Wiki source code of 1 Communication
Version 112.1 by Ben on 2022/08/25 13:36
Show last authors
author | version | line-number | content |
---|---|---|---|
1 | = (% style="color:inherit; font-family:inherit" %)**WECON PLC**(%%) = | ||
2 | |||
3 | == **LX3V Serial Protocol** == | ||
4 | |||
5 | Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM | ||
6 | |||
7 | **1)PLC Settings** | ||
8 | |||
9 | |**Item**|**Settings**|**Note** | ||
10 | |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM| | ||
11 | |Connection|RS422/RS485| | ||
12 | |Baud rate|9600| | ||
13 | |Data bit|7| | ||
14 | |Parity|EVEN| | ||
15 | |Stop bit|1| | ||
16 | |PLC station No.|1| | ||
17 | |||
18 | **2)PLC Address List** | ||
19 | |||
20 | |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note** | ||
21 | |(% rowspan="6" %)Bit|X|X|Xo|0~~303237| | ||
22 | |Y|Y|Y o|0~~303237| | ||
23 | |M|M|M d|0~~99999| | ||
24 | |T|T|T d|0~~99999| | ||
25 | |C|C|C d|0~~99999| | ||
26 | |S|S|S d|0~~99999| | ||
27 | |(% rowspan="8" %)Word|X|X|Xo|0~~303237| | ||
28 | |Y|Y|Y o|0~~303237| | ||
29 | |M|M|M d|0~~99999| | ||
30 | |T|T|T d|0~~99999| | ||
31 | |C|C|C d|0~~199| | ||
32 | |D|D|D d|0~~7999| | ||
33 | |S|S|S d|0~~99999| | ||
34 | |SD|SD|SD d|8000~~9999| | ||
35 | |||
36 | **3)Configure the communication protocol** | ||
37 | |||
38 | [[image:image-20220824152217-1.png]] | ||
39 | |||
40 | **4)hardware connection** | ||
41 | |||
42 | * **RS422** | ||
43 | |||
44 | [[image:image-20220824120614-5.png]] | ||
45 | |||
46 | * **RS485** | ||
47 | |||
48 | [[image:image-20220824120524-3.png]] | ||
49 | |||
50 | == **LX5V Serial Protocol** == | ||
51 | |||
52 | This example introduces the establishment of serial port communication between V-BOX and LX5V. It is introduced through three parts: PLC software configuration, V-BOX software configuration, and hardware wiring. | ||
53 | |||
54 | **Software configuration of PLC** | ||
55 | |||
56 | **1)PLC programming software** | ||
57 | |||
58 | [[image:image-20220824142722-1.png]] | ||
59 | |||
60 | **2)New PLC project** | ||
61 | |||
62 | Click New Project and select the PLC model. | ||
63 | |||
64 | [[image:image-20220822172623-2.png]] | ||
65 | |||
66 | **3)Set Serial port parameters** | ||
67 | |||
68 | Follow the steps below to configure Serial port parameters | ||
69 | |||
70 | Baud rate:115200 | ||
71 | |||
72 | Data bit:8 | ||
73 | |||
74 | Stop bit:1 | ||
75 | |||
76 | Parity:No verification | ||
77 | |||
78 | [[image:image-20220822172657-3.png]] | ||
79 | |||
80 | **4)Registers list** | ||
81 | |||
82 | [[image:image-20220822172730-4.png]] | ||
83 | |||
84 | **V-BOX software configuration** | ||
85 | |||
86 | **1)V-BOX programming software** | ||
87 | |||
88 | [[image:image-20220824104124-1.png]] | ||
89 | |||
90 | **2)V-NET add device** | ||
91 | |||
92 | Open V-NET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the access key, password and remark, to add the device. | ||
93 | |||
94 | [[image:image-20220824104909-2.png]] | ||
95 | |||
96 | **3)Set communication port parameters** | ||
97 | |||
98 | Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port. | ||
99 | |||
100 | Baud rate:115200 | ||
101 | |||
102 | Data bit:8 | ||
103 | |||
104 | Stop bit:1 | ||
105 | |||
106 | Parity:No verification | ||
107 | |||
108 | [[image:image-20220824142130-1.png]] | ||
109 | |||
110 | **hardware connection** | ||
111 | |||
112 | **1)Hardware wiring diagram** | ||
113 | |||
114 | [[image:image-20220824142546-2.png]] | ||
115 | |||
116 | [[image:image-20220824142643-3.png]] | ||
117 | |||
118 | The above are all the steps for establishing serial port communication between V-BOX with LX5V PLC. | ||
119 | |||
120 | == **LX5V-N Ethernet protocol** == | ||
121 | |||
122 | This example introduces the establishment of Ethernet communication between V-BOX and LX5V-N. It is introduced through three parts: PLC software configuration, V-BOX software configuration, and hardware wiring. | ||
123 | |||
124 | **Software configuration of PLC** | ||
125 | |||
126 | **1)PLC programming software** | ||
127 | |||
128 | [[image:image-20220824142722-1.png]] | ||
129 | |||
130 | **2)New PLC project** | ||
131 | |||
132 | Click New Project and select the PLC model. | ||
133 | |||
