1 = **1 General communication with PLC** =
2
3 == **Modbus RTU** ==
4
5 === **V-BOX as master** ===
6
7 Select the protocol “(% class="mark" %)Modbus RTU Slave(All Fuction)”,
8
9 (% class="mark" %)then set BaudRate,Port,Stop Bit,Data Bit,Parity
10
11 (% style="text-align:center" %)
12 [[image:1624342015914-382.png||height="486" width="800" class="img-thumbnail"]]
13
14 === **V-BOX as slave** ===
15
16 Select the protocol “(% class="mark" %)**Modbus RTU Master”**,
17
18 (% class="mark" %)then set BaudRate,Port,Stop Bit,Data Bit,Parity
19
20 (% style="text-align:center" %)
21 [[image:1624348709622-711.png||queryString="width=809&height=493" height="488" width="800" class="img-thumbnail"]]
22
23 **Address List**
24
25 (% class="table-bordered" %)
26 |**Type**|**Register**|**Function code & Description**
27 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
28 |06 (write single register: write a binary value to a holding register)
29 |10 (write values to multiple addresses )
30 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
31 |06 (write single register: write a binary value to a holding register)
32 |10 (write values to multiple addresses )
33 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
34 |06 (write single register: write a binary value to a holding register)
35 |10 (write values to multiple addresses )
36 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
37 |10 (write values to multiple addresses )
38 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
39 |05 (Force a single coil to force the on/off state of a logic coil)
40 |0F (Write multiple bits, ie write continuously)
41 |(% rowspan="3" %)1|02 (Read the input state)
42 |05 (Force a single coil to force the on/off state of a logic coil)
43 |0F (Write multiple bits)
44 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
45 |05 (Force a single coil to force the on/off state of a logic coil)
46 |0F (Write multiple bits)
47 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
48 |0F (Write multiple bits)
49
50 == **WECON LX3V PLC** ==
51
52 Select the protocol (% class="mark" %)"WECON LX3V"
53
54 (% class="mark" %)then set BaudRate,Port,Stop Bit,Data Bit,Parity same with PLC.
55
56 (% class="mark" %)WECON PLC RS422 port,default communication parameters is 9600,1,7,ZEVEN
57
58 (% style="text-align:center" %)
59 [[image:1624348978863-771.png||queryString="width=812&height=494" height="487" width="800" class="img-thumbnail"]]
60
61 == **2 Communication with Allen-Bradley CompactLogix L1769** ==
62
63 === **Overview** ===
64
65 (((
66 This example introduces the establishment of Ethernet communication between Wecon V-box and Allen-Bradley L1769. It is introduced through three parts: PLC software configuration, V-box software configuration, and hardware wiring.
67 )))
68
69 (((
70
71 )))
72
73 (((
74 == **Software configuration of PLC** ==
75
76 === **PLC programming software** ===
77
78 [[image:image-20220714113935-3.png]]
79
80 === **New PLC project** ===
81
82 (((
83 Click New Project and select the PLC model.
84 )))
85
86 (((
87 [[image:image-20220714114247-4.png]]
88 )))
89
90 (((
91 [[image:image-20220714114257-5.png]]
92 )))
93
94 (((
95
96 )))
97
98 (((
99 === **Set Ethernet parameters** ===
100
101 (((
102 Follow the steps below to configure Ethernet parameters
103 )))
104
105 (((
106 PLC IP address:192.168.40.101
107 )))
108
109 (((
110 default gateway:192.168.40.1
111 )))
112
113 (((
114 subnet mask:255.255.255.0
115 )))
116
117 (((
118 [[image:image-20220714115012-6.png]]
119 )))
120
121 (((
122
123 )))
124
125 (((
126 == **V-box software configuration** ==
127
128 === **V-box programming software** ===
129
130 [[image:image-20220714115214-7.png]]
131
132
133 === **Configure device network** ===
134
135 (((
136 Click the Configuration Download button[[image:image-20220714115308-8.png||height="22" width="15"]], It is used to configure the device network, update the device time, obtain the device machine code, check the device network, etc.
137 )))
138
139 (((
140 In the example below, the IP address of V-Box is configured as 192.168.40.66, and the networking method is 4G connection.
141 )))
142
143 [[image:image-20220714115440-9.png||height="425" width="791"]]
144 )))
145 )))
146
147 == **V-net add device** ==
148 )))
149
150 (((
151 Open VNET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the device machine code/product code, device password, and device alias to add the device. 
152 )))
153
154 (((
155 [[image:image-20220714115640-10.png||height="430" width="797"]]
156 )))
157
158 (((
159
160 )))
161
162 (((
163 === **Set communication port parameters** ===
164
165 In the device list on the left, find the Vbox that communicates with the L1769, click it and select configuration,communication port configuration in the main interface to add a communication protocol.
