Wiki source code of 1 Communication

Version 138.1 by Ben on 2022/08/29 13:57

Show last authors
1 = Create communication with WECON PLC =
2
3 == **LX3V Serial Protocol** ==
4
5 Supported series: Wecon LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
6
7 **1)V-BOX setting**
8
9 |**Item**|**Settings**|**Note**
10 |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
11 |Connection|RS422/RS485|
12 |Baud rate|9600|
13 |Data bit|7|
14 |Parity|EVEN|
15 |Stop bit|1|
16 |PLC station No.|1|
17
18 **2)Address List**
19
20
21 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
22 |(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
23 |Y|Y|Y o|0~~303237|
24 |M|M|M d|0~~99999|
25 |T|T|T d|0~~99999|
26 |C|C|C d|0~~99999|
27 |S|S|S d|0~~99999|
28 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
29 |Y|Y|Y o|0~~303237|
30 |M|M|M d|0~~99999|
31 |T|T|T d|0~~99999|
32 |C|C|C d|0~~199|
33 |D|D|D d|0~~7999|
34 |S|S|S d|0~~99999|
35 |SD|SD|SD d|8000~~9999|
36
37 **3)Configure the communication protocol**
38
39 [[image:image-20220824152217-1.png||alt="图片-20220824152217-1.png"]]
40
41 **4)Cable Wiring**
42
43 * **RS422**
44
45 [[image:image-20220824120614-5.png]]
46
47 * **RS485**
48
49 [[image:image-20220824120524-3.png]]
50
51 == **LX5V Serial Protocol** ==
52
53 This example introduces the establishment of serial port communication between V-BOX and LX5V. It is introduced through three parts: PLC software configuration, V-BOX software configuration, and hardware wiring.
54
55 **Software configuration of PLC**
56
57 **1)PLC programming software**
58
59 [[image:image-20220824142722-1.png]]
60
61 **2)New PLC project**
62
63 Click New Project and select the PLC model.
64
65 [[image:image-20220822172623-2.png]]
66
67 **3)Set Serial port parameters**
68
69 Follow the steps below to configure Serial port parameters
70
71 Baud rate:115200
72
73 Data bit:8
74
75 Stop bit:1
76
77 Parity:No verification
78
79 [[image:image-20220822172657-3.png]]
80
81 **4)Registers list**
82
83 [[image:image-20220822172730-4.png]]
84
85 **V-BOX software configuration**
86
87 **1)V-BOX programming software**
88
89 [[image:image-20220824104124-1.png]]
90
91 **2)V-NET add device**
92
93 Open V-NET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the access key, password and remark, to add the device.
94
95 [[image:image-20220824104909-2.png]]
96
97 **3)Set communication port parameters**
98
99 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
100
101 Baud rate:115200
102
103 Data bit:8
104
105 Stop bit:1
106
107 Parity:No verification
108
109 [[image:image-20220824142130-1.png]]
110
111 **hardware connection**
112
113 **1)Hardware wiring diagram**
114
115 [[image:image-20220824142546-2.png]]
116
117 [[image:image-20220824142643-3.png]]
118
119 The above are all the steps for establishing serial port communication between V-BOX with LX5V PLC.
120
121 == **LX5V-N Ethernet protocol** ==
122
123 This example introduces the establishment of Ethernet communication between V-BOX and LX5V-N. It is introduced through three parts: PLC software configuration, V-BOX software configuration, and hardware wiring.
124
125 **Software configuration of PLC**
126
127 **1)PLC programming software**
128
129 [[image:image-20220824142722-1.png]]
130
131 **2)New PLC project**
132
133 Click New Project and select the PLC model.
134
135 [[image:image-20220824143613-1.png]]
136
137 **3)Set Ethernet port parameters**
138
139 Follow the steps below to configure Ethernet parameters
140
141 PLC IP address:192.168.39.200
142
143 default gateway:192.168.39.1
144
145 subnet mask:255.255.255.0
146
147 [[image:image-20220824143744-2.png]]
148
149 **4)Registers list**
150
151 [[image:image-20220822172730-4.png]]
152
153 (% id="cke_bm_22473S" style="display:none" %)** **(%%)**V-BOX software configuration**
154
155 **1)V-BOX programming software**
156
157 [[image:image-20220824104124-1.png]]
158
159 **2)V-NET add device**
160
161 Open V-NET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the access key, password and remark, to add the device.
