Wiki source code of 1 Communication

Version 185.1 by Bob on 2022/11/25 17:13

Show last authors
1 = Create communication with WECON PLC =
2
3 == **LX3V Serial Protocol** ==
4
5 Supported series: Wecon LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
6
7 **1)V-BOX setting**
8
9 |**Item**|**Settings**|**Note**
10 |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
11 |Connection|RS422/RS485|
12 |Baud rate|9600|
13 |Data bit|7|
14 |Parity|EVEN|
15 |Stop bit|1|
16 |PLC station No.|1|
17
18 **2)Address List**
19
20
21 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
22 |(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
23 |Y|Y|Y o|0~~303237|
24 |M|M|M d|0~~99999|
25 |T|T|T d|0~~99999|
26 |C|C|C d|0~~99999|
27 |S|S|S d|0~~99999|
28 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
29 |Y|Y|Y o|0~~303237|
30 |M|M|M d|0~~99999|
31 |T|T|T d|0~~99999|
32 |C|C|C d|0~~199|
33 |D|D|D d|0~~7999|
34 |S|S|S d|0~~99999|
35 |SD|SD|SD d|8000~~9999|
36
37 **3)Configure the communication protocol**
38
39 [[image:image-20220824152217-1.png||alt="图片-20220824152217-1.png"]]
40
41 **4)Cable Wiring**
42
43 * **RS422**
44
45 [[image:image-20220824120614-5.png]]
46
47 * **RS485**
48
49 [[image:image-20220824120524-3.png]]
50
51 == **LX5V Serial Protocol** ==
52
53 This example introduces the establishment of serial port communication between V-BOX and LX5V. It is introduced through three parts: PLC software configuration, V-BOX software configuration, and hardware wiring.
54
55 **Software configuration of PLC**
56
57 **1)PLC programming software**
58
59 [[image:image-20220824142722-1.png]]
60
61 **2)New PLC project**
62
63 Click New Project and select the PLC model.
64
65 [[image:image-20220822172623-2.png]]
66
67 **3)Set Serial port parameters**
68
69 Follow the steps below to configure Serial port parameters
70
71 Baud rate:115200
72
73 Data bit:8
74
75 Stop bit:1
76
77 Parity:No verification
78
79 [[image:image-20220822172657-3.png]]
80
81 **4)Registers list**
82
83 [[image:image-20220822172730-4.png]]
84
85 **V-BOX software configuration**
86
87 **1)V-BOX programming software**
88
89 [[image:image-20220824104124-1.png]]
90
91 **2)V-NET add device**
92
93 Open V-NET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the access key, password and remark, to add the device.
94
95 [[image:image-20220824104909-2.png]]
96
97 **3)Set communication port parameters**
98
99 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
100
101 Baud rate:115200
102
103 Data bit:8
104
105 Stop bit:1
106
107 Parity:No verification
108
109 [[image:image-20220824142130-1.png]]
110
111 **hardware connection**
112
113 **1)Hardware wiring diagram**
114
115 [[image:image-20220824142546-2.png]]
116
117 [[image:image-20220824142643-3.png]]
118
119 The above are all the steps for establishing serial port communication between V-BOX with LX5V PLC.
120
121 == **LX5V-N Ethernet protocol** ==
122
123 This example introduces the establishment of Ethernet communication between V-BOX and LX5V-N. It is introduced through three parts: PLC software configuration, V-BOX software configuration, and hardware wiring.
124
125 **Software configuration of PLC**
126
127 **1)PLC programming software**
128
129 [[image:image-20220824142722-1.png]]
130
131 **2)New PLC project**
132
133 Click New Project and select the PLC model.
134
135 [[image:image-20220824143613-1.png]]
136
137 **3)Set Ethernet port parameters**
138
139 Follow the steps below to configure Ethernet parameters
140
141 PLC IP address:192.168.39.200
142
143 default gateway:192.168.39.1
144
145 subnet mask:255.255.255.0
146
147 [[image:image-20220824143744-2.png]]
148
149 **4)Registers list**
150
151 [[image:image-20220822172730-4.png]]
152
153 (% id="cke_bm_22473S" style="display:none" %)** **(%%)**V-BOX software configuration**
154
155 **1)V-BOX programming software**
156
157 [[image:image-20220824104124-1.png]]
158
159 **2)V-NET add device**
160
161 Open V-NET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the access key, password and remark, to add the device.
162
163 [[image:image-20220824104909-2.png]]
164
165 **3)Set communication Protocol**
166
167 Click Communication to configure the LX5V plc protocol and IP address.
168
169 [[image:image-20220824144619-1.png]]
170
171 **hardware connection**
172
173 **1)Hardware wiring diagram**
174
175 [[image:image-20220824151127-2.png]]