134 | [[image:image-20220824143613-1.png]] | ||
135 | |||
136 | **3)Set Ethernet port parameters** | ||
137 | |||
138 | Follow the steps below to configure Ethernet parameters | ||
139 | |||
140 | PLC IP address:192.168.39.200 | ||
141 | |||
142 | default gateway:192.168.39.1 | ||
143 | |||
144 | subnet mask:255.255.255.0 | ||
145 | |||
146 | [[image:image-20220824143744-2.png]] | ||
147 | |||
148 | **4)Registers list** | ||
149 | |||
150 | [[image:image-20220822172730-4.png]] | ||
151 | |||
152 | (% id="cke_bm_22473S" style="display:none" %)** **(%%)**V-BOX software configuration** | ||
153 | |||
154 | **1)V-BOX programming software** | ||
155 | |||
156 | [[image:image-20220824104124-1.png]] | ||
157 | |||
158 | **2)V-NET add device** | ||
159 | |||
160 | Open V-NET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the access key, password and remark, to add the device. | ||
161 | |||
162 | [[image:image-20220824104909-2.png]] | ||
163 | |||
164 | **3)Set communication Protocol** | ||
165 | |||
166 | Click Communication to configure the LX5V plc protocol and IP address. | ||
167 | |||
168 | [[image:image-20220824144619-1.png]] | ||
169 | |||
170 | **hardware connection** | ||
171 | |||
172 | **1)Hardware wiring diagram** | ||
173 | |||
174 | [[image:image-20220824151127-2.png]] | ||
175 | |||
176 | The above are all the steps for establishing ethernet communication between V-BOX with LX5V PLC. | ||
177 | |||
178 | = **Rockwell PLC** = | ||
179 | |||
180 | == (% id="cke_bm_5621S" style="display:none" %)** **(%%)**MicroLogix Protocol** == | ||
181 | |||
182 | MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5 | ||
183 | |||
184 | **1)PLC Settings** | ||
185 | |||
186 | |**Item**|**Settings**|**Note** | ||
187 | |Protocol|Allen-Bradlley DF1 Advanced| | ||
188 | |Connection|RS232| | ||
189 | |Baud rate|19200| | ||
190 | |Data bit|8| | ||
191 | |Parity|None| | ||
192 | |Stop bit|1| | ||
193 | |PLC station No.|1| | ||
194 | |||
195 | **2)Address List** | ||
196 | |||
197 | |**Type**|**Device registers**|**Format**|**Range**|**Note** | ||
198 | |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15| | ||
199 | |O|O d.d|0.0~~255.15| | ||
200 | |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex) | ||
201 | |S|S d.d|0.0~~255.15| | ||
202 | |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex) | ||
203 | |(% rowspan="9" %)Word|S|S d|0~~255| | ||
204 | |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex) | ||
205 | |TP|TP nnhh|0~~ffff | ||
206 | |CS|CS nnhh|0~~ffff | ||
207 | |CP|CP nnhh|0~~ffff | ||
208 | |N|N nnhh|0~~ffff | ||
209 | |C|C nnhh|0~~ffff | ||
210 | |T|T nnhh|0~~ffff | ||
211 | |R|R nnhh|0~~ffff | ||
212 | |||
213 | **3)Configure the communication protocol**[[image:image-20220824152928-1.png]] | ||
214 | |||
215 | **4)Configure the communication protocol** | ||
216 | |||
217 | [[image:image-20220824110724-1.png]] | ||
218 | |||
219 | == **Micro850_FreeTag** == | ||
220 | |||
221 | ((( | ||
222 | ((( | ||
223 | This example introduces the establishment of Ethernet communication between Wecon V-box and CompactLogix L1769. It is introduced through three parts: PLC software configuration, V-box software configuration, and hardware wiring. | ||
224 | ))) | ||
225 | ))) | ||
226 | |||
227 | ((( | ||
228 | (% class="wikigeneratedid" id="HSoftwareconfigurationofPLC" %) | ||
229 | ((( | ||
230 | **Software configuration of PLC** | ||
231 | ))) | ||
232 | |||
233 | (% class="wikigeneratedid" id="HPLCprogrammingsoftware" %) | ||
234 | ((( | ||
235 | **1)PLC programming software** | ||
236 | ))) | ||
237 | |||
238 | [[image:image-20220714162600-1.png]] | ||
239 | |||
240 | (% class="wikigeneratedid" id="HNewPLCproject" %) | ||
241 | ((( | ||
242 | **2)New PLC project** | ||
243 | ))) | ||
244 | |||
245 | ((( | ||
246 | ((( | ||
247 | Click New Project and select the PLC model. | ||
248 | ))) | ||
249 | ))) | ||
250 | |||
251 | ((( | ||
252 | [[image:image-20220714162617-2.png]] | ||
253 | ))) | ||
254 | |||
255 | ((( | ||
256 | |||
257 | |||
258 | [[image:image-20220714162652-4.png]] | ||
259 | ))) | ||
260 | |||
261 | ((( | ||
262 | (% class="wikigeneratedid" id="HSetEthernetparameters" %) | ||
263 | ((( | ||
264 | **3)Set Ethernet parameters** | ||
265 | ))) | ||
266 | |||
267 | ((( | ||
