Changes for page 1 Communication

Last modified by Hunter on 2024/07/01 10:54

From version 48.1
edited by Ben
on 2022/08/24 11:30
Change comment: There is no comment for this version
To version 36.1
edited by Ben
on 2022/08/24 11:02
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -47,7 +47,7 @@
47 47  
48 48  = **WECON PLC** =
49 49  
50 -== **LX3V 串行通信** ==
50 +== **V-BOX 和维控 LX3V 串行通信** ==
51 51  
52 52  Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
53 53  
... ... @@ -98,8 +98,9 @@
98 98  
99 99  [[https:~~/~~/drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing>>url:https://drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing]]
100 100  
101 -== **LX5V serial communication** ==
102 102  
102 +== **V-BOX and Wecon LX5V serial communication** ==
103 +
103 103  This example introduces the establishment of serial port communication between Wecon V-BOX and LX5V. It is introduced through three parts: PLC software configuration, HMI software configuration, and hardware wiring.
104 104  
105 105  **Software configuration of PLC**
... ... @@ -174,7 +174,7 @@
174 174  
175 175  The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC.
176 176  
177 -== **LX5V-N Ethernet communication** ==
178 +== **V-BOX and Wecon LX5V-N Ethernet communication** ==
178 178  
179 179   This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V. It is introduced through three parts: PLC software configuration, HMI software configuration, and hardware wiring.
180 180  
... ... @@ -249,51 +249,14 @@
249 249  
250 250  = **Rockwell PLC** =
251 251  
252 -== (% id="cke_bm_5621S" style="display:none" %)** **(%%)**MicroLogix** ==
253 +== **Communication with AB CompactLogix L1769** ==
253 253  
254 -MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
255 -
256 -**HMI Settings**
257 -
258 -|**Item**|**Settings**|**Note**
259 -|Protocol|Allen-Bradlley MicroLogix|
260 -|Connection|RS232|
261 -|Baud rate|19200|
262 -|Data bit|8|
263 -|Parity|None|
264 -|Stop bit|1|
265 -|PLC station No.|1|
266 -
267 -**Address List**
268 -
269 -|**Type**|**Device registers**|**Format**|**Range**|**Note**
270 -|(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
271 -|O|O d.d|0.0~~255.15|
272 -|B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
273 -|S|S d.d|0.0~~255.15|
274 -|N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
275 -|(% rowspan="9" %)Word|S|S d|0~~255|
276 -|TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
277 -|TP|TP nnhh|0~~ffff
278 -|CS|CS nnhh|0~~ffff
279 -|CP|CP nnhh|0~~ffff
280 -|N|N nnhh|0~~ffff
281 -|C|C nnhh|0~~ffff
282 -|T|T nnhh|0~~ffff
283 -|R|R nnhh|0~~ffff
284 -
285 -**Cable Wiring**
286 -
287 -[[image:image-20220824110724-1.png]]
288 -
289 -
290 -
291 -== **CompactLogix** ==
292 -
293 293  (((
294 294  (((
295 -This example introduces the establishment of Ethernet communication between Wecon V-box and CompactLogix L1769. It is introduced through three parts: PLC software configuration, V-box software configuration, and hardware wiring.
257 +This example introduces the establishment of Ethernet communication between Wecon V-box and Allen-Bradley L1769. It is introduced through three parts: PLC software configuration, V-box software configuration, and hardware wiring.
296 296  )))
259 +
260 +
297 297  )))
298 298  
299 299  (((
... ... @@ -488,9 +488,46 @@
488 488  [[image:image-20220714162856-13.png]]
489 489  
490 490  (((
491 -The above are all the steps for establishing Ethernet communication between Wecon V-box with CompactLogix L1769 PLC.
455 +The above are all the steps for establishing Ethernet communication between Wecon V-box with Allen-Bradley L1769 PLC.
492 492  
457 +== **MicroLogix** ==
493 493  
459 +MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
460 +
461 +**HMI Settings**
462 +
463 +|**Item**|**Settings**|**Note**
464 +|Protocol|Allen-Bradlley MicroLogix|
465 +|Connection|RS232|
466 +|Baud rate|19200|
467 +|Data bit|8|
468 +|Parity|None|
469 +|Stop bit|1|
470 +|PLC station No.|1|
471 +
472 +**Address List**
473 +
474 +|**Type**|**Device registers**|**Format**|**Range**|**Note**
475 +|(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
476 +|O|O d.d|0.0~~255.15|
477 +|B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
478 +|S|S d.d|0.0~~255.15|
479 +|N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
480 +|(% rowspan="9" %)Word|S|S d|0~~255|
481 +|TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
482 +|TP|TP nnhh|0~~ffff
483 +|CS|CS nnhh|0~~ffff
484 +|CP|CP nnhh|0~~ffff
485 +|N|N nnhh|0~~ffff
486 +|C|C nnhh|0~~ffff
487 +|T|T nnhh|0~~ffff
488 +|R|R nnhh|0~~ffff
489 +
490 +**Cable Wiring**
491 +
492 +
493 +
494 +
494 494  == **Allen-Bradley Ethernet DF1** ==
495 495  
496 496  [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Allen-Bradley%20Ethernet%20DF1.zip]]
... ... @@ -518,8 +518,6 @@
518 518  
519 519  [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Delta%20DVP%20Ethernet.zip]]
520 520  
521 -= **Mitsubishi PLC** =
522 -
523 523  == **Communicate with Mitsubishi FX Series** ==
524 524  
525 525  [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20Mitsubishi%20FX%20Series.zip]]
... ... @@ -528,8 +528,6 @@
528 528  
529 529  [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20VB%20inverter.zip]]
530 530  
531 -= **Omron PLC** =
532 -
533 533  == **Omron CP1 Series** ==
534 534  
535 535  [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CP1%20Series.zip]]
image-20220824110724-1.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Ben
Size
... ... @@ -1,1 +1,0 @@
1 -79.1 KB
Content