176
177 The above are all the steps for establishing ethernet communication between V-BOX with LX5V PLC.
178
179 = Create communication with **Rockwell PLC** =
180
181 == (% id="cke_bm_5621S" style="display:none" %)** **(%%)**MicroLogix Protocol** ==
182
183 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
184
185 **1)V-BOX setting**
186
187 |**Item**|**Settings**|**Note**
188 |Protocol|Allen-Bradlley DF1 Advanced|
189 |Connection|RS232|
190 |Baud rate|19200|
191 |Data bit|8|
192 |Parity|None|
193 |Stop bit|1|
194 |PLC station No.|1|
195
196 **2)Address List**
197
198 |**Type**|**Device registers**|**Format**|**Range**|**Note**
199 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
200 |O|O d.d|0.0~~255.15|
201 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
202 |S|S d.d|0.0~~255.15|
203 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
204 |(% rowspan="9" %)Word|S|S d|0~~255|
205 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
206 |TP|TP nnhh|0~~ffff
207 |CS|CS nnhh|0~~ffff
208 |CP|CP nnhh|0~~ffff
209 |N|N nnhh|0~~ffff
210 |C|C nnhh|0~~ffff
211 |T|T nnhh|0~~ffff
212 |R|R nnhh|0~~ffff
213
214 **3)Configure the communication protocol**[[image:image-20220824152928-1.png]]
215
216 **4)Configure the communication protocol**
217
218 [[image:image-20220824110724-1.png]]
219
220 == **Micro850_FreeTag Protocol** ==
221
222 (((
223 (((
224 This example introduces the establishment of Ethernet communication between Wecon V-box and CompactLogix L1769. It is introduced through three parts: PLC software configuration, V-box software configuration, and hardware wiring.
225 )))
226 )))
227
228 (((
229 (% class="wikigeneratedid" id="HSoftwareconfigurationofPLC" %)
230 (((
231 **Software configuration of PLC**
232 )))
233
234 (% class="wikigeneratedid" id="HPLCprogrammingsoftware" %)
235 (((
236 **1)PLC programming software**
237 )))
238
239 [[image:image-20220714162600-1.png]]
240
241 (% class="wikigeneratedid" id="HNewPLCproject" %)
242 (((
243 **2)New PLC project**
244 )))
245
246 (((
247 (((
248 Click New Project and select the PLC model.
249 )))
250 )))
251
252 (((
253 [[image:image-20220714162617-2.png]]
254 )))
255
256 (((
257
258
259 [[image:image-20220714162652-4.png]]
260 )))
261
262 (((
263 (% class="wikigeneratedid" id="HSetEthernetparameters" %)
264 (((
265 **3)Set Ethernet parameters**
266 )))
267
268 (((
269 (((
270 (((
271 Follow the steps below to configure Ethernet parameters
272 )))
273 )))
274 )))
275
276 (((
277 (((
278 (((
279 PLC IP address:192.168.40.101
280 )))
281 )))
282 )))
283
284 (((
285 (((
286 (((
287 default gateway:192.168.40.1
288 )))
289 )))
290 )))
291
292 (((
293 (((
294 (((
295 subnet mask:255.255.255.0
296 )))
297 )))
298 )))
299
300 (((
301 [[image:image-20220714162713-5.png]]
302 )))
303
304 (((
305
306 )))
307
308 (((
309 (% class="wikigeneratedid" id="HV-boxsoftwareconfiguration" %)
310 (((
311 **V-box software configuration**
312 )))
313
314 (% class="wikigeneratedid" id="HV-boxprogrammingsoftware" %)
315 (((
316 **1)V-box programming software**
317 )))
318
319 (% class="wikigeneratedid" %)
320 (((
321 [[image:image-20220714162725-6.png]]
322 )))
323
324 (% class="wikigeneratedid" id="HConfiguredevicenetwork" %)
325 (((
326 **2)Configure device network**
327 )))
328
329 (((
330 (((
331 (((
332 Click the Configuration Download button[[image:image-20220714115308-8.png||height="22" width="15"]], It is used to configure the device network, update the device time, obtain the device machine code, check the device network, etc.
333 )))
334
335 (((
336 In the example below, the IP address of V-Box is configured as 192.168.40.66, and the networking method is 4G connection
337 )))
338 )))
339 )))
340
341 (((
342 (((
343 [[image:image-20220714162737-7.png]]
344
345
346 )))
347 )))
348 )))
349 )))
350
351 (% class="wikigeneratedid" id="HV-netadddevice" %)
352 (((
353 **3)V-net add device**
354 )))
355 )))
356
357 (((
358 (((
359 Open VNET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the device machine code/product code, device password, and device alias to add the device.   [[image:image-20220714162752-8.png]]
360 )))
361
362
363 )))
364
365 (((
366 (% class="wikigeneratedid" id="HSetcommunicationportparameters" %)
367 (((
368 **4)Set communication port parameters**
369 )))
370
371 (((
372 In the device list on the left, find the Vbox that communicates with the L1769, click it and select configuration,communication port configuration in the main interface to add a communication protocol.
373 )))
374
375 [[image:image-20220714162805-9.png]]
376 )))
377
378 (((
379 The communication port is selected as Ethernet, the device type is selected as Allen-Bradley, the protocol is Allen-BradleyMicro850_FreeTag EthemetIP, and the IP is the internal IP address of the L1769 PLC. The port number is 44818.
380 )))
381
382 [[image:image-20220824164346-1.png]]
383
384
385 (((
386 After adding the protocol Allen-BradleyMicro850_FreeTag, click[[image:image-20220714143838-2.png]]icon add label.[[image:image-20220714162827-11.png]]
387 )))
388
389 (% class="wikigeneratedid" id="HEngineeringproduction" %)
390 (((
391 **5)Engineering production**
392 )))
393
394 (% class="wikigeneratedid" %)
395 (((
396 (((
397 According to your own needs, use the V-NET client software to edit the required data monitoring points.
398 )))
399
400 [[image:image-20220714162841-12.png]]
401
402
403 (((
404 **hardware connection**
405 )))
406 )))
407
408 (((
409 **1)Hardware wiring diagram**
410 )))
411
412 (((
413 (((
414 This example introduces Wecon V-box with Allen-Bradley L1769 PLC to establish communication through Ethernet. The connection diagram is as follows:
415 )))
416
417 [[image:image-20220714162856-13.png]]
