|CP|-|0-6|Read controller intrinsic property
1828 -|CS|-|0-2|Read controller states
1829 -|CA|-|0-17|Action command
1830 -
1831 -**3)Device Settings**
1832 -
1833 -Omron E5CC PLC configuration
1834 -
1835 -After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
1836 -
1837 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_3d95e093792ba98a.png?width=550&height=229&rev=1.1||alt="12.PLC Protocol_html_3d95e093792ba98a.png" height="229" width="550"]]
1838 -
1839 -According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
1840 -
1841 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_be583aa69dd6cf4c.png?width=550&height=242&rev=1.1||alt="12.PLC Protocol_html_be583aa69dd6cf4c.png" height="242" width="550"]]
1842 -
1843 -**✎Note:** The communication settings for HMI should be consistent with this setting.
1844 -
1845 -**4)Configure the communication protocol**
1846 -
1847 -[[image:image-20220831161041-1.png]]
1848 -
1849 -**5)Cable Wiring**
1850 -
1851 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5e9a81a14106da9e.png?width=392&height=223&rev=1.1||alt="12.PLC Protocol_html_5e9a81a14106da9e.png" height="223" width="392"]]
1852 -
1853 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_1897d92be6948d58.png?width=393&height=223&rev=1.1||alt="12.PLC Protocol_html_1897d92be6948d58.png" height="223" width="393"]]
1854 -
1855 -**✎Note:**
1856 -
1857 -* COM3 only available in PI8000/PI9000 series.
1858 -* CA address could not support continuous writing function;
1859 -* Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
1860 -* When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
1861 -* When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
1862 -* Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
1863 -* When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
1864 -* Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
1865 -* [[image:image-20220831161356-1.png]]Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
1866 -
1867 -= Create communication with Xinje** PLC** =
1868 -
1869 -== **XC serial protocol** ==
1870 -
1871 -**1)V-BOX Settings**
1872 -
1873 -|**Item**|**Settings**|**Note**
1874 -|Protocol|XINJE XC MODBUS|
1875 -|Connection|RS232|
1876 -|Baud rate|19200|
1877 -|Data bit|8|
1878 -|Parity|EVEN|
1879 -|Stop bit|1|
1880 -|PLC station No.|1|
1881 -
1882 -**2)Address List**
1883 -
1884 -|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1885 -|Bit|M|M|M d|0~~8511|
1886 -|Bit|X|X|X o|0~~1747|
1887 -|Bit|Y|Y|Y o|0~~1747|
1888 -|Bit|S|S|S d|0~~1023|
1889 -|Bit|T|T|T d|0~~4095|
1890 -|Bit|C|C|C d|0~~634|
1891 -|Word|D|D|D d|0~~8511|
1892 -|Word|TD|TD|TD d|0~~618|
1893 -|Word|CD|CD|CD d|0~~634|
1894 -|Word|FD|FD|FD d|0~~8511|
1895 -
1896 -**3)Configure the communication protocol**
1897 -
1898 -
1899 -[[image:image-20220831163041-1.png]]
1900 -
1901 -**4)Cable Wiring**
1902 -
1903 -Figure
1904 -