162
163 [[image:image-20220824104909-2.png]]
164
165 **3)Set communication Protocol**
166
167 Click Communication to configure the LX5V plc protocol and IP address.
168
169 [[image:image-20220824144619-1.png]]
170
171 **hardware connection**
172
173 **1)Hardware wiring diagram**
174
175 [[image:image-20220824151127-2.png]]
176
177 The above are all the steps for establishing ethernet communication between V-BOX with LX5V PLC.
178
179 = Create communication with **Rockwell PLC** =
180
181 == (% id="cke_bm_5621S" style="display:none" %)** **(%%)**MicroLogix Protocol** ==
182
183 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
184
185 **1)PLC Settings**
186
187 |**Item**|**Settings**|**Note**
188 |Protocol|Allen-Bradlley DF1 Advanced|
189 |Connection|RS232|
190 |Baud rate|19200|
191 |Data bit|8|
192 |Parity|None|
193 |Stop bit|1|
194 |PLC station No.|1|
195
196 **2)Address List**
197
198 |**Type**|**Device registers**|**Format**|**Range**|**Note**
199 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
200 |O|O d.d|0.0~~255.15|
201 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
202 |S|S d.d|0.0~~255.15|
203 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
204 |(% rowspan="9" %)Word|S|S d|0~~255|
205 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
206 |TP|TP nnhh|0~~ffff
207 |CS|CS nnhh|0~~ffff
208 |CP|CP nnhh|0~~ffff
209 |N|N nnhh|0~~ffff
210 |C|C nnhh|0~~ffff
211 |T|T nnhh|0~~ffff
212 |R|R nnhh|0~~ffff
213
214 **3)Configure the communication protocol**[[image:image-20220824152928-1.png]]
215
216 **4)Configure the communication protocol**
217
218 [[image:image-20220824110724-1.png]]
219
220 == **Micro850_FreeTag** ==
221
222 (((
223 (((
224 This example introduces the establishment of Ethernet communication between Wecon V-box and CompactLogix L1769. It is introduced through three parts: PLC software configuration, V-box software configuration, and hardware wiring.
225 )))
226 )))
227
228 (((
229 (% class="wikigeneratedid" id="HSoftwareconfigurationofPLC" %)
230 (((
231 **Software configuration of PLC**
232 )))
233
234 (% class="wikigeneratedid" id="HPLCprogrammingsoftware" %)
235 (((
236 **1)PLC programming software**
237 )))
238
239 [[image:image-20220714162600-1.png]]
240
241 (% class="wikigeneratedid" id="HNewPLCproject" %)
242 (((
243 **2)New PLC project**
244 )))
245
246 (((
247 (((
248 Click New Project and select the PLC model.
249 )))
250 )))
251
252 (((
253 [[image:image-20220714162617-2.png]]
254 )))
255
256 (((
257
258
259 [[image:image-20220714162652-4.png]]
260 )))
261
262 (((
263 (% class="wikigeneratedid" id="HSetEthernetparameters" %)
264 (((
265 **3)Set Ethernet parameters**
266 )))
267
268 (((
269 (((
270 (((
271 Follow the steps below to configure Ethernet parameters
272 )))
273 )))
274 )))
275
276 (((
277 (((
278 (((
279 PLC IP address:192.168.40.101
280 )))
281 )))
282 )))
283
284 (((
285 (((
286 (((
287 default gateway:192.168.40.1
288 )))
289 )))
290 )))
291
292 (((
293 (((
294 (((
295 subnet mask:255.255.255.0
296 )))
297 )))
298 )))
299
300 (((
301 [[image:image-20220714162713-5.png]]
302 )))
303
304 (((
305
306 )))
307
308 (((
309 (% class="wikigeneratedid" id="HV-boxsoftwareconfiguration" %)
310 (((
311 **V-box software configuration**
312 )))
313
314 (% class="wikigeneratedid" id="HV-boxprogrammingsoftware" %)
315 (((
316 **1)V-box programming software**
317 )))
318
319 (% class="wikigeneratedid" %)
320 (((
321 [[image:image-20220714162725-6.png]]
322 )))
323
324 (% class="wikigeneratedid" id="HConfiguredevicenetwork" %)
325 (((
326 **2)Configure device network**
327 )))
328
329 (((
330 (((
331 (((
332 Click the Configuration Download button[[image:image-20220714115308-8.png||height="22" width="15"]], It is used to configure the device network, update the device time, obtain the device machine code, check the device network, etc.
333 )))
334
335 (((
336 In the example below, the IP address of V-Box is configured as 192.168.40.66, and the networking method is 4G connection
337 )))
338 )))
339 )))
340
341 (((
342 (((
343 [[image:image-20220714162737-7.png]]
344
345
346 )))
347 )))
348 )))
349 )))
350
351 (% class="wikigeneratedid" id="HV-netadddevice" %)
352 (((
353 **3)V-net add device**
354 )))
355 )))
356
357 (((
358 (((
359 Open VNET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the device machine code/product code, device password, and device alias to add the device.   [[image:image-20220714162752-8.png]]
360 )))
361
362
363 )))
364
365 (((
366 (% class="wikigeneratedid" id="HSetcommunicationportparameters" %)
367 (((
368 **4)Set communication port parameters**
369 )))
370
371 (((
372 In the device list on the left, find the Vbox that communicates with the L1769, click it and select configuration,communication port configuration in the main interface to add a communication protocol.
