1 -= WECON =
2 -
3 -== **LX3V Serial ** ==
4 -
5 -Supported series: Wecon LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
6 -
7 -**1)V-BOX setting**
8 -
9 -|**Item**|**Settings**|**Note**
10 -|Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
11 -|Connection|RS422/RS485|
12 -|Baud rate|9600|
13 -|Data bit|7|
14 -|Parity|EVEN|
15 -|Stop bit|1|
16 -|PLC station No.|1|
17 -
18 -**2)Address List**
19 -
20 -
21 -|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
22 -|(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
23 -|Y|Y|Y o|0~~303237|
24 -|M|M|M d|0~~99999|
25 -|T|T|T d|0~~99999|
26 -|C|C|C d|0~~99999|
27 -|S|S|S d|0~~99999|
28 -|(% rowspan="8" %)Word|X|X|Xo|0~~303237|
29 -|Y|Y|Y o|0~~303237|
30 -|M|M|M d|0~~99999|
31 -|T|T|T d|0~~99999|
32 -|C|C|C d|0~~199|
33 -|D|D|D d|0~~7999|
34 -|S|S|S d|0~~99999|
35 -|SD|SD|SD d|8000~~9999|
36 -
37 -**3)Configure the communication protocol**
38 -
39 -[[image:image-20220824152217-1.png||alt="图片-20220824152217-1.png"]]
40 -
41 -**4)Cable Wiring**
42 -
43 -* **RS422**
44 -
45 - [[image:image-20220824120614-5.png]]
46 -
47 -* **RS485**
48 -
49 - [[image:image-20220824120524-3.png]]
50 -
51 -== **LX5V Serial ** ==
52 -
53 -This example introduces the establishment of serial port communication between V-BOX and LX5V. It is introduced through three parts: PLC software configuration, V-BOX software configuration, and hardware wiring.
54 -
55 -**Software configuration of PLC**
56 -
57 -**1)PLC programming software**
58 -
59 -[[image:image-20220824142722-1.png]]
60 -
61 -**2)New PLC project**
62 -
63 -Click New Project and select the PLC model.
64 -
65 -[[image:image-20220822172623-2.png]]
66 -
67 -**3)Set Serial port parameters**
68 -
69 -Follow the steps below to configure Serial port parameters
70 -
71 -Baud rate:115200
72 -
73 -Data bit:8
74 -
75 -Stop bit:1
76 -
77 -Parity:No verification
78 -
79 -[[image:image-20220822172657-3.png]]
80 -
81 -**4)Registers list**
82 -
83 -[[image:image-20220822172730-4.png]]
84 -
85 -**V-BOX software configuration**
86 -
87 -**1)V-BOX programming software**
88 -
89 - [[image:image-20220824104124-1.png]]
90 -
91 -**2)V-NET add device**
92 -
93 -Open V-NET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the access key, password and remark, to add the device.
94 -
95 -[[image:image-20220824104909-2.png]]
96 -
97 -**3)Set communication port parameters**
98 -
99 -Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
100 -
101 -Baud rate:115200
102 -
103 -Data bit:8
104 -
105 -Stop bit:1
106 -
107 -Parity:No verification
108 -
109 -[[image:image-20220824142130-1.png]]
110 -
111 -**hardware connection**
112 -
113 -**1)Hardware wiring diagram**
114 -
115 -[[image:image-20220824142546-2.png]]
116 -
117 -[[image:image-20220824142643-3.png]]
118 -
119 -The above are all the steps for establishing serial port communication between V-BOX with LX5V PLC.
120 -
121 -== **LX5V-N Ethernet ** ==
122 -
123 -This example introduces the establishment of Ethernet communication between V-BOX and LX5V-N. It is introduced through three parts: PLC software configuration, V-BOX software configuration, and hardware wiring.
124 -
125 -**Software configuration of PLC**
126 -
127 -**1)PLC programming software**
128 -
129 -[[image:image-20220824142722-1.png]]
130 -
131 -**2)New PLC project**
132 -
133 -Click New Project and select the PLC model.
134 -
135 -[[image:image-20220824143613-1.png]]
136 -
137 -**3)Set Ethernet port parameters**
138 -
139 -Follow the steps below to configure Ethernet parameters
140 -
141 -PLC IP address:192.168.39.200
142 -
143 -default gateway:192.168.39.1
144 -
145 -subnet mask:255.255.255.0
146 -
147 -[[image:image-20220824143744-2.png]]
148 -
149 -**4)Registers list**
150 -
151 -[[image:image-20220822172730-4.png]]
152 -
153 -(% id="cke_bm_22473S" style="display:none" %)** **(%%)**V-BOX software configuration**
154 -
155 -**1)V-BOX programming software**
156 -
157 - [[image:image-20220824104124-1.png]]
158 -
159 -**2)V-NET add device**
160 -
161 -Open V-NET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the access key, password and remark, to add the device.
162 -
163 -[[image:image-20220824104909-2.png]]
164 -
165 -**3)Set communication Protocol**
166 -
167 -Click Communication to configure the LX5V plc protocol and IP address.
168 -
169 -[[image:image-20220824144619-1.png]]
170 -
171 -**hardware connection**
172 -
173 -**1)Hardware wiring diagram**
174 -
175 -[[image:image-20220824151127-2.png]]
176 -
177 -The above are all the steps for establishing ethernet communication between V-BOX with LX5V PLC.
178 -
179 -= Allen-Bradley(**Rockwell**) =
180 -
181 -== **DF1 Advanced  Serial** ==
182 -
183 -MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
184 -
185 -**1) V-Box Settings**
186 -
187 -|=Item|=Recommended |=Note
188 -|=Protocol|Allen Bradley DF1 Advanced|
189 -|=Connection|RS232|
190 -|=Baud rate|19200|
191 -|=Stop bits|1|
192 -|=Data bits|8|
193 -|=Parity|None|
194 -|=PLC Station No.|1|
195 -|=HMI Station No.|0|
196 -
197 -**2) Address List**
198 -
199 -|=**Type**|=**Device registers**|=**Format**|=**Range**|=Note
200 -|(% colspan="1" rowspan="7" %)Bit|I1|I1ddd.dd|0.0~~255.15|Only able to communicate with file number I1
201 -|O0|O0ddd.dd|0.0~~255.15|Only able to communicate with file number O0
202 -|S2|S2ddd.dd|0.0~~255.15|Only able to communicate with file number S2
203 -|B3|B3ddd.dd|0.0~~255.15|Only able to communicate with file number B3
204 -|BN|BNddddd.dd|0.0~~99255.15|(((
205 -Bit data file B0~~B99
206 -
207 -First two digits is for file number
208 -
209 -For example, BN13001.00 represents file number B13, address 001, the 0th bit.
210 -)))
211 -|N7|N7ddd.dd|0.0~~255.15|Only able to communicate with file number N7
212 -|NN|NNddddd.dd|0.0~~99255.15|(((
213 -Integer data file bit format N0~~N99
214 -
215 -First two digits is for file number
216 -
217 -For example, NN13001.00 represents file number N13, address 001, the 0th bit.
218 -)))
219 -|(% rowspan="11" %)Word|S2|S2ddd|0~~255|Only able to communicate with file number S2
220 -|T4S|T4Sddd|0~~255|Only able to communicate with file number T4 (Timer Preset Value)
221 -|T4P|T4Pddd|0~~255|Only able to communicate with file number T4 (Timer Accumulator Value)
222 -|TNS|TNSddddd|0~~99255|(((
223 -Timer Preset Value
224 -
225 -First two digits is for file number
226 -
227 -For example, TNS99255 represents file number T99, address 255.
228 -)))
229 -|TNP|TNPddddd|0~~99255|(((
230 -Timer Accumulator Value
231 -
232 -First two digits is for file number
233 -
234 -For example, TNP99255 represents file number T99, address 255.
235 -)))
236 -|C5S|C5Sddd|0~~255|Only able to communicate with file number C5 (Counter Preset Value)
237 -|C5P|C5Pddd|0~~255|Only able to communicate with file number C5 (Counter Accumulator Value)
238 -|CNS|CNSddddd|0~~99255|(((
239 -Counter Preset Value
240 -
241 -First two digits is for file number
242 -
243 -For example, CNS99255 represents file number C99, address 255.
244 -)))
245 -|CNP|CNPddddd|0~~99255|(((
246 -Counter Accumulator Value
247 -
248 -First two digits is for file number
249 -
250 -For example, CNP99255 represents file number C99, address 255.
251 -)))
252 -|N7|N7ddd|0~~255|Only able to communicate with file number N7
253 -|NN|NNddd|0~~99255|(((
254 -Integer data file
255 -
256 -First two digits is for file number
257 -
258 -For example, NN99255 represents file number N99, address 255.
259 -)))
260 -|(% colspan="1" rowspan="3" %)Double Word|F8|F8ddd|0~~255|(((
261 -Only able to communicate with file number N7
262 -)))
263 -|FN|FNddddd|0~~99255|(((
264 -Floating point data file
265 -
266 -First two digits is for file number
267 -
268 -For example, FN99255 represents file number F99, address 255.
269 -)))
270 -|LN|LNddddd|0~~99255|Long
271 -
272 -**3) Cable Wiring**
273 -
274 -(% style="text-align:center" %)
275 -[[image:ABRS232.gif]]
276 -
277 -(% class="wikigeneratedid" id="HMicroLogixA0Protocol" %)
278 -(% id="cke_bm_5621S" style="display:none" %)** **
279 -
280 -== **MicroLogix Serial** ==
281 -
282 -(% class="wikigeneratedid" %)
283 -MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
284 -
285 -**1)V-BOX setting**
286 -
287 -|**Item**|**Settings**|**Note**
288 -|Protocol|Allen-Bradley DF1 Advanced|
289 -|Connection|RS232|
290 -|Baud rate|19200|
291 -|Data bit|8|
292 -|Parity|None|
293 -|Stop bit|1|
294 -|PLC station No.|1|
295 -
296 -**2)Address List**
297 -
298 -|**Type**|**Device registers**|**Format**|**Range**|**Note**
299 -|(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
300 -|O|O d.d|0.0~~255.15|
301 -|B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
302 -|S|S d.d|0.0~~255.15|
303 -|N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
304 -|(% rowspan="9" %)Word|S|S d|0~~255|
305 -|TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
306 -|TP|TP nnhh|0~~ffff
307 -|CS|CS nnhh|0~~ffff
308 -|CP|CP nnhh|0~~ffff
309 -|N|N nnhh|0~~ffff
310 -|C|C nnhh|0~~ffff
311 -|T|T nnhh|0~~ffff
312 -|R|R nnhh|0~~ffff
313 -
314 -**3)Configure the communication protocol**[[image:image-20220824152928-1.png]]
315 -
316 -**4)Configure the communication protocol**
317 -
318 -[[image:image-20220824110724-1.png]]
319 -
320 -== **Micro850_FreeTag Ethernet** ==
321 -
322 -(((
323 -(((
324 -This example introduces the establishment of Ethernet communication between Wecon V-box and CompactLogix L1769. It is introduced through three parts: PLC software configuration, V-box software configuration, and hardware wiring.
325 -)))
326 -)))
327 -
328 -(((
329 -(% class="wikigeneratedid" id="HSoftwareconfigurationofPLC" %)
330 -(((
331 -**Software configuration of PLC**
332 -)))
333 -
334 -(% class="wikigeneratedid" id="HPLCprogrammingsoftware" %)
335 -(((
336 -**1)PLC programming software**
337 -)))
338 -
339 -[[image:image-20220714162600-1.png]]
340 -
341 -(% class="wikigeneratedid" id="HNewPLCproject" %)
342 -(((
343 -**2)New PLC project**
344 -)))
345 -
346 -(((
347 -(((
348 -Click New Project and select the PLC model.