268 | ((( | ||
269 | ((( | ||
270 | Follow the steps below to configure Ethernet parameters | ||
271 | ))) | ||
272 | ))) | ||
273 | ))) | ||
274 | |||
275 | ((( | ||
276 | ((( | ||
277 | ((( | ||
278 | PLC IP address:192.168.40.101 | ||
279 | ))) | ||
280 | ))) | ||
281 | ))) | ||
282 | |||
283 | ((( | ||
284 | ((( | ||
285 | ((( | ||
286 | default gateway:192.168.40.1 | ||
287 | ))) | ||
288 | ))) | ||
289 | ))) | ||
290 | |||
291 | ((( | ||
292 | ((( | ||
293 | ((( | ||
294 | subnet mask:255.255.255.0 | ||
295 | ))) | ||
296 | ))) | ||
297 | ))) | ||
298 | |||
299 | ((( | ||
300 | [[image:image-20220714162713-5.png]] | ||
301 | ))) | ||
302 | |||
303 | ((( | ||
304 | |||
305 | ))) | ||
306 | |||
307 | ((( | ||
308 | (% class="wikigeneratedid" id="HV-boxsoftwareconfiguration" %) | ||
309 | ((( | ||
310 | **V-box software configuration** | ||
311 | ))) | ||
312 | |||
313 | (% class="wikigeneratedid" id="HV-boxprogrammingsoftware" %) | ||
314 | ((( | ||
315 | **1)V-box programming software** | ||
316 | ))) | ||
317 | |||
318 | (% class="wikigeneratedid" %) | ||
319 | ((( | ||
320 | [[image:image-20220714162725-6.png]] | ||
321 | ))) | ||
322 | |||
323 | (% class="wikigeneratedid" id="HConfiguredevicenetwork" %) | ||
324 | ((( | ||
325 | **2)Configure device network** | ||
326 | ))) | ||
327 | |||
328 | ((( | ||
329 | ((( | ||
330 | ((( | ||
331 | Click the Configuration Download button[[image:image-20220714115308-8.png||height="22" width="15"]], It is used to configure the device network, update the device time, obtain the device machine code, check the device network, etc. | ||
332 | ))) | ||
333 | |||
334 | ((( | ||
335 | In the example below, the IP address of V-Box is configured as 192.168.40.66, and the networking method is 4G connection | ||
336 | ))) | ||
337 | ))) | ||
338 | ))) | ||
339 | |||
340 | ((( | ||
341 | ((( | ||
342 | [[image:image-20220714162737-7.png]] | ||
343 | |||
344 | |||
345 | ))) | ||
346 | ))) | ||
347 | ))) | ||
348 | ))) | ||
349 | |||
350 | (% class="wikigeneratedid" id="HV-netadddevice" %) | ||
351 | ((( | ||
352 | **3)V-net add device** | ||
353 | ))) | ||
354 | ))) | ||
355 | |||
356 | ((( | ||
357 | ((( | ||
358 | Open VNET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the device machine code/product code, device password, and device alias to add the device. [[image:image-20220714162752-8.png]] | ||
359 | ))) | ||
360 | |||
361 | |||
362 | ))) | ||
363 | |||
364 | ((( | ||
365 | (% class="wikigeneratedid" id="HSetcommunicationportparameters" %) | ||
366 | ((( | ||
367 | **4)Set communication port parameters** | ||
368 | ))) | ||
369 | |||
370 | ((( | ||
371 | In the device list on the left, find the Vbox that communicates with the L1769, click it and select configuration,communication port configuration in the main interface to add a communication protocol. | ||
372 | ))) | ||
373 | |||
374 | [[image:image-20220714162805-9.png]] | ||
375 | ))) | ||
376 | |||
377 | ((( | ||
378 | The communication port is selected as Ethernet, the device type is selected as Allen-Bradley, the protocol is Allen-BradleyMicro850_FreeTag EthemetIP, and the IP is the internal IP address of the L1769 PLC. The port number is 44818. | ||
379 | ))) | ||
380 | |||
381 | [[image:image-20220824164346-1.png]] | ||
382 | |||
383 | |||
384 | ((( | ||
385 | After adding the protocol Allen-BradleyMicro850_FreeTag, click[[image:image-20220714143838-2.png]]icon add label.[[image:image-20220714162827-11.png]] | ||
386 | ))) | ||
387 | |||
388 | (% class="wikigeneratedid" id="HEngineeringproduction" %) | ||
389 | ((( | ||
390 | **5)Engineering production** | ||
391 | ))) | ||
392 | |||
393 | (% class="wikigeneratedid" %) | ||
394 | ((( | ||
395 | ((( | ||
396 | According to your own needs, use the V-NET client software to edit the required data monitoring points. | ||
397 | ))) | ||
398 | |||
399 | [[image:image-20220714162841-12.png]] | ||
400 | |||
401 | |||
402 | ((( | ||
403 | **hardware connection** | ||
404 | ))) | ||
405 | ))) | ||
406 | |||
407 | ((( | ||
408 | **1)Hardware wiring diagram** | ||
409 | ))) | ||
410 | |||
411 | ((( | ||
412 | ((( | ||
413 | This example introduces Wecon V-box with Allen-Bradley L1769 PLC to establish communication through Ethernet. The connection diagram is as follows: | ||