373 )))
374
375 [[image:image-20220714162805-9.png]]
376 )))
377
378 (((
379 The communication port is selected as Ethernet, the device type is selected as Allen-Bradley, the protocol is Allen-BradleyMicro850_FreeTag EthemetIP, and the IP is the internal IP address of the L1769 PLC. The port number is 44818.
380 )))
381
382 [[image:image-20220824164346-1.png]]
383
384
385 (((
386 After adding the protocol Allen-BradleyMicro850_FreeTag, click[[image:image-20220714143838-2.png]]icon add label.[[image:image-20220714162827-11.png]]
387 )))
388
389 (% class="wikigeneratedid" id="HEngineeringproduction" %)
390 (((
391 **5)Engineering production**
392 )))
393
394 (% class="wikigeneratedid" %)
395 (((
396 (((
397 According to your own needs, use the V-NET client software to edit the required data monitoring points.
398 )))
399
400 [[image:image-20220714162841-12.png]]
401
402
403 (((
404 **hardware connection**
405 )))
406 )))
407
408 (((
409 **1)Hardware wiring diagram**
410 )))
411
412 (((
413 (((
414 This example introduces Wecon V-box with Allen-Bradley L1769 PLC to establish communication through Ethernet. The connection diagram is as follows:
415 )))
416
417 [[image:image-20220714162856-13.png]]
418
419 (((
420 The above are all the steps for establishing Ethernet communication between Wecon V-box with CompactLogix L1769 PLC.
421
422
423 == **Allen-Bradley Ethernet DF1** ==
424
425 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Allen-Bradley%20Ethernet%20DF1.zip]]
426
427
428 = Create communication with **Siemens PLC** =
429
430 == **S7-200 Smart Ethernet Protocol** ==
431
432 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20S7-200%20Smart.zip]]
433
434
435 == **S7-300 Ethernet Protocol** ==
436
437 Supported Series: Siemens S7-300 series PLC
438
439 **1)PLC Setting**
440
441 |**Items**|**Settings**|**Note**
442 |Protocol|Simens S7-300 Ethernet|
443 |Connection|Ethernet|
444 |Port No.|102|
445 |PLC station No.|2|Need to be same as the PLC setting
446
447 **2)Address List**
448
449 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
450 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
451 |Q|Q|Q ddddd.o|0.0~~99999.7|
452 |M|M|M ddddd.o|0.0~~99999.7|
453 |DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
454 nn: block number;
455
456 dddd: address;
457 )))
458 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
459 |Q|QW|QW ddddd|0~~99999|
460 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
461 |MW|MW ddddd|0~~99999|(((
462 MW0=MB(0~~1)
463
464 MW2=MB(2~~3)
465
466 Address value is a multiple of 2
467 )))
468 |MD|MD ddddd|0~~99999|(((
469 MD0=MB(0~~3)
470
471 MD4=MB(4~~7)
472
473 Address value is a multiple of 4
474 )))
475 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
476 nn: block number;
477
478 dddd: address
479 )))
480 |DBxDBW|DBxDBW nndddd|0~~99999999
481 |DBxDBD|DBxDBD nndddd|0~~99999999
482
483 **3)Configure the communication protocol**
484
485 [[image:image-20220824161345-1.png]]
486
487 **4)Cable Wiring**
488
489 [[image:image-20220824161450-2.png]]
490 )))
491 )))
492
493 == **S7-1200 Ethernet Protocol** ==
494
495 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]]
496
497 == **S7-XXX Ethernet Protocol** ==
498
499 Supported Series: Siemens S7-400, S7-1200 and S7-1500
500
501 **1)PLC Setting**
502
503 |=**Items**|=**Settings**|=**Note**
504 |Protocol|Siemens S7-XXX|
505 |Connection|Ethernet|
506 |Port No.|102|
507 |Device No.|Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|
508 |HMI No.|Rack (Default as 0)|
509
510 Slot from TIA Portal is equal to Device No. of V-net
511
512 Rack from TIA Portal is equal to HMI No. of V-net
513
514 [[image:image-20220824162459-3.png]]
515
516 [[image:image-20220824163305-2.png]]
517
518 **2)Address List**
519
520 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
521 |(% rowspan="4" %)Bit|I|I|M d.o|(((
522 d:0~-~-9999
523
524 o:0-7
525 )))|
526 |Q|Q|Q d.o|(((
527 d:0~-~-9999
528
529 o:0-7
530 )))|
531 |M|M|M d.o|(((
532 d:0~-~-9999
533
534 o:0-7
535 )))|
536 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
537 nn:0-9999,
538
539 dddd:0-9999,
540
541 o:0-7
542 )))|(((
543 nn:DB No.