349 -)))
350 -)))
351 -
352 -(((
353 -[[image:image-20220714162617-2.png]]
354 -)))
355 -
356 -(((
357 -
358 -
359 -[[image:image-20220714162652-4.png]]
360 -)))
361 -
362 -(((
363 -(% class="wikigeneratedid" id="HSetEthernetparameters" %)
364 -(((
365 -**3)Set Ethernet parameters**
366 -)))
367 -
368 -(((
369 -(((
370 -(((
371 -Follow the steps below to configure Ethernet parameters
372 -)))
373 -)))
374 -)))
375 -
376 -(((
377 -(((
378 -(((
379 -PLC IP address:192.168.40.101
380 -)))
381 -)))
382 -)))
383 -
384 -(((
385 -(((
386 -(((
387 -default gateway:192.168.40.1
388 -)))
389 -)))
390 -)))
391 -
392 -(((
393 -(((
394 -(((
395 -subnet mask:255.255.255.0
396 -)))
397 -)))
398 -)))
399 -
400 -(((
401 -[[image:image-20220714162713-5.png]]
402 -)))
403 -
404 -(((
405 -
406 -)))
407 -
408 -(((
409 -(% class="wikigeneratedid" id="HV-boxsoftwareconfiguration" %)
410 -(((
411 -**V-box software configuration**
412 -)))
413 -
414 -(% class="wikigeneratedid" id="HV-boxprogrammingsoftware" %)
415 -(((
416 -**1)V-box programming software**
417 -)))
418 -
419 -(% class="wikigeneratedid" %)
420 -(((
421 - [[image:image-20220714162725-6.png]]
422 -)))
423 -
424 -(% class="wikigeneratedid" id="HConfiguredevicenetwork" %)
425 -(((
426 -**2)Configure device network**
427 -)))
428 -
429 -(((
430 -(((
431 -(((
432 -Click the Configuration Download button[[image:image-20220714115308-8.png||height="22" width="15"]], It is used to configure the device network, update the device time, obtain the device machine code, check the device network, etc.
433 -)))
434 -
435 -(((
436 -In the example below, the IP address of V-Box is configured as 192.168.40.66, and the networking method is 4G connection
437 -)))
438 -)))
439 -)))
440 -
441 -(((
442 -(((
443 -[[image:image-20220714162737-7.png]]
444 -
445 -
446 -)))
447 -)))
448 -)))
449 -)))
450 -
451 -(% class="wikigeneratedid" id="HV-netadddevice" %)
452 -(((
453 -**3)V-net add device**
454 -)))
455 -)))
456 -
457 -(((
458 -(((
459 -Open VNET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the device machine code/product code, device password, and device alias to add the device.   [[image:image-20220714162752-8.png]]
460 -)))
461 -
462 -
463 -)))
464 -
465 -(((
466 -(% class="wikigeneratedid" id="HSetcommunicationportparameters" %)
467 -(((
468 -**4)Set communication port parameters**
469 -)))
470 -
471 -(((
472 -In the device list on the left, find the Vbox that communicates with the L1769, click it and select configuration,communication port configuration in the main interface to add a communication protocol.
473 -)))
474 -
475 -[[image:image-20220714162805-9.png]]
476 -)))
477 -
478 -(((
479 -The communication port is selected as Ethernet, the device type is selected as Allen-Bradley, the protocol is Allen-BradleyMicro850_FreeTag EthemetIP, and the IP is the internal IP address of the L1769 PLC. The port number is 44818.
480 -)))
481 -
482 -[[image:image-20220824164346-1.png]]
483 -
484 -
485 -(((
486 -After adding the protocol Allen-BradleyMicro850_FreeTag, click[[image:image-20220714143838-2.png]]icon add label.[[image:image-20220714162827-11.png]]
487 -)))
488 -
489 -(% class="wikigeneratedid" id="HEngineeringproduction" %)
490 -(((
491 -**5)Engineering production**
492 -)))
493 -
494 -(% class="wikigeneratedid" %)
495 -(((
496 -(((
497 -According to your own needs, use the V-NET client software to edit the required data monitoring points.
498 -)))
499 -
500 -[[image:image-20220714162841-12.png]]
501 -
502 -
503 -(((
504 -**hardware connection**
505 -)))
506 -)))
507 -
508 -(((
509 -**1)Hardware wiring diagram**
510 -)))
511 -
512 -(((
513 -(((
514 -This example introduces Wecon V-box with Allen-Bradley L1769 PLC to establish communication through Ethernet. The connection diagram is as follows:
515 -)))
516 -
517 -[[image:image-20220714162856-13.png]]
518 -
519 -(((
520 -The above are all the steps for establishing Ethernet communication between Wecon V-box with CompactLogix L1769 PLC.
521 -
522 -
523 -== **Micro850_FreeTag Ethernet(new)** ==
524 -
525 -This example introduces the establishment of Ethernet communication between Wecon V-box and 2080-LC50-48QWB,Micro850. It is introduced through three parts: PLC software configuration, V-box software configuration.
526 -
527 -(% class="wikigeneratedid" id="HSoftwareconfigurationofPLC" %)
528 -(((
529 -**Software configuration of PLC**
530 -)))
531 -
532 -(% class="wikigeneratedid" id="HPLCprogrammingsoftware" %)
533 -(((
534 -**1)PLC programming software:Connected Components Workbench™**
535 -
536 -(% style="text-align:center" %)
537 -[[image:software.png]]
538 -
539 -**2)New PLC project**
540 -
541 -Click New Project and select the PLC model.
542 -
543 -(% style="text-align:center" %)
544 -[[image:project create.png]]
545 -
546 -**3)Set Ethernet parameters**
547 -
548 -Follow the steps below to configure Ethernet parameters
549 -
550 -PLC IP address:192.168.39.56
551 -
552 -default gateway:192.168.39.1
553 -
554 -subnet mask:255.255.255.0
555 -
556 -(% style="text-align:center" %)
557 -[[image:Ethernet.png]]
558 -
559 -**4)connect PLC**
560 -
561 -**When downloading the setting, need to change the status of the PLC to PRG**
562 -
563 -(% style="text-align:center" %)
564 -[[image:conne ab plc.png]]
565 -
566 -**V-box software configuration**
567 -
568 -**1)V-box programming software**
569 -
570 -(% style="text-align:center" %)
571 -[[image:v-net client vers.png]]
572 -
573 -**2)Set communication port parameters**
574 -
575 -In the device list on the left, find the Vbox that communicates with the L1769, click it and select configuration,communication port configuration in the main interface to add a communication protocol.
576 -
577 -(% style="text-align:center" %)
578 -[[image:V-NET_Client_t2Rg2wpSoY.png]]
579 -
580 -The communication port is selected as Ethernet, the device type is selected as Allen-Bradley, the protocol is Allen-BradleyMicro850_FreeTag EthemetIP, and the IP is the internal IP address of the L1769 PLC. The port number is 44818.
581 -
582 -(% style="text-align:center" %)
583 -[[image:V-NET_Client_communication.png]]
584 -
585 -Export variables from PLC, select CSV file, comma delimited.(% id="cke_bm_1950S" style="display:none" %)
586 -
587 -(% style="text-align:center" %)
588 -[[image:export1.png]]
589 -
590 -(% style="text-align:center" %)
591 -[[image:CCW.Shell_E5Cwj4tUL3.png]]
592 -
593 -After adding the protocol Allen-BradleyMicro850_FreeTag, click[[image:https://docs.we-con.com.cn/bin/download/V-BOX/V-Net/Training/1%20Communication/WebHome/image-20220714143838-2.png?rev=1.1||alt="image-20220714143838-2.png"]]icon add label.
594 -
595 -(% style="text-align:center" %)
596 -[[image:V-NET_Client_TNBuqy7T5r.png]]
597 -
598 -**3)Engineering production**
599 -
600 -According to your own needs, use the V-NET client software to edit the required data monitoring points.
601 -
602 -(% style="text-align:center" %)
603 -[[image:V-NET_Client_KOR0AHEA4M.png]]
604 -
605 -
606 -)))
607 -
608 -== **Ethernet DF1** ==
609 -
610 -[[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Allen-Bradley%20Ethernet%20DF1.zip]]
611 -
612 -= **Crouzet PLC** =
613 -
614 -== **CROUZET M3 (FBD) Serial** ==
615 -
616 -Support Series: Crouzet Millenium 3 CD12/CB12
617 -
618 -**1)V-BOX setting**
619 -
620 -|=Item|=Recommended |=Note
621 -|=Protocol|CROUZET M3 (FBD)|
622 -|=Connection|RS232|
623 -|=Baud rate|115200|
624 -|=Stop bits|1|
625 -|=Data bits|7|
626 -|=Parity|EVEN|
627 -
628 -**2)Address List**
629 -
630 -|=**Type**|=**Device registers**|=**Format**|=**Range**|=Note
631 -|(% rowspan="4" %)Bit|I|I DD|1~~99|Input
632 -|SLIBit|SLIBit DD.dd|1.0~~24.15|Serial Link Input
633 -|SLOBit|SLOBit DD.dd|25.0~~48.15|Serial Link Output(Read only)
634 -|State|State D|1~~1|PLC state(Read only)
635 -|(% rowspan="5" %)Word|AI|AI DD|1~~99|Analog Input
636 -|SLIn|SLIn DD|1~~24|Serial Link Input
637 -|SLOut|SLOut DD|25~~48|Serial Link Output(Read only)
638 -|Time|Time D|1~~6|(((
639 -Time1: Second
640 -
641 -Time2: Minute
642 -
643 -Time3: Hour
644 -
645 -Time4: Day
646 -
647 -Time5: Month
648 -
649 -Time6: Year
650 -)))
651 -|Order|Order D|1~~1|(((
652 -Running command(Write only)
653 -
654 -~=2: Run mode; =1: Stop mode;
655 -)))
656 -
657 -**3)Cable Wiring**
658 -
659 -(% style="text-align:center" %)
660 -[[image:CrouzetRS232 VBox.png]]
661 -
662 -{{info}}
663 -**✎Note: **As the wiring diagram indicated, this protocol requires the DB9 serial port pin 4. But pin 4 is undefined for all V-Box, so it need the user to solder a Pull-up resistor to make the pin 4 working. As for how to solder the resistor on the motherboard, please contact with Wecon technical support for the details.
664 -{{/info}}
665 -
666 -= EMERSON =
667 -
668 -= **RTU Slave ** =
669 -
670 -Supported series: EC10 series
671 -
672 -**1)V-BOX setting**
673 -
674 -|**Items**|**Settings**|**Note**
675 -|Protocol|Emerson 984 RTU Slave MODBUS|
676 -|Connection|RS485|
677 -|Baud rate|19200|
678 -|Data bit|8|
679 -|Parity|EVEN|
680 -|Stop bit|1|
681 -|Device station No.|1|Need to be same as the PLC setting
682 -
683 -(% class="wikigeneratedid" %)
684 -**2)PLC Setting**
685 -
686 -(% class="wikigeneratedid" %)
687 -Remember to use the Control Star to enable the Modbus RTU communication for port 1 in system block before dowload into PLC.