414 | ))) | ||
415 | |||
416 | [[image:image-20220714162856-13.png]] | ||
417 | |||
418 | ((( | ||
419 | The above are all the steps for establishing Ethernet communication between Wecon V-box with CompactLogix L1769 PLC. | ||
420 | |||
421 | |||
422 | == **Allen-Bradley Ethernet DF1** == | ||
423 | |||
424 | [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Allen-Bradley%20Ethernet%20DF1.zip]] | ||
425 | |||
426 | |||
427 | = **Siemens PLC** = | ||
428 | |||
429 | == **S7-200 Smart Ethernet Protocol** == | ||
430 | |||
431 | [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20S7-200%20Smart.zip]] | ||
432 | |||
433 | |||
434 | == **S7-300 Ethernet Protocol** == | ||
435 | |||
436 | Supported Series: Siemens S7-300 series PLC | ||
437 | |||
438 | **1)PLC Setting** | ||
439 | |||
440 | |**Items**|**Settings**|**Note** | ||
441 | |Protocol|Simens S7-300 Ethernet| | ||
442 | |Connection|Ethernet| | ||
443 | |Port No.|102| | ||
444 | |PLC station No.|2|Need to be same as the PLC setting | ||
445 | |||
446 | **2)Address List** | ||
447 | |||
448 | |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note** | ||
449 | |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7| | ||
450 | |Q|Q|Q ddddd.o|0.0~~99999.7| | ||
451 | |M|M|M ddddd.o|0.0~~99999.7| | ||
452 | |DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|((( | ||
453 | nn: block number; | ||
454 | |||
455 | dddd: address; | ||
456 | ))) | ||
457 | |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999| | ||
458 | |Q|QW|QW ddddd|0~~99999| | ||
459 | |(% rowspan="3" %)M|MB|MB ddddd|0~~99999| | ||
460 | |MW|MW ddddd|0~~99999|((( | ||
461 | MW0=MB(0~~1) | ||
462 | |||
463 | MW2=MB(2~~3) | ||
464 | |||
465 | Address value is a multiple of 2 | ||
466 | ))) | ||
467 | |MD|MD ddddd|0~~99999|((( | ||
468 | MD0=MB(0~~3) | ||
469 | |||
470 | MD4=MB(4~~7) | ||
471 | |||
472 | Address value is a multiple of 4 | ||
473 | ))) | ||
474 | |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)((( | ||
475 | nn: block number; | ||
476 | |||
477 | dddd: address | ||
478 | ))) | ||
479 | |DBxDBW|DBxDBW nndddd|0~~99999999 | ||
480 | |DBxDBD|DBxDBD nndddd|0~~99999999 | ||
481 | |||
482 | **3)Configure the communication protocol** | ||
483 | |||
484 | [[image:image-20220824161345-1.png]] | ||
485 | |||
486 | **4)Cable Wiring** | ||
487 | |||
488 | [[image:image-20220824161450-2.png]] | ||
489 | ))) | ||
490 | ))) | ||
491 | |||
492 | == **S7-1200 Ethernet Protocol** == | ||
493 | |||
494 | [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]] | ||
495 | |||
496 | == **S7-XXX Ethernet Protocol** == | ||
497 | |||
498 | Supported Series: Siemens S7-400, S7-1200 and S7-1500 | ||
499 | |||
500 | **1)PLC Setting** | ||
501 | |||
502 | |=**Items**|=**Settings**|=**Note** | ||
503 | |Protocol|Siemens S7-XXX| | ||
504 | |Connection|Ethernet| | ||
505 | |Port No.|102| | ||
506 | |Device No.|Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)| | ||
507 | |HMI No.|Rack (Default as 0)| | ||
508 | |||
509 | Slot from TIA Portal is equal to Device No. of V-net | ||
510 | |||
511 | Rack from TIA Portal is equal to HMI No. of V-net | ||
512 | |||
513 | [[image:image-20220824162459-3.png]] | ||
514 | |||
515 | [[image:image-20220824163305-2.png]] | ||
516 | |||
517 | **2)Address List** | ||
518 | |||
519 | |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note** | ||
520 | |(% rowspan="4" %)Bit|I|I|M d.o|((( | ||
521 | d:0~-~-9999 | ||
522 | |||
523 | o:0-7 | ||
524 | )))| | ||
525 | |Q|Q|Q d.o|((( | ||
526 | d:0~-~-9999 | ||
527 | |||
528 | o:0-7 | ||
529 | )))| | ||
530 | |M|M|M d.o|((( | ||
531 | d:0~-~-9999 | ||
532 | |||
533 | o:0-7 | ||
534 | )))| | ||
535 | |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|((( | ||
536 | nn:0-9999, | ||
537 | |||
538 | dddd:0-9999, | ||
539 | |||
540 | o:0-7 | ||
541 | )))|((( | ||
542 | nn:DB No. | ||
543 | |||
544 | dddd:address value | ||
545 | |||
546 | o: digit address | ||
547 | ))) | ||
548 | |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999| | ||
549 | |M|MW|MW d|d:0-99999|((( | ||
550 | MW0=MB(0~~1) | ||
551 | |||
552 | MW2=MB(2~~3) | ||
553 | |||
554 | Address value is a multiple of 2 | ||
555 | ))) | ||
556 | |M|MD|MD d|d:0-99999|((( | ||