418
419 (((
420 The above are all the steps for establishing Ethernet communication between Wecon V-box with CompactLogix L1769 PLC.
421
422
423 = **Allen-Bradley Ethernet DF1** =
424
425 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Allen-Bradley%20Ethernet%20DF1.zip]]
426
427
428 = Create communication with **Siemens PLC** =
429
430 == **S7-200 Smart Ethernet Protocol** ==
431
432 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20S7-200%20Smart.zip]]
433
434
435 == **S7-300 Ethernet Protocol** ==
436
437 Supported Series: Siemens S7-300 series PLC
438
439 **1)V-BOX setting**
440
441 |**Items**|**Settings**|**Note**
442 |Protocol|Simens S7-300 Ethernet|
443 |Connection|Ethernet|
444 |Port No.|102|
445 |PLC station No.|2|Need to be same as the PLC setting
446
447 **2)Address List**
448
449 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
450 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
451 |Q|Q|Q ddddd.o|0.0~~99999.7|
452 |M|M|M ddddd.o|0.0~~99999.7|
453 |DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
454 nn: block number;
455
456 dddd: address;
457 )))
458 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
459 |Q|QW|QW ddddd|0~~99999|
460 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
461 |MW|MW ddddd|0~~99999|(((
462 MW0=MB(0~~1)
463
464 MW2=MB(2~~3)
465
466 Address value is a multiple of 2
467 )))
468 |MD|MD ddddd|0~~99999|(((
469 MD0=MB(0~~3)
470
471 MD4=MB(4~~7)
472
473 Address value is a multiple of 4
474 )))
475 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
476 nn: block number;
477
478 dddd: address
479 )))
480 |DBxDBW|DBxDBW nndddd|0~~99999999
481 |DBxDBD|DBxDBD nndddd|0~~99999999
482
483 **3)Configure the communication protocol**
484
485 [[image:image-20220824161345-1.png]]
486
487 **4)Cable Wiring**
488
489 [[image:image-20220824161450-2.png]]
490 )))
491 )))
492
493 == **S7-1200 Ethernet Protocol** ==
494
495 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]]
496
497 == **S7-XXX Ethernet Protocol** ==
498
499 Supported Series: Siemens S7-400, S7-1200 and S7-1500
500
501 **1)V-BOX setting**
502
503 |=**Items**|=**Settings**|=**Note**
504 |Protocol|Siemens S7-XXX|
505 |Connection|Ethernet|
506 |Port No.|102|
507 |Device No.|Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|
508 |HMI No.|Rack (Default as 0)|
509
510 Slot from TIA Portal is equal to Device No. of V-net
511
512 Rack from TIA Portal is equal to HMI No. of V-net
513
514 [[image:image-20220824162459-3.png]]
515
516 [[image:image-20220824163305-2.png]]
517
518 **2)Address List**
519
520 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
521 |(% rowspan="4" %)Bit|I|I|M d.o|(((
522 d:0~-~-9999
523
524 o:0-7
525 )))|
526 |Q|Q|Q d.o|(((
527 d:0~-~-9999
528
529 o:0-7
530 )))|
531 |M|M|M d.o|(((
532 d:0~-~-9999
533
534 o:0-7
535 )))|
536 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
537 nn:0-9999,
538
539 dddd:0-9999,
540
541 o:0-7
542 )))|(((
543 nn:DB No.
544
545 dddd:address value
546
547 o: digit address
548 )))
549 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
550 |M|MW|MW d|d:0-99999|(((
551 MW0=MB(0~~1)
552
553 MW2=MB(2~~3)
554
555 Address value is a multiple of 2
556 )))
557 |M|MD|MD d|d:0-99999|(((
558 MD0=MB(0~~3)
559
560 MD4=MB(4~~7)
561
562 Address value is a multiple of 4
563 )))
564 |I|IW|IW d|d:0-99999|
565 |Q|QW|QW d|d:0-99999|
566 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
567 nn:0-9999
568
569 dddd:0-9999
570 )))|(((
571 nn:DB No.
572
573 dddd:address value
574 )))
575 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
576 nn:0-9999
577
578 dddd:0-9999
579 )))|(((
580 nn:DB No.
581
582 dddd:address value
583
584 Address value is a multiple of 2
585 )))
586 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
587 nn:0-9999
588
589 dddd:0-9999
590 )))|(((
591 nn:DB No.
592
593 dddd:address value
594
595 Address value is a multiple of 4
596 )))
597
598 **3)Configure the communication protocol**
599
600 [[image:image-20220824163448-3.png]]
601
602 **✎Note:**
603
604 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three V-BOX.