1905 -[[image:image-20220831163406-2.png]][[image:image-20220831163422-3.png]]
1906 -
1907 -Pin Definition Diagram
1908 -
1909 -[[image:image-20220831163441-4.png]]
1910 -
1911 -== **XD serial protocol** ==
1912 -
1913 -**1)V-BOX Settings**
1914 -
1915 -Supported Series: Xinjie XD/XE Series PLC
1916 -
1917 -|**Item**|**Settings**|**Note**
1918 -|Protocol|XINJE XD/XC MODBUS|
1919 -|Connection|RS232|
1920 -|Baud rate|19200|
1921 -|Data bit|8|
1922 -|Parity|EVEN|
1923 -|Stop bit|1|
1924 -|PLC station No.|1|
1925 -
1926 -**2)Address List**
1927 -
1928 -|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1929 -|Bit|M|M|M d|0~~74999|
1930 -|Bit|X1xx|X1xx|X1xx o|0~~1177|
1931 -|Bit|X2xx|X2xx|X2xx o|0~~277|
1932 -|Bit|X|X|X o|0~~77|
1933 -|Bit|Y1xx|Y1xx|Y1xx o|0~~1177|
1934 -|Bit|Y2xx|Y2xx|Y2xx o|0~~277|
1935 -|Bit|Y|Y|Y o|0~~4095|
1936 -|Bit|SM|SM|SM d|0~~4999|(((
1937 -
1938 -)))
1939 -|Bit|T|T|T d|0~~4999|
1940 -|Bit|C|C|C d|0~~4999|
1941 -|Bit|ET|ET|ET d|0~~31|
1942 -|Bit|SE|SE|SE d|0~~31|
1943 -|Bit|HM|HM|HM d|0~~11999|
1944 -|Bit|HSC|HSC|HSC d|0~~39|
1945 -|Bit|HS|HS|HS d|0~~999|
1946 -|Bit|HT|HT|HT d|0~~1999|
1947 -|Bit|HC|HC|HC d|0~~1999|
1948 -|Bit|S|S|S d|0~~7999|
1949 -|Word|D|D|D d|0~~69999|
1950 -|Word|ID|ID|ID d|0~~99|
1951 -|Word|ID1xx|ID1xx|ID1xx d|0~~999|
1952 -|Word|ID2xx|ID2xx|ID2xx d|0~~299|
1953 -|Word|QD|QD|QD d|0~~99|
1954 -|Word|QD1xx|QD1xx|QD1xx d|0~~999|
1955 -|Word|QD2xx|QD2xx|QD2xx d|0~~299|
1956 -|Word|SD|SD|SD d|0~~4999|
1957 -|Word|TD|TD|TD d|0~~575|
1958 -|Word|CD|CD|CD d|0~~575|
1959 -|Word|ETD|ETD|ETD d|0~~31|
1960 -|Word|HD|HD|HD d|0~~24999|
1961 -|Word|HSD|HSD|HSD d|0~~1023|
1962 -|Word|HTD|HTD|HTD d|0~~95|
1963 -|Word|HCD|HCD|HCD d|0~~95|
1964 -|Word|HSCD|HSCD|HSCD d|0~~31|
1965 -|Word|FD|FD|FD d|0~~8191|
1966 -|Word|SFD|SFD|SFD d|0~~5999|
1967 -|Word|FS|FS|FS d|0~~47|
1968 -
1969 -**3)Configure the communication protocol**
1970 -
1971 -[[image:image-20220831163923-7.png]]
1972 -
1973 -
1974 -
1975 -**4)Cable Wiring**
1976 -
1977 -Figure
1978 -
1979 -[[image:image-20220831163406-2.png]][[image:image-20220831163553-6.png]]
1980 -
1981 -Pin Definition Diagram
1982 -
1983 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830160232-3.png?rev=1.1||alt="image-20220830160232-3.png"]]
1984 -
1985 -= Create communication with **Schneider PLC** =
1986 -
1987 -== **Schneider MODBUS RTU** ==
1988 -
1989 -**1)V-BOX Setting**
1990 -
1991 -|=**Parameters**|=**Recommended**|=**Notes**
1992 -|**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
1993 -|**Connection**|RS485|
1994 -|**Baud rate**|19200|
1995 -|**Data bit**|8|
1996 -|**Parity**|Even|
1997 -|**Stop bit**|1|
1998 -|**PLC station No.**|1|
1999 -
2000 -**2)Address List**
2001 -
2002 -|=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2003 -|B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
2004 -|B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