557 | MD0=MB(0~~3) | ||
558 | |||
559 | MD4=MB(4~~7) | ||
560 | |||
561 | Address value is a multiple of 4 | ||
562 | ))) | ||
563 | |I|IW|IW d|d:0-99999| | ||
564 | |Q|QW|QW d|d:0-99999| | ||
565 | |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|((( | ||
566 | nn:0-9999 | ||
567 | |||
568 | dddd:0-9999 | ||
569 | )))|((( | ||
570 | nn:DB No. | ||
571 | |||
572 | dddd:address value | ||
573 | ))) | ||
574 | |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|((( | ||
575 | nn:0-9999 | ||
576 | |||
577 | dddd:0-9999 | ||
578 | )))|((( | ||
579 | nn:DB No. | ||
580 | |||
581 | dddd:address value | ||
582 | |||
583 | Address value is a multiple of 2 | ||
584 | ))) | ||
585 | |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|((( | ||
586 | nn:0-9999 | ||
587 | |||
588 | dddd:0-9999 | ||
589 | )))|((( | ||
590 | nn:DB No. | ||
591 | |||
592 | dddd:address value | ||
593 | |||
594 | Address value is a multiple of 4 | ||
595 | ))) | ||
596 | |||
597 | **3)Configure the communication protocol** | ||
598 | |||
599 | [[image:image-20220824163448-3.png]] | ||
600 | |||
601 | **✎Note:** | ||
602 | |||
603 | * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three V-BOX. | ||
604 | * V-BOX access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200. | ||
605 | |||
606 | **4)Cable Wiring** | ||
607 | |||
608 | [[image:image-20220824162342-2.png]] | ||
609 | |||
610 | |||
611 | = **Mitsubishi PLC** = | ||
612 | |||
613 | == **FX1S,1N,2N Serial Protocol** == | ||
614 | |||
615 | Supported Series: Mitsubishi FX1S, FX1N, FX2N series | ||
616 | |||
617 | **1)V-BOX Settings** | ||
618 | |||
619 | |**Item**|**Settings**|**Note** | ||
620 | |Protocol|Mitsubishi FX1S/FX1N/FX2N| | ||
621 | |Connection|RS422/RS485/RS232| | ||
622 | |Baud rate|9600~~115200| | ||
623 | |Data bit|7/8| | ||
624 | |Parity|EVEN/Odd/None| | ||
625 | |Stop bit|1/2| | ||
626 | |PLC station No.|1~~255| | ||
627 | |||
628 | **2)Address List** | ||
629 | |||
630 | |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note** | ||
631 | |(% rowspan="7" %)Bit|X|X|Xo|0~~303237| | ||
632 | |Y|Y|Y o|0~~303237| | ||
633 | |M|M|M d|0~~99999| | ||
634 | |T|T|T d|0~~99999| | ||
635 | |C|C|C d|0~~99999| | ||
636 | |S|S|S d|0~~99999| | ||
637 | |SM|SM|SM d|8000~~9999| | ||
638 | |(% rowspan="8" %)Word|X|X|Xo|0~~303237| | ||
639 | |Y|Y|Y o|0~~303237| | ||
640 | |M|M|M d|0~~99999| | ||
641 | |T|T|T d|0~~99999| | ||
642 | |C|C|C d|0~~199| | ||
643 | |D|D|D d|0~~7999| | ||
644 | |S|S|S d|0~~99999| | ||
645 | |SD|SD|SD d|8000~~9999| | ||
646 | |||
647 | **3)Configure the communication protocol** | ||
648 | |||
649 | [[image:image-20220825102844-3.png]] | ||
650 | |||
651 | **4)Cable Wiring** | ||
652 | |||
653 | * **RS422** | ||
654 | |||
655 | [[image:image-20220825103350-4.png]] | ||
656 | |||
657 | [[image:image-20220825100845-4.png]] | ||
658 | |||
659 | |||
660 | == **FX3U,3G,3GA Serial Protocol** == | ||
661 | |||
662 | Supported Series: Mitsubishi FX3U, FX3G, FX3GA series | ||
663 | |||
664 | **1)V-BOX Settings** | ||
665 | |||
666 | |**Item**|**Settings**|**Note** | ||
667 | |Protocol|Mitsubishi FX3U/3G/3GA| | ||
668 | |Connection|RS422/RS485/RS232| | ||
669 | |Baud rate|9600~~115200| | ||
670 | |Data bit|7/8| | ||
671 | |Parity|EVEN/Odd/None| | ||
672 | |Stop bit|1/2| | ||
673 | |PLC station No.|1~~255| | ||
674 | |||
675 | **2)Address List** | ||
676 | |||
677 | |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note** | ||
678 | |(% rowspan="7" %)Bit|X|X|Xo|0~~303237| | ||
679 | |Y|Y|Y o|0~~303237| | ||
680 | |M|M|M d|0~~99999| | ||
681 | |T|T|T d|0~~99999| | ||
682 | |C|C|C d|0~~99999| | ||
683 | |S|S|S d|0~~99999| | ||
684 | |SM|SM|SM d|8000~~9999| | ||
685 | |(% rowspan="8" %)Word|X|X|Xo|0~~303237| | ||
686 | |Y|Y|Y o|0~~303237| | ||
687 | |M|M|M d|0~~99999| | ||
688 | |T|T|T d|0~~99999| | ||
689 | |C|C|C d|0~~199| | ||
690 | |D|D|D d|0~~7999| | ||
691 | |S|S|S d|0~~99999| | ||
692 | |SD|SD|SD d|8000~~9999| | ||
693 | |||
694 | **3)Configure the communication protocol** | ||
695 | |||
696 | [[image:image-20220825102649-2.png]] | ||
697 | |||
698 | **4)Cable Wiring** | ||
699 | |||
700 | * **RS422** | ||
701 | |||
702 | [[image:image-20220825103421-5.png]] | ||
703 | |||
704 | [[image:image-20220825100845-4.png]] | ||