688 -
689 -(% style="text-align:center" %)
690 -[[image:ControlStarSystemBlock.png]]
691 -
692 -(% style="text-align:center" %)
693 -[[image:ControlStarCommunicate.png]]
694 -
695 -(% style="text-align:center" %)
696 -[[image:ControlStarModbus.png]]
697 -
698 -(% class="wikigeneratedid" %)
699 -**3)Address List**
700 -
701 -|**Type**|**Device registers**|**Format**|**Range**|**Note**
702 -|(% colspan="1" rowspan="12" %)Bit|Y|YOOO|0~~377|
703 -|X|XOOO|0~~377|
704 -|M0|M0DDDD|0~~2047|
705 -|M1|M1DDDDD|2048~~10239|
706 -|SM0|SM0DDD|0~~255|
707 -|SM1|SM1DDD|256~~511|
708 -|S0|S0DDDD|0~~1023|
709 -|S1|S1DDDD|1024~~4095|
710 -|T0|T0DDD|0~~255|
711 -|T1|T1DDD|256~~511|
712 -|C0|C0DDD|0~~255|
713 -|C1|C1DDD|256~~306|
714 -|(% colspan="1" rowspan="7" %)Word|D|DDDDD|0~~7999|
715 -|Z|ZDD|0~~15|
716 -|TW0|TW0DDD|0~~255|
717 -|TW1|TW1DDD|256~~511|
718 -|SD0|SD0DDD|0~~255|
719 -|SD1|SD1DDD|256~~511|
720 -|CW|CWDDD|0~~306|
721 -|(% colspan="1" rowspan="2" %)Double Word|CW0|CW0DDD|200~~255|
722 -|CW1|CW1DDDDD|256~~99999|
723 -
724 -**4) Cable Wiring**
725 -
726 -(% style="text-align:center" %)
727 -[[image:Emerson.png]]
728 -
729 -= HollySys PLC =
730 -
731 -== **LK Modbus RTU ** ==
732 -
733 -Supported Series: HollySys LK series PLC
734 -
735 -**1)V-BOX setting**
736 -
737 -|**Items**|**Settings**|**Note**
738 -|Protocol|HollySys LK Modbus RTU|
739 -|Connection|RS485|
740 -|Baud rate|38400|
741 -|Data bit|8|
742 -|Parity|None|
743 -|Stop bit|1|
744 -|Device station No.|1|
745 -
746 -**2)Address List**
747 -
748 -|=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note**
749 -|Bit|QX|QXDDDDD.dd|0~~65535.15|
750 -|Bit|IX|IXDDDDD.dd|0~~65535.15|
751 -|Bit|MX|MXDDDDD.dd|0~~65535.15|
752 -|Word|QW|QWDDDDD|0~~99999|
753 -|Word|IW|IWDDDDD|0~~99999|
754 -|Word|MW|MWDDDDD|0~~99999|
755 -|Word|MD|MDDDDDD|0~~99999|
756 -
757 -**3)Cable Wiring**
758 -
759 -(% style="text-align:center" %)
760 -[[image:Hollysys485-2.png]]
761 -
762 -== **LM Modbus RTU** ==
763 -
764 -(% class="wikigeneratedid" %)
765 -Supported Series: HollySys LM3109/LM3107 PLC
766 -
767 -(% class="wikigeneratedid" %)
768 -**1)V-BOX setting**
769 -
770 -|(% style="width:208px" %)**Items**|(% style="width:310px" %)**Settings**|(% style="width:365px" %)**Optional**|(% style="width:152px" %)**Note**
771 -|(% style="width:208px" %)Protocol|(% style="width:310px" %)HollySys LM Modbus RTU|(% style="width:365px" %)HollySys LM Modbus RTU|(% style="width:152px" %)
772 -|(% style="width:208px" %)Connection|(% style="width:310px" %)RS232|(% style="width:365px" %)RS485|(% style="width:152px" %)
773 -|(% style="width:208px" %)Baud rate|(% style="width:310px" %)38400|(% style="width:365px" %)38400|(% style="width:152px" %)
774 -|(% style="width:208px" %)Data bit|(% style="width:310px" %)8|(% style="width:365px" %)8|(% style="width:152px" %)
775 -|(% style="width:208px" %)Parity|(% style="width:310px" %)None|(% style="width:365px" %)None|(% style="width:152px" %)
776 -|(% style="width:208px" %)Stop bit|(% style="width:310px" %)1|(% style="width:365px" %)1|(% style="width:152px" %)
777 -|(% style="width:208px" %)Device station No.|(% style="width:310px" %)1|(% style="width:365px" %)1|(% style="width:152px" %)
778 -
779 -**2)Address List**
780 -
781 -|=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note**
782 -|Bit|QX|QXDDDDD.o|0~~99999.7|
783 -|Bit|IX|IXDDDDD.o|0~~99999.7|
784 -|Bit|MX|MXDDDDD.o|0~~99999.7|
785 -|Word|QW|QWDDDDD|0~~99999|
786 -|Word|IW|IWDDDDD|0~~99999|
787 -|Word|MW|MWDDDDD|0~~99999|
788 -|Word|MD|MDDDDDD|0~~99999|
789 -
790 -**Cable Wiring**
791 -
792 -RS232
793 -
794 -(% style="text-align:center" %)
795 -[[image:HollySysRS232.png]]
796 -
797 -RS485
798 -
799 -(% style="text-align:center" %)
800 -[[image:Hollysys LM Modbus RTU.gif]]
801 -
802 -= **Siemens ** =
803 -
804 -== **S7-200 Smart Ethernet ** ==
805 -
806 -[[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20S7-200%20Smart.zip]]
807 -
808 -== **S7-300 Ethernet ** ==
809 -
810 -Supported Series: Siemens S7-300 series PLC
811 -
812 -**1)V-BOX setting**
813 -
814 -|**Items**|**Settings**|**Note**
815 -|Protocol|Simens S7-300 Ethernet|
816 -|Connection|Ethernet|
817 -|Port No.|102|
818 -|PLC station No.|2|Need to be same as the PLC setting
819 -
820 -**2)Address List**
821 -
822 -|**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
823 -|(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
824 -|Q|Q|Q ddddd.o|0.0~~99999.7|
825 -|M|M|M ddddd.o|0.0~~99999.7|
826 -|DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
827 -nn: block number;
828 -
829 -dddd: address;
830 -)))
831 -|(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
832 -|Q|QW|QW ddddd|0~~99999|
833 -|(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
834 -|MW|MW ddddd|0~~99999|(((
835 -MW0=MB(0~~1)
836 -
837 -MW2=MB(2~~3)
838 -
839 -Address value is a multiple of 2
840 -)))
841 -|MD|MD ddddd|0~~99999|(((
842 -MD0=MB(0~~3)
843 -
844 -MD4=MB(4~~7)
845 -
846 -Address value is a multiple of 4
847 -)))
848 -|(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
849 -nn: block number;
850 -
851 -dddd: address
852 -)))
853 -|DBxDBW|DBxDBW nndddd|0~~99999999
854 -|DBxDBD|DBxDBD nndddd|0~~99999999
855 -
856 -**3)Configure the communication protocol**
857 -
858 -[[image:image-20220824161345-1.png]]
859 -
860 -**4)Cable Wiring**
861 -
862 -[[image:image-20220824161450-2.png]]
863 -)))
864 -)))
865 -
866 -== **S7-1200 Ethernet ** ==
867 -
868 -[[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]]
869 -
870 -== **S7-XXX Ethernet l** ==
871 -
872 -Supported Series: Siemens S7-400, S7-1200 and S7-1500
873 -
874 -**1)V-BOX setting**
875 -
876 -|=**Items**|=**Settings**|=**Note**
877 -|Protocol|Siemens S7-XXX|
878 -|Connection|Ethernet|
879 -|Port No.|102|
880 -|Device No.|Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|
881 -|HMI No.|Rack (Default as 0)|
882 -
883 -Slot from TIA Portal is equal to Device No. of V-net
884 -
885 -Rack from TIA Portal is equal to HMI No. of V-net
886 -
887 -[[image:image-20220824162459-3.png]]
888 -
889 -[[image:image-20220824163305-2.png]]
890 -
891 -**2)Address List**
892 -
893 -|**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
894 -|(% rowspan="4" %)Bit|I|I|M d.o|(((
895 -d:0~-~-9999
896 -
897 -o:0-7
898 -)))|
899 -|Q|Q|Q d.o|(((
900 -d:0~-~-9999
901 -
902 -o:0-7
903 -)))|
904 -|M|M|M d.o|(((
905 -d:0~-~-9999
906 -
907 -o:0-7
908 -)))|
909 -|DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
910 -nn:0-9999,
911 -
912 -dddd:0-9999,
913 -
914 -o:0-7
915 -)))|(((
916 -nn:DB No.
917 -
918 -dddd:address value
919 -
920 -o: digit address
921 -)))
922 -|(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
923 -|M|MW|MW d|d:0-99999|(((
924 -MW0=MB(0~~1)
925 -
926 -MW2=MB(2~~3)
927 -
928 -Address value is a multiple of 2
929 -)))
930 -|M|MD|MD d|d:0-99999|(((
931 -MD0=MB(0~~3)
932 -
933 -MD4=MB(4~~7)
934 -
935 -Address value is a multiple of 4
936 -)))
937 -|I|IW|IW d|d:0-99999|
938 -|Q|QW|QW d|d:0-99999|
939 -|DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
940 -nn:0-9999
941 -
942 -dddd:0-9999
943 -)))|(((
944 -nn:DB No.
945 -
946 -dddd:address value
947 -)))
948 -|DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
949 -nn:0-9999
950 -
951 -dddd:0-9999
952 -)))|(((
953 -nn:DB No.
954 -
955 -dddd:address value
956 -
957 -Address value is a multiple of 2
958 -)))
959 -|DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
960 -nn:0-9999
961 -
962 -dddd:0-9999
963 -)))|(((
964 -nn:DB No.
965 -
966 -dddd:address value
967 -
968 -Address value is a multiple of 4
969 -)))
970 -
971 -**3)Configure the communication protocol**
972 -
973 -[[image:image-20220824163448-3.png]]
974 -
975 -**✎Note:**
976 -
977 -* The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three V-BOX.
978 -* V-BOX access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
979 -
980 -**4)Cable Wiring**
981 -
982 -[[image:image-20220824162342-2.png]]
983 -
984 -== **LOGO Ethernet ** ==
985 -
986 -Supported Series: Siemens Logo 0BA0, 0BA1 series
987 -
988 -**V-BOX Settings**
989 -
990 -
991 -|**Items**|**Settings**|**Note**
992 -|Protocol|Siemens LOGO|
993 -|Connection|Ethernet|
994 -|Port No.|102|
995 -|PLC station No.|2|
996 -
997 -**Address List**
998 -
999 -
1000 -|**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
1001 -|1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
1002 -|2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
1003 -|3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
1004 -|4|VW|Word|0-1468|DB1.DBX0.0|0x000000
1005 -|5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
1006 -|6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
1007 -|7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
1008 -|8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
1009 -|9|AI|Word|1-16|DB1.DBX1032.0|0x002040
1010 -|10|I|Bit|1-64|DB1.DBX1024.0|0x002000
1011 -|11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
1012 -|12|M|Bit|1-112|DB1.DBX1104.0|0x002280
1013 -|13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
1014 -|14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
1015 -|15|V|Bit|0-14697|DB1.DBX0.0|0x000000
1016 -
1017 -**PLC Settings in LOGO Software:**
1018 -
1019 -Click [Tools]~-~-[Ethernet Connections],shown as below.
1020 -
1021 -(% style="text-align:center" %)
1022 -[[image:PIStudio.12\.PLC protocols.WebHome@12.PLC Protocol_html_8b9d2322edf89519.png]]
1023 -
1024 -Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
1025 -
1026 -(% style="text-align:center" %)
1027 -[[image:PIStudio.12\.PLC protocols.WebHome@image-20221228142937-4.png]]
1028 -
1029 -**TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
1030 -
1031 -(% style="text-align:center" %)
1032 -[[image:PIStudio.12\.PLC protocols.WebHome@image-20221228143047-5.png]]
1033 -
1034 - **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
1035 -
1036 -(% style="text-align:center" %)
1037 -[[image:PIStudio.12\.PLC protocols.WebHome@image-20221228143246-6.png]]
1038 -
1039 -**V-BOX Communication Settings**
1040 -
1041 -Set PLC IP in [IP Address] settings;
1042 -
1043 -(% style="text-align:center" %)
1044 -[[image:LldwDGntf4.png]]
1045 -
1046 -Enable V-BOX Ethernet in [Network];
1047 -
1048 -(% style="text-align:center" %)
1049 -[[image:WgvjfWbQif.png]]
1050 -
1051 -TSAP setting
1052 -
1053 -* The initialization script needs to set the source TSAP address and the target TSAP address, otherwise the communication will not be successful.
1054 -
1055 -{{code language="LUA"}}
1056 -function init.main()
1057 -addr_setword("@W_0#HSW1200",8192) -- Set the source TSAP address
1058 -addr_setword("@W_0#HSW1201",4096) -- Set the destination TSAP address
1059 -end
1060 -{{/code}}
1061 -
1062 -Note: The name of the test script is init, 8192 and 4096 are the data used for the test, there is no HSW address in the register option, but you can directly set the value of the corresponding address through the code.
1063 -
1064 -**✎Note:**
1065 -
1066 -* **Communication port configuration: **
1067 -** Continuous length needs to be set to 0.
1068 -** Integration interval needs to be set to 1. (no change may result in data errors)
1069 -** Set Port and Device Station NO.
1070 -** Other set as defaulted.
1071 -* **Notes on the use of registers:**
1072 -** Register VD: Use only registers that are multiples of 4, such as 0, 4, 8, etc.