2005 -|B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
2006 -|W|MW|DDDDDD|0 ~~ 999999|Output register
2007 -|DW|MD|DDDDDD|0 ~~ 999999|Output register
2008 -
2009 -**3)Configure the communication protocol**
2010 -
2011 -[[image:image-20220902104329-1.png]]
2012 -
2013 -**4)Cable Wiring**
2014 -
2015 -**RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
2016 -
2017 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220817154212-1.jpeg?width=554&height=315&rev=1.1||alt="image-20220817154212-1.jpeg" height="315" width="554"]]
2018 -
2019 -= Create communication with Inovance** PLC** =
2020 -
2021 -== **H3U serial protocol** ==
2022 -
2023 -**1)V-BOX Settings**
2024 -
2025 -|**Item**|**Settings**|**Note**
2026 -|Protocol|INOVANCE H3U PLC|
2027 -|Connection|RS422|
2028 -|Baud rate|9600|
2029 -|Data bit|7|
2030 -|Parity|EVEN|
2031 -|Stop bit|1|
2032 -|PLC station No.|0|
2033 -
2034 -**2)Address List**
2035 -
2036 -|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
2037 -|Bit|X|X|X o|0~~303237|
2038 -|Bit|Y|Y|Y o|0~~303237|
2039 -|Bit|M|M|M d|0~~99999|
2040 -|Bit|T|T|T d|0~~99999|
2041 -|Bit|C|C|C d|0~~99999|
2042 -|Bit|SM|SM|SM d|8000~~999|
2043 -|Bit|S|T|S d|0~~99999|
2044 -|Bit|Lamp|Lamp|Lamp d|0~~0|
2045 -|Word|X|X|X o|0~~303237|
2046 -|Word|Y|Y|Y o|0~~303237|
2047 -|Word|M|M|M d|0~~99999|
2048 -|Word|T|T|T d|0~~99999|
2049 -|Word|C|C|C d|0~~199|
2050 -|Word|D|D|D d|0~~7999|
2051 -|Word|S|S|S d|0~~99999|
2052 -|Word|SD|SD|SD d|8000~~9999|
2053 -|Word|R|R|R d|0~~32767|
2054 -
2055 -**3)Configure the communication protocol**
2056 -
2057 -[[image:image-20220831164626-1.png]]
2058 -
2059 -
2060 -
2061 -**4)Cable Wiring**
2062 -
2063 -Figure
2064 -
2065 -[[image:image-20220831164646-2.png]][[image:image-20220831164700-3.png]]
2066 -
2067 -Pin Definition Diagram
2068 -
2069 -[[image:image-20220831164731-4.png]]
2070 -
2071 -= Create communication with Panasonic** PLC** =
2072 -
2073 -== **FP serial protocol** ==
2074 -
2075 -**1)V-BOX Settings**
2076 -
2077 -|**Item**|**Settings**|**Note**
2078 -|Protocol|Panasonic FP MFWTOCOL|
2079 -|Connection|RS232|
2080 -|Baud rate|9600|
2081 -|Data bit|8|
2082 -|Parity|ODD|
2083 -|Stop bit|1|
2084 -|PLC station No.|1|
2085 -
2086 -**2)Address List**
2087 -
2088 -|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
2089 -|Bit|X|X|X d|0~~9999|
2090 -|Bit|Y|Y|Y d|0~~9999|
2091 -|Bit|R|R|R d|0~~9999|
2092 -|Bit|T|T|T d|0~~9999|
2093 -|Bit|C|C|C d|0~~9999|
2094 -|Bit|L|L|L d|0~~9999|
2095 -|Word|WX|WX|WX d|0~~9999|
2096 -|Word|WY|WY|WY d|0~~9999|
2097 -|Word|WR|WR|WR d|0~~9999|
2098 -|Word|WL|WL|WL d|0~~9999|
2099 -|Word|LD|LD|LD d|0~~9999|
2100 -|Word|DT|DT|DT d|0~~65535|
2101 -|Word|FL|FL|FL d|0~~9999|
2102 -|Word|EV|EV|EV d|0~~9999|
2103 -|Word|SV|SV|SV d|0~~9999|
2104 -
2105 -**3)Configure the communication protocol**
2106 -
2107 -[[image:image-20220831165238-4.png]]
2108 -
2109 -
2110 -