544
545 dddd:address value
546
547 o: digit address
548 )))
549 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
550 |M|MW|MW d|d:0-99999|(((
551 MW0=MB(0~~1)
552
553 MW2=MB(2~~3)
554
555 Address value is a multiple of 2
556 )))
557 |M|MD|MD d|d:0-99999|(((
558 MD0=MB(0~~3)
559
560 MD4=MB(4~~7)
561
562 Address value is a multiple of 4
563 )))
564 |I|IW|IW d|d:0-99999|
565 |Q|QW|QW d|d:0-99999|
566 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
567 nn:0-9999
568
569 dddd:0-9999
570 )))|(((
571 nn:DB No.
572
573 dddd:address value
574 )))
575 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
576 nn:0-9999
577
578 dddd:0-9999
579 )))|(((
580 nn:DB No.
581
582 dddd:address value
583
584 Address value is a multiple of 2
585 )))
586 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
587 nn:0-9999
588
589 dddd:0-9999
590 )))|(((
591 nn:DB No.
592
593 dddd:address value
594
595 Address value is a multiple of 4
596 )))
597
598 **3)Configure the communication protocol**
599
600 [[image:image-20220824163448-3.png]]
601
602 **✎Note:**
603
604 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three V-BOX.
605 * V-BOX access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
606
607 **4)Cable Wiring**
608
609 [[image:image-20220824162342-2.png]]
610
611 = Create communication with **Mitsubishi PLC** =
612
613 == **FX1S,1N,2N Serial Protocol** ==
614
615 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
616
617 **1)V-BOX Settings**
618
619 |**Item**|**Settings**|**Note**
620 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
621 |Connection|RS422/RS485/RS232|
622 |Baud rate|9600~~115200|
623 |Data bit|7/8|
624 |Parity|EVEN/Odd/None|
625 |Stop bit|1/2|
626 |PLC station No.|1~~255|
627
628 **2)Address List**
629
630 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
631 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
632 |Y|Y|Y o|0~~303237|
633 |M|M|M d|0~~99999|
634 |T|T|T d|0~~99999|
635 |C|C|C d|0~~99999|
636 |S|S|S d|0~~99999|
637 |SM|SM|SM d|8000~~9999|
638 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
639 |Y|Y|Y o|0~~303237|
640 |M|M|M d|0~~99999|
641 |T|T|T d|0~~99999|
642 |C|C|C d|0~~199|
643 |D|D|D d|0~~7999|
644 |S|S|S d|0~~99999|
645 |SD|SD|SD d|8000~~9999|
646
647 **3)Configure the communication protocol**
648
649 [[image:image-20220825102844-3.png]]
650
651 **4)Cable Wiring**
652
653 * **RS422**
654
655 [[image:image-20220825103350-4.png]]
656
657 [[image:image-20220825100845-4.png]]
658
659
660 == **FX3U,3G,3GA Serial Protocol** ==
661
662 Supported Series: Mitsubishi FX3U, FX3G, FX3GA series
663
664 **1)V-BOX Settings**
665
666 |**Item**|**Settings**|**Note**
667 |Protocol|Mitsubishi FX3U/3G/3GA|
668 |Connection|RS422/RS485/RS232|
669 |Baud rate|9600~~115200|
670 |Data bit|7/8|
671 |Parity|EVEN/Odd/None|
672 |Stop bit|1/2|
673 |PLC station No.|1~~255|
674
675 **2)Address List**
676
677 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
678 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
679 |Y|Y|Y o|0~~303237|
680 |M|M|M d|0~~99999|
681 |T|T|T d|0~~99999|
682 |C|C|C d|0~~99999|
683 |S|S|S d|0~~99999|
684 |SM|SM|SM d|8000~~9999|
685 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
686 |Y|Y|Y o|0~~303237|
687 |M|M|M d|0~~99999|
688 |T|T|T d|0~~99999|
689 |C|C|C d|0~~199|
690 |D|D|D d|0~~7999|
691 |S|S|S d|0~~99999|
692 |SD|SD|SD d|8000~~9999|
693
694 **3)Configure the communication protocol**
695
696 [[image:image-20220825102649-2.png]]
697
698 **4)Cable Wiring**
699
700 * **RS422**
701
702 [[image:image-20220825103421-5.png]]
703
704 [[image:image-20220825100845-4.png]]
705
706
707 == **FX5U Serial Protocol** ==
708
709 Mitsubishi FX5U series PLC
710
711 **1)V-BOX Settings**
712
713 |**Item**|**Settings**|**Note**
714 |Protocol|Mitsubishi FX5U|
715 |Connection|RS422/RS485|
716 |Baud rate|9600|
717 |Data bit|7|
718 |Parity|Odd|
719 |Stop bit|1|
720 |PLC station No.|1~~255|Need to be the same as PLC settings
721
722 **2)Address List**
723
724 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
725 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
726 |Y|Y|Y o|0~~303237|
727 |M|M|M d|0~~99999|
728 |B|B|B h|0~~7FFF|
729 |F|F|F d|0~~32767|
730 |SB|SB|SB h|0~~7FFF|
731 |TS|TS|TS d|0~~1023|
732 |TC|TC|TC d|0~~1023|
733 |STS|STS|STS d|0~~1023|
734 |STC|STC|STS d|0~~1023|
735 |CS|CS|CS d|0~~1023|
736 |CC|CC|CC d|0~~1023|
737 |SM|SM|SM d|0~~9999|
738 |L|L|L d|0~~32767|
739 |S|S|S d|0~~4095|
740 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
741 |TN|TN|TN d|0~~1023|
742 |STN|STN|STN d|0~~1023|
743 |CN|CN|CN d|0~~1023|
744 |R|R|R d|0~~32767|
745 |SW|SW|SW h|0~~7FFF|
746 |Z|Z|Z d|0~~23|
747 |D|D|D d|0~~7999|
748 |SD|SD|SD d|0~~11999|
749
750 **3)PLC Settings (GX Works 3)**
751
752 Create a blank FX5U project
753
754 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
755
756 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5c9cb13fac1e6c93.png?width=200&height=462&rev=1.1||alt="12.PLC Protocol_html_5c9cb13fac1e6c93.png" height="462" width="200"]]