1073 -** Register VW: Use only registers thay are multiples of 2, such as 0, 2, 4 etc. (Using an odd-length register may result in data errors, such as 2 3 4 )
1074 -
1075 -= **Mitsubishi ** =
1076 -
1077 -== **FX1S,1N,2N Serial ** ==
1078 -
1079 -Supported Series: Mitsubishi FX1S, FX1N, FX2N series
1080 -
1081 -**1)V-BOX Settings**
1082 -
1083 -|**Item**|**Settings**|**Note**
1084 -|Protocol|Mitsubishi FX1S/FX1N/FX2N|
1085 -|Connection|RS422/RS485/RS232|
1086 -|Baud rate|9600~~115200|
1087 -|Data bit|7/8|
1088 -|Parity|EVEN/Odd/None|
1089 -|Stop bit|1/2|
1090 -|PLC station No.|1~~255|
1091 -
1092 -**2)Address List**
1093 -
1094 -|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1095 -|(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1096 -|Y|Y|Y o|0~~303237|
1097 -|M|M|M d|0~~99999|
1098 -|T|T|T d|0~~99999|
1099 -|C|C|C d|0~~99999|
1100 -|S|S|S d|0~~99999|
1101 -|SM|SM|SM d|8000~~9999|
1102 -|(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1103 -|Y|Y|Y o|0~~303237|
1104 -|M|M|M d|0~~99999|
1105 -|T|T|T d|0~~99999|
1106 -|C|C|C d|0~~199|
1107 -|D|D|D d|0~~7999|
1108 -|S|S|S d|0~~99999|
1109 -|SD|SD|SD d|8000~~9999|
1110 -
1111 -**3)Configure the communication protocol**
1112 -
1113 -[[image:image-20220825102844-3.png]]
1114 -
1115 -**4)Cable Wiring**
1116 -
1117 -* **RS422**
1118 -
1119 -[[image:image-20220825103350-4.png]]
1120 -
1121 -[[image:image-20220825100845-4.png]]
1122 -
1123 -
1124 -== **FX3U,3G,3GA Serial ** ==
1125 -
1126 -Supported Series: Mitsubishi FX3U, FX3G, FX3GA series
1127 -
1128 -**1)V-BOX Settings**
1129 -
1130 -|**Item**|**Settings**|**Note**
1131 -|Protocol|Mitsubishi FX3U/3G/3GA|
1132 -|Connection|RS422/RS485/RS232|
1133 -|Baud rate|9600~~115200|
1134 -|Data bit|7/8|
1135 -|Parity|EVEN/Odd/None|
1136 -|Stop bit|1/2|
1137 -|PLC station No.|1~~255|
1138 -
1139 -**2)Address List**
1140 -
1141 -|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1142 -|(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1143 -|Y|Y|Y o|0~~303237|
1144 -|M|M|M d|0~~99999|
1145 -|T|T|T d|0~~99999|
1146 -|C|C|C d|0~~99999|
1147 -|S|S|S d|0~~99999|
1148 -|SM|SM|SM d|8000~~9999|
1149 -|(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1150 -|Y|Y|Y o|0~~303237|
1151 -|M|M|M d|0~~99999|
1152 -|T|T|T d|0~~99999|
1153 -|C|C|C d|0~~199|
1154 -|D|D|D d|0~~7999|
1155 -|S|S|S d|0~~99999|
1156 -|SD|SD|SD d|8000~~9999|
1157 -
1158 -**3)Configure the communication protocol**
1159 -
1160 -[[image:image-20220825102649-2.png]]
1161 -
1162 -**4)Cable Wiring**
1163 -
1164 -* **RS422**
1165 -
1166 -[[image:image-20220825103421-5.png]]
1167 -
1168 -[[image:image-20220825100845-4.png]]
1169 -
1170 -
1171 -== **FX3U Ethernet ** ==
1172 -
1173 -Supported Modules: FX3U-ENET-ADP, FX3U-ENET-L
1174 -
1175 -**1)V-BOX Settings**
1176 -
1177 -|Items|Settings|Note
1178 -|Protocol|Mitsubishi FX3U|
1179 -|Connection|Ethernet|
1180 -|Port No.|5009|Must be the same as the PLC setting
1181 -|PLC station No.|0|
1182 -
1183 -**2)Address List**
1184 -
1185 -|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1186 -|(% colspan="1" rowspan="7" %)Bit|X|X|X OOO|0~~377|
1187 -|Y|Y|Y OOO|0~~377|
1188 -|M|M|M DDDD|0~~7679|
1189 -|SM|SM|SM DDDD|8000~~8511|
1190 -|S|S|S DDDD|0~~4095|
1191 -|TS|TS|TS DDD|0~~511|
1192 -|CS|CS|CS DDD|0~~255|
1193 -|(% colspan="1" rowspan="9" %)Word|CN|CN|CN DDD|0~~199|
1194 -|TN|TN|TN DDD|0~~511|
1195 -|D|D|D DDDD|0~~7999|
1196 -|SD|SD|SD DDDD|8000~~8511|
1197 -|R|R|R DDDDD|0~~32767|
1198 -
1199 -**3)Ethernet Module Settings**
1200 -
1201 -FX3U-ENET-L module configuration
1202 -Set up the FX3U-ENET-L Ethernet module settings as follows.
1203 -Select the module location, which in this document is Module 0.
1204 -
1205 -[[image:image-20221116105850-1.png]]
1206 -
1207 -Select "Operational setting" to enter the following screen.
1208 -
1209 -The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default.
1210 -
1211 -[[image:image-20221116105947-1.png]]
1212 -
1213 -Select "Open setting" to enter the setting interface, the settings are as follows.
1214 -
1215 -The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the
1216 -
1217 -Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module.
1218 -
1219 -[[image:image-20221116110802-1.png]]
1220 -
1221 -Click on "transter setup" - "PC side I/F setting", see the following figure.
1222 -
1223 -After setting, the first download must use the programming cable, as shown in the figure; after that, can
1224 -
1225 -use the IP set in the "Ethernet board" to communicate directly with the network cable.
1226 -
1227 -[[image:image-20221116110832-2.png||height="423" width="708"]]
1228 -
1229 -Read and write data from the Ethernet module
1230 -
1231 -[[image:image-20221116110907-3.png]]
1232 -
1233 -Set "Transter setup" to COM communication, and read or write operation as shown below
1234 -
1235 -[[image:image-20221116110917-4.png]]
1236 -
1237 -**4)PLC Settings (GX Works 2)**
1238 -
1239 -Create a blank FX5U project
1240 -
1241 -Find Current Connection in the navigation
1242 -
1243 -[[image:image-20221116111427-1.png||height="421" width="705"]]
1244 -
1245 -Select Connection Channel List
1246 -
1247 -Select Ethernet board communication
1248 -
1249 -[[image:image-20221116111451-2.png||height="421" width="705"]]
1250 -
1251 -Select Ethernet Module
1252 -Set the IP address of the PLC
1253 -
1254 -[[image:image-20221116111509-3.png||height="666" width="699"]]
1255 -
1256 -Read or write PLC data, in this document is read
1257 -
1258 -[[image:image-20221116111651-4.png||height="416" width="697"]]
1259 -
1260 -[[image:image-20221116111727-5.png||height="416" width="697"]]
1261 -
1262 -**4)Configure the communication protocol**
1263 -
1264 -[[image:image-20221119101946-2.png||height="395" width="695"]]
1265 -
1266 -== **FX5U Serial ** ==
1267 -
1268 -Mitsubishi FX5U series PLC
1269 -
1270 -**1)V-BOX Settings**
1271 -
1272 -|**Item**|**Settings**|**Note**
1273 -|Protocol|Mitsubishi FX5U|
1274 -|Connection|RS422/RS485|
1275 -|Baud rate|9600|
1276 -|Data bit|7|
1277 -|Parity|Odd|
1278 -|Stop bit|1|
1279 -|PLC station No.|1~~255|Need to be the same as PLC settings
1280 -
1281 -**2)Address List**
1282 -
1283 -|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1284 -|(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1285 -|Y|Y|Y o|0~~303237|
1286 -|M|M|M d|0~~99999|
1287 -|B|B|B h|0~~7FFF|
1288 -|F|F|F d|0~~32767|
1289 -|SB|SB|SB h|0~~7FFF|
1290 -|TS|TS|TS d|0~~1023|
1291 -|TC|TC|TC d|0~~1023|
1292 -|STS|STS|STS d|0~~1023|
1293 -|STC|STC|STS d|0~~1023|
1294 -|CS|CS|CS d|0~~1023|
1295 -|CC|CC|CC d|0~~1023|
1296 -|SM|SM|SM d|0~~9999|
1297 -|L|L|L d|0~~32767|
1298 -|S|S|S d|0~~4095|
1299 -|(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1300 -|TN|TN|TN d|0~~1023|
1301 -|STN|STN|STN d|0~~1023|
1302 -|CN|CN|CN d|0~~1023|
1303 -|R|R|R d|0~~32767|
1304 -|SW|SW|SW h|0~~7FFF|
1305 -|Z|Z|Z d|0~~23|
1306 -|D|D|D d|0~~7999|
1307 -|SD|SD|SD d|0~~11999|
1308 -
1309 -**3)PLC Settings (GX Works 3)**
1310 -
1311 -Create a blank FX5U project
1312 -
1313 -Find the 485 serial port module in the system navigation bar and double click to enter the settings.
1314 -
1315 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5c9cb13fac1e6c93.png?width=200&height=462&rev=1.1||alt="12.PLC Protocol_html_5c9cb13fac1e6c93.png" height="462" width="200"]]
1316 -
1317 -Select protocol in the setting item, and set parameters.
1318 -
1319 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_de942589ca070228.png?width=600&height=324&rev=1.1||alt="12.PLC Protocol_html_de942589ca070228.png" height="324" width="600"]]
1320 -
1321 -Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
1322 -
1323 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_387ec7d00b5feb59.png?width=600&height=323&rev=1.1||alt="12.PLC Protocol_html_387ec7d00b5feb59.png" height="323" width="600"]]
1324 -
1325 -Click the [Apply] button to finish the setting.
1326 -
1327 -Click download and select the items as below, then click [execute] to download the configuration to PLC.
1328 -
1329 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_cdef1c5ec8cc2105.png?width=600&height=434&rev=1.1||alt="12.PLC Protocol_html_cdef1c5ec8cc2105.png" height="434" width="600"]]
1330 -
1331 - As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
1332 -
1333 -Done.
1334 -
1335 -**4)Configure the communication protocol**
1336 -
1337 -[[image:image-20220825104904-1.png]]
1338 -
1339 -**5)Cable Wiring**
1340 -
1341 -
1342 -* **RS422**
1343 -
1344 -[[image:image-20220825105105-2.png]]
1345 -
1346 -[[image:image-20220825105533-3.png]]
1347 -
1348 -== **FX5U Ethernet ** ==
1349 -
1350 -Mitsubishi FX5U series PLC
1351 -
1352 -**1)V-BOX Settings**
1353 -
1354 -|**Items**|**Settings**|**Note**
1355 -|Protocol|Mitsubishi FX5U|
1356 -|Connection|Ethernet|
1357 -|Port No.|5002|Must be the same as the PLC setting
1358 -|PLC station No.|0|
1359 -
1360 -**2)Address List**
1361 -
1362 -|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1363 -|(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1364 -|Y|Y|Y o|0~~303237|
1365 -|M|M|M d|0~~99999|
1366 -|B|B|B h|0~~7FFF|
1367 -|F|F|F d|0~~32767|
1368 -|SB|SB|SB h|0~~7FFF|
1369 -|TS|TS|TS d|0~~1023|
1370 -|TC|TC|TC d|0~~1023|
1371 -|STS|STS|STS d|0~~1023|
1372 -|STC|STC|STS d|0~~1023|
1373 -|CS|CS|CS d|0~~1023|
1374 -|CC|CC|CC d|0~~1023|
1375 -|SM|SM|SM d|0~~9999|
1376 -|L|L|L d|0~~32767|
1377 -|S|S|S d|0~~4095|
1378 -|(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1379 -|TN|TN|TN d|0~~1023|
1380 -|STN|STN|STN d|0~~1023|
1381 -|CN|CN|CN d|0~~1023|
1382 -|R|R|R d|0~~32767|
1383 -|SW|SW|SW h|0~~7FFF|
1384 -|Z|Z|Z d|0~~23|
1385 -|D|D|D d|0~~7999|
1386 -|SD|SD|SD d|0~~11999|
1387 -
1388 -**3)PLC Settings (GX Works 3)**
1389 -
1390 -Find the [Ethernet port] in the navigation area.
1391 -
1392 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_8e8f85ace087346c.png?width=300&height=593&rev=1.1||alt="12.PLC Protocol_html_8e8f85ace087346c.png" height="593" width="300"]]
1393 -
1394 -Select [Own Node Settings] in the [Setting Item List];
1395 -
1396 -Set [IP Address], [Subnet Mask], [Default Gateway];
1397 -
1398 -Click [Detailed Settings] into [Ethernet Configuration (Built-in Ethernet Port)] windows;
1399 -
1400 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5d98495052c8c10e.png?width=600&height=339&rev=1.1||alt="12.PLC Protocol_html_5d98495052c8c10e.png" height="339" width="600"]]
1401 -
1402 -Select [SLMP Connection Module] and add into host station as below picture shows;
1403 -
1404 -Set Port number as 5002 (this is necessary settings);
1405 -
1406 -Click [Close with Reflecting the Setting] to save and close window;
1407 -
1408 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_14b489fdc6c6589d.png?width=600&height=350&rev=1.1||alt="12.PLC Protocol_html_14b489fdc6c6589d.png" height="350" width="600"]]
1409 -
1410 -Click [Apply] to completed Etherenet settings;
1411 -
1412 -Switch to the [On line data operation] interface as below, check the item and click [Execute] to download.