705 | |||
706 | |||
707 | == **FX5U Serial Protocol** == | ||
708 | |||
709 | Mitsubishi FX5U series PLC | ||
710 | |||
711 | **1)V-BOX Settings** | ||
712 | |||
713 | |**Item**|**Settings**|**Note** | ||
714 | |Protocol|Mitsubishi FX5U| | ||
715 | |Connection|RS422/RS485| | ||
716 | |Baud rate|9600| | ||
717 | |Data bit|7| | ||
718 | |Parity|Odd| | ||
719 | |Stop bit|1| | ||
720 | |PLC station No.|1~~255|Need to be the same as PLC settings | ||
721 | |||
722 | **2)Address List** | ||
723 | |||
724 | |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note** | ||
725 | |(% rowspan="15" %)Bit|X|X|X o|0~~303237| | ||
726 | |Y|Y|Y o|0~~303237| | ||
727 | |M|M|M d|0~~99999| | ||
728 | |B|B|B h|0~~7FFF| | ||
729 | |F|F|F d|0~~32767| | ||
730 | |SB|SB|SB h|0~~7FFF| | ||
731 | |TS|TS|TS d|0~~1023| | ||
732 | |TC|TC|TC d|0~~1023| | ||
733 | |STS|STS|STS d|0~~1023| | ||
734 | |STC|STC|STS d|0~~1023| | ||
735 | |CS|CS|CS d|0~~1023| | ||
736 | |CC|CC|CC d|0~~1023| | ||
737 | |SM|SM|SM d|0~~9999| | ||
738 | |L|L|L d|0~~32767| | ||
739 | |S|S|S d|0~~4095| | ||
740 | |(% rowspan="9" %)Word|W|W|W h|0~~3FF| | ||
741 | |TN|TN|TN d|0~~1023| | ||
742 | |STN|STN|STN d|0~~1023| | ||
743 | |CN|CN|CN d|0~~1023| | ||
744 | |R|R|R d|0~~32767| | ||
745 | |SW|SW|SW h|0~~7FFF| | ||
746 | |Z|Z|Z d|0~~23| | ||
747 | |D|D|D d|0~~7999| | ||
748 | |SD|SD|SD d|0~~11999| | ||
749 | |||
750 | **3)PLC Settings (GX Works 3)** | ||
751 | |||
752 | Create a blank FX5U project | ||
753 | |||
754 | Find the 485 serial port module in the system navigation bar and double click to enter the settings. | ||
755 | |||
756 | [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5c9cb13fac1e6c93.png?width=200&height=462&rev=1.1||alt="12.PLC Protocol_html_5c9cb13fac1e6c93.png" height="462" width="200"]] | ||
757 | |||
758 | Select protocol in the setting item, and set parameters. | ||
759 | |||
760 | [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_de942589ca070228.png?width=600&height=324&rev=1.1||alt="12.PLC Protocol_html_de942589ca070228.png" height="324" width="600"]] | ||
761 | |||
762 | Set station number, and [Message Pattern] (Pattern 1 or Pattern 4) | ||
763 | |||
764 | [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_387ec7d00b5feb59.png?width=600&height=323&rev=1.1||alt="12.PLC Protocol_html_387ec7d00b5feb59.png" height="323" width="600"]] | ||
765 | |||
766 | Click the [Apply] button to finish the setting. | ||
767 | |||
768 | Click download and select the items as below, then click [execute] to download the configuration to PLC. | ||
769 | |||
770 | [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_cdef1c5ec8cc2105.png?width=600&height=434&rev=1.1||alt="12.PLC Protocol_html_cdef1c5ec8cc2105.png" height="434" width="600"]] | ||
771 | |||
772 | As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection]. | ||
773 | |||
774 | Done. | ||
775 | |||
776 | **4)Configure the communication protocol** | ||
777 | |||
778 | [[image:image-20220825104904-1.png]] | ||
779 | |||
780 | **5)Cable Wiring** | ||
781 | |||
782 | |||
783 | * **RS422** | ||
784 | |||
785 | [[image:image-20220825105105-2.png]] | ||
786 | |||
787 | [[image:image-20220825105533-3.png]] | ||
788 | |||
789 | == **FX5U Ethernet Protocol** == | ||
790 | |||
791 | Mitsubishi FX5U series PLC | ||
792 | |||
793 | **1)V-BOX Settings** | ||
794 | |||
795 | |**Items**|**Settings**|**Note** | ||
796 | |Protocol|Mitsubishi FX5U| | ||
797 | |Connection|Ethernet| | ||
798 | |Port No.|5002|Must be the same as the PLC setting | ||
799 | |PLC station No.|0| | ||
800 | |||
801 | **2)Address List** | ||
802 | |||
803 | |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note** | ||
804 | |(% rowspan="15" %)Bit|X|X|X o|0~~303237| | ||
805 | |Y|Y|Y o|0~~303237| | ||
806 | |M|M|M d|0~~99999| | ||
807 | |B|B|B h|0~~7FFF| | ||
808 | |F|F|F d|0~~32767| | ||
809 | |SB|SB|SB h|0~~7FFF| | ||
810 | |TS|TS|TS d|0~~1023| | ||
811 | |TC|TC|TC d|0~~1023| | ||
812 | |STS|STS|STS d|0~~1023| | ||
813 | |STC|STC|STS d|0~~1023| | ||
814 | |CS|CS|CS d|0~~1023| | ||
815 | |CC|CC|CC d|0~~1023| | ||
816 | |SM|SM|SM d|0~~9999| | ||
817 | |L|L|L d|0~~32767| | ||
818 | |S|S|S d|0~~4095| | ||
819 | |(% rowspan="9" %)Word|W|W|W h|0~~3FF| | ||
820 | |TN|TN|TN d|0~~1023| | ||
