Summary

Details

Page properties
Content
... ... @@ -1,33 +1,53 @@
1 -= =
1 += **Modbus RTU** =
2 2  
3 +=== **V-BOX as master** ===
4 +
5 +Select the protocol “(% class="mark" %)Modbus RTU Slave(All Fuction)”,
6 +
7 +(% class="mark" %)then set BaudRate,Port,Stop Bit,Data Bit,Parity
8 +
9 +(% style="text-align:center" %)
10 +[[image:1624342015914-382.png||height="486" width="800" class="img-thumbnail"]]
11 +
12 +=== **V-BOX as slave** ===
13 +
14 +Select the protocol “(% class="mark" %)**Modbus RTU Master”**,
15 +
16 +(% class="mark" %)then set BaudRate,Port,Stop Bit,Data Bit,Parity
17 +
18 +(% style="text-align:center" %)
19 +[[image:1624348709622-711.png||queryString="width=809&height=493" height="488" width="800" class="img-thumbnail"]]
20 +
21 +**Address List**
22 +
3 3  (% class="table-bordered" %)
4 -| | |
5 -|(% rowspan="11" %) |(% rowspan="3" %) |
6 -|
7 -|
8 -|(% rowspan="3" %) |
9 -|
10 -|
11 -|(% rowspan="3" %) |
12 -|
13 -|
14 -|(% rowspan="2" %) |
15 -|
16 -|(% rowspan="11" %) |(% rowspan="3" %) |
17 -|
18 -|
19 -|(% rowspan="3" %) |
20 -|
21 -|
22 -|(% rowspan="3" %) |
23 -|
24 -|
25 -|(% rowspan="2" %) |
26 -|
24 +|**Type**|**Register**|**Function code & Description**
25 +|(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
26 +|06 (write single register: write a binary value to a holding register)
27 +|10 (write values to multiple addresses )
28 +|(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
29 +|06 (write single register: write a binary value to a holding register)
30 +|10 (write values to multiple addresses )
31 +|(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
32 +|06 (write single register: write a binary value to a holding register)
33 +|10 (write values to multiple addresses )
34 +|(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
35 +|10 (write values to multiple addresses )
36 +|(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
37 +|05 (Force a single coil to force the on/off state of a logic coil)
38 +|0F (Write multiple bits, ie write continuously)
39 +|(% rowspan="3" %)1|02 (Read the input state)
40 +|05 (Force a single coil to force the on/off state of a logic coil)
41 +|0F (Write multiple bits)
42 +|(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
43 +|05 (Force a single coil to force the on/off state of a logic coil)
44 +|0F (Write multiple bits)
45 +|(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
46 +|0F (Write multiple bits)
27 27  
28 28  = **WECON PLC** =
29 29  
30 -== **LX3V 串行通信** ==
50 +== **V-BOX 和维控 LX3V 串行通信** ==
31 31  
32 32  Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
33 33  
... ... @@ -78,8 +78,9 @@
78 78  
79 79  [[https:~~/~~/drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing>>url:https://drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing]]
80 80  
81 -== **LX5V serial communication** ==
82 82  
102 +== **V-BOX and Wecon LX5V serial communication** ==
103 +
83 83  This example introduces the establishment of serial port communication between Wecon V-BOX and LX5V. It is introduced through three parts: PLC software configuration, HMI software configuration, and hardware wiring.
84 84  
85 85  **Software configuration of PLC**
... ... @@ -154,7 +154,7 @@
154 154  
155 155  The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC.
156 156  
157 -== **LX5V-N Ethernet communication** ==
178 +== **V-BOX and Wecon LX5V-N Ethernet communication** ==
158 158  
159 159   This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V. It is introduced through three parts: PLC software configuration, HMI software configuration, and hardware wiring.