1413 -
1414 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_c93025a968a8a9e7.png?width=600&height=434&rev=1.1||alt="12.PLC Protocol_html_c93025a968a8a9e7.png" height="434" width="600"]]
1415 -
1416 -**4)Configure the communication protocol**
1417 -
1418 -[[image:image-20220825112403-1.png||alt="图片-20220825112403-1.png"]]
1419 -
1420 -**5)Cable Wiring**
1421 -
1422 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1423 -
1424 -== **L02 Serial ** ==
1425 -
1426 -Mitsubishi L02 series CPU built-in serial port.
1427 -
1428 -**1)V-BOX Settings**
1429 -
1430 -|**Item**|**Settings**|**Note**
1431 -|Protocol|Mitsubishi L02|
1432 -|Connection|RS422|
1433 -|Baud rate|115200|
1434 -|Data bit|8|
1435 -|Parity|Odd|
1436 -|Stop bit|1|
1437 -|PLC station No.|1~~255|Need to be the same as PLC settings
1438 -
1439 -**2)Address List**
1440 -
1441 -|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1442 -|Bit|X|X|X h|0~~FFFF|
1443 -|Bit|Y|Y|Y h|0~~FFFF|
1444 -|Bit|M|M|M d|0~~9999|
1445 -|Bit|L|L|L d|0~~9999|
1446 -|Bit|F|F|F d|0~~9999|
1447 -|Bit|B|B|B h|0~~FFFF|
1448 -|Bit|V|V|V d|0~~2047|
1449 -|Bit|TC|TC|TC d|0~~9999|
1450 -|Bit|SS|SS|SS d|0~~9999|
1451 -|Bit|SC|SC|SC d|0~~9999|
1452 -|Bit|CS|CS|CS d|0~~9999|
1453 -|Bit|CC|CC|CC d|0~~9999|
1454 -|Bit|SB|SB|SB h|0~~FFFF|
1455 -|Bit|SM|SM|SM d|0~~2047|
1456 -|Bit|STS|STS|STS d|0~~1023|
1457 -|Bit|S|S|S d|0~~9999|
1458 -|Bit|DX|DX|DX h|0~~FFFF|
1459 -|Bit|DY|DY|DY h|0~~FFFF|
1460 -|Bit|TS|TS|TS d|0~~9999|
1461 -|Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1462 -|Word|W|W|W h|0~~FFFF|
1463 -|Word|TN|TN|TN d|0~~99999|
1464 -|Word|SN|SN|SN d|0~~99999|
1465 -|Word|CN|CN|CN d|0~~99999|
1466 -|Word|R|R|R d|0~~99999|
1467 -|Word|SW|SW|SW h|0~~FFFF|
1468 -|Word|Z|Z|Z d|0~~99999|
1469 -|Word|ZR|ZR|ZR h|0~~FFFF|
1470 -|Word|D|D|D d|0~~99999|
1471 -
1472 -**3)Communication Settings**
1473 -
1474 -[[image:image-20220825160648-3.png]]
1475 -
1476 -**4)Cable Wiring**
1477 -
1478 -* **RS422**
1479 -
1480 -[[image:image-20220825161612-8.png]]
1481 -
1482 -[[image:image-20220825160820-4.png]]
1483 -
1484 -== **L02 Ethernet ** ==
1485 -
1486 -Mitsubishi L series CPU built-in Ethernet port.
1487 -
1488 -**1)V-BOX Settings**
1489 -
1490 -|**Items**|**Settings**|**Note**
1491 -|Protocol|MIT L02 CPU MELSEC|
1492 -|Connection|Ethernet|
1493 -|Port No.|1025|Must be the same as the PLC setting
1494 -|PLC station No.|0|Must be the same as the PLC setting
1495 -
1496 -**2)Address List**
1497 -
1498 -|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1499 -|Bit|X|X|X h|0~~FFFF|
1500 -|Bit|Y|Y|Y h|0~~FFFF|
1501 -|Bit|M|M|M d|0~~9999|
1502 -|Bit|L|L|L d|0~~9999|
1503 -|Bit|F|F|F d|0~~9999|
1504 -|Bit|B|B|B h|0~~FFFF|
1505 -|Bit|V|V|V d|0~~2047|
1506 -|Bit|TC|TC|TC d|0~~9999|
1507 -|Bit|SS|SS|SS d|0~~9999|
1508 -|Bit|SC|SC|SC d|0~~9999|
1509 -|Bit|CS|CS|CS d|0~~9999|
1510 -|Bit|CC|CC|CC d|0~~9999|
1511 -|Bit|SB|SB|SB h|0~~FFFF|
1512 -|Bit|SM|SM|SM d|0~~2047|
1513 -|Bit|STS|STS|STS d|0~~1023|
1514 -|Bit|S|S|S d|0~~9999|
1515 -|Bit|DX|DX|DX h|0~~FFFF|
1516 -|Bit|DY|DY|DY h|0~~FFFF|
1517 -|Bit|TS|TS|TS d|0~~9999|
1518 -|Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1519 -|Word|W|W|W h|0~~FFFF|
1520 -|Word|TN|TN|TN d|0~~99999|
1521 -|Word|SN|SN|SN d|0~~99999|
1522 -|Word|CN|CN|CN d|0~~99999|
1523 -|Word|R|R|R d|0~~99999|
1524 -|Word|SW|SW|SW h|0~~FFFF|
1525 -|Word|Z|Z|Z d|0~~99999|
1526 -|Word|ZR|ZR|ZR h|0~~FFFF|
1527 -|Word|D|D|D d|0~~99999|
1528 -
1529 -**3)PLC Settings (GX Works2 )**
1530 -
1531 -Create a project
1532 -
1533 -Set PLC IP, subnet mask and gateway;
1534 -
1535 -Select [Binary Code] as communication data code;
1536 -
1537 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_776e17505f3fc6c0.png?width=600&height=524&rev=1.1||alt="12.PLC Protocol_html_776e17505f3fc6c0.png" height="524" width="600"]]
1538 -
1539 -Set PLC port number, for example 1025
1540 -
1541 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_8d0d1a22d388f70b.png?width=600&height=524&rev=1.1||alt="12.PLC Protocol_html_8d0d1a22d388f70b.png" height="524" width="600"]]
1542 -
1543 -Save settings;
1544 -
1545 -Download project into PLC device;
1546 -
1547 -Restart PLC device;
1548 -
1549 -**4)Configure the communication protocol**
1550 -
1551 -[[image:image-20220825142659-1.png]]
1552 -
1553 -**5)Cable Wiring**
1554 -
1555 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1556 -
1557 -== **Q12H Serial ** ==
1558 -
1559 -This Demo shows V-BOX communicate with Q12H PLC by Q02H serial Protocol
1560 -
1561 -[[**Download link**>>https://ftp.we-con.com.cn/Download/WIKI/PI%20HMI/Demo/Communication/V-Box%20connect%20PLC%20Q12H.rar]]
1562 -
1563 -== **QJ71E71 Ethernet ** ==
1564 -
1565 -Mitsubishi QJ71E71 Ethernet communication module;
1566 -
1567 -**1)V-BOX Settings**
1568 -
1569 -|**Items**|**Settings**|**Note**
1570 -|Protocol|MIT QJ71E71 MELSEC|
1571 -|Connection|Ethernet|
1572 -|Port No.|1025|Must be the same as the PLC setting
1573 -|PLC station No.|0|Must be the same as the PLC setting
1574 -
1575 -**2)Address List**
1576 -
1577 -|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1578 -|(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1579 -|Y|Y|Y h|0~~1FFF|
1580 -|M|M|M d|0~~99999|
1581 -|L|L|L d|0~~8191|
1582 -|F|F|F d|0~~2047|
1583 -|B|B|B h|0~~1FFF|
1584 -|V|V|V d|0~~2047|
1585 -|TS|TS|TS d|0~~2047|
1586 -|TC|TC|TC d|0~~2047|
1587 -|SS|SS|SS d|0~~2047|
1588 -|SC|SC|SC d|0~~2047|
1589 -|CS|CS|CS d|0~~1023|
1590 -|CC|CC|CC d|0~~1023|
1591 -|SB|SB|SB h|0~~7FF|
1592 -|S|S|S d|0~~8191|
1593 -|DX|DX|DX h|0~~1FFF|
1594 -|DY|DY|DY h|0~~1FFF|
1595 -|SM|SM|SM d|8000~~9999|
1596 -|(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1597 -|D|D|D d|0~~12287|
1598 -|W|W|W h|0~~1FFF|
1599 -|TN|TN|TN d|0~~2047|
1600 -|SN|SN|SN d|0~~2047|
1601 -|CN|CN|CN d|0~~1023|
1602 -|R|R|R d|0~~32767|
1603 -|SW|SW|SW h|0~~7FF|
1604 -|Z|Z|Z d|0~~15|
1605 -|ZR|ZR|ZR h|0~~FE7FF|
1606 -
1607 -**3)PLC Settings(GX Works2)**
1608 -
1609 -* Click [Ethernet/CC IE/MELSECNET];
1610 -* Please select [Ethernet] as network type;
1611 -* Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order);
1612 -* Select [Online] as Mode;
1613 -* [[image:image-20221119171343-2.png||height="341" width="587"]]
1614 -* Click [Operation setting] to set IP;
1615 -* Select [Binary Code] as [Communication Data Code];
1616 -* [[image:image-20221119171436-3.png||height="354" width="588"]]
1617 -* Click [Open setting]
1618 -* Set protocol: TCP;
1619 -* Set [unpassive] in [Open system];
1620 -* Set [receive] in [Fixed buffer];
1621 -* Set [procedure Exist] in [Fixed buffer communication];
1622 -* Disable [Pairing open];
1623 -* Set [No confirm] in [Existence confirmation];
1624 -* Host station port number: 5009;
1625 -* Save settings;
1626 -* [[image:image-20221119171611-4.png||height="354" width="588"]]
1627 -* Download project into PLC and restart it
1628 -
1629 -**4)Configure the communication protocol**
1630 -
1631 -[[image:image-20221119171832-5.png||height="354" width="625"]]
1632 -
1633 -
1634 -**5)Cable Wiring**
1635 -
1636 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png"]]
1637 -
1638 -= **Delta** =
1639 -
1640 -== **DVP Ethernet** ==
1641 -
1642 -Supoort Series: DELTA DVP20/32/40/60ES200RE/200TE or any DVP models with built-in Ethernet port, DELTA DVPEN01-SL module
1643 -
1644 -**1)V-BOX Settings**
1645 -
1646 -|=**Items**|=**Settings**|=**Note**
1647 -|Protocol|DELTA DVP MODBUS TCP|
1648 -|Connection|Ethernet|
1649 -|Port No.|502|
1650 -|Device No.|1|
1651 -|VBox Device No.|0|
1652 -
1653 -**2)Address List **
1654 -
1655 -|=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 217px;" %)**VBox registers**|=(% style="width: 168px;" %)**Format**|=(% style="width: 225px;" %)**Range**|=**Note**
1656 -|Bit|(% style="width:191px" %)X|(% style="width:217px" %)X|(% style="width:168px" %)X OOO|(% style="width:225px" %)0~~377|
1657 -|Bit|(% style="width:191px" %)Y|(% style="width:217px" %)Y|(% style="width:168px" %)Y OOO|(% style="width:225px" %)0~~377|
1658 -|Bit|(% style="width:191px" %)M0|(% style="width:217px" %)M0|(% style="width:168px" %)M0DDDD|(% style="width:225px" %)0~~1535|
1659 -|Bit|(% style="width:191px" %)M1|(% style="width:217px" %)M1|(% style="width:168px" %)M1DDDD|(% style="width:225px" %)1536~~4096|
1660 -|Bit|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDD|(% style="width:225px" %)0~~255|
1661 -|Bit|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~255|
1662 -|Bit|(% style="width:191px" %)S|(% style="width:217px" %)S|(% style="width:168px" %)SDDDD|(% style="width:225px" %)0~~1023|
1663 -|Word|(% style="width:191px" %)D0|(% style="width:217px" %)D0|(% style="width:168px" %)D0DDDD|(% style="width:225px" %)0~~4095|
1664 -|Word|(% style="width:191px" %)D1|(% style="width:217px" %)D1|(% style="width:168px" %)D1DDDD|(% style="width:225px" %)4096~~11999|
1665 -|Word|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDD|(% style="width:225px" %)0~~255|
1666 -|Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~199|
1667 -|Double Word|(% style="width:191px" %)HC|(% style="width:217px" %)HC|(% style="width:168px" %)HCDDD|(% style="width:225px" %)200~~255|
1668 -
1669 -**3) PLC Setting:**
1670 -