605 * V-BOX access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
606
607 **4)Cable Wiring**
608
609 [[image:image-20220824162342-2.png]]
610
611 = Create communication with **Mitsubishi PLC** =
612
613 == **FX1S,1N,2N Serial Protocol** ==
614
615 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
616
617 **1)V-BOX Settings**
618
619 |**Item**|**Settings**|**Note**
620 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
621 |Connection|RS422/RS485/RS232|
622 |Baud rate|9600~~115200|
623 |Data bit|7/8|
624 |Parity|EVEN/Odd/None|
625 |Stop bit|1/2|
626 |PLC station No.|1~~255|
627
628 **2)Address List**
629
630 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
631 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
632 |Y|Y|Y o|0~~303237|
633 |M|M|M d|0~~99999|
634 |T|T|T d|0~~99999|
635 |C|C|C d|0~~99999|
636 |S|S|S d|0~~99999|
637 |SM|SM|SM d|8000~~9999|
638 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
639 |Y|Y|Y o|0~~303237|
640 |M|M|M d|0~~99999|
641 |T|T|T d|0~~99999|
642 |C|C|C d|0~~199|
643 |D|D|D d|0~~7999|
644 |S|S|S d|0~~99999|
645 |SD|SD|SD d|8000~~9999|
646
647 **3)Configure the communication protocol**
648
649 [[image:image-20220825102844-3.png]]
650
651 **4)Cable Wiring**
652
653 * **RS422**
654
655 [[image:image-20220825103350-4.png]]
656
657 [[image:image-20220825100845-4.png]]
658
659
660 == **FX3U,3G,3GA Serial Protocol** ==
661
662 Supported Series: Mitsubishi FX3U, FX3G, FX3GA series
663
664 **1)V-BOX Settings**
665
666 |**Item**|**Settings**|**Note**
667 |Protocol|Mitsubishi FX3U/3G/3GA|
668 |Connection|RS422/RS485/RS232|
669 |Baud rate|9600~~115200|
670 |Data bit|7/8|
671 |Parity|EVEN/Odd/None|
672 |Stop bit|1/2|
673 |PLC station No.|1~~255|
674
675 **2)Address List**
676
677 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
678 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
679 |Y|Y|Y o|0~~303237|
680 |M|M|M d|0~~99999|
681 |T|T|T d|0~~99999|
682 |C|C|C d|0~~99999|
683 |S|S|S d|0~~99999|
684 |SM|SM|SM d|8000~~9999|
685 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
686 |Y|Y|Y o|0~~303237|
687 |M|M|M d|0~~99999|
688 |T|T|T d|0~~99999|
689 |C|C|C d|0~~199|
690 |D|D|D d|0~~7999|
691 |S|S|S d|0~~99999|
692 |SD|SD|SD d|8000~~9999|
693
694 **3)Configure the communication protocol**
695
696 [[image:image-20220825102649-2.png]]
697
698 **4)Cable Wiring**
699
700 * **RS422**
701
702 [[image:image-20220825103421-5.png]]
703
704 [[image:image-20220825100845-4.png]]
705
706
707 == **FX3U Ethernet Protocol** ==
708
709 Supported Modules: FX3U-ENET-ADP, FX3U-ENET-L
710
711 **1)V-BOX Settings**
712
713 |Items|Settings|Note
714 |Protocol|Mitsubishi FX3U|
715 |Connection|Ethernet|
716 |Port No.|5009|Must be the same as the PLC setting
717 |PLC station No.|0|
718
719 **2)Address List**
720
721 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
722 |(% colspan="1" rowspan="7" %)Bit|X|X|X OOO|0~~377|
723 |Y|Y|Y OOO|0~~377|
724 |M|M|M DDDD|0~~7679|
725 |SM|SM|SM DDDD|8000~~8511|
726 |S|S|S DDDD|0~~4095|
727 |TS|TS|TS DDD|0~~511|
728 |CS|CS|CS DDD|0~~255|
729 |(% colspan="1" rowspan="9" %)Word|CN|CN|CN DDD|0~~199|
730 |TN|TN|TN DDD|0~~511|
731 |D|D|D DDDD|0~~7999|
732 |SD|SD|SD DDDD|8000~~8511|
733 |R|R|R DDDDD|0~~32767|
734
735 **3)Ethernet Module Settings**
736
737 FX3U-ENET-L module configuration
738 Set up the FX3U-ENET-L Ethernet module settings as follows.
739 Select the module location, which in this document is Module 0.
740
741 [[image:image-20221116105850-1.png]]
742
743 Select "Operational setting" to enter the following screen.
744
745 The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default.
746
747 [[image:image-20221116105947-1.png]]
748
749 Select "Open setting" to enter the setting interface, the settings are as follows.
750
751 The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the
752
753 Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module.
754
755 [[image:image-20221116110802-1.png]]
756
757 Click on "transter setup" - "PC side I/F setting", see the following figure.
758
759 After setting, the first download must use the programming cable, as shown in the figure; after that, can
760
761 use the IP set in the "Ethernet board" to communicate directly with the network cable.
762
763 [[image:image-20221116110832-2.png||height="423" width="708"]]
764
765 Read and write data from the Ethernet module
766
767 [[image:image-20221116110907-3.png]]
768
769 Set "Transter setup" to COM communication, and read or write operation as shown below
770
771 [[image:image-20221116110917-4.png]]
772
773 **4)PLC Settings (GX Works 2)**
774
775 Create a blank FX5U project
776
777 Find Current Connection in the navigation
778
779 [[image:image-20221116111427-1.png||height="421" width="705"]]
780
781 Select Connection Channel List
782
783 Select Ethernet board communication
784
785 [[image:image-20221116111451-2.png||height="421" width="705"]]
786
787 Select Ethernet Module
788 Set the IP address of the PLC
789
790 [[image:image-20221116111509-3.png||height="666" width="699"]]
791
792 Read or write PLC data, in this document is read
793
794 [[image:image-20221116111651-4.png||height="416" width="697"]]
795
796 [[image:image-20221116111727-5.png||height="416" width="697"]]
797
798 **4)Configure the communication protocol**
799
800 [[image:image-20221119101946-2.png||height="395" width="695"]]
801
802 == **FX5U Serial Protocol** ==
803
804 Mitsubishi FX5U series PLC
805
806 **1)V-BOX Settings**
807
808 |**Item**|**Settings**|**Note**
809 |Protocol|Mitsubishi FX5U|
810 |Connection|RS422/RS485|
811 |Baud rate|9600|
812 |Data bit|7|
813 |Parity|Odd|
814 |Stop bit|1|
815 |PLC station No.|1~~255|Need to be the same as PLC settings
816
817 **2)Address List**
818
819 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
820 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
821 |Y|Y|Y o|0~~303237|
822 |M|M|M d|0~~99999|
823 |B|B|B h|0~~7FFF|
824 |F|F|F d|0~~32767|
825 |SB|SB|SB h|0~~7FFF|
826 |TS|TS|TS d|0~~1023|
827 |TC|TC|TC d|0~~1023|
828 |STS|STS|STS d|0~~1023|
829 |STC|STC|STS d|0~~1023|
830 |CS|CS|CS d|0~~1023|
831 |CC|CC|CC d|0~~1023|
832 |SM|SM|SM d|0~~9999|
833 |L|L|L d|0~~32767|
834 |S|S|S d|0~~4095|
835 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
836 |TN|TN|TN d|0~~1023|
837 |STN|STN|STN d|0~~1023|
838 |CN|CN|CN d|0~~1023|
839 |R|R|R d|0~~32767|
840 |SW|SW|SW h|0~~7FFF|
841 |Z|Z|Z d|0~~23|
842 |D|D|D d|0~~7999|
843 |SD|SD|SD d|0~~11999|
844
845 **3)PLC Settings (GX Works 3)**
846
847 Create a blank FX5U project
848
849 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
850
851 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5c9cb13fac1e6c93.png?width=200&height=462&rev=1.1||alt="12.PLC Protocol_html_5c9cb13fac1e6c93.png" height="462" width="200"]]
