Changes for page 1 Communication

Last modified by Hunter on 2024/07/01 10:54

From version 85.1
edited by Ben
on 2022/08/24 15:32
Change comment: There is no comment for this version
To version 90.1
edited by Ben
on 2022/08/24 16:14
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -181,7 +181,7 @@
181 181  
182 182  MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
183 183  
184 -**HMI Settings**
184 +**1)PLC Settings**
185 185  
186 186  |**Item**|**Settings**|**Note**
187 187  |Protocol|Allen-Bradlley DF1 Advanced|
... ... @@ -192,7 +192,7 @@
192 192  |Stop bit|1|
193 193  |PLC station No.|1|
194 194  
195 -**Address List**
195 +**2)Address List**
196 196  
197 197  |**Type**|**Device registers**|**Format**|**Range**|**Note**
198 198  |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
... ... @@ -210,9 +210,9 @@
210 210  |T|T nnhh|0~~ffff
211 211  |R|R nnhh|0~~ffff
212 212  
213 -[[image:image-20220824152928-1.png]]
213 +**3)Configure the communication protocol**[[image:image-20220824152928-1.png]]
214 214  
215 -**Cable Wiring**
215 +**4)Configure the communication protocol**
216 216  
217 217  [[image:image-20220824110724-1.png]]
218 218  
... ... @@ -429,9 +429,66 @@
429 429  == **S7-200 Smart Ethernet Protocol** ==
430 430  
431 431  [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20S7-200%20Smart.zip]]
432 +
433 +
434 +== ** S7-300 Ethernet Protocol** ==
435 +
436 +Supported Series: Siemens S7-300 series PLC
437 +
438 +**1)PLC Setting**
439 +
440 +|**Items**|**Settings**|**Note**
441 +|Protocol|Simens S7-300 Ethernet|
442 +|Connection|Ethernet|
443 +|Port No.|102|
444 +|PLC station No.|2|Need to be same as the PLC setting
445 +
446 +**2)Address List**
447 +
448 +|**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
449 +|(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
450 +|Q|Q|Q ddddd.o|0.0~~99999.7|
451 +|M|M|M ddddd.o|0.0~~99999.7|
452 +|DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
453 +nn: block number;
454 +
455 +dddd: address;
432 432  )))
457 +|(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
458 +|Q|QW|QW ddddd|0~~99999|
459 +|(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
460 +|MW|MW ddddd|0~~99999|(((
461 +MW0=MB(0~~1)
462 +
463 +MW2=MB(2~~3)
464 +
465 +Address value is a multiple of 2
433 433  )))
467 +|MD|MD ddddd|0~~99999|(((
468 +MD0=MB(0~~3)
434 434  
470 +MD4=MB(4~~7)
471 +
472 +Address value is a multiple of 4
473 +)))
474 +|(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
475 +nn: block number;
476 +
477 +dddd: address
478 +)))
479 +|DBxDBW|DBxDBW nndddd|0~~99999999
480 +|DBxDBD|DBxDBD nndddd|0~~99999999
481 +
482 +**3)Configure the communication protocol**
483 +
484 +[[image:image-20220824161345-1.png]]
485 +
486 +**Cable Wiring**
487 +
488 +[[image:image-20220824161450-2.png]]
489 +)))
490 +)))
491 +
435 435  == **S7-1200 Ethernet Protocol** ==
436 436  
437 437  [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]]
image-20220824161345-1.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Ben
Size
... ... @@ -1,0 +1,1 @@
1 +126.0 KB
Content
image-20220824161450-2.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Ben
Size
... ... @@ -1,0 +1,1 @@
1 +107.1 KB
Content