2111 -**4)Cable Wiring**
2112 -
2113 -Figure
2114 -
2115 -[[image:image-20220831165031-3.png]][[image:image-20220831165017-2.png]]
2116 -
2117 -Pin Definition Diagram
2118 -
2119 -[[image:image-20220831165008-1.png]]
2120 -
2121 -= Create communication with LS** PLC** =
2122 -
2123 -== **XBC serial protocol** ==
2124 -
2125 -**1)V-BOX Settings**
2126 -
2127 -|**Item**|**Settings**|**Note**
2128 -|Protocol|LS XBC CNet|
2129 -|Connection|RS232|
2130 -|Baud rate|115200|
2131 -|Data bit|8|
2132 -|Parity|NONE|
2133 -|Stop bit|1|
2134 -|PLC station No.|1|
2135 -
2136 -**2)Address List**
2137 -
2138 -|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
2139 -|Bit|P|P|P d|0~~2047|
2140 -|Bit|M|M|M d|0~~2047|
2141 -|Bit|L|L|L d|0~~11263|
2142 -|Bit|K|K|K d|0~~16183|
2143 -|Bit|F|F|F d|0~~2047|
2144 -|Bit|D|D|D d|0~~32767|
2145 -|Bit|R|R|R d|0~~32767|
2146 -|Bit|U|U|U d|0~~4095|
2147 -|Word|P|P|P d|0~~2047|
2148 -|Word|M|M|M d|0~~2047|
2149 -|Word|L|L|L d|0~~11263|
2150 -|Word|K|K|K d|0~~16183|
2151 -|Word|F|F|F d|0~~2047|
2152 -|Word|C|C|C d|0~~2047|
2153 -|Word|T|T|T d|0~~2047|
2154 -|Word|D|D|D d|0~~32767|
2155 -|Word|N|N|N d|0~~21503|
2156 -|Word|R|R|R d|0~~32767|
2157 -|Word|U|U|U d|0~~4095|
2158 -|Word|Z|Z|Z d|0~~127|
2159 -|Word|S|S|S d|0~~127|
2160 -
2161 -**3)Configure the communication protocol**
2162 -
2163 -[[image:image-20220831170147-1.png]]
2164 -
2165 -**4)Cable Wiring**
2166 -
2167 -Figure
2168 -
2169 -[[image:image-20220831170306-4.png]][[image:image-20220831170254-3.png]]
2170 -
2171 -Pin Definition Diagram
2172 -
2173 -[[image:image-20220831170215-2.png]]
2174 -
2175 -== **XGK FEnet Ethernet protocol** ==
2176 -
2177 -Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
2178 -
2179 -**1)V-BOX Settings**
2180 -
2181 -|**Items**|**Settings**|**Note**
2182 -|Protocol|LG XGK FEnet(Ethernet)|
2183 -|Connection|Ethernet|
2184 -|Port No.|2004|
2185 -
2186 -**2)Address List**
2187 -
2188 -|**Type**|**Register**|**Range**|**Format**|**Note**
2189 -|(% rowspan="14" %)Word|P|0~~2047|P d|
2190 -|M|0~~2047|M d|
2191 -|K|0~~2047|K d|
2192 -|F|0~~2047|F d|
2193 -|T|0~~2047|T d|
2194 -|C|0~~2047|C d|
2195 -|Z|0~~127|Z d|
2196 -|S|0~~127|S d|
2197 -|L|0~~11263|L d|
2198 -|N|0~~21503|N d|
2199 -|D|0~~32767|D d|
2200 -|R|0~~32767|R d|
2201 -|ZR|0~~65535|ZR d|
2202 -|UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
2203 -
2204 -**✎Note:**
2205 -
2206 -* In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
2207 -* The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
2208 -* All bit registers are in the form of bits in word, and the range is the same as the word register;
2209 -
2210 -**3)Communication Settings**
2211 -
2212 -[[image:image-20220831171127-1.png]]
2213 -
2214 -**4)Cable Wiring**
2215 -
2216 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2217 -
2218 -= Create communication with INVT PLC =
2219 -
2220 -**1)V-BOX setting**