852
853 Select protocol in the setting item, and set parameters.
854
855 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_de942589ca070228.png?width=600&height=324&rev=1.1||alt="12.PLC Protocol_html_de942589ca070228.png" height="324" width="600"]]
856
857 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
858
859 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_387ec7d00b5feb59.png?width=600&height=323&rev=1.1||alt="12.PLC Protocol_html_387ec7d00b5feb59.png" height="323" width="600"]]
860
861 Click the [Apply] button to finish the setting.
862
863 Click download and select the items as below, then click [execute] to download the configuration to PLC.
864
865 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_cdef1c5ec8cc2105.png?width=600&height=434&rev=1.1||alt="12.PLC Protocol_html_cdef1c5ec8cc2105.png" height="434" width="600"]]
866
867 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
868
869 Done.
870
871 **4)Configure the communication protocol**
872
873 [[image:image-20220825104904-1.png]]
874
875 **5)Cable Wiring**
876
877
878 * **RS422**
879
880 [[image:image-20220825105105-2.png]]
881
882 [[image:image-20220825105533-3.png]]
883
884 == **FX5U Ethernet Protocol** ==
885
886 Mitsubishi FX5U series PLC
887
888 **1)V-BOX Settings**
889
890 |**Items**|**Settings**|**Note**
891 |Protocol|Mitsubishi FX5U|
892 |Connection|Ethernet|
893 |Port No.|5002|Must be the same as the PLC setting
894 |PLC station No.|0|
895
896 **2)Address List**
897
898 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
899 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
900 |Y|Y|Y o|0~~303237|
901 |M|M|M d|0~~99999|
902 |B|B|B h|0~~7FFF|
903 |F|F|F d|0~~32767|
904 |SB|SB|SB h|0~~7FFF|
905 |TS|TS|TS d|0~~1023|
906 |TC|TC|TC d|0~~1023|
907 |STS|STS|STS d|0~~1023|
908 |STC|STC|STS d|0~~1023|
909 |CS|CS|CS d|0~~1023|
910 |CC|CC|CC d|0~~1023|
911 |SM|SM|SM d|0~~9999|
912 |L|L|L d|0~~32767|
913 |S|S|S d|0~~4095|
914 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
915 |TN|TN|TN d|0~~1023|
916 |STN|STN|STN d|0~~1023|
917 |CN|CN|CN d|0~~1023|
918 |R|R|R d|0~~32767|
919 |SW|SW|SW h|0~~7FFF|
920 |Z|Z|Z d|0~~23|
921 |D|D|D d|0~~7999|
922 |SD|SD|SD d|0~~11999|
923
924 **3)PLC Settings (GX Works 3)**
925
926 Find the [Ethernet port] in the navigation area.
927
928 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_8e8f85ace087346c.png?width=300&height=593&rev=1.1||alt="12.PLC Protocol_html_8e8f85ace087346c.png" height="593" width="300"]]
929
930 Select [Own Node Settings] in the [Setting Item List];
931
932 Set [IP Address], [Subnet Mask], [Default Gateway];
933
934 Click [Detailed Settings] into [Ethernet Configuration (Built-in Ethernet Port)] windows;
935
936 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5d98495052c8c10e.png?width=600&height=339&rev=1.1||alt="12.PLC Protocol_html_5d98495052c8c10e.png" height="339" width="600"]]
937
938 Select [SLMP Connection Module] and add into host station as below picture shows;
939
940 Set Port number as 5002 (this is necessary settings);
941
942 Click [Close with Reflecting the Setting] to save and close window;
943
944 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_14b489fdc6c6589d.png?width=600&height=350&rev=1.1||alt="12.PLC Protocol_html_14b489fdc6c6589d.png" height="350" width="600"]]
945
946 Click [Apply] to completed Etherenet settings;
947
948 Switch to the [On line data operation] interface as below, check the item and click [Execute] to download.
949
950 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_c93025a968a8a9e7.png?width=600&height=434&rev=1.1||alt="12.PLC Protocol_html_c93025a968a8a9e7.png" height="434" width="600"]]
951
952 **4)Configure the communication protocol**
953
954 [[image:image-20220825112403-1.png||alt="图片-20220825112403-1.png"]]