166
167 [[image:image-20220714115848-11.png||height="432" width="802"]]
168 )))
169
170
171 The communication port is selected as Ethernet, the device type is selected as Allen-Bradley, the protocol is Allen-BradleyMicro850_FreeTag EthemetIP, and the IP is the internal IP address of the L1769 PLC. The port number is 44818.
172
173
174
175 == **Siemens S7-1200** ==
176
177 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]]
178
179 == **Allen-Bradley Ethernet DF1** ==
180
181 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Allen-Bradley%20Ethernet%20DF1.zip]]
182
183 == **Communication with S7-200 Smart** ==
184
185 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20S7-200%20Smart.zip]]
186
187 == **Delta DVP Ethernet** ==
188
189 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Delta%20DVP%20Ethernet.zip]]
190
191 == **Delta DVP Serial Protocol** ==
192
193 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Delta%20DVP%20Ethernet.zip]]
194
195 == **Communicate with Mitsubishi FX Series** ==
196
197 [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20Mitsubishi%20FX%20Series.zip]]
198
199 == **Communicate with VB inverter** ==
200
201 [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20VB%20inverter.zip]]
202
203 == **Omron CP1 Series** ==
204
205 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CP1%20Series.zip]]
206
207 == **Omron CJ2M** ==
208
209 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CJ2M.zip]]
210
211 = **2 User define protocol** =
212
213 More serial port script instruction,please refer manual:[[Lua script function>>doc:V-BOX.V-Net.1\.User Manual.04 Lua Script.01 Lua Functions.WebHome]]~-~-->[[3.Serial port operation>>url:http://docs.we-con.com.cn/wiki/vbox/view/HMI/04.Lua%20script%20%20function%20and%20operation/01.Lua%20script%20function/#H3.Serialportoperation]]
214
215 == **Read the temperature sensor.** ==
216
217 the commond format is as beliow:
218
219 Send commond:01 03 02 00 00 03 04 73
220
221 Feedback commond:01 03 06 07 F7 0E 7E B7 35
222
223 Temperature data:07 F7,desimal = 2039,it means temperature is 20.39℃.
224
225 Humidity data:0E 7E,desimal = 3710, it mean humidity is 37.10%RH.
226
227 Script Demo:
228
229 ~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~--
230
231 function com.main()
232 ~-~-dosomething
233 openPlc()
234 end
235 function openPlc()
236 if obj then
237 ~-~- If the serial port opened,then read/write data by timing
238
239 local wri = string.pack(">HHHH",0X0103,0X0200,0X0003,0X0473)
240 local arr = reading(wri)
241 ~-~- if arr ~~=nil then
242 ~-~- if arr[1] ==33 and arr[2] ==v[2][2] and arr[3] ==v[2][3] then
243 ~-~- local A = arr[4]*256
244 ~-~- local B = A+arr[5]
245 ~-~- addr_setword(v[1],B)
246 ~-~- end
247 ~-~- end
248
249 else
250 ~-~-judge if there is a serial object, then initialize and open the serial port
251 local configs = {
252 name = 'COM1', ~-~-Select serial port COM1
253 mode = 485, ~-~-Communication mode RS485
254 baud_rate = 9600, ~-~-Baud rate 9600
255 stop_bit = 1, ~-~-stop bit 1
256 data_len = 8, ~-~-data length 8
257 check_bit = 'NONE', ~-~-no parity
258
259 }
260 obj,err = serial.open(configs) ~-~-Open serial port
261 if not obj then
262 print("serial open :failed", err) ~-~- Open serial port failed
263 end
264 end
265 end
266
267 function reading(wri)
268 obj:flush() ~-~- Clear serial port
269 obj:write(wri) ~-~- Write serial port
270 print(string.byte(wri,1,#wri))
271 obj:flush() ~-~- Clear serial port 
272 local readed =obj:read(9,1000) ~-~- Read 9 bytes, timeout 1 second
273 if readed and readed ~~= "" then 
274 ~-~- judge that a non-empty string is read
275 print(string.byte(readed,1,#readed))
276 a={string.byte(readed, 1, #readed)}
277 if nil ~~= a[4] and nil ~~= a[5] and nil ~~= a[6] and nil ~~= a[7] then
278 a1=a[4]*256+a[5]
279 a2=a[6]*256+a[7]
280 addr_setword("@HDW0",a1)
281 addr_setword("@HDW1",a2)
282 end
283 return {string.byte(readed, 1, #readed)}
284 elseif readed == nil then
285 print("serial read err:", err or "")
286 return nil
287 end
288 return nil
289 end
290
291 ~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-