2221 -
2222 -|**Item**|**Settings**|**Note**
2223 -|Protocol|INVT_IVC2L|
2224 -|Connection|RS232|
2225 -|Baud rate|19200|
2226 -|Data bit|8|
2227 -|Parity|EVEN|
2228 -|Stop bit|1|
2229 -|PLC station No.|1
2230 -
2231 -**2)Address List**
2232 -
2233 -
2234 -|**Type**|**Device registers**|**Format**|**Range**|**Note**
2235 -|(% colspan="1" rowspan="7" %)Bit|X|XOOO|0~~377|
2236 -|Y|YOOO|0~~377|
2237 -|M|MDDDD|0~~1999|
2238 -|SM|SMDDD|0~~255|
2239 -|S|SDDD|0~~991|
2240 -|T|TDDD|0~~255|
2241 -|C|CDDD|0~~255|
2242 -|(% rowspan="5" %)Word|D|DDDDD|0~~7999|
2243 -|SD|SDDDD|0~~255|
2244 -|Z|ZDD|0~~15|
2245 -|T|TDDD|0~~255|
2246 -|C|CDDD|0~~199|
2247 -|Double word|C|CDDD|200~~255|
2248 -
2249 -**3)Communication Settings**
2250 -
2251 -(% style="text-align:center" %)
2252 -[[image:盒子创建英威腾.png]]
2253 -
2254 -**4)PLC software**
2255 -
2256 -(% style="text-align:center" %)
2257 -[[image:英威腾软件.png]]
2258 -
2259 -**5)PLC setting **
2260 -
2261 -Open the INVI plc software, create a new project or open a project that has already been created
2262 -
2263 -(% style="text-align:center" %)
2264 -[[image:英威腾创建1.png]]
2265 -
2266 -Configure serial port parameters.
2267 -
2268 -(% style="text-align:center" %)
2269 -[[image:英威腾创建2.png]]
2270 -
2271 -PC connect PLC
2272 -
2273 -(% style="text-align:center" %)
2274 -[[image:英威腾创建3.png]]
2275 -
2276 -Download
2277 -
2278 -(% style="text-align:center" %)
2279 -[[image:英威腾下载.png]]
2280 -
2281 -**6)Cable Wiring**
2282 -
2283 -(% style="text-align:center" %)
2284 -[[image:wire.png]]
2285 -
2286 -= Create communication with **Modbus ** =
2287 -
2288 -== **MODBUS RTU Slave (All function)** ==
2289 -
2290 -Select the protocol "Modbus RTU Slave (All Fuction)",
2291 -
2292 -Then set baud rate, port, stop bits, data bits, parity.
2293 -
2294 -(% style="text-align:center" %)
2295 -[[image:1624342015914-382.png||height="486" width="800" class="img-thumbnail"]]
2296 -
2297 -== **Communicate with Modbus Meter** ==
2298 -
2299 -The following example is using the Linfee meter LNF96EY to demonstrate how to set up the Modbus communication.
2300 -
2301 -~1. Wiring the RS485 cable first. Because the pin 58 is A, the pin 59 is B for meter. Here we use the COM1 to connect. So the diagram like follows:
2302 -
2303 -(% style="text-align:center" %)
2304 -[[image:LinfeeTerminalDiagram.png]]
2305 -
2306 -2. Check the specific Modbus parameter in the communication menu from LED display.
2307 -
2308 -So from the following pictures, we can know the Meter Address is 85, Baud rate is 9600, CRC None.
2309 -
2310 -{{info}}
2311 -**✎Note: **Meter address usually corresponding to the Modbus Slave Station No. on the Modbus communication.
2312 -{{/info}}
2313 -
2314 -(% style="text-align:center" %)
2315 -[[image:MeterModbusAllView.png]]
2316 -
2317 -(% class="wikigeneratedid" %)
2318 -3. Set up the communication in the Configuration tab.
