1 = Create communication with WECON PLC =
2
3 == **LX3V Serial Protocol** ==
4
5 Supported series: Wecon LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
6
7 **1)V-BOX setting**
8
9 |**Item**|**Settings**|**Note**
10 |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
11 |Connection|RS422/RS485|
12 |Baud rate|9600|
13 |Data bit|7|
14 |Parity|EVEN|
15 |Stop bit|1|
16 |PLC station No.|1|
17
18 **2)Address List**
19
20
21 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
22 |(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
23 |Y|Y|Y o|0~~303237|
24 |M|M|M d|0~~99999|
25 |T|T|T d|0~~99999|
26 |C|C|C d|0~~99999|
27 |S|S|S d|0~~99999|
28 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
29 |Y|Y|Y o|0~~303237|
30 |M|M|M d|0~~99999|
31 |T|T|T d|0~~99999|
32 |C|C|C d|0~~199|
33 |D|D|D d|0~~7999|
34 |S|S|S d|0~~99999|
35 |SD|SD|SD d|8000~~9999|
36
37 **3)Configure the communication protocol**
38
39 [[image:image-20220824152217-1.png||alt="图片-20220824152217-1.png"]]
40
41 **4)Cable Wiring**
42
43 * **RS422**
44
45 [[image:image-20220824120614-5.png]]
46
47 * **RS485**
48
49 [[image:image-20220824120524-3.png]]
50
51 == **LX5V Serial Protocol** ==
52
53 This example introduces the establishment of serial port communication between V-BOX and LX5V. It is introduced through three parts: PLC software configuration, V-BOX software configuration, and hardware wiring.
54
55 **Software configuration of PLC**
56
57 **1)PLC programming software**
58
59 [[image:image-20220824142722-1.png]]
60
61 **2)New PLC project**
62
63 Click New Project and select the PLC model.
64
65 [[image:image-20220822172623-2.png]]
66
67 **3)Set Serial port parameters**
68
69 Follow the steps below to configure Serial port parameters
70
71 Baud rate:115200
72
73 Data bit:8
74
75 Stop bit:1
76
77 Parity:No verification
78
79 [[image:image-20220822172657-3.png]]
80
81 **4)Registers list**
82
83 [[image:image-20220822172730-4.png]]
84
85 **V-BOX software configuration**
86
87 **1)V-BOX programming software**
88
89 [[image:image-20220824104124-1.png]]
90
91 **2)V-NET add device**
92
93 Open V-NET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the access key, password and remark, to add the device.
94
95 [[image:image-20220824104909-2.png]]
96
97 **3)Set communication port parameters**
98
99 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
100
101 Baud rate:115200
102
103 Data bit:8
104
105 Stop bit:1
106
107 Parity:No verification
108
109 [[image:image-20220824142130-1.png]]
110
111 **hardware connection**
112
113 **1)Hardware wiring diagram**
114
115 [[image:image-20220824142546-2.png]]
116
117 [[image:image-20220824142643-3.png]]
118
119 The above are all the steps for establishing serial port communication between V-BOX with LX5V PLC.
120
121 == **LX5V-N Ethernet protocol** ==
122
123 This example introduces the establishment of Ethernet communication between V-BOX and LX5V-N. It is introduced through three parts: PLC software configuration, V-BOX software configuration, and hardware wiring.
124
125 **Software configuration of PLC**
126
127 **1)PLC programming software**
128
129 [[image:image-20220824142722-1.png]]
130
131 **2)New PLC project**
132
133 Click New Project and select the PLC model.
134
135 [[image:image-20220824143613-1.png]]
136
137 **3)Set Ethernet port parameters**
138
139 Follow the steps below to configure Ethernet parameters
140
141 PLC IP address:192.168.39.200
142
143 default gateway:192.168.39.1
144
145 subnet mask:255.255.255.0
146
147 [[image:image-20220824143744-2.png]]
148
149 **4)Registers list**
150
151 [[image:image-20220822172730-4.png]]
152
153 (% id="cke_bm_22473S" style="display:none" %)** **(%%)**V-BOX software configuration**
154
155 **1)V-BOX programming software**
156
157 [[image:image-20220824104124-1.png]]
158
159 **2)V-NET add device**
160
161 Open V-NET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the access key, password and remark, to add the device.
162
163 [[image:image-20220824104909-2.png]]
164
165 **3)Set communication Protocol**
166
167 Click Communication to configure the LX5V plc protocol and IP address.
168
169 [[image:image-20220824144619-1.png]]
170
171 **hardware connection**
172
173 **1)Hardware wiring diagram**
174
175 [[image:image-20220824151127-2.png]]
176
177 The above are all the steps for establishing ethernet communication between V-BOX with LX5V PLC.
178
179 = Create communication with **Rockwell PLC** =
180
181 == (% id="cke_bm_5621S" style="display:none" %)** **(%%)**MicroLogix Protocol** ==
182
183 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
184
185 **1)V-BOX setting**
186
187 |**Item**|**Settings**|**Note**
188 |Protocol|Allen-Bradlley DF1 Advanced|
189 |Connection|RS232|
190 |Baud rate|19200|
191 |Data bit|8|
192 |Parity|None|
193 |Stop bit|1|
194 |PLC station No.|1|
195
196 **2)Address List**
197
198 |**Type**|**Device registers**|**Format**|**Range**|**Note**
199 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
200 |O|O d.d|0.0~~255.15|
201 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
202 |S|S d.d|0.0~~255.15|
203 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
204 |(% rowspan="9" %)Word|S|S d|0~~255|
205 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
206 |TP|TP nnhh|0~~ffff
207 |CS|CS nnhh|0~~ffff
208 |CP|CP nnhh|0~~ffff
209 |N|N nnhh|0~~ffff
210 |C|C nnhh|0~~ffff
211 |T|T nnhh|0~~ffff
212 |R|R nnhh|0~~ffff
213
214 **3)Configure the communication protocol**[[image:image-20220824152928-1.png]]
215
216 **4)Configure the communication protocol**
217
218 [[image:image-20220824110724-1.png]]
219
220 == **Micro850_FreeTag Protocol** ==
221
222 (((
223 (((
224 This example introduces the establishment of Ethernet communication between Wecon V-box and CompactLogix L1769. It is introduced through three parts: PLC software configuration, V-box software configuration, and hardware wiring.
225 )))
226 )))
227
228 (((
229 (% class="wikigeneratedid" id="HSoftwareconfigurationofPLC" %)
230 (((
231 **Software configuration of PLC**
232 )))
233
234 (% class="wikigeneratedid" id="HPLCprogrammingsoftware" %)
235 (((
236 **1)PLC programming software**
237 )))
238
239 [[image:image-20220714162600-1.png]]
240
241 (% class="wikigeneratedid" id="HNewPLCproject" %)
242 (((
243 **2)New PLC project**
244 )))
245
246 (((
247 (((
248 Click New Project and select the PLC model.
249 )))
250 )))
251
252 (((
253 [[image:image-20220714162617-2.png]]
254 )))
255
256 (((
257
258
259 [[image:image-20220714162652-4.png]]
260 )))
261
262 (((
263 (% class="wikigeneratedid" id="HSetEthernetparameters" %)
264 (((
265 **3)Set Ethernet parameters**
266 )))
267
268 (((
269 (((
270 (((
271 Follow the steps below to configure Ethernet parameters
272 )))
273 )))
274 )))
275
276 (((
277 (((
278 (((
279 PLC IP address:192.168.40.101
280 )))
281 )))
282 )))
283
284 (((
285 (((
286 (((
287 default gateway:192.168.40.1
288 )))
289 )))
290 )))
291
292 (((
293 (((
294 (((
295 subnet mask:255.255.255.0
296 )))
297 )))
298 )))
299
300 (((
301 [[image:image-20220714162713-5.png]]
302 )))
303
304 (((
305
306 )))
307
308 (((
309 (% class="wikigeneratedid" id="HV-boxsoftwareconfiguration" %)
310 (((
311 **V-box software configuration**
312 )))
313
314 (% class="wikigeneratedid" id="HV-boxprogrammingsoftware" %)
315 (((
316 **1)V-box programming software**
317 )))
318
319 (% class="wikigeneratedid" %)
320 (((
321 [[image:image-20220714162725-6.png]]
322 )))
323
324 (% class="wikigeneratedid" id="HConfiguredevicenetwork" %)
325 (((
326 **2)Configure device network**
327 )))
328
329 (((
330 (((
331 (((
332 Click the Configuration Download button[[image:image-20220714115308-8.png||height="22" width="15"]], It is used to configure the device network, update the device time, obtain the device machine code, check the device network, etc.