821 | |STN|STN|STN d|0~~1023| | ||
822 | |CN|CN|CN d|0~~1023| | ||
823 | |R|R|R d|0~~32767| | ||
824 | |SW|SW|SW h|0~~7FFF| | ||
825 | |Z|Z|Z d|0~~23| | ||
826 | |D|D|D d|0~~7999| | ||
827 | |SD|SD|SD d|0~~11999| | ||
828 | |||
829 | **3)PLC Settings (GX Works 3)** | ||
830 | |||
831 | Find the [Ethernet port] in the navigation area. | ||
832 | |||
833 | [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_8e8f85ace087346c.png?width=300&height=593&rev=1.1||alt="12.PLC Protocol_html_8e8f85ace087346c.png" height="593" width="300"]] | ||
834 | |||
835 | Select [Own Node Settings] in the [Setting Item List]; | ||
836 | |||
837 | Set [IP Address], [Subnet Mask], [Default Gateway]; | ||
838 | |||
839 | Click [Detailed Settings] into [Ethernet Configuration (Built-in Ethernet Port)] windows; | ||
840 | |||
841 | [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5d98495052c8c10e.png?width=600&height=339&rev=1.1||alt="12.PLC Protocol_html_5d98495052c8c10e.png" height="339" width="600"]] | ||
842 | |||
843 | Select [SLMP Connection Module] and add into host station as below picture shows; | ||
844 | |||
845 | Set Port number as 5002 (this is necessary settings); | ||
846 | |||
847 | Click [Close with Reflecting the Setting] to save and close window; | ||
848 | |||
849 | [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_14b489fdc6c6589d.png?width=600&height=350&rev=1.1||alt="12.PLC Protocol_html_14b489fdc6c6589d.png" height="350" width="600"]] | ||
850 | |||
851 | Click [Apply] to completed Etherenet settings; | ||
852 | |||
853 | Switch to the [On line data operation] interface as below, check the item and click [Execute] to download. | ||
854 | |||
855 | [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_c93025a968a8a9e7.png?width=600&height=434&rev=1.1||alt="12.PLC Protocol_html_c93025a968a8a9e7.png" height="434" width="600"]] | ||
856 | |||
857 | **4)Configure the communication protocol** | ||
858 | |||
859 | [[image:image-20220825112403-1.png]] | ||
860 | |||
861 | **5)Cable Wiring** | ||
862 | |||
863 | [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]] | ||
864 | |||
865 | = **Delta PLC** = | ||
866 | |||
867 | == **DVP Ethernet Protocol** == | ||
868 | |||
869 | [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Delta%20DVP%20Ethernet.zip]] | ||
870 | |||
871 | == **DVP Serial Protocol** == | ||
872 | |||
873 | [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Delta%20DVP%20Ethernet.zip]] | ||
874 | |||
875 | = **Omron PLC** = | ||
876 | |||
877 | == **CP1 Series Protocol** == | ||
878 | |||
879 | [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CP1%20Series.zip]] | ||
880 | |||
881 | == **CJ2M Series Protocol** == | ||
882 | |||
883 | [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CJ2M.zip]] | ||
884 | |||
885 | = **Modbus RTU** = | ||
886 | |||
887 | == **V-BOX as master** == | ||
888 | |||
889 | Select the protocol “(% class="mark" %)Modbus RTU Slave(All Fuction)”, | ||
890 | |||
891 | (% class="mark" %)then set BaudRate,Port,Stop Bit,Data Bit,Parity | ||
892 | |||
893 | (% style="text-align:center" %) | ||
894 | [[image:1624342015914-382.png||height="486" width="800" class="img-thumbnail"]] | ||
895 | |||
896 | == **V-BOX as slave** == | ||
897 | |||
898 | Select the protocol “(% class="mark" %)**Modbus RTU Master”**, | ||
899 | |||
900 | (% class="mark" %)then set BaudRate,Port,Stop Bit,Data Bit,Parity | ||
901 | |||
902 | (% style="text-align:center" %) | ||
903 | [[image:1624348709622-711.png||queryString="width=809&height=493" height="488" width="800" class="img-thumbnail"]] | ||
904 | |||
905 | **Address List** | ||
906 | |||
907 | (% class="table-bordered" %) | ||
908 | |**Type**|**Register**|**Function code & Description** | ||
909 | |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers) | ||
910 | |06 (write single register: write a binary value to a holding register) | ||
911 | |10 (write values to multiple addresses ) | ||
912 | |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers) | ||
913 | |06 (write single register: write a binary value to a holding register) | ||
914 | |10 (write values to multiple addresses ) | ||
915 | |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers) | ||
916 | |06 (write single register: write a binary value to a holding register) | ||