2319 -
2320 -(% class="wikigeneratedid" %)
2321 -Select the protocol as **ModBus RTU Slave (All Function)**. And set the communication parameters like below.
2322 -
2323 -(% style="text-align:center" %)
2324 -[[image:VNETCommunicationtabmeter.png]]
2325 -
2326 -(% class="wikigeneratedid" %)
2327 -4. Create new real-time monitoring tag accroding to Modbus manual
2328 -
2329 -(% class="wikigeneratedid" %)
2330 -Enter the address we want to read from the meter. The following table is intercept part of the manual for Linfee Modbus manual.
2331 -
2332 -(% class="wikigeneratedid" %)
2333 -**0x03/0x04 command data register address**:
2334 -
2335 -(% style="width:1142.22px" %)
2336 -|(% style="display:none" %) |=(% colspan="2" rowspan="1" style="width: 165px;" %)Address(% style="display:none" %) |=Description|=Data Format|=(% style="width: 254px;" %)Data Length(Word)|=(% style="width: 282px;" %)Remark
2337 -|(%%)(% style="display:none" %) (%%) HEX|(% style="width:107px" %)DEC|(%%)(% style="display:none" %) (%%) |(% style="width:100px" %) |(%%)(% style="display:none" %) (%%) |(% style="width:318px" %)
2338 -|(% style="width:107px" %)0x00|(% style="width:100px" %)0|Reserved| | |(% style="width:318px" %)
2339 -|(% style="width:107px" %)0x02|(% style="width:100px" %)2|Reserved| | |(% style="width:318px" %)
2340 -|(% style="width:107px" %)0x04|(% style="width:100px" %)4|Reserved| | |(% style="width:318px" %)
2341 -|(% style="width:107px" %)0x06|(% style="width:100px" %)6|Ua|float|2|(% style="width:318px" %)Phase Voltage data, Unit V
2342 -|(% style="width:107px" %)0x08|(% style="width:100px" %)8|Ub|float|2|(% style="width:318px" %)Phase Voltage data, Unit V
2343 -|(% style="width:107px" %)0x0A|(% style="width:100px" %)10|Uc|float|2|(% style="width:318px" %)Phase Voltage data, Unit V
2344 -|(% style="width:107px" %)0x0C|(% style="width:100px" %)12|Uab|float|2|(% style="width:318px" %)Line Voltage data, Unit V
2345 -|(% style="width:107px" %)0x0E|(% style="width:100px" %)14|Ubc|float|2|(% style="width:318px" %)Line Voltage data, Unit V
2346 -|(% style="width:107px" %)0x10|(% style="width:100px" %)16|Uca|float|2|(% style="width:318px" %)Line Voltage data, Unit V
2347 -|(% style="width:107px" %)0x12|(% style="width:100px" %)18|Ia|float|2|(% style="width:318px" %)Phase Current data, Unit A
2348 -|(% style="width:107px" %)0x14|(% style="width:100px" %)20|Ib|float|2|(% style="width:318px" %)Phase Current data, Unit A
2349 -|(% style="width:107px" %)0x16|(% style="width:100px" %)22|Ic|float|2|(% style="width:318px" %)Phase Current data, Unit A
2350 -
2351 -{{info}}
2352 -**✎Note: **We usually use the Data Type 4 for read the Modbus registers(Function Code 03)
2353 -{{/info}}
2354 -
2355 -For example, here we want to read the Phase Voltage Ua (Modbus offset 0006), the Modbus register main No. requires input decimal number, and check whether the actual address has one address offset, so the tag configured like the following screenshot:
2356 -
2357 -(% style="text-align:center" %)
2358 -[[image:VNETModbusTagSettings.png]]
2359 -
2360 -(% style="text-align:center" %)
2361 -[[image:VNETModbusTagByteSettings.png]]
2362 -
2363 -{{info}}
2364 -**✎Note: **If the read value is incorrect, please check whether need to change the Byte order.