333 )))
334
335 (((
336 In the example below, the IP address of V-Box is configured as 192.168.40.66, and the networking method is 4G connection
337 )))
338 )))
339 )))
340
341 (((
342 (((
343 [[image:image-20220714162737-7.png]]
344
345
346 )))
347 )))
348 )))
349 )))
350
351 (% class="wikigeneratedid" id="HV-netadddevice" %)
352 (((
353 **3)V-net add device**
354 )))
355 )))
356
357 (((
358 (((
359 Open VNET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the device machine code/product code, device password, and device alias to add the device.   [[image:image-20220714162752-8.png]]
360 )))
361
362
363 )))
364
365 (((
366 (% class="wikigeneratedid" id="HSetcommunicationportparameters" %)
367 (((
368 **4)Set communication port parameters**
369 )))
370
371 (((
372 In the device list on the left, find the Vbox that communicates with the L1769, click it and select configuration,communication port configuration in the main interface to add a communication protocol.
373 )))
374
375 [[image:image-20220714162805-9.png]]
376 )))
377
378 (((
379 The communication port is selected as Ethernet, the device type is selected as Allen-Bradley, the protocol is Allen-BradleyMicro850_FreeTag EthemetIP, and the IP is the internal IP address of the L1769 PLC. The port number is 44818.
380 )))
381
382 [[image:image-20220824164346-1.png]]
383
384
385 (((
386 After adding the protocol Allen-BradleyMicro850_FreeTag, click[[image:image-20220714143838-2.png]]icon add label.[[image:image-20220714162827-11.png]]
387 )))
388
389 (% class="wikigeneratedid" id="HEngineeringproduction" %)
390 (((
391 **5)Engineering production**
392 )))
393
394 (% class="wikigeneratedid" %)
395 (((
396 (((
397 According to your own needs, use the V-NET client software to edit the required data monitoring points.
398 )))
399
400 [[image:image-20220714162841-12.png]]
401
402
403 (((
404 **hardware connection**
405 )))
406 )))
407
408 (((
409 **1)Hardware wiring diagram**
410 )))
411
412 (((
413 (((
414 This example introduces Wecon V-box with Allen-Bradley L1769 PLC to establish communication through Ethernet. The connection diagram is as follows:
415 )))
416
417 [[image:image-20220714162856-13.png]]
418
419 (((
420 The above are all the steps for establishing Ethernet communication between Wecon V-box with CompactLogix L1769 PLC.
421
422
423 == **Allen-Bradley Ethernet DF1** ==
424
425 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Allen-Bradley%20Ethernet%20DF1.zip]]
426
427
428 = Create communication with **Siemens PLC** =
429
430 == **S7-200 Smart Ethernet Protocol** ==
431
432 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20S7-200%20Smart.zip]]
433
434
435 == **S7-300 Ethernet Protocol** ==
436
437 Supported Series: Siemens S7-300 series PLC
438
439 **1)V-BOX setting**
440
441 |**Items**|**Settings**|**Note**
442 |Protocol|Simens S7-300 Ethernet|
443 |Connection|Ethernet|
444 |Port No.|102|
445 |PLC station No.|2|Need to be same as the PLC setting
446
447 **2)Address List**
448
449 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
450 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
451 |Q|Q|Q ddddd.o|0.0~~99999.7|
452 |M|M|M ddddd.o|0.0~~99999.7|
453 |DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
454 nn: block number;
455
456 dddd: address;
457 )))
458 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
459 |Q|QW|QW ddddd|0~~99999|
460 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
461 |MW|MW ddddd|0~~99999|(((
462 MW0=MB(0~~1)
463
464 MW2=MB(2~~3)
465
466 Address value is a multiple of 2
467 )))
468 |MD|MD ddddd|0~~99999|(((
469 MD0=MB(0~~3)
470
471 MD4=MB(4~~7)
472
473 Address value is a multiple of 4
474 )))
475 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
476 nn: block number;
477
478 dddd: address
479 )))
480 |DBxDBW|DBxDBW nndddd|0~~99999999
481 |DBxDBD|DBxDBD nndddd|0~~99999999
482
483 **3)Configure the communication protocol**
484
485 [[image:image-20220824161345-1.png]]
486
487 **4)Cable Wiring**
488
489 [[image:image-20220824161450-2.png]]
490 )))
491 )))
492
493 == **S7-1200 Ethernet Protocol** ==
494
495 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]]
496
497 == **S7-XXX Ethernet Protocol** ==
498
499 Supported Series: Siemens S7-400, S7-1200 and S7-1500
500
501 **1)V-BOX setting**
502
503 |=**Items**|=**Settings**|=**Note**
504 |Protocol|Siemens S7-XXX|
505 |Connection|Ethernet|
506 |Port No.|102|
507 |Device No.|Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|
508 |HMI No.|Rack (Default as 0)|
509
510 Slot from TIA Portal is equal to Device No. of V-net
511
512 Rack from TIA Portal is equal to HMI No. of V-net
513
514 [[image:image-20220824162459-3.png]]
515
516 [[image:image-20220824163305-2.png]]
517
518 **2)Address List**
519
520 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
521 |(% rowspan="4" %)Bit|I|I|M d.o|(((
522 d:0~-~-9999
523
524 o:0-7
525 )))|
526 |Q|Q|Q d.o|(((
527 d:0~-~-9999
528
529 o:0-7
530 )))|
531 |M|M|M d.o|(((
532 d:0~-~-9999
533
534 o:0-7
535 )))|
536 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
537 nn:0-9999,
538
539 dddd:0-9999,
540
541 o:0-7
542 )))|(((
543 nn:DB No.
544
545 dddd:address value
546
547 o: digit address
548 )))
549 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
550 |M|MW|MW d|d:0-99999|(((
551 MW0=MB(0~~1)
552
553 MW2=MB(2~~3)
554
555 Address value is a multiple of 2
556 )))
557 |M|MD|MD d|d:0-99999|(((
558 MD0=MB(0~~3)
559
560 MD4=MB(4~~7)
561
562 Address value is a multiple of 4
563 )))
564 |I|IW|IW d|d:0-99999|
565 |Q|QW|QW d|d:0-99999|
566 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
567 nn:0-9999
568
569 dddd:0-9999
570 )))|(((
571 nn:DB No.
572
573 dddd:address value
574 )))
575 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
576 nn:0-9999
577
578 dddd:0-9999
579 )))|(((
580 nn:DB No.
581
582 dddd:address value
583
584 Address value is a multiple of 2
585 )))
586 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
587 nn:0-9999
588
589 dddd:0-9999
590 )))|(((
591 nn:DB No.