1671 -~1. Create new project in Delta WPL Soft, and click Setting to open the communication settings:
1672 -
1673 -(% style="text-align:center" %)
1674 -[[image:DVPEthernetWPLSoft2.png]]
1675 -
1676 -2. Set up the communication type and PLC IP:
1677 -
1678 -(% style="text-align:center" %)
1679 -[[image:DVPEthernetSetup.png]]
1680 -
1681 -(% class="wikigeneratedid" %)
1682 -3. Click OK and save the settings. Then click Communication on toolbar, then click Transfer Setup to open new window:
1683 -
1684 -(% style="text-align:center" %)
1685 -[[image:DVPEthernetTransfer.png]]
1686 -
1687 -(% class="wikigeneratedid" %)
1688 -4. Select Communication Mode as PC => PLC to download or select PC <=PLC to upload:
1689 -
1690 -(% style="text-align:center" %)
1691 -[[image:DVPEthernetPLCtoPC.png]]
1692 -
1693 -5. Click Auto-Search Ethernet Module to find the PLC on the same LAN network:
1694 -
1695 -(% style="text-align:center" %)
1696 -[[image:DVPEthernetAutoSearch.png]]
1697 -
1698 -**4) V-BOX Setting:**
1699 -
1700 -Set the same IP address according to the setting from WPL Soft:
1701 -
1702 -(% style="text-align:center" %)
1703 -[[image:DVPEthernetVNETPortocol.png]]
1704 -
1705 -== **DVP serial** ==
1706 -
1707 -Supoort Series: DELTA DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX
1708 -
1709 -**1)V-BOX Settings**
1710 -
1711 -|=**Items**|=**Settings**|=**Note**
1712 -|Protocol|DELTA DVP PROTOCOL|
1713 -|Connection|RS232|
1714 -|Baud Rate|9600|
1715 -|Stop Bit|1|
1716 -|Data Bit|7|
1717 -|Parity|EVEN|
1718 -|Device No.|1|
1719 -
1720 -(% class="wikigeneratedid" %)
1721 -**2)Address List**
1722 -
1723 -|=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 217px;" %)**VBox registers**|=(% style="width: 168px;" %)**Format**|=(% style="width: 225px;" %)**Range**|=**Note**
1724 -|Bit|(% style="width:191px" %)X|(% style="width:217px" %)X|(% style="width:168px" %)X OOOOOO|(% style="width:225px" %)0~~303237|
1725 -|Bit|(% style="width:191px" %)Y|(% style="width:217px" %)Y|(% style="width:168px" %)Y OOOOOO|(% style="width:225px" %)0~~303237|
1726 -|Bit|(% style="width:191px" %)M|(% style="width:217px" %)M|(% style="width:168px" %)MDDDDD|(% style="width:225px" %)0~~99999|
1727 -|Bit|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDDDD|(% style="width:225px" %)0~~99999|
1728 -|Bit|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDDDD|(% style="width:225px" %)0~~99999|
1729 -|Bit|(% style="width:191px" %)S|(% style="width:217px" %)S|(% style="width:168px" %)SDDDDD|(% style="width:225px" %)0~~99999|
1730 -|Word|(% style="width:191px" %)D|(% style="width:217px" %)D|(% style="width:168px" %)D DDDDD|(% style="width:225px" %)0~~99999|
1731 -|Word|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDDDD|(% style="width:225px" %)0~~99999|
1732 -|Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~199|
1733 -|Double Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDDDD|(% style="width:225px" %)200~~99999|
1734 -
1735 -(% class="wikigeneratedid" %)
1736 -**3)Wiring Diagram**
1737 -
1738 -(% style="text-align:center" %)
1739 -[[image:Delta DVP PROTOCOLSerial232.png]]
1740 -
1741 -== **AS Ethernet** ==
1742 -
1743 -**1)V-BOX Settings**
1744 -
1745 -|=**Items**|=**Settings**|=**Note**
1746 -|Protocol|DELTA AS300 MODBUS TCP|
1747 -|Connection|Ethernet|
1748 -|Port No.|502|
1749 -|Device No.|1|
1750 -|HMI No.|0|
1751 -
1752 -**2)Address List**
1753 -
1754 -|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1755 -|Bit|X|X|X d|0~~63|
1756 -|Bit|Y|Y|Y d|0~~63|
1757 -|Bit|D|D|D d|0~~29999|
1758 -|Bit|M|M|M d|0~~8191|
1759 -|Bit|SM|SM|SM d|0~~4095|
1760 -|Bit|S|S|S h|0~~2047|
1761 -|Bit|T|T|T d|0~~511|
1762 -|Bit|C|C|C d|0~~511|
1763 -|Bit|HC|HC|HC d|0~~255|
1764 -|Word|X|X|X h|0~~63|
1765 -|Word|Y|Y|Y d|0~~63|
1766 -|Word|SR|SR|SR d|0~~2047|
1767 -|Word|D|D|D d|0~~29999|
1768 -|Word|T|T|T d|0~~511|
1769 -|Word|C|C|C h|0~~511|
1770 -|Word|E|E|E d|0~~9|
1771 -
1772 -**3)Configure the communication protocol**
1773 -
1774 -[[image:image-20220831160010-4.png]]
1775 -
1776 -**4)Cable Wiring**
1777 -
1778 -Figure
1779 -
1780 -[[image:image-20220831155101-1.png]][[image:image-20220831160055-5.png]]
1781 -
1782 -Pin Definition Diagram
1783 -
1784 -[[image:image-20220831155157-3.png]]
1785 -
1786 -= **Omron** =
1787 -
1788 -== **CP1 Series** ==
1789 -
1790 -[[Download>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CP1%20Series.zip]]
1791 -
1792 -== **CP2M Series** ==
1793 -
1794 -[[Download>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CJ2M.zip]]
1795 -
1796 -== **EC55 Series ** ==
1797 -
1798 -Supported device: EC55 temperature instrument
1799 -
1800 -**1)V-BOX Settings**
1801 -
1802 -|**Items**|**Settings**|**Note**
1803 -|Protocol|Omron EC55|
1804 -|Connection|RS485 (9600, 2, 7, EVEN)|
1805 -|Port No.|None|
1806 -|PLC station No.|0|
1807 -
1808 -**2)Address List**
1809 -
1810 -|**Type**|**Register**|**Device range**|**HMI range**|**Function**
1811 -|(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
1812 -|C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
1813 -|C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
1814 -|(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
1815 -|81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
1816 -|83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
1817 -|CP|-|0-6|Read controller intrinsic property
1818 -|CS|-|0-2|Read controller states
1819 -|CA|-|0-17|Action command
1820 -
1821 -**3)Device Settings**
1822 -
1823 -Omron E5CC PLC configuration
1824 -
1825 -After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
1826 -
1827 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_3d95e093792ba98a.png?width=550&height=229&rev=1.1||alt="12.PLC Protocol_html_3d95e093792ba98a.png" height="229" width="550"]]
1828 -
1829 -According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
1830 -
1831 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_be583aa69dd6cf4c.png?width=550&height=242&rev=1.1||alt="12.PLC Protocol_html_be583aa69dd6cf4c.png" height="242" width="550"]]
1832 -
1833 -**✎Note:** The communication settings for HMI should be consistent with this setting.
1834 -
1835 -**4)Configure the communication protocol**
1836 -
1837 -[[image:image-20220831161041-1.png]]
1838 -
1839 -**5)Cable Wiring**
1840 -
1841 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5e9a81a14106da9e.png?width=392&height=223&rev=1.1||alt="12.PLC Protocol_html_5e9a81a14106da9e.png" height="223" width="392"]]
1842 -
1843 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_1897d92be6948d58.png?width=393&height=223&rev=1.1||alt="12.PLC Protocol_html_1897d92be6948d58.png" height="223" width="393"]]
1844 -
1845 -**✎Note:**
1846 -
1847 -* COM3 only available in PI8000/PI9000 series.
1848 -* CA address could not support continuous writing function;
1849 -* Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
1850 -* When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
1851 -* When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
1852 -* Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
1853 -* When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
1854 -* Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
1855 -* [[image:image-20220831161356-1.png]]Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
1856 -
1857 -= Xinje =
1858 -
1859 -== **XC serial** ==
1860 -
1861 -**1)V-BOX Settings**
1862 -
1863 -|**Item**|**Settings**|**Note**
1864 -|Protocol|XINJE XC MODBUS|
1865 -|Connection|RS232|
1866 -|Baud rate|19200|
1867 -|Data bit|8|
1868 -|Parity|EVEN|
1869 -|Stop bit|1|
1870 -|PLC station No.|1|
1871 -
1872 -**2)Address List**
1873 -
1874 -|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1875 -|Bit|M|M|M d|0~~8511|
1876 -|Bit|X|X|X o|0~~1747|
1877 -|Bit|Y|Y|Y o|0~~1747|
1878 -|Bit|S|S|S d|0~~1023|
1879 -|Bit|T|T|T d|0~~4095|
1880 -|Bit|C|C|C d|0~~634|
1881 -|Word|D|D|D d|0~~8511|
1882 -|Word|TD|TD|TD d|0~~618|
1883 -|Word|CD|CD|CD d|0~~634|
1884 -|Word|FD|FD|FD d|0~~8511|
1885 -
1886 -**3)Configure the communication protocol**
1887 -
1888 -
1889 -[[image:image-20220831163041-1.png]]
1890 -
1891 -**4)Cable Wiring**
1892 -
1893 -Figure
1894 -
1895 -[[image:image-20220831163406-2.png]][[image:image-20220831163422-3.png]]
1896 -
1897 -Pin Definition Diagram
1898 -
1899 -[[image:image-20220831163441-4.png]]
1900 -
1901 -== **XD serial** ==
1902 -
1903 -**1)V-BOX Settings**
1904 -
1905 -Supported Series: Xinjie XD/XE Series PLC
1906 -
1907 -|**Item**|**Settings**|**Note**
1908 -|Protocol|XINJE XD/XC MODBUS|
1909 -|Connection|RS232|
1910 -|Baud rate|19200|
1911 -|Data bit|8|
1912 -|Parity|EVEN|
1913 -|Stop bit|1|
1914 -|PLC station No.|1|
1915 -
1916 -**2)Address List**
1917 -
1918 -|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1919 -|Bit|M|M|M d|0~~74999|
1920 -|Bit|X1xx|X1xx|X1xx o|0~~1177|
1921 -|Bit|X2xx|X2xx|X2xx o|0~~277|
1922 -|Bit|X|X|X o|0~~77|
1923 -|Bit|Y1xx|Y1xx|Y1xx o|0~~1177|
1924 -|Bit|Y2xx|Y2xx|Y2xx o|0~~277|
1925 -|Bit|Y|Y|Y o|0~~4095|
1926 -|Bit|SM|SM|SM d|0~~4999|(((
1927 -
1928 -)))
1929 -|Bit|T|T|T d|0~~4999|
1930 -|Bit|C|C|C d|0~~4999|
1931 -|Bit|ET|ET|ET d|0~~31|
1932 -|Bit|SE|SE|SE d|0~~31|
1933 -|Bit|HM|HM|HM d|0~~11999|