955
956 **5)Cable Wiring**
957
958 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
959
960 == **L02 Serial Protocol** ==
961
962 Mitsubishi L02 series CPU built-in serial port.
963
964 **1)V-BOX Settings**
965
966 |**Item**|**Settings**|**Note**
967 |Protocol|Mitsubishi L02|
968 |Connection|RS422|
969 |Baud rate|115200|
970 |Data bit|8|
971 |Parity|Odd|
972 |Stop bit|1|
973 |PLC station No.|1~~255|Need to be the same as PLC settings
974
975 **2)Address List**
976
977 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
978 |Bit|X|X|X h|0~~FFFF|
979 |Bit|Y|Y|Y h|0~~FFFF|
980 |Bit|M|M|M d|0~~9999|
981 |Bit|L|L|L d|0~~9999|
982 |Bit|F|F|F d|0~~9999|
983 |Bit|B|B|B h|0~~FFFF|
984 |Bit|V|V|V d|0~~2047|
985 |Bit|TC|TC|TC d|0~~9999|
986 |Bit|SS|SS|SS d|0~~9999|
987 |Bit|SC|SC|SC d|0~~9999|
988 |Bit|CS|CS|CS d|0~~9999|
989 |Bit|CC|CC|CC d|0~~9999|
990 |Bit|SB|SB|SB h|0~~FFFF|
991 |Bit|SM|SM|SM d|0~~2047|
992 |Bit|STS|STS|STS d|0~~1023|
993 |Bit|S|S|S d|0~~9999|
994 |Bit|DX|DX|DX h|0~~FFFF|
995 |Bit|DY|DY|DY h|0~~FFFF|
996 |Bit|TS|TS|TS d|0~~9999|
997 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
998 |Word|W|W|W h|0~~FFFF|
999 |Word|TN|TN|TN d|0~~99999|
1000 |Word|SN|SN|SN d|0~~99999|
1001 |Word|CN|CN|CN d|0~~99999|
1002 |Word|R|R|R d|0~~99999|
1003 |Word|SW|SW|SW h|0~~FFFF|
1004 |Word|Z|Z|Z d|0~~99999|
1005 |Word|ZR|ZR|ZR h|0~~FFFF|
1006 |Word|D|D|D d|0~~99999|
1007
1008 **3)Communication Settings**
1009
1010 [[image:image-20220825160648-3.png]]
1011
1012 **4)Cable Wiring**
1013
1014 * **RS422**
1015
1016 [[image:image-20220825161612-8.png]]
1017
1018 [[image:image-20220825160820-4.png]]
1019
1020 == **L02 Ethernet Protocol** ==
1021
1022 Mitsubishi L series CPU built-in Ethernet port.
1023
1024 **1)V-BOX Settings**
1025
1026 |**Items**|**Settings**|**Note**
1027 |Protocol|MIT L02 CPU MELSEC|
1028 |Connection|Ethernet|
1029 |Port No.|1025|Must be the same as the PLC setting
1030 |PLC station No.|0|Must be the same as the PLC setting
1031
1032 **2)Address List**
1033
1034 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1035 |Bit|X|X|X h|0~~FFFF|
1036 |Bit|Y|Y|Y h|0~~FFFF|
1037 |Bit|M|M|M d|0~~9999|
1038 |Bit|L|L|L d|0~~9999|
1039 |Bit|F|F|F d|0~~9999|
1040 |Bit|B|B|B h|0~~FFFF|
1041 |Bit|V|V|V d|0~~2047|
1042 |Bit|TC|TC|TC d|0~~9999|
1043 |Bit|SS|SS|SS d|0~~9999|
1044 |Bit|SC|SC|SC d|0~~9999|
1045 |Bit|CS|CS|CS d|0~~9999|
1046 |Bit|CC|CC|CC d|0~~9999|
1047 |Bit|SB|SB|SB h|0~~FFFF|
1048 |Bit|SM|SM|SM d|0~~2047|
1049 |Bit|STS|STS|STS d|0~~1023|
1050 |Bit|S|S|S d|0~~9999|
1051 |Bit|DX|DX|DX h|0~~FFFF|
1052 |Bit|DY|DY|DY h|0~~FFFF|
1053 |Bit|TS|TS|TS d|0~~9999|
1054 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1055 |Word|W|W|W h|0~~FFFF|
1056 |Word|TN|TN|TN d|0~~99999|
1057 |Word|SN|SN|SN d|0~~99999|
1058 |Word|CN|CN|CN d|0~~99999|
1059 |Word|R|R|R d|0~~99999|
1060 |Word|SW|SW|SW h|0~~FFFF|
1061 |Word|Z|Z|Z d|0~~99999|
1062 |Word|ZR|ZR|ZR h|0~~FFFF|
1063 |Word|D|D|D d|0~~99999|
1064
1065 **3)PLC Settings (GX Works2 )**
1066
1067 Create a project
1068
1069 Set PLC IP, subnet mask and gateway;
1070
1071 Select [Binary Code] as communication data code;
1072
1073 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_776e17505f3fc6c0.png?width=600&height=524&rev=1.1||alt="12.PLC Protocol_html_776e17505f3fc6c0.png" height="524" width="600"]]
1074
1075 Set PLC port number, for example 1025
1076
1077 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_8d0d1a22d388f70b.png?width=600&height=524&rev=1.1||alt="12.PLC Protocol_html_8d0d1a22d388f70b.png" height="524" width="600"]]
1078
1079 Save settings;
1080
1081 Download project into PLC device;
1082
1083 Restart PLC device;
1084
1085 **4)Configure the communication protocol**
1086
1087 [[image:image-20220825142659-1.png]]
1088
1089 **5)Cable Wiring**
1090
1091 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1092
1093 == **Q12H port Protocal** ==
1094
1095 == **QJ71E71 Ethernet Protocol** ==
1096
1097 Mitsubishi QJ71E71 Ethernet communication module;
1098
1099 **1)V-BOX Settings**
1100
1101 |**Items**|**Settings**|**Note**
1102 |Protocol|MIT QJ71E71 MELSEC|
1103 |Connection|Ethernet|
1104 |Port No.|1025|Must be the same as the PLC setting
1105 |PLC station No.|0|Must be the same as the PLC setting
1106
1107 **2)Address List**
1108
1109 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1110 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1111 |Y|Y|Y h|0~~1FFF|
1112 |M|M|M d|0~~99999|
1113 |L|L|L d|0~~8191|
1114 |F|F|F d|0~~2047|
1115 |B|B|B h|0~~1FFF|
1116 |V|V|V d|0~~2047|
1117 |TS|TS|TS d|0~~2047|
1118 |TC|TC|TC d|0~~2047|
1119 |SS|SS|SS d|0~~2047|
1120 |SC|SC|SC d|0~~2047|
1121 |CS|CS|CS d|0~~1023|
1122 |CC|CC|CC d|0~~1023|
1123 |SB|SB|SB h|0~~7FF|
1124 |S|S|S d|0~~8191|
1125 |DX|DX|DX h|0~~1FFF|