592
593 dddd:address value
594
595 Address value is a multiple of 4
596 )))
597
598 **3)Configure the communication protocol**
599
600 [[image:image-20220824163448-3.png]]
601
602 **✎Note:**
603
604 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three V-BOX.
605 * V-BOX access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
606
607 **4)Cable Wiring**
608
609 [[image:image-20220824162342-2.png]]
610
611 = Create communication with **Mitsubishi PLC** =
612
613 == **FX1S,1N,2N Serial Protocol** ==
614
615 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
616
617 **1)V-BOX Settings**
618
619 |**Item**|**Settings**|**Note**
620 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
621 |Connection|RS422/RS485/RS232|
622 |Baud rate|9600~~115200|
623 |Data bit|7/8|
624 |Parity|EVEN/Odd/None|
625 |Stop bit|1/2|
626 |PLC station No.|1~~255|
627
628 **2)Address List**
629
630 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
631 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
632 |Y|Y|Y o|0~~303237|
633 |M|M|M d|0~~99999|
634 |T|T|T d|0~~99999|
635 |C|C|C d|0~~99999|
636 |S|S|S d|0~~99999|
637 |SM|SM|SM d|8000~~9999|
638 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
639 |Y|Y|Y o|0~~303237|
640 |M|M|M d|0~~99999|
641 |T|T|T d|0~~99999|
642 |C|C|C d|0~~199|
643 |D|D|D d|0~~7999|
644 |S|S|S d|0~~99999|
645 |SD|SD|SD d|8000~~9999|
646
647 **3)Configure the communication protocol**
648
649 [[image:image-20220825102844-3.png]]
650
651 **4)Cable Wiring**
652
653 * **RS422**
654
655 [[image:image-20220825103350-4.png]]
656
657 [[image:image-20220825100845-4.png]]
658
659
660 == **FX3U,3G,3GA Serial Protocol** ==
661
662 Supported Series: Mitsubishi FX3U, FX3G, FX3GA series
663
664 **1)V-BOX Settings**
665
666 |**Item**|**Settings**|**Note**
667 |Protocol|Mitsubishi FX3U/3G/3GA|
668 |Connection|RS422/RS485/RS232|
669 |Baud rate|9600~~115200|
670 |Data bit|7/8|
671 |Parity|EVEN/Odd/None|
672 |Stop bit|1/2|
673 |PLC station No.|1~~255|
674
675 **2)Address List**
676
677 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
678 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
679 |Y|Y|Y o|0~~303237|
680 |M|M|M d|0~~99999|
681 |T|T|T d|0~~99999|
682 |C|C|C d|0~~99999|
683 |S|S|S d|0~~99999|
684 |SM|SM|SM d|8000~~9999|
685 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
686 |Y|Y|Y o|0~~303237|
687 |M|M|M d|0~~99999|
688 |T|T|T d|0~~99999|
689 |C|C|C d|0~~199|
690 |D|D|D d|0~~7999|
691 |S|S|S d|0~~99999|
692 |SD|SD|SD d|8000~~9999|
693
694 **3)Configure the communication protocol**
695
696 [[image:image-20220825102649-2.png]]
697
698 **4)Cable Wiring**
699
700 * **RS422**
701
702 [[image:image-20220825103421-5.png]]
703
704 [[image:image-20220825100845-4.png]]
705
706
707 == ** FX3U Ethernet Protocol** ==
708
709 Mitsubishi FX3U series PLC
710
711 **HMI Settings**
712
713 |Items|Settings|Note
714 |Protocol|Mitsubishi FX3U|
715 |Connection|Ethernet|
716 |Port No.|5009|Must be the same as the PLC setting
717 |PLC station No.|0|
718
719 **Address List**
720
721 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
722 |(% colspan="1" rowspan="7" %)Bit|X|X|X OOO|0~~377|
723 |Y|Y|Y OOO|0~~377|
724 |M|M|M DDDD|0~~7679|
725 |SM|SM|SM DDDD|8000~~8511|
726 |S|S|S DDDD|0~~4095|
727 |TS|TS|TS DDD|0~~511|
728 |CS|CS|CS DDD|0~~255|
729 |(% colspan="1" rowspan="9" %)Word|CN|CN|CN DDD|0~~199|
730 |TN|TN|TN DDD|0~~511|
731 |D|D|D DDDD|0~~7999|
732 |SD|SD|SD DDDD|8000~~8511|
733 |R|R|R DDDDD|0~~32767|
734
735 **Ethernet Module Settings**
736
737 FX3U-ENET-L module configuration
738 Set up the FX3U-ENET-L Ethernet module settings as follows.
739 Select the module location, which in this document is Module 0.
740
741 [[image:image-20221115140802-1.png]]
742
743 Select "Operational setting" to enter the following screen.
744
745 The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default.
746
747 [[image:image-20221115142728-4.png]]
748
749 Select "Open setting" to enter the setting interface, the settings are as follows.
750
751 The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the
752
753 Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module.
754
755 [[image:image-20221115142945-5.png]]
756
757 Click on "transter setup" - "PC side I/F setting", see the following figure.
758
759 After setting, the first download must use the programming cable, as shown in the figure; after that, can
760
761 use the IP set in the "Ethernet board" to communicate directly with the network cable.
762
763 [[image:image-20221115143341-6.png||height="426" width="712"]]
764
765 Read and write data from the Ethernet module
766
767 [[image:image-20221115143703-7.png]]
768
769 Set "Transter setup" to COM communication, and read or write operation as shown below
770
771 [[image:image-20221115143809-8.png]]
772
773 **PLC Settings (GX Works 2)**
774
775 Create a blank FX5U project
776
777 Find Current Connection in the navigation
778
779 [[image:image-20221115144335-9.png||height="422" width="706"]]
780
781 Select Connection Channel List
782
783 Select Ethernet board communication
784
785 [[image:image-20221115144824-10.png||height="421" width="705"]]
786
787 Select Ethernet Module
788 Set the IP address of the PLC
789
790 [[image:image-20221115145228-11.png||height="674" width="708"]]
791
792 Read or write PLC data, in this document is read
793
794 [[image:image-20221115145553-12.png||height="424" width="711"]]
795
796 [[image:image-20221115145559-13.png||height="424" width="711"]]
797
798
799 == **FX5U Serial Protocol** ==
800
801 Mitsubishi FX5U series PLC
802
803 **1)V-BOX Settings**
804
805 |**Item**|**Settings**|**Note**
806 |Protocol|Mitsubishi FX5U|
807 |Connection|RS422/RS485|
808 |Baud rate|9600|
809 |Data bit|7|
810 |Parity|Odd|
811 |Stop bit|1|
812 |PLC station No.|1~~255|Need to be the same as PLC settings
813
814 **2)Address List**
815
816 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
817 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
818 |Y|Y|Y o|0~~303237|
819 |M|M|M d|0~~99999|
820 |B|B|B h|0~~7FFF|
821 |F|F|F d|0~~32767|
822 |SB|SB|SB h|0~~7FFF|
823 |TS|TS|TS d|0~~1023|
824 |TC|TC|TC d|0~~1023|
825 |STS|STS|STS d|0~~1023|
826 |STC|STC|STS d|0~~1023|
827 |CS|CS|CS d|0~~1023|
828 |CC|CC|CC d|0~~1023|
829 |SM|SM|SM d|0~~9999|
830 |L|L|L d|0~~32767|
831 |S|S|S d|0~~4095|
832 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
833 |TN|TN|TN d|0~~1023|
834 |STN|STN|STN d|0~~1023|
835 |CN|CN|CN d|0~~1023|
836 |R|R|R d|0~~32767|
837 |SW|SW|SW h|0~~7FFF|
838 |Z|Z|Z d|0~~23|
839 |D|D|D d|0~~7999|
840 |SD|SD|SD d|0~~11999|
841
842 **3)PLC Settings (GX Works 3)**
843
844 Create a blank FX5U project
845
846 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
847
848 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5c9cb13fac1e6c93.png?width=200&height=462&rev=1.1||alt="12.PLC Protocol_html_5c9cb13fac1e6c93.png" height="462" width="200"]]