2365 -{{/info}}
2366 -
2367 -Set the Modbus Slave Station No.
2368 -
2369 -(% style="text-align:center" %)
2370 -[[image:ModbusStationSettings.png]]
2371 -
2372 -If the communication is setup successfully, the tag will show green light.
2373 -
2374 -(% style="text-align:center" %)
2375 -[[image:Monitoringtaggreenlight.png]]
2376 -
2377 -== **MODBUS RTU Master** ==
2378 -
2379 -Select the protocol "Modbus RTU Master",
2380 -
2381 -Then set baud rate, port, stop bits, data bits, parity
2382 -
2383 -(% style="text-align:center" %)
2384 -[[image:1624348709622-711.png||queryString="width=809&height=493" height="488" width="800" class="img-thumbnail"]]
2385 -
2386 -**address list**
2387 -
2388 -(% class="table-bordered" %)
2389 -|=(% scope="row" %)**Type**|=**Data Type**|=**Function code and description**
2390 -|(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (Read Input Registers: Read the current binary value in one or more input registers)
2391 -|06 (write single register: write a binary value to a holding register)
2392 -|10 (write values to multiple addresses )
2393 -|(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
2394 -|06 (write single register: write a binary value to a holding register)
2395 -|10 (write values to multiple addresses )
2396 -|(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
2397 -|06 (write single register: write a binary value to a holding register)
2398 -|10 (write values to multiple addresses )
2399 -|(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
2400 -|10 (write values to multiple addresses )
2401 -|(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
2402 -|05 (Force a single coil to force the on/off state of a logic coil)
2403 -|0F (Write multiple bits, ie write continuously)
2404 -|(% rowspan="3" %)1|02 (Read the input state)
2405 -|05 (Force a single coil to force the on/off state of a logic coil)
2406 -|0F (Write multiple bits)
2407 -|(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
2408 -|05 (Force a single coil to force the on/off state of a logic coil)
2409 -|0F (Write multiple bits)
2410 -|(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
2411 -|0F (Write multiple bits)
2412 -
2413 -== **MODBUS TCP Slave (All function)** ==
2414 -
2415 -Supported series: MODBUS TCP controller
2416 -
2417 -V-B0X works as MODBUS TCP MASTER connecting with TCP SLAVE
2418 -
2419 -**1)V-BOX Setting**
2420 -
2421 -|**Items**|**Settings**|**Note**
2422 -|Protocol|MODBUS TCP Slave (All function)|
2423 -|Connection|Ethernet|
2424 -|Port No.|502|
2425 -|PLC station No.|1
2426 -
2427 -**2)Address List**
2428 -
2429 -|=**Type**|=**Data Type**|=**Function code & Description**
2430 -|(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
2431 -|06 (write single register: write a binary value to a holding register)
2432 -|10 (write values to multiple addresses )
2433 -|(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
2434 -|06 (write single register: write a binary value to a holding register)
2435 -|10 (write values to multiple addresses )
2436 -|(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
2437 -|06 (write single register: write a binary value to a holding register)
2438 -|10 (write values to multiple addresses )
2439 -|(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
2440 -|10 (write values to multiple addresses )
2441 -|(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
2442 -|05 (Force a single coil to force the on/off state of a logic coil)
2443 -|0F (Write multiple bits, ie write continuously)
2444 -|(% rowspan="3" %)1|02 (Read the input state)
2445 -|05 (Force a single coil to force the on/off state of a logic coil)
2446 -|0F (Write multiple bits)
2447 -|(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
2448 -|05 (Force a single coil to force the on/off state of a logic coil)
2449 -|0F (Write multiple bits)
2450 -|(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
2451 -|0F (Write multiple bits)
2452 -
2453 -**3)Communication Settings**
2454 -
2455 -Configure V-BOX Ethernet IP in Networking Settings
2456 -
2457 -[[image:image-20220902111833-3.png]]
2458 -
2459 -
2460 -Configure PLC Ethernet IP in Communication;
2461 -
2462 -[[image:image-20220902111121-1.png]]
2463 -
2464 -**4)Cable Wiring**
2465 -
2466 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2467 -
2468 -== **communicate with VB inverter** ==
2469 -
2470 -[[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20VB%20inverter.zip]]
2471 -
2472 -= **User define protocol** =
2473 -
2474 -More serial port script instruction,please refer manual:[[Lua script function>>doc:V-BOX.V-Net.Manual.04 Lua Script.01 Lua Functions.WebHome]]~-~-->[[3.Serial port operation>>url:http://docs.we-con.com.cn/wiki/vbox/view/HMI/04.Lua%20script%20%20function%20and%20operation/01.Lua%20script%20function/#H3.Serialportoperation]]
2475 -
2476 -== **Read the temperature sensor.** ==
2477 -
2478 -the commond format is as beliow:
2479 -
2480 -Send commond:01 03 02 00 00 03 04 73
2481 -
2482 -Feedback commond:01 03 06 07 F7 0E 7E B7 35
2483 -
2484 -Temperature data:07 F7,desimal = 2039,it means temperature is 20.39℃.