1934 -|Bit|HSC|HSC|HSC d|0~~39|
1935 -|Bit|HS|HS|HS d|0~~999|
1936 -|Bit|HT|HT|HT d|0~~1999|
1937 -|Bit|HC|HC|HC d|0~~1999|
1938 -|Bit|S|S|S d|0~~7999|
1939 -|Word|D|D|D d|0~~69999|
1940 -|Word|ID|ID|ID d|0~~99|
1941 -|Word|ID1xx|ID1xx|ID1xx d|0~~999|
1942 -|Word|ID2xx|ID2xx|ID2xx d|0~~299|
1943 -|Word|QD|QD|QD d|0~~99|
1944 -|Word|QD1xx|QD1xx|QD1xx d|0~~999|
1945 -|Word|QD2xx|QD2xx|QD2xx d|0~~299|
1946 -|Word|SD|SD|SD d|0~~4999|
1947 -|Word|TD|TD|TD d|0~~575|
1948 -|Word|CD|CD|CD d|0~~575|
1949 -|Word|ETD|ETD|ETD d|0~~31|
1950 -|Word|HD|HD|HD d|0~~24999|
1951 -|Word|HSD|HSD|HSD d|0~~1023|
1952 -|Word|HTD|HTD|HTD d|0~~95|
1953 -|Word|HCD|HCD|HCD d|0~~95|
1954 -|Word|HSCD|HSCD|HSCD d|0~~31|
1955 -|Word|FD|FD|FD d|0~~8191|
1956 -|Word|SFD|SFD|SFD d|0~~5999|
1957 -|Word|FS|FS|FS d|0~~47|
1958 -
1959 -**3)Configure the communication protocol**
1960 -
1961 -[[image:image-20220831163923-7.png]]
1962 -
1963 -
1964 -
1965 -**4)Cable Wiring**
1966 -
1967 -Figure
1968 -
1969 -[[image:image-20220831163406-2.png]][[image:image-20220831163553-6.png]]
1970 -
1971 -Pin Definition Diagram
1972 -
1973 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830160232-3.png?rev=1.1||alt="image-20220830160232-3.png"]]
1974 -
1975 -= **Schneider** =
1976 -
1977 -== **Schneider MODBUS RTU** ==
1978 -
1979 -**1)V-BOX Setting**
1980 -
1981 -|=**Parameters**|=**Recommended**|=**Notes**
1982 -|**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
1983 -|**Connection**|RS485|
1984 -|**Baud rate**|19200|
1985 -|**Data bit**|8|
1986 -|**Parity**|Even|
1987 -|**Stop bit**|1|
1988 -|**PLC station No.**|1|
1989 -
1990 -**2)Address List**
1991 -
1992 -|=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
1993 -|B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
1994 -|B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
1995 -|B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
1996 -|W|MW|DDDDDD|0 ~~ 999999|Output register
1997 -|DW|MD|DDDDDD|0 ~~ 999999|Output register
1998 -
1999 -**3)Configure the communication protocol**
2000 -
2001 -[[image:image-20220902104329-1.png]]
2002 -
2003 -**4)Cable Wiring**
2004 -
2005 -**RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
2006 -
2007 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220817154212-1.jpeg?width=554&height=315&rev=1.1||alt="image-20220817154212-1.jpeg" height="315" width="554"]]
2008 -
2009 -= Inovance =
2010 -
2011 -== **H3U serial** ==
2012 -
2013 -**1)V-BOX Settings**
2014 -
2015 -|**Item**|**Settings**|**Note**
2016 -|Protocol|INOVANCE H3U PLC|
2017 -|Connection|RS422|
2018 -|Baud rate|9600|
2019 -|Data bit|7|
2020 -|Parity|EVEN|
2021 -|Stop bit|1|
2022 -|PLC station No.|0|
2023 -
2024 -**2)Address List**
2025 -
2026 -|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
2027 -|Bit|X|X|X o|0~~303237|
2028 -|Bit|Y|Y|Y o|0~~303237|
2029 -|Bit|M|M|M d|0~~99999|
2030 -|Bit|T|T|T d|0~~99999|
2031 -|Bit|C|C|C d|0~~99999|
2032 -|Bit|SM|SM|SM d|8000~~999|
2033 -|Bit|S|T|S d|0~~99999|
2034 -|Bit|Lamp|Lamp|Lamp d|0~~0|
2035 -|Word|X|X|X o|0~~303237|
2036 -|Word|Y|Y|Y o|0~~303237|
2037 -|Word|M|M|M d|0~~99999|
2038 -|Word|T|T|T d|0~~99999|
2039 -|Word|C|C|C d|0~~199|
2040 -|Word|D|D|D d|0~~7999|
2041 -|Word|S|S|S d|0~~99999|
2042 -|Word|SD|SD|SD d|8000~~9999|
2043 -|Word|R|R|R d|0~~32767|
2044 -
2045 -**3)Configure the communication protocol**
2046 -
2047 -[[image:image-20220831164626-1.png]]
2048 -
2049 -
2050 -
2051 -**4)Cable Wiring**
2052 -
2053 -Figure
2054 -
2055 -[[image:image-20220831164646-2.png]][[image:image-20220831164700-3.png]]
2056 -
2057 -Pin Definition Diagram
2058 -
2059 -[[image:image-20220831164731-4.png]]
2060 -
2061 -= Panasonic =
2062 -
2063 -== **FP serial** ==
2064 -
2065 -**1)V-BOX Settings**
2066 -
2067 -|**Item**|**Settings**|**Note**
2068 -|Protocol|Panasonic FP MFWTOCOL|
2069 -|Connection|RS232|
2070 -|Baud rate|9600|
2071 -|Data bit|8|
2072 -|Parity|ODD|
2073 -|Stop bit|1|
2074 -|PLC station No.|1|
2075 -
2076 -**2)Address List**
2077 -
2078 -|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
2079 -|Bit|X|X|X d|0~~9999|
2080 -|Bit|Y|Y|Y d|0~~9999|
2081 -|Bit|R|R|R d|0~~9999|
2082 -|Bit|T|T|T d|0~~9999|
2083 -|Bit|C|C|C d|0~~9999|
2084 -|Bit|L|L|L d|0~~9999|
2085 -|Word|WX|WX|WX d|0~~9999|
2086 -|Word|WY|WY|WY d|0~~9999|
2087 -|Word|WR|WR|WR d|0~~9999|
2088 -|Word|WL|WL|WL d|0~~9999|
2089 -|Word|LD|LD|LD d|0~~9999|
2090 -|Word|DT|DT|DT d|0~~65535|
2091 -|Word|FL|FL|FL d|0~~9999|
2092 -|Word|EV|EV|EV d|0~~9999|
2093 -|Word|SV|SV|SV d|0~~9999|
2094 -
2095 -**3)Configure the communication protocol**
2096 -
2097 -[[image:image-20220831165238-4.png]]
2098 -
2099 -
2100 -
2101 -**4)Cable Wiring**
2102 -
2103 -Figure
2104 -
2105 -[[image:image-20220831165031-3.png]][[image:image-20220831165017-2.png]]
2106 -
2107 -Pin Definition Diagram
2108 -
2109 -[[image:image-20220831165008-1.png]]
2110 -
2111 -= LS =
2112 -
2113 -== **XBC serial** ==
2114 -
2115 -**1)V-BOX Settings**
2116 -
2117 -|**Item**|**Settings**|**Note**
2118 -|Protocol|LS XBC CNet|
2119 -|Connection|RS232|
2120 -|Baud rate|115200|
2121 -|Data bit|8|
2122 -|Parity|NONE|
2123 -|Stop bit|1|
2124 -|PLC station No.|1|
2125 -
2126 -**2)Address List**
2127 -
2128 -|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
2129 -|Bit|P|P|P d|0~~2047|
2130 -|Bit|M|M|M d|0~~2047|
2131 -|Bit|L|L|L d|0~~11263|
2132 -|Bit|K|K|K d|0~~16183|
2133 -|Bit|F|F|F d|0~~2047|
2134 -|Bit|D|D|D d|0~~32767|
2135 -|Bit|R|R|R d|0~~32767|
2136 -|Bit|U|U|U d|0~~4095|
2137 -|Word|P|P|P d|0~~2047|
2138 -|Word|M|M|M d|0~~2047|
2139 -|Word|L|L|L d|0~~11263|
2140 -|Word|K|K|K d|0~~16183|
2141 -|Word|F|F|F d|0~~2047|
2142 -|Word|C|C|C d|0~~2047|
2143 -|Word|T|T|T d|0~~2047|
2144 -|Word|D|D|D d|0~~32767|
2145 -|Word|N|N|N d|0~~21503|
2146 -|Word|R|R|R d|0~~32767|
2147 -|Word|U|U|U d|0~~4095|
2148 -|Word|Z|Z|Z d|0~~127|
2149 -|Word|S|S|S d|0~~127|
2150 -
2151 -**3)Configure the communication protocol**
2152 -
2153 -[[image:image-20220831170147-1.png]]
2154 -
2155 -**4)Cable Wiring**
2156 -
2157 -Figure
2158 -
2159 -[[image:image-20220831170306-4.png]][[image:image-20220831170254-3.png]]
2160 -
2161 -Pin Definition Diagram
2162 -
2163 -[[image:image-20220831170215-2.png]]
2164 -
2165 -== **XGK FEnet Ethernet** ==
2166 -
2167 -Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
2168 -
2169 -**1)V-BOX Settings**
2170 -
2171 -|**Items**|**Settings**|**Note**
2172 -|Protocol|LG XGK FEnet(Ethernet)|
2173 -|Connection|Ethernet|
2174 -|Port No.|2004|
2175 -
2176 -**2)Address List**
2177 -
2178 -|**Type**|**Register**|**Range**|**Format**|**Note**
2179 -|(% rowspan="14" %)Word|P|0~~2047|P d|
2180 -|M|0~~2047|M d|
2181 -|K|0~~2047|K d|
2182 -|F|0~~2047|F d|
2183 -|T|0~~2047|T d|
2184 -|C|0~~2047|C d|
2185 -|Z|0~~127|Z d|
2186 -|S|0~~127|S d|
2187 -|L|0~~11263|L d|
2188 -|N|0~~21503|N d|
2189 -|D|0~~32767|D d|
2190 -|R|0~~32767|R d|
2191 -|ZR|0~~65535|ZR d|
2192 -|UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
2193 -
2194 -**✎Note:**
2195 -
2196 -* In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
2197 -* The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
2198 -* All bit registers are in the form of bits in word, and the range is the same as the word register;
2199 -
2200 -**3)Communication Settings**
2201 -
2202 -[[image:image-20220831171127-1.png]]
2203 -
2204 -**4)Cable Wiring**
2205 -
2206 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2207 -
2208 -= INVT =
2209 -
2210 -**1)V-BOX setting**
2211 -
2212 -|**Item**|**Settings**|**Note**
2213 -|Protocol|INVT_IVC2L|
2214 -|Connection|RS232|
2215 -|Baud rate|19200|
2216 -|Data bit|8|
2217 -|Parity|EVEN|
2218 -|Stop bit|1|
2219 -|PLC station No.|1
2220 -
2221 -**2)Address List**
2222 -
2223 -
2224 -|**Type**|**Device registers**|**Format**|**Range**|**Note**
2225 -|(% colspan="1" rowspan="7" %)Bit|X|XOOO|0~~377|
2226 -|Y|YOOO|0~~377|
2227 -|M|MDDDD|0~~1999|
2228 -|SM|SMDDD|0~~255|
2229 -|S|SDDD|0~~991|
2230 -|T|TDDD|0~~255|
2231 -|C|CDDD|0~~255|
2232 -|(% rowspan="5" %)Word|D|DDDDD|0~~7999|
2233 -|SD|SDDDD|0~~255|
2234 -|Z|ZDD|0~~15|
2235 -|T|TDDD|0~~255|
2236 -|C|CDDD|0~~199|
2237 -|Double word|C|CDDD|200~~255|
2238 -
2239 -**3)Communication Settings**
2240 -
2241 -(% style="text-align:center" %)
2242 -[[image:盒子创建英威腾.png]]
2243 -
2244 -**4)PLC software**
2245 -
2246 -(% style="text-align:center" %)
2247 -[[image:英威腾软件.png]]
2248 -
2249 -**5)PLC setting **
2250 -
2251 -Open the INVI plc software, create a new project or open a project that has already been created
2252 -
2253 -(% style="text-align:center" %)
2254 -[[image:英威腾创建1.png]]
2255 -
2256 -Configure serial port parameters.
2257 -
2258 -(% style="text-align:center" %)
2259 -[[image:英威腾创建2.png]]
2260 -
2261 -PC connect PLC
2262 -
2263 -(% style="text-align:center" %)
2264 -[[image:英威腾创建3.png]]
2265 -
2266 -Download
2267 -
2268 -(% style="text-align:center" %)
2269 -[[image:英威腾下载.png]]
2270 -
2271 -**6)Cable Wiring**
2272 -
2273 -(% style="text-align:center" %)
2274 -[[image:wire.png]]
2275 -
2276 -= **Modbus ** =
2277 -
2278 -== **MODBUS RTU Slave (All function)** ==
2279 -
2280 -Select the protocol "Modbus RTU Slave (All Fuction)",
2281 -
2282 -Then set baud rate, port, stop bits, data bits, parity.