849
850 Select protocol in the setting item, and set parameters.
851
852 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_de942589ca070228.png?width=600&height=324&rev=1.1||alt="12.PLC Protocol_html_de942589ca070228.png" height="324" width="600"]]
853
854 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
855
856 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_387ec7d00b5feb59.png?width=600&height=323&rev=1.1||alt="12.PLC Protocol_html_387ec7d00b5feb59.png" height="323" width="600"]]
857
858 Click the [Apply] button to finish the setting.
859
860 Click download and select the items as below, then click [execute] to download the configuration to PLC.
861
862 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_cdef1c5ec8cc2105.png?width=600&height=434&rev=1.1||alt="12.PLC Protocol_html_cdef1c5ec8cc2105.png" height="434" width="600"]]
863
864 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
865
866 Done.
867
868 **4)Configure the communication protocol**
869
870 [[image:image-20220825104904-1.png]]
871
872 **5)Cable Wiring**
873
874
875 * **RS422**
876
877 [[image:image-20220825105105-2.png]]
878
879 [[image:image-20220825105533-3.png]]
880
881 == **FX5U Ethernet Protocol** ==
882
883 Mitsubishi FX5U series PLC
884
885 **1)V-BOX Settings**
886
887 |**Items**|**Settings**|**Note**
888 |Protocol|Mitsubishi FX5U|
889 |Connection|Ethernet|
890 |Port No.|5002|Must be the same as the PLC setting
891 |PLC station No.|0|
892
893 **2)Address List**
894
895 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
896 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
897 |Y|Y|Y o|0~~303237|
898 |M|M|M d|0~~99999|
899 |B|B|B h|0~~7FFF|
900 |F|F|F d|0~~32767|
901 |SB|SB|SB h|0~~7FFF|
902 |TS|TS|TS d|0~~1023|
903 |TC|TC|TC d|0~~1023|
904 |STS|STS|STS d|0~~1023|
905 |STC|STC|STS d|0~~1023|
906 |CS|CS|CS d|0~~1023|
907 |CC|CC|CC d|0~~1023|
908 |SM|SM|SM d|0~~9999|
909 |L|L|L d|0~~32767|
910 |S|S|S d|0~~4095|
911 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
912 |TN|TN|TN d|0~~1023|
913 |STN|STN|STN d|0~~1023|
914 |CN|CN|CN d|0~~1023|
915 |R|R|R d|0~~32767|
916 |SW|SW|SW h|0~~7FFF|
917 |Z|Z|Z d|0~~23|
918 |D|D|D d|0~~7999|
919 |SD|SD|SD d|0~~11999|
920
921 **3)PLC Settings (GX Works 3)**
922
923 Find the [Ethernet port] in the navigation area.
924
925 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_8e8f85ace087346c.png?width=300&height=593&rev=1.1||alt="12.PLC Protocol_html_8e8f85ace087346c.png" height="593" width="300"]]
926
927 Select [Own Node Settings] in the [Setting Item List];
928
929 Set [IP Address], [Subnet Mask], [Default Gateway];
930
931 Click [Detailed Settings] into [Ethernet Configuration (Built-in Ethernet Port)] windows;
932
933 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5d98495052c8c10e.png?width=600&height=339&rev=1.1||alt="12.PLC Protocol_html_5d98495052c8c10e.png" height="339" width="600"]]
934
935 Select [SLMP Connection Module] and add into host station as below picture shows;
936
937 Set Port number as 5002 (this is necessary settings);
938
939 Click [Close with Reflecting the Setting] to save and close window;
940
941 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_14b489fdc6c6589d.png?width=600&height=350&rev=1.1||alt="12.PLC Protocol_html_14b489fdc6c6589d.png" height="350" width="600"]]
942
943 Click [Apply] to completed Etherenet settings;
944
945 Switch to the [On line data operation] interface as below, check the item and click [Execute] to download.
946
947 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_c93025a968a8a9e7.png?width=600&height=434&rev=1.1||alt="12.PLC Protocol_html_c93025a968a8a9e7.png" height="434" width="600"]]
948
949 **4)Configure the communication protocol**
950
951 [[image:image-20220825112403-1.png||alt="图片-20220825112403-1.png"]]
952
953 **5)电缆布线**
954
955 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
956
957
958 == **L02 Serial Protocol** ==
959
960 Mitsubishi L02 series CPU built-in serial port.
961
962 **1)V-BOX Settings**
963
964 |**Item**|**Settings**|**Note**
965 |Protocol|Mitsubishi L02|
966 |Connection|RS422|
967 |Baud rate|115200|
968 |Data bit|8|
969 |Parity|Odd|
970 |Stop bit|1|
971 |PLC station No.|1~~255|Need to be the same as PLC settings
972
973 **2)Address List**
974
975 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
976 |Bit|X|X|X h|0~~FFFF|
977 |Bit|Y|Y|Y h|0~~FFFF|
978 |Bit|M|M|M d|0~~9999|
979 |Bit|L|L|L d|0~~9999|
980 |Bit|F|F|F d|0~~9999|
981 |Bit|B|B|B h|0~~FFFF|
982 |Bit|V|V|V d|0~~2047|
983 |Bit|TC|TC|TC d|0~~9999|
984 |Bit|SS|SS|SS d|0~~9999|
985 |Bit|SC|SC|SC d|0~~9999|
986 |Bit|CS|CS|CS d|0~~9999|
987 |Bit|CC|CC|CC d|0~~9999|
988 |Bit|SB|SB|SB h|0~~FFFF|
989 |Bit|SM|SM|SM d|0~~2047|
990 |Bit|STS|STS|STS d|0~~1023|
991 |Bit|S|S|S d|0~~9999|
992 |Bit|DX|DX|DX h|0~~FFFF|
993 |Bit|DY|DY|DY h|0~~FFFF|
994 |Bit|TS|TS|TS d|0~~9999|
995 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
996 |Word|W|W|W h|0~~FFFF|
997 |Word|TN|TN|TN d|0~~99999|
998 |Word|SN|SN|SN d|0~~99999|
999 |Word|CN|CN|CN d|0~~99999|
1000 |Word|R|R|R d|0~~99999|
1001 |Word|SW|SW|SW h|0~~FFFF|
1002 |Word|Z|Z|Z d|0~~99999|
1003 |Word|ZR|ZR|ZR h|0~~FFFF|
1004 |Word|D|D|D d|0~~99999|
1005
1006 **3)Communication Settings**
1007
1008 [[image:image-20220825160648-3.png]]
1009
1010 **4)Cable Wiring**
1011
1012 * **RS422**
1013
1014 [[image:image-20220825161612-8.png]]
1015
1016 [[image:image-20220825160820-4.png]]