160 160  
... ... @@ -229,6 +229,7 @@
229 229  
230 230  = **Rockwell PLC** =
231 231  
253 +
232 232  == (% id="cke_bm_5621S" style="display:none" %)** **(%%)**MicroLogix** ==
233 233  
234 234  MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
... ... @@ -468,9 +468,11 @@
468 468  [[image:image-20220714162856-13.png]]
469 469  
470 470  (((
471 -The above are all the steps for establishing Ethernet communication between Wecon V-box with CompactLogix L1769 PLC.
493 +The above are all the steps for establishing Ethernet communication between Wecon V-box with Allen-Bradley L1769 PLC.
472 472  
495 +== ==
473 473  
497 +
474 474  == **Allen-Bradley Ethernet DF1** ==
475 475  
476 476  [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Allen-Bradley%20Ethernet%20DF1.zip]]
... ... @@ -498,8 +498,6 @@
498 498  
499 499  [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Delta%20DVP%20Ethernet.zip]]
500 500  
501 -= **Mitsubishi PLC** =
502 -
503 503  == **Communicate with Mitsubishi FX Series** ==
504 504  
505 505  [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20Mitsubishi%20FX%20Series.zip]]
... ... @@ -508,8 +508,6 @@
508 508  
509 509  [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20VB%20inverter.zip]]
510 510  
511 -= **Omron PLC** =
512 -
513 513  == **Omron CP1 Series** ==
514 514  
515 515  [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CP1%20Series.zip]]
... ... @@ -518,54 +518,6 @@
518 518  
519 519  [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CJ2M.zip]]
520 520  
521 -
522 -= **Modbus RTU** =
523 -
524 -=== **V-BOX as master** ===
525 -
526 -Select the protocol “(% class="mark" %)Modbus RTU Slave(All Fuction)”,
527 -
528 -(% class="mark" %)then set BaudRate,Port,Stop Bit,Data Bit,Parity
529 -
530 -(% style="text-align:center" %)
531 -[[image:1624342015914-382.png||height="486" width="800" class="img-thumbnail"]]
532 -
533 -=== **V-BOX as slave** ===
534 -
535 -Select the protocol “(% class="mark" %)**Modbus RTU Master”**,
536 -
537 -(% class="mark" %)then set BaudRate,Port,Stop Bit,Data Bit,Parity
538 -
539 -(% style="text-align:center" %)
540 -[[image:1624348709622-711.png||queryString="width=809&height=493" height="488" width="800" class="img-thumbnail"]]
541 -
542 -**Address List**
543 -
544 -(% class="table-bordered" %)
545 -|**Type**|**Register**|**Function code & Description**
546 -|(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
547 -|06 (write single register: write a binary value to a holding register)
548 -|10 (write values to multiple addresses )
549 -|(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
550 -|06 (write single register: write a binary value to a holding register)
551 -|10 (write values to multiple addresses )
552 -|(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
553 -|06 (write single register: write a binary value to a holding register)
554 -|10 (write values to multiple addresses )
555 -|(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
556 -|10 (write values to multiple addresses )
557 -|(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
558 -|05 (Force a single coil to force the on/off state of a logic coil)
559 -|0F (Write multiple bits, ie write continuously)
560 -|(% rowspan="3" %)1|02 (Read the input state)
561 -|05 (Force a single coil to force the on/off state of a logic coil)
562 -|0F (Write multiple bits)
563 -|(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
564 -|05 (Force a single coil to force the on/off state of a logic coil)
565 -|0F (Write multiple bits)
566 -|(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
567 -|0F (Write multiple bits)
568 -
569 569  = **2 User define protocol** =
570 570  
571 571  More serial port script instruction,please refer manual:[[Lua script function>>doc:V-BOX.V-Net.Manual.04 Lua Script.01 Lua Functions.WebHome]]~-~-->[[3.Serial port operation>>url:http://docs.we-con.com.cn/wiki/vbox/view/HMI/04.Lua%20script%20%20function%20and%20operation/01.Lua%20script%20function/#H3.Serialportoperation]]