757
758 Select protocol in the setting item, and set parameters.
759
760 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_de942589ca070228.png?width=600&height=324&rev=1.1||alt="12.PLC Protocol_html_de942589ca070228.png" height="324" width="600"]]
761
762 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
763
764 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_387ec7d00b5feb59.png?width=600&height=323&rev=1.1||alt="12.PLC Protocol_html_387ec7d00b5feb59.png" height="323" width="600"]]
765
766 Click the [Apply] button to finish the setting.
767
768 Click download and select the items as below, then click [execute] to download the configuration to PLC.
769
770 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_cdef1c5ec8cc2105.png?width=600&height=434&rev=1.1||alt="12.PLC Protocol_html_cdef1c5ec8cc2105.png" height="434" width="600"]]
771
772 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
773
774 Done.
775
776 **4)Configure the communication protocol**
777
778 [[image:image-20220825104904-1.png]]
779
780 **5)Cable Wiring**
781
782
783 * **RS422**
784
785 [[image:image-20220825105105-2.png]]
786
787 [[image:image-20220825105533-3.png]]
788
789 == **FX5U Ethernet Protocol** ==
790
791 Mitsubishi FX5U series PLC
792
793 **1)V-BOX Settings**
794
795 |**Items**|**Settings**|**Note**
796 |Protocol|Mitsubishi FX5U|
797 |Connection|Ethernet|
798 |Port No.|5002|Must be the same as the PLC setting
799 |PLC station No.|0|
800
801 **2)Address List**
802
803 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
804 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
805 |Y|Y|Y o|0~~303237|
806 |M|M|M d|0~~99999|
807 |B|B|B h|0~~7FFF|
808 |F|F|F d|0~~32767|
809 |SB|SB|SB h|0~~7FFF|
810 |TS|TS|TS d|0~~1023|
811 |TC|TC|TC d|0~~1023|
812 |STS|STS|STS d|0~~1023|
813 |STC|STC|STS d|0~~1023|
814 |CS|CS|CS d|0~~1023|
815 |CC|CC|CC d|0~~1023|
816 |SM|SM|SM d|0~~9999|
817 |L|L|L d|0~~32767|
818 |S|S|S d|0~~4095|
819 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
820 |TN|TN|TN d|0~~1023|
821 |STN|STN|STN d|0~~1023|
822 |CN|CN|CN d|0~~1023|
823 |R|R|R d|0~~32767|
824 |SW|SW|SW h|0~~7FFF|
825 |Z|Z|Z d|0~~23|
826 |D|D|D d|0~~7999|
827 |SD|SD|SD d|0~~11999|
828
829 **3)PLC Settings (GX Works 3)**
830
831 Find the [Ethernet port] in the navigation area.
832
833 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_8e8f85ace087346c.png?width=300&height=593&rev=1.1||alt="12.PLC Protocol_html_8e8f85ace087346c.png" height="593" width="300"]]
834
835 Select [Own Node Settings] in the [Setting Item List];
836
837 Set [IP Address], [Subnet Mask], [Default Gateway];
838
839 Click [Detailed Settings] into [Ethernet Configuration (Built-in Ethernet Port)] windows;
840
841 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5d98495052c8c10e.png?width=600&height=339&rev=1.1||alt="12.PLC Protocol_html_5d98495052c8c10e.png" height="339" width="600"]]
842
843 Select [SLMP Connection Module] and add into host station as below picture shows;
844
845 Set Port number as 5002 (this is necessary settings);
846
847 Click [Close with Reflecting the Setting] to save and close window;
848
849 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_14b489fdc6c6589d.png?width=600&height=350&rev=1.1||alt="12.PLC Protocol_html_14b489fdc6c6589d.png" height="350" width="600"]]