1017
1018 == **L02 Ethernet Protocol** ==
1019
1020 Mitsubishi L series CPU built-in Ethernet port.
1021
1022 **1)V-BOX Settings**
1023
1024 |**Items**|**Settings**|**Note**
1025 |Protocol|MIT L02 CPU MELSEC|
1026 |Connection|Ethernet|
1027 |Port No.|1025|Must be the same as the PLC setting
1028 |PLC station No.|0|Must be the same as the PLC setting
1029
1030 **2)Address List**
1031
1032 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1033 |Bit|X|X|X h|0~~FFFF|
1034 |Bit|Y|Y|Y h|0~~FFFF|
1035 |Bit|M|M|M d|0~~9999|
1036 |Bit|L|L|L d|0~~9999|
1037 |Bit|F|F|F d|0~~9999|
1038 |Bit|B|B|B h|0~~FFFF|
1039 |Bit|V|V|V d|0~~2047|
1040 |Bit|TC|TC|TC d|0~~9999|
1041 |Bit|SS|SS|SS d|0~~9999|
1042 |Bit|SC|SC|SC d|0~~9999|
1043 |Bit|CS|CS|CS d|0~~9999|
1044 |Bit|CC|CC|CC d|0~~9999|
1045 |Bit|SB|SB|SB h|0~~FFFF|
1046 |Bit|SM|SM|SM d|0~~2047|
1047 |Bit|STS|STS|STS d|0~~1023|
1048 |Bit|S|S|S d|0~~9999|
1049 |Bit|DX|DX|DX h|0~~FFFF|
1050 |Bit|DY|DY|DY h|0~~FFFF|
1051 |Bit|TS|TS|TS d|0~~9999|
1052 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1053 |Word|W|W|W h|0~~FFFF|
1054 |Word|TN|TN|TN d|0~~99999|
1055 |Word|SN|SN|SN d|0~~99999|
1056 |Word|CN|CN|CN d|0~~99999|
1057 |Word|R|R|R d|0~~99999|
1058 |Word|SW|SW|SW h|0~~FFFF|
1059 |Word|Z|Z|Z d|0~~99999|
1060 |Word|ZR|ZR|ZR h|0~~FFFF|
1061 |Word|D|D|D d|0~~99999|
1062
1063 **3)PLC Settings (GX Works2 )**
1064
1065 Create a project
1066
1067 Set PLC IP, subnet mask and gateway;
1068
1069 Select [Binary Code] as communication data code;
1070
1071 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_776e17505f3fc6c0.png?width=600&height=524&rev=1.1||alt="12.PLC Protocol_html_776e17505f3fc6c0.png" height="524" width="600"]]
1072
1073 Set PLC port number, for example 1025
1074
1075 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_8d0d1a22d388f70b.png?width=600&height=524&rev=1.1||alt="12.PLC Protocol_html_8d0d1a22d388f70b.png" height="524" width="600"]]
1076
1077 Save settings;
1078
1079 Download project into PLC device;
1080
1081 Restart PLC device;
1082
1083 **4)Configure the communication protocol**
1084
1085 [[image:image-20220825142659-1.png]]
1086
1087 **5)Cable Wiring**
1088
1089 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1090
1091 == **QJ71E71 Ethernet Protocol** ==
1092
1093 Mitsubishi QJ71E71 Ethernet communication module;
1094
1095 **1)V-BOX Settings**
1096
1097 |**Items**|**Settings**|**Note**
1098 |Protocol|MIT QJ71E71 MELSEC|
1099 |Connection|Ethernet|
1100 |Port No.|1025|Must be the same as the PLC setting
1101 |PLC station No.|0|Must be the same as the PLC setting
1102
1103 **2)Address List**
1104
1105 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1106 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1107 |Y|Y|Y h|0~~1FFF|
1108 |M|M|M d|0~~99999|
1109 |L|L|L d|0~~8191|
1110 |F|F|F d|0~~2047|
1111 |B|B|B h|0~~1FFF|
1112 |V|V|V d|0~~2047|
1113 |TS|TS|TS d|0~~2047|
1114 |TC|TC|TC d|0~~2047|
1115 |SS|SS|SS d|0~~2047|
1116 |SC|SC|SC d|0~~2047|
1117 |CS|CS|CS d|0~~1023|
1118 |CC|CC|CC d|0~~1023|
1119 |SB|SB|SB h|0~~7FF|
1120 |S|S|S d|0~~8191|
1121 |DX|DX|DX h|0~~1FFF|
1122 |DY|DY|DY h|0~~1FFF|
1123 |SM|SM|SM d|8000~~9999|
1124 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1125 |D|D|D d|0~~12287|
1126 |W|W|W h|0~~1FFF|
1127 |TN|TN|TN d|0~~2047|
1128 |SN|SN|SN d|0~~2047|
1129 |CN|CN|CN d|0~~1023|
1130 |R|R|R d|0~~32767|
1131 |SW|SW|SW h|0~~7FF|
1132 |Z|Z|Z d|0~~15|
1133 |ZR|ZR|ZR h|0~~FE7FF|
1134
1135 **3)PLC Settings(GX Works2)**
1136
1137 * Click [Ethernet/CC IE/MELSECNET];
1138 * Please select [Ethernet] as network type;
1139 * Set station I/O number according to situation (For example, 0000 means that the module is connected to PLC CPU in first order);
1140 * Select [Online] as Mode;
1141 * Click [Operation setting] to set IP;
1142 * Select [Binary Code] as [Communication Data Code];
1143 * Set protocol: TCP;
1144 * Set [unpassive] in [Open system];
1145 * Set [receive] in [Fixed buffer];
1146 * Set [procedure Exist] in [Fixed buffer communication];
1147 * Disable [Pairing open];
1148 * Set [No confirm] in [Existence confirmation];
1149 * Host station port number: 1025;
1150 * Save settings;
1151 * Download project into PLC and restart it
1152
1153 **4)Configure the communication protocol**
1154
1155 [[image:image-20220825143728-1.png]]
1156
1157 **5)Cable Wiring**
1158
1159 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png"]]
1160
1161 = Create communication with **Delta PLC** =
1162
1163 == **DVP Ethernet Protocol** ==
1164
1165 [[下载链接>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Delta%20DVP%20Ethernet.zip]]
1166
1167 == **DVP serial protocol** ==
1168
1169 [[下载链接>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Delta%20DVP%20Ethernet.zip]]
1170
1171 == **AS Ethernet Protocol** ==
1172
1173 **1)V-BOX Settings**
1174
1175 |=**Items**|=**Settings**|=**Note**
1176 |Protocol|DELTA AS300 MODBUS TCP|
1177 |Connection|Ethernet|
1178 |Port No.|502|
1179 |Device No.|1|
1180 |HMI No.|0|
1181
1182 **2)Address List**
1183
1184 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1185 |Bit|X|X|X d|0~~63|
1186 |Bit|Y|Y|Y d|0~~63|
1187 |Bit|D|D|D d|0~~29999|
1188 |Bit|M|M|M d|0~~8191|
1189 |Bit|SM|SM|SM d|0~~4095|
1190 |Bit|S|S|S h|0~~2047|
1191 |Bit|T|T|T d|0~~511|
1192 |Bit|C|C|C d|0~~511|
1193 |Bit|HC|HC|HC d|0~~255|
1194 |Word|X|X|X h|0~~63|
1195 |Word|Y|Y|Y d|0~~63|
1196 |Word|SR|SR|SR d|0~~2047|
1197 |Word|D|D|D d|0~~29999|
1198 |Word|T|T|T d|0~~511|
1199 |Word|C|C|C h|0~~511|
1200 |Word|E|E|E d|0~~9|
1201
1202 **3)Configure the communication protocol**
1203
1204
1205 [[image:image-20220831160010-4.png]]
1206
1207 **4)Cable Wiring**
1208
1209 Figure
1210
1211 [[image:image-20220831155101-1.png]][[image:image-20220831160055-5.png]]
1212
1213 Pin Definition Diagram
1214
1215 [[image:image-20220831155157-3.png]]
1216
1217 = Create communication with **Omron PLC** =
1218
1219 == **CP1 Series Protocol ** ==
1220
1221 [[下载链接>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CP1%20Series.zip]]
1222
1223 == **CP2M Series Protocol** ==
1224
1225 [[下载链接>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CJ2M.zip]]
1226
1227
1228 == **EC55 Series Protocol** ==
1229
1230 Supported device: EC55 temperature instrument
1231
1232 **1)V-BOX Settings**
1233
1234 |**Items**|**Settings**|**Note**
1235 |Protocol|Omron EC55|
1236 |Connection|RS485 (9600, 2, 7, EVEN)|
1237 |Port No.|None|
1238 |PLC station No.|0|
1239
1240 **2)Address List**
1241
1242 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
1243 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
1244 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
1245 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
1246 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
1247 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
1248 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
1249 |CP|-|0-6|Read controller intrinsic property
1250 |CS|-|0-2|Read controller states
1251 |CA|-|0-17|Action command
1252
1253 **3)Device Settings**
1254
1255 Omron E5CC PLC configuration
1256
1257 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
1258
1259 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_3d95e093792ba98a.png?width=550&height=229&rev=1.1||alt="12.PLC Protocol_html_3d95e093792ba98a.png" height="229" width="550"]]
1260
1261 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
1262
1263 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_be583aa69dd6cf4c.png?width=550&height=242&rev=1.1||alt="12.PLC Protocol_html_be583aa69dd6cf4c.png" height="242" width="550"]]
1264
1265 **✎Note:** The communication settings for HMI should be consistent with this setting.