1126 |DY|DY|DY h|0~~1FFF|
1127 |SM|SM|SM d|8000~~9999|
1128 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1129 |D|D|D d|0~~12287|
1130 |W|W|W h|0~~1FFF|
1131 |TN|TN|TN d|0~~2047|
1132 |SN|SN|SN d|0~~2047|
1133 |CN|CN|CN d|0~~1023|
1134 |R|R|R d|0~~32767|
1135 |SW|SW|SW h|0~~7FF|
1136 |Z|Z|Z d|0~~15|
1137 |ZR|ZR|ZR h|0~~FE7FF|
1138
1139 **3)PLC Settings(GX Works2)**
1140
1141 * Click [Ethernet/CC IE/MELSECNET];
1142 * Please select [Ethernet] as network type;
1143 * Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order);
1144 * Select [Online] as Mode;
1145 * [[image:image-20221119171343-2.png||height="341" width="587"]]
1146 * Click [Operation setting] to set IP;
1147 * Select [Binary Code] as [Communication Data Code];
1148 * [[image:image-20221119171436-3.png||height="354" width="588"]]
1149 * Click [Open setting]
1150 * Set protocol: TCP;
1151 * Set [unpassive] in [Open system];
1152 * Set [receive] in [Fixed buffer];
1153 * Set [procedure Exist] in [Fixed buffer communication];
1154 * Disable [Pairing open];
1155 * Set [No confirm] in [Existence confirmation];
1156 * Host station port number: 5009;
1157 * Save settings;
1158 * [[image:image-20221119171611-4.png||height="354" width="588"]]
1159 * Download project into PLC and restart it
1160
1161 **4)Configure the communication protocol**
1162
1163 [[image:image-20221119171832-5.png||height="354" width="625"]]
1164
1165
1166 **5)Cable Wiring**
1167
1168 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png"]]
1169
1170 = Create communication with **Delta PLC** =
1171
1172 == **DVP Ethernet Protocol** ==
1173
1174 [[下载链接>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Delta%20DVP%20Ethernet.zip]]
1175
1176 == **DVP serial protocol** ==
1177
1178 [[下载链接>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Delta%20DVP%20Ethernet.zip]]
1179
1180 == **AS Ethernet Protocol** ==
1181
1182 **1)V-BOX Settings**
1183
1184 |=**Items**|=**Settings**|=**Note**
1185 |Protocol|DELTA AS300 MODBUS TCP|
1186 |Connection|Ethernet|
1187 |Port No.|502|
1188 |Device No.|1|
1189 |HMI No.|0|
1190
1191 **2)Address List**
1192
1193 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1194 |Bit|X|X|X d|0~~63|
1195 |Bit|Y|Y|Y d|0~~63|
1196 |Bit|D|D|D d|0~~29999|
1197 |Bit|M|M|M d|0~~8191|
1198 |Bit|SM|SM|SM d|0~~4095|
1199 |Bit|S|S|S h|0~~2047|
1200 |Bit|T|T|T d|0~~511|
1201 |Bit|C|C|C d|0~~511|
1202 |Bit|HC|HC|HC d|0~~255|
1203 |Word|X|X|X h|0~~63|
1204 |Word|Y|Y|Y d|0~~63|
1205 |Word|SR|SR|SR d|0~~2047|
1206 |Word|D|D|D d|0~~29999|
1207 |Word|T|T|T d|0~~511|
1208 |Word|C|C|C h|0~~511|
1209 |Word|E|E|E d|0~~9|
1210
1211 **3)Configure the communication protocol**
1212
1213
1214 [[image:image-20220831160010-4.png]]
1215
1216 **4)Cable Wiring**
1217
1218 Figure
1219
1220 [[image:image-20220831155101-1.png]][[image:image-20220831160055-5.png]]
1221
1222 Pin Definition Diagram
1223
1224 [[image:image-20220831155157-3.png]]
1225
1226 = Create communication with **Omron PLC** =
1227
1228 == **CP1 Series Protocol ** ==
1229
1230 [[下载链接>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CP1%20Series.zip]]
1231
1232 == **CP2M Series Protocol** ==
1233
1234 [[下载链接>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CJ2M.zip]]
1235
1236
1237 == **EC55 Series Protocol** ==
1238
1239 Supported device: EC55 temperature instrument
1240
1241 **1)V-BOX Settings**
1242
1243 |**Items**|**Settings**|**Note**
1244 |Protocol|Omron EC55|
1245 |Connection|RS485 (9600, 2, 7, EVEN)|
1246 |Port No.|None|
1247 |PLC station No.|0|
1248
1249 **2)Address List**
1250
1251 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
1252 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
1253 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
1254 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
1255 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
1256 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
1257 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
1258 |CP|-|0-6|Read controller intrinsic property
1259 |CS|-|0-2|Read controller states
1260 |CA|-|0-17|Action command
1261
1262 **3)Device Settings**
1263
1264 Omron E5CC PLC configuration
1265
1266 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
1267
1268 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_3d95e093792ba98a.png?width=550&height=229&rev=1.1||alt="12.PLC Protocol_html_3d95e093792ba98a.png" height="229" width="550"]]
1269
1270 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
1271
1272 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_be583aa69dd6cf4c.png?width=550&height=242&rev=1.1||alt="12.PLC Protocol_html_be583aa69dd6cf4c.png" height="242" width="550"]]
1273
1274 **✎Note:** The communication settings for HMI should be consistent with this setting.