850
851 Click [Apply] to completed Etherenet settings;
852
853 Switch to the [On line data operation] interface as below, check the item and click [Execute] to download.
854
855 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_c93025a968a8a9e7.png?width=600&height=434&rev=1.1||alt="12.PLC Protocol_html_c93025a968a8a9e7.png" height="434" width="600"]]
856
857 **4)Configure the communication protocol**
858
859 [[image:image-20220825112403-1.png||alt="图片-20220825112403-1.png"]]
860
861 **5)电缆布线**
862
863 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
864
865
866 == **L02 Serial Protocol** ==
867
868 Mitsubishi L02 series CPU built-in serial port.
869
870 **1)V-BOX Settings**
871
872 |**Item**|**Settings**|**Note**
873 |Protocol|Mitsubishi L02|
874 |Connection|RS422|
875 |Baud rate|115200|
876 |Data bit|8|
877 |Parity|Odd|
878 |Stop bit|1|
879 |PLC station No.|1~~255|Need to be the same as PLC settings
880
881 **2)Address List**
882
883 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
884 |Bit|X|X|X h|0~~FFFF|
885 |Bit|Y|Y|Y h|0~~FFFF|
886 |Bit|M|M|M d|0~~9999|
887 |Bit|L|L|L d|0~~9999|
888 |Bit|F|F|F d|0~~9999|
889 |Bit|B|B|B h|0~~FFFF|
890 |Bit|V|V|V d|0~~2047|
891 |Bit|TC|TC|TC d|0~~9999|
892 |Bit|SS|SS|SS d|0~~9999|
893 |Bit|SC|SC|SC d|0~~9999|
894 |Bit|CS|CS|CS d|0~~9999|
895 |Bit|CC|CC|CC d|0~~9999|
896 |Bit|SB|SB|SB h|0~~FFFF|
897 |Bit|SM|SM|SM d|0~~2047|
898 |Bit|STS|STS|STS d|0~~1023|
899 |Bit|S|S|S d|0~~9999|
900 |Bit|DX|DX|DX h|0~~FFFF|
901 |Bit|DY|DY|DY h|0~~FFFF|
902 |Bit|TS|TS|TS d|0~~9999|
903 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
904 |Word|W|W|W h|0~~FFFF|
905 |Word|TN|TN|TN d|0~~99999|
906 |Word|SN|SN|SN d|0~~99999|
907 |Word|CN|CN|CN d|0~~99999|
908 |Word|R|R|R d|0~~99999|
909 |Word|SW|SW|SW h|0~~FFFF|
910 |Word|Z|Z|Z d|0~~99999|
911 |Word|ZR|ZR|ZR h|0~~FFFF|
912 |Word|D|D|D d|0~~99999|
913
914 **3)Communication Settings**
915
916 [[image:image-20220825160648-3.png]]
917
918 **4)Cable Wiring**
919
920 * **RS422**
921
922 [[image:image-20220825161612-8.png]]
923
924 [[image:image-20220825160820-4.png]]
925
926 == **L02 Ethernet Protocol** ==
927
928 Mitsubishi L series CPU built-in Ethernet port.
929
930 **1)V-BOX Settings**
931
932 |**Items**|**Settings**|**Note**
933 |Protocol|MIT L02 CPU MELSEC|
934 |Connection|Ethernet|
935 |Port No.|1025|Must be the same as the PLC setting
936 |PLC station No.|0|Must be the same as the PLC setting
937
938 **2)Address List**
939
940 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
941 |Bit|X|X|X h|0~~FFFF|
942 |Bit|Y|Y|Y h|0~~FFFF|
943 |Bit|M|M|M d|0~~9999|
944 |Bit|L|L|L d|0~~9999|
945 |Bit|F|F|F d|0~~9999|
946 |Bit|B|B|B h|0~~FFFF|
947 |Bit|V|V|V d|0~~2047|
948 |Bit|TC|TC|TC d|0~~9999|
949 |Bit|SS|SS|SS d|0~~9999|
950 |Bit|SC|SC|SC d|0~~9999|
951 |Bit|CS|CS|CS d|0~~9999|
952 |Bit|CC|CC|CC d|0~~9999|
953 |Bit|SB|SB|SB h|0~~FFFF|
954 |Bit|SM|SM|SM d|0~~2047|
955 |Bit|STS|STS|STS d|0~~1023|
956 |Bit|S|S|S d|0~~9999|
957 |Bit|DX|DX|DX h|0~~FFFF|
958 |Bit|DY|DY|DY h|0~~FFFF|
959 |Bit|TS|TS|TS d|0~~9999|
960 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
961 |Word|W|W|W h|0~~FFFF|
962 |Word|TN|TN|TN d|0~~99999|
963 |Word|SN|SN|SN d|0~~99999|
964 |Word|CN|CN|CN d|0~~99999|
965 |Word|R|R|R d|0~~99999|
966 |Word|SW|SW|SW h|0~~FFFF|
967 |Word|Z|Z|Z d|0~~99999|
968 |Word|ZR|ZR|ZR h|0~~FFFF|
969 |Word|D|D|D d|0~~99999|
970
971 **3)PLC Settings (GX Works2 )**
972
973 Create a project
974
975 Set PLC IP, subnet mask and gateway;
976
977 Select [Binary Code] as communication data code;