1266
1267 **4)Configure the communication protocol**
1268
1269 [[image:image-20220831161041-1.png]]
1270
1271 **5)Cable Wiring**
1272
1273 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5e9a81a14106da9e.png?width=392&height=223&rev=1.1||alt="12.PLC Protocol_html_5e9a81a14106da9e.png" height="223" width="392"]]
1274
1275 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_1897d92be6948d58.png?width=393&height=223&rev=1.1||alt="12.PLC Protocol_html_1897d92be6948d58.png" height="223" width="393"]]
1276
1277 **✎Note:**
1278
1279 * COM3 only available in PI8000/PI9000 series.
1280 * CA address could not support continuous writing function;
1281 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
1282 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
1283 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
1284 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
1285 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
1286 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
1287 * [[image:image-20220831161356-1.png]]Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
1288
1289 = Create communication with Xinje** PLC** =
1290
1291 == **XC serial protocol** ==
1292
1293 **1)V-BOX Settings**
1294
1295 |**Item**|**Settings**|**Note**
1296 |Protocol|XINJE XC MODBUS|
1297 |Connection|RS232|
1298 |Baud rate|19200|
1299 |Data bit|8|
1300 |Parity|EVEN|
1301 |Stop bit|1|
1302 |PLC station No.|1|
1303
1304 **2)Address List**
1305
1306 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1307 |Bit|M|M|M d|0~~8511|
1308 |Bit|X|X|X o|0~~1747|
1309 |Bit|Y|Y|Y o|0~~1747|
1310 |Bit|S|S|S d|0~~1023|
1311 |Bit|T|T|T d|0~~4095|
1312 |Bit|C|C|C d|0~~634|
1313 |Word|D|D|D d|0~~8511|
1314 |Word|TD|TD|TD d|0~~618|
1315 |Word|CD|CD|CD d|0~~634|
1316 |Word|FD|FD|FD d|0~~8511|
1317
1318 **3)Configure the communication protocol**
1319
1320
1321 [[image:image-20220831163041-1.png]]
1322
1323 **4)Cable Wiring**
1324
1325 Figure
1326
1327 [[image:image-20220831163406-2.png]][[image:image-20220831163422-3.png]]
1328
1329 Pin Definition Diagram
1330
1331 [[image:image-20220831163441-4.png]]
1332
1333 == **XD serial protocol** ==
1334
1335 **1)V-BOX Settings**
1336
1337 Supported Series: Delta Xinjie XD/XE Series PLC
1338
1339 |**Item**|**Settings**|**Note**
1340 |Protocol|XINJE XD/XC MODBUS|
1341 |Connection|RS232|
1342 |Baud rate|19200|
1343 |Data bit|8|
1344 |Parity|EVEN|
1345 |Stop bit|1|
1346 |PLC station No.|1|
1347
1348 **2)Address List**
1349
1350 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1351 |Bit|M|M|M d|0~~74999|
1352 |Bit|X1xx|X1xx|X1xx o|0~~1177|
1353 |Bit|X2xx|X2xx|X2xx o|0~~277|
1354 |Bit|X|X|X o|0~~77|
1355 |Bit|Y1xx|Y1xx|Y1xx o|0~~1177|
1356 |Bit|Y2xx|Y2xx|Y2xx o|0~~277|
1357 |Bit|Y|Y|Y o|0~~4095|
1358 |Bit|SM|SM|SM d|0~~4999|(((
1359
1360 )))
1361 |Bit|T|T|T d|0~~4999|
1362 |Bit|C|C|C d|0~~4999|
1363 |Bit|ET|ET|ET d|0~~31|
1364 |Bit|SE|SE|SE d|0~~31|
1365 |Bit|HM|HM|HM d|0~~11999|
1366 |Bit|HSC|HSC|HSC d|0~~39|
1367 |Bit|HS|HS|HS d|0~~999|
1368 |Bit|HT|HT|HT d|0~~1999|
1369 |Bit|HC|HC|HC d|0~~1999|
1370 |Bit|S|S|S d|0~~7999|
1371 |Word|D|D|D d|0~~69999|
1372 |Word|ID|ID|ID d|0~~99|
1373 |Word|ID1xx|ID1xx|ID1xx d|0~~999|
1374 |Word|ID2xx|ID2xx|ID2xx d|0~~299|
1375 |Word|QD|QD|QD d|0~~99|
1376 |Word|QD1xx|QD1xx|QD1xx d|0~~999|
1377 |Word|QD2xx|QD2xx|QD2xx d|0~~299|
1378 |Word|SD|SD|SD d|0~~4999|
1379 |Word|TD|TD|TD d|0~~575|
1380 |Word|CD|CD|CD d|0~~575|
1381 |Word|ETD|ETD|ETD d|0~~31|
1382 |Word|HD|HD|HD d|0~~24999|
1383 |Word|HSD|HSD|HSD d|0~~1023|
1384 |Word|HTD|HTD|HTD d|0~~95|
1385 |Word|HCD|HCD|HCD d|0~~95|
1386 |Word|HSCD|HSCD|HSCD d|0~~31|
1387 |Word|FD|FD|FD d|0~~8191|
1388 |Word|SFD|SFD|SFD d|0~~5999|
1389 |Word|FS|FS|FS d|0~~47|
1390
1391 **3)Configure the communication protocol**
1392
1393 [[image:image-20220831163923-7.png]]
1394
1395
1396
1397 **4)Cable Wiring**
1398
1399 Figure
1400
1401 [[image:image-20220831163406-2.png]][[image:image-20220831163553-6.png]]
1402
1403 Pin Definition Diagram
1404
1405 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830160232-3.png?rev=1.1||alt="image-20220830160232-3.png"]]
1406
1407
1408 = Create communication with **Schneider PLC** =
1409
1410 == **Schneider MODBUS RTU** ==
1411
1412 **1)V-BOX Setting**
1413
1414 |=**Parameters**|=**Recommended**|=**Notes**
1415 |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
1416 |**Connection**|RS485|
1417 |**Baud rate**|19200|
1418 |**Data bit**|8|
1419 |**Parity**|Even|
1420 |**Stop bit**|1|
1421 |**PLC station No.**|1|
1422
1423 **2)Address List**
1424
1425 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
1426 |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
1427 |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
1428 |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
1429 |W|MW|DDDDDD|0 ~~ 999999|Output register
1430 |DW|MD|DDDDDD|0 ~~ 999999|Output register
1431
1432 **3)Configure the communication protocol**
1433
1434 [[image:image-20220902104329-1.png]]
1435
1436 **4)Cable Wiring**
1437
