... ... @@ -378,7 +378,7 @@
378 378  The communication port is selected as Ethernet, the device type is selected as Allen-Bradley, the protocol is Allen-BradleyMicro850_FreeTag EthemetIP, and the IP is the internal IP address of the L1769 PLC. The port number is 44818.
379 379  )))
380 380  
381 -[[image:image-20220714162814-10.png]]
381 +[[image:image-20220824164346-1.png]]
382 382  
383 383  
384 384  (((
... ... @@ -431,7 +431,7 @@
431 431  [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20S7-200%20Smart.zip]]
432 432  
433 433  
434 -== ** S7-300 Ethernet Protocol** ==
434 +== **S7-300 Ethernet Protocol** ==
435 435  
436 436  Supported Series: Siemens S7-300 series PLC
437 437  
... ... @@ -607,12 +607,90 @@
607 607  
608 608  [[image:image-20220824162342-2.png]]
609 609  
610 +
610 610  = **Mitsubishi PLC** =
611 611  
612 -== **Mitsubishi FX Series Protocol** ==
613 +== **FX3U Serial Protocol** ==
613 613  
614 614  [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20Mitsubishi%20FX%20Series.zip]]
615 615  
617 +== **FX5U Ethernet Protocol** ==
618 +
619 +Mitsubishi FX5U series PLC
620 +
621 +**HMI Settings**
622 +
623 +|**Items**|**Settings**|**Note**
624 +|Protocol|Mitsubishi FX5U|
625 +|Connection|Ethernet|
626 +|Port No.|5002|Must be the same as the PLC setting
627 +|PLC station No.|0|
628 +
629 +**Address List**
630 +
631 +|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
632 +|(% rowspan="15" %)Bit|X|X|X o|0~~303237|
633 +|Y|Y|Y o|0~~303237|
634 +|M|M|M d|0~~99999|
635 +|B|B|B h|0~~7FFF|
636 +|F|F|F d|0~~32767|
637 +|SB|SB|SB h|0~~7FFF|
638 +|TS|TS|TS d|0~~1023|
639 +|TC|TC|TC d|0~~1023|
640 +|STS|STS|STS d|0~~1023|
641 +|STC|STC|STS d|0~~1023|
642 +|CS|CS|CS d|0~~1023|
643 +|CC|CC|CC d|0~~1023|
644 +|SM|SM|SM d|0~~9999|
645 +|L|L|L d|0~~32767|
646 +|S|S|S d|0~~4095|
647 +|(% rowspan="9" %)Word|W|W|W h|0~~3FF|
648 +|TN|TN|TN d|0~~1023|
649 +|STN|STN|STN d|0~~1023|
650 +|CN|CN|CN d|0~~1023|
651 +|R|R|R d|0~~32767|
652 +|SW|SW|SW h|0~~7FFF|
653 +|Z|Z|Z d|0~~23|
654 +|D|D|D d|0~~7999|
655 +|SD|SD|SD d|0~~11999|
656 +
657 +**PLC Settings (GX Works 3)**
658 +
659 +Find the [Ethernet port] in the navigation area.
660 +
661 +(% style="text-align:center" %)
662 +[[image:12.PLC Protocol_html_8e8f85ace087346c.png||data-xwiki-image-style-alignment="center" height="593" width="300" class="img-thumbnail"]]
663 +
664 +Select [Own Node Settings] in the [Setting Item List];
665 +
666 +Set [IP Address], [Subnet Mask], [Default Gateway];
667 +
668 +Click [Detailed Settings] into [Ethernet Configuration (Built-in Ethernet Port)] windows;
669 +
670 +(% style="text-align:center" %)
671 +[[image:12.PLC Protocol_html_5d98495052c8c10e.png||data-xwiki-image-style-alignment="center" height="339" width="600" class="img-thumbnail"]]
672 +
673 +Select [SLMP Connection Module] and add into host station as below picture shows;
674 +
675 +Set Port number as 5002 (this is necessary settings);
676 +
677 +Click [Close with Reflecting the Setting] to save and close window;
678 +
679 +(% style="text-align:center" %)
680 +[[image:12.PLC Protocol_html_14b489fdc6c6589d.png||data-xwiki-image-style-alignment="center" height="350" width="600" class="img-thumbnail"]]
681 +
682 +Click [Apply] to completed Etherenet settings;
683 +
684 +Switch to the [On line data operation] interface as below, check the item and click [Execute] to download.
685 +
686 +(% style="text-align:center" %)
687 +[[image:12.PLC Protocol_html_c93025a968a8a9e7.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
688 +
689 +**Cable Wiring**
690 +
691 +(% style="text-align:center" %)
692 +[[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
693 +
616 616  = **Delta PLC** =
617 617  
618 618  == **DVP Ethernet Protocol** ==
image-20220824164346-1.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Ben
Size
... ... @@ -1,0 +1,1 @@
1 +43.2 KB
Content