978
979 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_776e17505f3fc6c0.png?width=600&height=524&rev=1.1||alt="12.PLC Protocol_html_776e17505f3fc6c0.png" height="524" width="600"]]
980
981 Set PLC port number, for example 1025
982
983 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_8d0d1a22d388f70b.png?width=600&height=524&rev=1.1||alt="12.PLC Protocol_html_8d0d1a22d388f70b.png" height="524" width="600"]]
984
985 Save settings;
986
987 Download project into PLC device;
988
989 Restart PLC device;
990
991 **4)Configure the communication protocol**
992
993 [[image:image-20220825142659-1.png]]
994
995 **5)Cable Wiring**
996
997 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
998
999 == **QJ71E71 Ethernet Protocol** ==
1000
1001 Mitsubishi QJ71E71 Ethernet communication module;
1002
1003 **1)V-BOX Settings**
1004
1005 |**Items**|**Settings**|**Note**
1006 |Protocol|MIT QJ71E71 MELSEC|
1007 |Connection|Ethernet|
1008 |Port No.|1025|Must be the same as the PLC setting
1009 |PLC station No.|0|Must be the same as the PLC setting
1010
1011 **2)Address List**
1012
1013 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1014 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1015 |Y|Y|Y h|0~~1FFF|
1016 |M|M|M d|0~~99999|
1017 |L|L|L d|0~~8191|
1018 |F|F|F d|0~~2047|
1019 |B|B|B h|0~~1FFF|
1020 |V|V|V d|0~~2047|
1021 |TS|TS|TS d|0~~2047|
1022 |TC|TC|TC d|0~~2047|
1023 |SS|SS|SS d|0~~2047|
1024 |SC|SC|SC d|0~~2047|
1025 |CS|CS|CS d|0~~1023|
1026 |CC|CC|CC d|0~~1023|
1027 |SB|SB|SB h|0~~7FF|
1028 |S|S|S d|0~~8191|
1029 |DX|DX|DX h|0~~1FFF|
1030 |DY|DY|DY h|0~~1FFF|
1031 |SM|SM|SM d|8000~~9999|
1032 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1033 |D|D|D d|0~~12287|
1034 |W|W|W h|0~~1FFF|
1035 |TN|TN|TN d|0~~2047|
1036 |SN|SN|SN d|0~~2047|
1037 |CN|CN|CN d|0~~1023|
1038 |R|R|R d|0~~32767|
1039 |SW|SW|SW h|0~~7FF|
1040 |Z|Z|Z d|0~~15|
1041 |ZR|ZR|ZR h|0~~FE7FF|
1042
1043 **3)PLC Settings(GX Works2)**
1044
1045 * Click [Ethernet/CC IE/MELSECNET];
1046 * Please select [Ethernet] as network type;
1047 * Set station I/O number according to situation (For example, 0000 means that the module is connected to PLC CPU in first order);
1048 * Select [Online] as Mode;
1049 * Click [Operation setting] to set IP;
1050 * Select [Binary Code] as [Communication Data Code];
1051 * Set protocol: TCP;
1052 * Set [unpassive] in [Open system];
1053 * Set [receive] in [Fixed buffer];
1054 * Set [procedure Exist] in [Fixed buffer communication];
1055 * Disable [Pairing open];
1056 * Set [No confirm] in [Existence confirmation];
1057 * Host station port number: 1025;
1058 * Save settings;
1059 * Download project into PLC and restart it
1060
1061 **4)Configure the communication protocol**
1062
1063 [[image:image-20220825143728-1.png]]
1064
1065 **5)Cable Wiring**
1066
1067 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png"]]
1068
1069 = Create communication with **Delta PLC** =
1070
1071 == **DVP Ethernet Protocol** ==
1072
1073 [[下载链接>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Delta%20DVP%20Ethernet.zip]]
1074
1075 == **DVP serial protocol** ==
1076
1077 [[下载链接>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Delta%20DVP%20Ethernet.zip]]
1078
1079 = Create communication with **Omron PLC** =
1080
1081 == **CP1 Series Protocols** ==
1082
1083 [[下载链接>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CP1%20Series.zip]]
1084
1085 == **CP2M Series Protocols** ==
1086
1087 [[下载链接>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CJ2M.zip]]