2283 -
2284 -(% style="text-align:center" %)
2285 -[[image:1624342015914-382.png||height="486" width="800" class="img-thumbnail"]]
2286 -
2287 -== **Modbus Meter** ==
2288 -
2289 -The following example is using the Linfee meter LNF96EY to demonstrate how to set up the Modbus communication.
2290 -
2291 -~1. Wiring the RS485 cable first. Because the pin 58 is A, the pin 59 is B for meter. Here we use the COM1 to connect. So the diagram like follows:
2292 -
2293 -(% style="text-align:center" %)
2294 -[[image:LinfeeTerminalDiagram.png]]
2295 -
2296 -2. Check the specific Modbus parameter in the communication menu from LED display.
2297 -
2298 -So from the following pictures, we can know the Meter Address is 85, Baud rate is 9600, CRC None.
2299 -
2300 -{{info}}
2301 -**✎Note: **Meter address usually corresponding to the Modbus Slave Station No. on the Modbus communication.
2302 -{{/info}}
2303 -
2304 -(% style="text-align:center" %)
2305 -[[image:MeterModbusAllView.png]]
2306 -
2307 -(% class="wikigeneratedid" %)
2308 -3. Set up the communication in the Configuration tab.
2309 -
2310 -(% class="wikigeneratedid" %)
2311 -Select the protocol as **ModBus RTU Slave (All Function)**. And set the communication parameters like below.
2312 -
2313 -(% style="text-align:center" %)
2314 -[[image:VNETCommunicationtabmeter.png]]
2315 -
2316 -(% class="wikigeneratedid" %)
2317 -4. Create new real-time monitoring tag accroding to Modbus manual
2318 -
2319 -(% class="wikigeneratedid" %)
2320 -Enter the address we want to read from the meter. The following table is intercept part of the manual for Linfee Modbus manual.
2321 -
2322 -(% class="wikigeneratedid" %)
2323 -**0x03/0x04 command data register address**:
2324 -
2325 -(% style="width:1142.22px" %)
2326 -|(% style="display:none" %) |=(% colspan="2" rowspan="1" style="width: 165px;" %)Address(% style="display:none" %) |=Description|=Data Format|=(% style="width: 254px;" %)Data Length(Word)|=(% style="width: 282px;" %)Remark
2327 -|(%%)(% style="display:none" %) (%%) HEX|(% style="width:107px" %)DEC|(%%)(% style="display:none" %) (%%) |(% style="width:100px" %) |(%%)(% style="display:none" %) (%%) |(% style="width:318px" %)
2328 -|(% style="width:107px" %)0x00|(% style="width:100px" %)0|Reserved| | |(% style="width:318px" %)
2329 -|(% style="width:107px" %)0x02|(% style="width:100px" %)2|Reserved| | |(% style="width:318px" %)
2330 -|(% style="width:107px" %)0x04|(% style="width:100px" %)4|Reserved| | |(% style="width:318px" %)
2331 -|(% style="width:107px" %)0x06|(% style="width:100px" %)6|Ua|float|2|(% style="width:318px" %)Phase Voltage data, Unit V
2332 -|(% style="width:107px" %)0x08|(% style="width:100px" %)8|Ub|float|2|(% style="width:318px" %)Phase Voltage data, Unit V
2333 -|(% style="width:107px" %)0x0A|(% style="width:100px" %)10|Uc|float|2|(% style="width:318px" %)Phase Voltage data, Unit V
2334 -|(% style="width:107px" %)0x0C|(% style="width:100px" %)12|Uab|float|2|(% style="width:318px" %)Line Voltage data, Unit V
2335 -|(% style="width:107px" %)0x0E|(% style="width:100px" %)14|Ubc|float|2|(% style="width:318px" %)Line Voltage data, Unit V
2336 -|(% style="width:107px" %)0x10|(% style="width:100px" %)16|Uca|float|2|(% style="width:318px" %)Line Voltage data, Unit V
2337 -|(% style="width:107px" %)0x12|(% style="width:100px" %)18|Ia|float|2|(% style="width:318px" %)Phase Current data, Unit A
2338 -|(% style="width:107px" %)0x14|(% style="width:100px" %)20|Ib|float|2|(% style="width:318px" %)Phase Current data, Unit A
2339 -|(% style="width:107px" %)0x16|(% style="width:100px" %)22|Ic|float|2|(% style="width:318px" %)Phase Current data, Unit A
2340 -
2341 -{{info}}
2342 -**✎Note: **We usually use the Data Type 4 for read the Modbus registers(Function Code 03)
2343 -{{/info}}
2344 -
2345 -For example, here we want to read the Phase Voltage Ua (Modbus offset 0006), the Modbus register main No. requires input decimal number, and check whether the actual address has one address offset, so the tag configured like the following screenshot:
2346 -
2347 -(% style="text-align:center" %)
2348 -[[image:VNETModbusTagSettings.png]]
2349 -
2350 -(% style="text-align:center" %)
2351 -[[image:VNETModbusTagByteSettings.png]]
2352 -
2353 -{{info}}
2354 -**✎Note: **If the read value is incorrect, please check whether need to change the Byte order.
2355 -{{/info}}
2356 -
2357 -Set the Modbus Slave Station No.
2358 -
2359 -(% style="text-align:center" %)
2360 -[[image:ModbusStationSettings.png]]
2361 -
2362 -If the communication is setup successfully, the tag will show green light.
2363 -
2364 -(% style="text-align:center" %)
2365 -[[image:Monitoringtaggreenlight.png]]
2366 -
2367 -== **MODBUS RTU Master** ==
2368 -
2369 -Select the protocol "Modbus RTU Master",
2370 -
2371 -Then set baud rate, port, stop bits, data bits, parity
2372 -
2373 -(% style="text-align:center" %)
2374 -[[image:1624348709622-711.png||queryString="width=809&height=493" height="488" width="800" class="img-thumbnail"]]
2375 -
2376 -**address list**
2377 -
2378 -(% class="table-bordered" %)
2379 -|=(% scope="row" %)**Type**|=**Data Type**|=**Function code and description**
2380 -|(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (Read Input Registers: Read the current binary value in one or more input registers)
2381 -|06 (write single register: write a binary value to a holding register)
2382 -|10 (write values to multiple addresses )
2383 -|(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
2384 -|06 (write single register: write a binary value to a holding register)
2385 -|10 (write values to multiple addresses )
2386 -|(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
2387 -|06 (write single register: write a binary value to a holding register)
2388 -|10 (write values to multiple addresses )
2389 -|(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
2390 -|10 (write values to multiple addresses )
2391 -|(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
2392 -|05 (Force a single coil to force the on/off state of a logic coil)
2393 -|0F (Write multiple bits, ie write continuously)
2394 -|(% rowspan="3" %)1|02 (Read the input state)
2395 -|05 (Force a single coil to force the on/off state of a logic coil)
2396 -|0F (Write multiple bits)
2397 -|(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
2398 -|05 (Force a single coil to force the on/off state of a logic coil)
2399 -|0F (Write multiple bits)
2400 -|(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
2401 -|0F (Write multiple bits)
2402 -
2403 -== **MODBUS TCP Slave (All function)** ==
2404 -
2405 -Supported series: MODBUS TCP controller
2406 -
2407 -V-B0X works as MODBUS TCP MASTER connecting with TCP SLAVE
2408 -
2409 -**1)V-BOX Setting**
2410 -
2411 -|**Items**|**Settings**|**Note**
2412 -|Protocol|MODBUS TCP Slave (All function)|
2413 -|Connection|Ethernet|
2414 -|Port No.|502|
2415 -|PLC station No.|1
2416 -
2417 -**2)Address List**
2418 -
2419 -|=**Type**|=**Data Type**|=**Function code & Description**
2420 -|(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
2421 -|06 (write single register: write a binary value to a holding register)
2422 -|10 (write values to multiple addresses )
2423 -|(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
2424 -|06 (write single register: write a binary value to a holding register)
2425 -|10 (write values to multiple addresses )
2426 -|(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
2427 -|06 (write single register: write a binary value to a holding register)
2428 -|10 (write values to multiple addresses )
2429 -|(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
2430 -|10 (write values to multiple addresses )
2431 -|(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
2432 -|05 (Force a single coil to force the on/off state of a logic coil)
2433 -|0F (Write multiple bits, ie write continuously)
2434 -|(% rowspan="3" %)1|02 (Read the input state)
2435 -|05 (Force a single coil to force the on/off state of a logic coil)
2436 -|0F (Write multiple bits)
2437 -|(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
2438 -|05 (Force a single coil to force the on/off state of a logic coil)
2439 -|0F (Write multiple bits)
2440 -|(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
2441 -|0F (Write multiple bits)
2442 -
2443 -**3)Communication Settings**
2444 -
2445 -Configure V-BOX Ethernet IP in Networking Settings
2446 -
2447 -[[image:image-20220902111833-3.png]]
2448 -
2449 -
2450 -Configure PLC Ethernet IP in Communication;
2451 -
2452 -[[image:image-20220902111121-1.png]]
2453 -
2454 -**4)Cable Wiring**
2455 -
2456 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2457 -
2458 -== **communicate with VB inverter** ==
2459 -
2460 -[[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20VB%20inverter.zip]]
2461 -
2462 -= **User define** =
2463 -
2464 -More serial port script instruction,please refer manual:[[Lua script function>>doc:V-BOX.V-Net.Manual.04 Lua Script.01 Lua Functions.WebHome]]~-~-->[[3.Serial port operation>>url:http://docs.we-con.com.cn/wiki/vbox/view/HMI/04.Lua%20script%20%20function%20and%20operation/01.Lua%20script%20function/#H3.Serialportoperation]]
2465 -
2466 -== **Read the temperature sensor.** ==
2467 -
2468 -the commond format is as beliow:
2469 -
2470 -Send commond:01 03 02 00 00 03 04 73
2471 -
2472 -Feedback commond:01 03 06 07 F7 0E 7E B7 35
2473 -
2474 -Temperature data:07 F7,desimal = 2039,it means temperature is 20.39℃.
2475 -
2476 -Humidity data:0E 7E,desimal = 3710, it mean humidity is 37.10%RH.
2477 -
2478 -Script Demo:
2479 -
2480 -{{code language="lua"}}
2481 -function com.main()
2482 - --dosomething
2483 - openPlc()
2484 -end
2485 -
2486 -function openPlc()
2487 - if obj then
2488 - -- If the serial port opened,then read/write data by timing
2489 - local wri = string.pack(">HHHH",0X0103,0X0200,0X0003,0X0473)
2490 - local arr = reading(wri)
2491 - -- if arr ~=nil then
2492 - if arr[1] ==33 and arr[2] ==v[2][2] and arr[3] ==v[2][3] then
2493 - local A = arr[4]*256
2494 - local B = A+arr[5]
2495 - -- addr_setword(v[1],B)
2496 - end
2497 --- end
2498 - else
2499 - --judge if there is a serial object, then initialize and open the serial port
2500 - local configs = {
2501 - name = 'COM1', --Select serial port COM1
2502 - mode = 485, --Communication mode RS485
2503 - baud_rate = 9600, --Baud rate 9600
2504 - stop_bit = 1, --stop bit 1
2505 - data_len = 8, --data length 8
2506 - check_bit = 'NONE', --no parity
2507 - }
2508 - obj,err = serial.open(configs) --Open serial port
2509 - if not obj then
2510 - print("serial open :failed", err) -- Open serial port failed
2511 - end
2512 - end
2513 - end
2514 -
2515 -
2516 -function reading(wri)
2517 - obj:flush() -- Clear serial port
2518 - obj:write(wri)-- Write serial port
2519 - print(string.byte(wri,1,#wri))
2520 - obj:flush() -- Clear serial port
2521 - local readed =obj:read(9,1000) -- Read 9 bytes, timeout 1 second
2522 - if readed and readed ~= "" then
2523 - -- judge that a non-empty string is read
2524 - print(string.byte(readed,1,#readed))
2525 - a={string.byte(readed, 1, #readed)}
2526 - if nil ~= a[4] and nil ~= a[5] and nil ~= a[6] and nil ~= a[7] then
2527 - a1=a[4]*256+a[5]
2528 - a2=a[6]*256+a[7]
2529 - addr_setword("@HDW0",a1)
2530 - addr_setword("@HDW1",a2)
2531 - end
2532 - return {string.byte(readed, 1, #readed)}
2533 - elseif readed == nil then
2534 - print("serial read err:", err or "")
2535 - return nil
2536 - end
2537 - return nil
2538 -end
2539 -{{/code}}