1438 **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
1439
1440 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220817154212-1.jpeg?width=554&height=315&rev=1.1||alt="image-20220817154212-1.jpeg" height="315" width="554"]]
1441
1442 = Create communication with Inovance** PLC** =
1443
1444 == **H3U serial protocol** ==
1445
1446 **1)V-BOX Settings**
1447
1448 |**Item**|**Settings**|**Note**
1449 |Protocol|INOVANCE H3U PLC|
1450 |Connection|RS422|
1451 |Baud rate|9600|
1452 |Data bit|7|
1453 |Parity|EVEN|
1454 |Stop bit|1|
1455 |PLC station No.|0|
1456
1457 **2)Address List**
1458
1459 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1460 |Bit|X|X|X o|0~~303237|
1461 |Bit|Y|Y|Y o|0~~303237|
1462 |Bit|M|M|M d|0~~99999|
1463 |Bit|T|T|T d|0~~99999|
1464 |Bit|C|C|C d|0~~99999|
1465 |Bit|SM|SM|SM d|8000~~999|
1466 |Bit|S|T|S d|0~~99999|
1467 |Bit|Lamp|Lamp|Lamp d|0~~0|
1468 |Word|X|X|X o|0~~303237|
1469 |Word|Y|Y|Y o|0~~303237|
1470 |Word|M|M|M d|0~~99999|
1471 |Word|T|T|T d|0~~99999|
1472 |Word|C|C|C d|0~~199|
1473 |Word|D|D|D d|0~~7999|
1474 |Word|S|S|S d|0~~99999|
1475 |Word|SD|SD|SD d|8000~~9999|
1476 |Word|R|R|R d|0~~32767|
1477
1478 **3)Configure the communication protocol**
1479
1480 [[image:image-20220831164626-1.png]]
1481
1482
1483
1484 **4)Cable Wiring**
1485
1486 Figure
1487
1488 [[image:image-20220831164646-2.png]][[image:image-20220831164700-3.png]]
1489
1490 Pin Definition Diagram
1491
1492 [[image:image-20220831164731-4.png]]
1493
1494 = Create communication with Panasonic** PLC** =
1495
1496 == **FP serial protocol** ==
1497
1498 **1)V-BOX Settings**
1499
1500 |**Item**|**Settings**|**Note**
1501 |Protocol|Panasonic FP MFWTOCOL|
1502 |Connection|RS232|
1503 |Baud rate|9600|
1504 |Data bit|8|
1505 |Parity|ODD|
1506 |Stop bit|1|
1507 |PLC station No.|1|
1508
1509 **2)Address List**
1510
1511 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1512 |Bit|X|X|X d|0~~9999|
1513 |Bit|Y|Y|Y d|0~~9999|
1514 |Bit|R|R|R d|0~~9999|
1515 |Bit|T|T|T d|0~~9999|
1516 |Bit|C|C|C d|0~~9999|
1517 |Bit|L|L|L d|0~~9999|
1518 |Word|WX|WX|WX d|0~~9999|
1519 |Word|WY|WY|WY d|0~~9999|
1520 |Word|WR|WR|WR d|0~~9999|
1521 |Word|WL|WL|WL d|0~~9999|
1522 |Word|LD|LD|LD d|0~~9999|
1523 |Word|DT|DT|DT d|0~~65535|
1524 |Word|FL|FL|FL d|0~~9999|
1525 |Word|EV|EV|EV d|0~~9999|
1526 |Word|SV|SV|SV d|0~~9999|
1527
1528 **3)Configure the communication protocol**
1529
1530 [[image:image-20220831165238-4.png]]
1531
1532
1533
1534 **4)Cable Wiring**
1535
1536 Figure
1537
1538 [[image:image-20220831165031-3.png]][[image:image-20220831165017-2.png]]
1539
1540 Pin Definition Diagram
1541
1542 [[image:image-20220831165008-1.png]]
1543
1544 = Create communication with LS** PLC** =
1545
1546 == **XBC serial protocol** ==
1547
1548 **1)V-BOX Settings**
1549
1550 |**Item**|**Settings**|**Note**
1551 |Protocol|LS XBC CNet|
1552 |Connection|RS232|
1553 |Baud rate|115200|
1554 |Data bit|8|
1555 |Parity|NONE|
1556 |Stop bit|1|
1557 |PLC station No.|1|
1558
1559 **2)Address List**
1560
1561 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1562 |Bit|P|P|P d|0~~2047|
1563 |Bit|M|M|M d|0~~2047|
1564 |Bit|L|L|L d|0~~11263|
1565 |Bit|K|K|K d|0~~16183|
1566 |Bit|F|F|F d|0~~2047|
1567 |Bit|D|D|D d|0~~32767|
1568 |Bit|R|R|R d|0~~32767|
1569 |Bit|U|U|U d|0~~4095|
1570 |Word|P|P|P d|0~~2047|
1571 |Word|M|M|M d|0~~2047|
1572 |Word|L|L|L d|0~~11263|
1573 |Word|K|K|K d|0~~16183|
1574 |Word|F|F|F d|0~~2047|
1575 |Word|C|C|C d|0~~2047|
1576 |Word|T|T|T d|0~~2047|
1577 |Word|D|D|D d|0~~32767|
1578 |Word|N|N|N d|0~~21503|
1579 |Word|R|R|R d|0~~32767|
1580 |Word|U|U|U d|0~~4095|
1581 |Word|Z|Z|Z d|0~~127|
1582 |Word|S|S|S d|0~~127|
1583
1584 **3)Configure the communication protocol**
1585
1586 [[image:image-20220831170147-1.png]]
1587
1588 **4)Cable Wiring**
1589
1590 Figure
1591
1592 [[image:image-20220831170306-4.png]][[image:image-20220831170254-3.png]]
1593
1594 Pin Definition Diagram
1595
1596 [[image:image-20220831170215-2.png]]
1597
1598 == **XGK FEnet Ethernet protocol** ==
1599
1600 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
1601
1602 **1)V-BOX Settings**
1603
1604 |**Items**|**Settings**|**Note**
1605 |Protocol|LG XGK FEnet(Ethernet)|
1606 |Connection|Ethernet|
1607 |Port No.|2004|
1608
1609 **2)Address List**
1610
1611 |**Type**|**Register**|**Range**|**Format**|**Note**
1612 |(% rowspan="14" %)Word|P|0~~2047|P d|
1613 |M|0~~2047|M d|
1614 |K|0~~2047|K d|
1615 |F|0~~2047|F d|
1616 |T|0~~2047|T d|
1617 |C|0~~2047|C d|
1618 |Z|0~~127|Z d|
1619 |S|0~~127|S d|
1620 |L|0~~11263|L d|
1621 |N|0~~21503|N d|
1622 |D|0~~32767|D d|
1623 |R|0~~32767|R d|
1624 |ZR|0~~65535|ZR d|
1625 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
1626
1627 **✎Note:**
1628
1629 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
1630 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
1631 * All bit registers are in the form of bits in word, and the range is the same as the word register;
1632
1633 **3)Communication Settings**
1634
1635 [[image:image-20220831171127-1.png]]