2485 -
2486 -Humidity data:0E 7E,desimal = 3710, it mean humidity is 37.10%RH.
2487 -
2488 -Script Demo:
2489 -
2490 -~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~--
2491 -
2492 -function com.main()
2493 - ~-~-dosomething
2494 - openPlc()
2495 - end
2496 - function openPlc()
2497 - if obj then
2498 - ~-~- If the serial port opened,then read/write data by timing
2499 -
2500 - local wri = string.pack(">HHHH",0X0103,0X0200,0X0003,0X0473)
2501 - local arr = reading(wri)
2502 - ~-~- if arr ~~=nil then
2503 - ~-~- if arr[1] ==33 and arr[2] ==v[2][2] and arr[3] ==v[2][3] then
2504 - ~-~- local A = arr[4]*256
2505 - ~-~- local B = A+arr[5]
2506 - ~-~- addr_setword(v[1],B)
2507 - ~-~- end
2508 - ~-~- end
2509 -
2510 - else
2511 - ~-~-judge if there is a serial object, then initialize and open the serial port
2512 - local configs = {
2513 - name = 'COM1', ~-~-Select serial port COM1
2514 - mode = 485, ~-~-Communication mode RS485
2515 - baud_rate = 9600, ~-~-Baud rate 9600
2516 - stop_bit = 1, ~-~-stop bit 1
2517 - data_len = 8, ~-~-data length 8
2518 - check_bit = 'NONE', ~-~-no parity
2519 -
2520 - }
2521 - obj,err = serial.open(configs) ~-~-Open serial port
2522 - if not obj then
2523 - print("serial open :failed", err) ~-~- Open serial port failed
2524 - end
2525 - end
2526 - end
2527 -
2528 - function reading(wri)
2529 - obj:flush() ~-~- Clear serial port
2530 - obj:write(wri) ~-~- Write serial port
2531 - print(string.byte(wri,1,#wri))
2532 - obj:flush() ~-~- Clear serial port 
2533 - local readed =obj:read(9,1000) ~-~- Read 9 bytes, timeout 1 second
2534 - if readed and readed ~~= "" then 
2535 - ~-~- judge that a non-empty string is read
2536 - print(string.byte(readed,1,#readed))
2537 - a={string.byte(readed, 1, #readed)}
2538 - if nil ~~= a[4] and nil ~~= a[5] and nil ~~= a[6] and nil ~~= a[7] then
2539 - a1=a[4]*256+a[5]
2540 - a2=a[6]*256+a[7]
2541 - addr_setword("@HDW0",a1)
2542 - addr_setword("@HDW1",a2)
2543 - end
2544 - return {string.byte(readed, 1, #readed)}
2545 - elseif readed == nil then
2546 - print("serial read err:", err or "")
2547 - return nil
2548 - end
2549 - return nil
2550 - end
2551 -
2552 -~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-