1088
1089 = Create communication with **Modbus RTU** =
1090
1091 == **V-BOX as Slave** ==
1092
1093 Select the protocol "Modbus RTU Slave (All Fuction)",
1094
1095 Then set baud rate, port, stop bits, data bits, parity.
1096
1097 (% style="text-align:center" %)
1098 [[image:1624342015914-382.png||height="486" width="800" class="img-thumbnail"]]
1099
1100 == **V-BOX as Master** ==
1101
1102 Select the protocol "Modbus RTU Master",
1103
1104 Then set baud rate, port, stop bits, data bits, parity
1105
1106 (% style="text-align:center" %)
1107 [[image:1624348709622-711.png||queryString="width=809&height=493" height="488" width="800" class="img-thumbnail"]]
1108
1109 **address list**
1110
1111 (% class="table-bordered" %)
1112 |**type**|**register**|**Function code and description**
1113 |(% rowspan="11" %)词|(% rowspan="3" %)3|04 (Read Input Registers: Read the current binary value in one or more input registers)
1114 |06 (write single register: write a binary value to a holding register)
1115 |10 (write values to multiple addresses )
1116 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1117 |06 (write single register: write a binary value to a holding register)
1118 |10 (write values to multiple addresses )
1119 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1120 |06 (write single register: write a binary value to a holding register)
1121 |10 (write values to multiple addresses )
1122 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1123 |10 (write values to multiple addresses )
1124 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1125 |05 (Force a single coil to force the on/off state of a logic coil)
1126 |0F (Write multiple bits, ie write continuously)
1127 |(% rowspan="3" %)1|02 (Read the input state)
1128 |05 (Force a single coil to force the on/off state of a logic coil)
1129 |0F (Write multiple bits)
1130 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1131 |05 (Force a single coil to force the on/off state of a logic coil)
1132 |0F (Write multiple bits)
1133 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1134 |0F (Write multiple bits)
1135
1136 == **communicate with VB inverter** ==
1137
1138 [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20VB%20inverter.zip]]
1139
1140 = **User define protocol** =
1141
1142 More serial port script instruction,please refer manual:[[Lua script function>>doc:V-BOX.V-Net.Manual.04 Lua Script.01 Lua Functions.WebHome]]~-~-->[[3.Serial port operation>>url:http://docs.we-con.com.cn/wiki/vbox/view/HMI/04.Lua%20script%20%20function%20and%20operation/01.Lua%20script%20function/#H3.Serialportoperation]]
1143
1144 == **Read the temperature sensor.** ==
1145
1146 the commond format is as beliow:
1147
1148 Send commond:01 03 02 00 00 03 04 73
1149
1150 Feedback commond:01 03 06 07 F7 0E 7E B7 35
1151
1152 Temperature data:07 F7,desimal = 2039,it means temperature is 20.39℃.
1153
1154 Humidity data:0E 7E,desimal = 3710, it mean humidity is 37.10%RH.
1155
1156 Script Demo:
1157
1158 ~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~--
1159
1160 function com.main()
1161 ~-~-dosomething
1162 openPlc()
1163 end
1164 function openPlc()
1165 if obj then
1166 ~-~- If the serial port opened,then read/write data by timing
1167
1168 local wri = string.pack(">HHHH",0X0103,0X0200,0X0003,0X0473)
1169 local arr = reading(wri)
1170 ~-~- if arr ~~=nil then
1171 ~-~- if arr[1] ==33 and arr[2] ==v[2][2] and arr[3] ==v[2][3] then
1172 ~-~- local A = arr[4]*256
1173 ~-~- local B = A+arr[5]
1174 ~-~- addr_setword(v[1],B)
1175 ~-~- end
1176 ~-~- end
1177
1178 else
1179 ~-~-judge if there is a serial object, then initialize and open the serial port
1180 local configs = {
1181 name = 'COM1', ~-~-Select serial port COM1
1182 mode = 485, ~-~-Communication mode RS485
1183 baud_rate = 9600, ~-~-Baud rate 9600
1184 stop_bit = 1, ~-~-stop bit 1
1185 data_len = 8, ~-~-data length 8
1186 check_bit = 'NONE', ~-~-no parity
1187
1188 }
1189 obj,err = serial.open(configs) ~-~-Open serial port
1190 if not obj then
1191 print("serial open :failed", err) ~-~- Open serial port failed
1192 end
1193 end
1194 end
1195
1196 function reading(wri)
1197 obj:flush() ~-~- Clear serial port
1198 obj:write(wri) ~-~- Write serial port
1199 print(string.byte(wri,1,#wri))
1200 obj:flush() ~-~- Clear serial port 
1201 local readed =obj:read(9,1000) ~-~- Read 9 bytes, timeout 1 second
1202 if readed and readed ~~= "" then 
1203 ~-~- judge that a non-empty string is read
1204 print(string.byte(readed,1,#readed))
1205 a={string.byte(readed, 1, #readed)}
1206 if nil ~~= a[4] and nil ~~= a[5] and nil ~~= a[6] and nil ~~= a[7] then
1207 a1=a[4]*256+a[5]
1208 a2=a[6]*256+a[7]
1209 addr_setword("@HDW0",a1)
1210 addr_setword("@HDW1",a2)
1211 end
1212 return {string.byte(readed, 1, #readed)}
1213 elseif readed == nil then
1214 print("serial read err:", err or "")
1215 return nil
1216 end
1217 return nil
1218 end
1219
1220 ~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-