917 | |10 (write values to multiple addresses ) | ||
918 | |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers) | ||
919 | |10 (write values to multiple addresses ) | ||
920 | |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state) | ||
921 | |05 (Force a single coil to force the on/off state of a logic coil) | ||
922 | |0F (Write multiple bits, ie write continuously) | ||
923 | |(% rowspan="3" %)1|02 (Read the input state) | ||
924 | |05 (Force a single coil to force the on/off state of a logic coil) | ||
925 | |0F (Write multiple bits) | ||
926 | |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils) | ||
927 | |05 (Force a single coil to force the on/off state of a logic coil) | ||
928 | |0F (Write multiple bits) | ||
929 | |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils) | ||
930 | |0F (Write multiple bits) | ||
931 | |||
932 | == **communicate with VB inverter** == | ||
933 | |||
934 | [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20VB%20inverter.zip]] | ||
935 | |||
936 | = **User define protocol** = | ||
937 | |||
938 | More serial port script instruction,please refer manual:[[Lua script function>>doc:V-BOX.V-Net.Manual.04 Lua Script.01 Lua Functions.WebHome]]~-~-->[[3.Serial port operation>>url:http://docs.we-con.com.cn/wiki/vbox/view/HMI/04.Lua%20script%20%20function%20and%20operation/01.Lua%20script%20function/#H3.Serialportoperation]] | ||
939 | |||
940 | == **Read the temperature sensor.** == | ||
941 | |||
942 | the commond format is as beliow: | ||
943 | |||
944 | Send commond:01 03 02 00 00 03 04 73 | ||
945 | |||
946 | Feedback commond:01 03 06 07 F7 0E 7E B7 35 | ||
947 | |||
948 | Temperature data:07 F7,desimal = 2039,it means temperature is 20.39℃. | ||
949 | |||
950 | Humidity data:0E 7E,desimal = 3710, it mean humidity is 37.10%RH. | ||
951 | |||
952 | Script Demo: | ||
953 | |||
954 | ~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-- | ||
955 | |||
956 | function com.main() | ||
957 | ~-~-dosomething | ||
958 | openPlc() | ||
959 | end | ||
960 | function openPlc() | ||
961 | if obj then | ||
962 | ~-~- If the serial port opened,then read/write data by timing | ||
963 | |||
964 | local wri = string.pack(">HHHH",0X0103,0X0200,0X0003,0X0473) | ||
965 | local arr = reading(wri) | ||
966 | ~-~- if arr ~~=nil then | ||
967 | ~-~- if arr[1] ==33 and arr[2] ==v[2][2] and arr[3] ==v[2][3] then | ||
968 | ~-~- local A = arr[4]*256 | ||
969 | ~-~- local B = A+arr[5] | ||
970 | ~-~- addr_setword(v[1],B) | ||
971 | ~-~- end | ||
972 | ~-~- end | ||
973 | |||
974 | else | ||
975 | ~-~-judge if there is a serial object, then initialize and open the serial port | ||
976 | local configs = { | ||
977 | name = 'COM1', ~-~-Select serial port COM1 | ||
978 | mode = 485, ~-~-Communication mode RS485 | ||
979 | baud_rate = 9600, ~-~-Baud rate 9600 | ||
980 | stop_bit = 1, ~-~-stop bit 1 | ||
981 | data_len = 8, ~-~-data length 8 | ||
982 | check_bit = 'NONE', ~-~-no parity | ||
983 | |||
984 | } | ||
985 | obj,err = serial.open(configs) ~-~-Open serial port | ||
986 | if not obj then | ||
987 | print("serial open :failed", err) ~-~- Open serial port failed | ||
988 | end | ||
989 | end | ||
990 | end | ||
991 | |||
992 | function reading(wri) | ||
993 | obj:flush() ~-~- Clear serial port | ||
994 | obj:write(wri) ~-~- Write serial port | ||
995 | print(string.byte(wri,1,#wri)) | ||
996 | obj:flush() ~-~- Clear serial port | ||
997 | local readed =obj:read(9,1000) ~-~- Read 9 bytes, timeout 1 second | ||
998 | if readed and readed ~~= "" then | ||
999 | ~-~- judge that a non-empty string is read | ||
1000 | print(string.byte(readed,1,#readed)) | ||
1001 | a={string.byte(readed, 1, #readed)} | ||
1002 | if nil ~~= a[4] and nil ~~= a[5] and nil ~~= a[6] and nil ~~= a[7] then | ||
1003 | a1=a[4]*256+a[5] | ||
1004 | a2=a[6]*256+a[7] | ||
1005 | addr_setword("@HDW0",a1) | ||
1006 | addr_setword("@HDW1",a2) | ||
1007 | end | ||
1008 | return {string.byte(readed, 1, #readed)} | ||
1009 | elseif readed == nil then | ||
1010 | print("serial read err:", err or "") | ||
1011 | return nil | ||
1012 | end | ||
1013 | return nil | ||
1014 | end | ||
1015 | |||
1016 | ~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~- |