1636
1637 **4)Cable Wiring**
1638
1639 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1640
1641 = Create communication with **Modbus ** =
1642
1643 == **MODBUS RTU Slave (All function)** ==
1644
1645 Select the protocol "Modbus RTU Slave (All Fuction)",
1646
1647 Then set baud rate, port, stop bits, data bits, parity.
1648
1649 (% style="text-align:center" %)
1650 [[image:1624342015914-382.png||height="486" width="800" class="img-thumbnail"]]
1651
1652 == **MODBUS RTU Master** ==
1653
1654 Select the protocol "Modbus RTU Master",
1655
1656 Then set baud rate, port, stop bits, data bits, parity
1657
1658 (% style="text-align:center" %)
1659 [[image:1624348709622-711.png||queryString="width=809&height=493" height="488" width="800" class="img-thumbnail"]]
1660
1661 **address list**
1662
1663 (% class="table-bordered" %)
1664 |**type**|**register**|**Function code and description**
1665 |(% rowspan="11" %)词|(% rowspan="3" %)3|04 (Read Input Registers: Read the current binary value in one or more input registers)
1666 |06 (write single register: write a binary value to a holding register)
1667 |10 (write values to multiple addresses )
1668 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1669 |06 (write single register: write a binary value to a holding register)
1670 |10 (write values to multiple addresses )
1671 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1672 |06 (write single register: write a binary value to a holding register)
1673 |10 (write values to multiple addresses )
1674 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1675 |10 (write values to multiple addresses )
1676 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1677 |05 (Force a single coil to force the on/off state of a logic coil)
1678 |0F (Write multiple bits, ie write continuously)
1679 |(% rowspan="3" %)1|02 (Read the input state)
1680 |05 (Force a single coil to force the on/off state of a logic coil)
1681 |0F (Write multiple bits)
1682 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1683 |05 (Force a single coil to force the on/off state of a logic coil)
1684 |0F (Write multiple bits)
1685 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1686 |0F (Write multiple bits)
1687
1688 == **MODBUS TCP Slave (All function)** ==
1689
1690 Supported series: MODBUS TCP controller
1691
1692 V-B0X works as MODBUS TCP MASTER connecting with TCP SLAVE
1693
1694 **1)V-BOX Setting**
1695
1696 |**Items**|**Settings**|**Note**
1697 |Protocol|MODBUS TCP Slave (All function)|
1698 |Connection|Ethernet|
1699 |Port No.|502|
1700 |PLC station No.|1
1701
1702 **2)Address List**
1703
1704 |**Type**|**Register**|**Function code & Description**
1705 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
1706 |06 (write single register: write a binary value to a holding register)
1707 |10 (write values to multiple addresses )
1708 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1709 |06 (write single register: write a binary value to a holding register)
1710 |10 (write values to multiple addresses )
1711 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1712 |06 (write single register: write a binary value to a holding register)
1713 |10 (write values to multiple addresses )
1714 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1715 |10 (write values to multiple addresses )
1716 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1717 |05 (Force a single coil to force the on/off state of a logic coil)
1718 |0F (Write multiple bits, ie write continuously)
1719 |(% rowspan="3" %)1|02 (Read the input state)
1720 |05 (Force a single coil to force the on/off state of a logic coil)
1721 |0F (Write multiple bits)
1722 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1723 |05 (Force a single coil to force the on/off state of a logic coil)
1724 |0F (Write multiple bits)
1725 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1726 |0F (Write multiple bits)
1727
1728 **3)Communication Settings**
1729
1730 Configure V-BOX Ethernet IP in Networking Settings
1731
1732 [[image:image-20220902111833-3.png]]
1733
1734
1735 Configure PLC Ethernet IP in Communication;
1736
1737 [[image:image-20220902111121-1.png]]
1738
1739 **4)Cable Wiring**
1740
1741 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1742
1743 == **communicate with VB inverter** ==
1744
1745 [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20VB%20inverter.zip]]
1746
1747 = **User define protocol** =
1748
1749 More serial port script instruction,please refer manual:[[Lua script function>>doc:V-BOX.V-Net.Manual.04 Lua Script.01 Lua Functions.WebHome]]~-~-->[[3.Serial port operation>>url:http://docs.we-con.com.cn/wiki/vbox/view/HMI/04.Lua%20script%20%20function%20and%20operation/01.Lua%20script%20function/#H3.Serialportoperation]]
1750
1751 == **Read the temperature sensor.** ==
1752
1753 the commond format is as beliow:
1754
1755 Send commond:01 03 02 00 00 03 04 73
1756
1757 Feedback commond:01 03 06 07 F7 0E 7E B7 35
1758
1759 Temperature data:07 F7,desimal = 2039,it means temperature is 20.39℃.
1760
1761 Humidity data:0E 7E,desimal = 3710, it mean humidity is 37.10%RH.
1762
1763 Script Demo:
1764
1765 ~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~--
1766
1767 function com.main()
1768 ~-~-dosomething
1769 openPlc()
1770 end
1771 function openPlc()
1772 if obj then
1773 ~-~- If the serial port opened,then read/write data by timing
1774
1775 local wri = string.pack(">HHHH",0X0103,0X0200,0X0003,0X0473)
1776 local arr = reading(wri)
1777 ~-~- if arr ~~=nil then
1778 ~-~- if arr[1] ==33 and arr[2] ==v[2][2] and arr[3] ==v[2][3] then
1779 ~-~- local A = arr[4]*256
1780 ~-~- local B = A+arr[5]
1781 ~-~- addr_setword(v[1],B)
1782 ~-~- end
1783 ~-~- end
1784
1785 else
1786 ~-~-judge if there is a serial object, then initialize and open the serial port
1787 local configs = {
1788 name = 'COM1', ~-~-Select serial port COM1
1789 mode = 485, ~-~-Communication mode RS485
1790 baud_rate = 9600, ~-~-Baud rate 9600
1791 stop_bit = 1, ~-~-stop bit 1
1792 data_len = 8, ~-~-data length 8
1793 check_bit = 'NONE', ~-~-no parity
1794
1795 }
1796 obj,err = serial.open(configs) ~-~-Open serial port
1797 if not obj then
1798 print("serial open :failed", err) ~-~- Open serial port failed
1799 end
1800 end
1801 end
1802
1803 function reading(wri)
1804 obj:flush() ~-~- Clear serial port
1805 obj:write(wri) ~-~- Write serial port
1806 print(string.byte(wri,1,#wri))
1807 obj:flush() ~-~- Clear serial port 
1808 local readed =obj:read(9,1000) ~-~- Read 9 bytes, timeout 1 second
1809 if readed and readed ~~= "" then 
1810 ~-~- judge that a non-empty string is read
1811 print(string.byte(readed,1,#readed))
1812 a={string.byte(readed, 1, #readed)}
1813 if nil ~~= a[4] and nil ~~= a[5] and nil ~~= a[6] and nil ~~= a[7] then
1814 a1=a[4]*256+a[5]
1815 a2=a[6]*256+a[7]
1816 addr_setword("@HDW0",a1)
1817 addr_setword("@HDW1",a2)
1818 end
1819 return {string.byte(readed, 1, #readed)}
1820 elseif readed == nil then
1821 print("serial read err:", err or "")
1822 return nil
1823 end
1824 return nil
1825 end
1826
1827 ~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-