1275
1276 **4)Configure the communication protocol**
1277
1278 [[image:image-20220831161041-1.png]]
1279
1280 **5)Cable Wiring**
1281
1282 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5e9a81a14106da9e.png?width=392&height=223&rev=1.1||alt="12.PLC Protocol_html_5e9a81a14106da9e.png" height="223" width="392"]]
1283
1284 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_1897d92be6948d58.png?width=393&height=223&rev=1.1||alt="12.PLC Protocol_html_1897d92be6948d58.png" height="223" width="393"]]
1285
1286 **✎Note:**
1287
1288 * COM3 only available in PI8000/PI9000 series.
1289 * CA address could not support continuous writing function;
1290 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
1291 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
1292 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
1293 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
1294 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
1295 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
1296 * [[image:image-20220831161356-1.png]]Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
1297
1298 = Create communication with Xinje** PLC** =
1299
1300 == **XC serial protocol** ==
1301
1302 **1)V-BOX Settings**
1303
1304 |**Item**|**Settings**|**Note**
1305 |Protocol|XINJE XC MODBUS|
1306 |Connection|RS232|
1307 |Baud rate|19200|
1308 |Data bit|8|
1309 |Parity|EVEN|
1310 |Stop bit|1|
1311 |PLC station No.|1|
1312
1313 **2)Address List**
1314
1315 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1316 |Bit|M|M|M d|0~~8511|
1317 |Bit|X|X|X o|0~~1747|
1318 |Bit|Y|Y|Y o|0~~1747|
1319 |Bit|S|S|S d|0~~1023|
1320 |Bit|T|T|T d|0~~4095|
1321 |Bit|C|C|C d|0~~634|
1322 |Word|D|D|D d|0~~8511|
1323 |Word|TD|TD|TD d|0~~618|
1324 |Word|CD|CD|CD d|0~~634|
1325 |Word|FD|FD|FD d|0~~8511|
1326
1327 **3)Configure the communication protocol**
1328
1329
1330 [[image:image-20220831163041-1.png]]
1331
1332 **4)Cable Wiring**
1333
1334 Figure
1335
1336 [[image:image-20220831163406-2.png]][[image:image-20220831163422-3.png]]
1337
1338 Pin Definition Diagram
1339
1340 [[image:image-20220831163441-4.png]]
1341
1342 == **XD serial protocol** ==
1343
1344 **1)V-BOX Settings**
1345
1346 Supported Series: Delta Xinjie XD/XE Series PLC
1347
1348 |**Item**|**Settings**|**Note**
1349 |Protocol|XINJE XD/XC MODBUS|
1350 |Connection|RS232|
1351 |Baud rate|19200|
1352 |Data bit|8|
1353 |Parity|EVEN|
1354 |Stop bit|1|
1355 |PLC station No.|1|
1356
1357 **2)Address List**
1358
1359 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1360 |Bit|M|M|M d|0~~74999|
1361 |Bit|X1xx|X1xx|X1xx o|0~~1177|
1362 |Bit|X2xx|X2xx|X2xx o|0~~277|
1363 |Bit|X|X|X o|0~~77|
1364 |Bit|Y1xx|Y1xx|Y1xx o|0~~1177|
1365 |Bit|Y2xx|Y2xx|Y2xx o|0~~277|
1366 |Bit|Y|Y|Y o|0~~4095|
1367 |Bit|SM|SM|SM d|0~~4999|(((
1368
1369 )))
1370 |Bit|T|T|T d|0~~4999|
1371 |Bit|C|C|C d|0~~4999|
1372 |Bit|ET|ET|ET d|0~~31|
1373 |Bit|SE|SE|SE d|0~~31|
1374 |Bit|HM|HM|HM d|0~~11999|
1375 |Bit|HSC|HSC|HSC d|0~~39|
1376 |Bit|HS|HS|HS d|0~~999|
1377 |Bit|HT|HT|HT d|0~~1999|
1378 |Bit|HC|HC|HC d|0~~1999|
1379 |Bit|S|S|S d|0~~7999|
1380 |Word|D|D|D d|0~~69999|
1381 |Word|ID|ID|ID d|0~~99|
1382 |Word|ID1xx|ID1xx|ID1xx d|0~~999|
1383 |Word|ID2xx|ID2xx|ID2xx d|0~~299|
1384 |Word|QD|QD|QD d|0~~99|
1385 |Word|QD1xx|QD1xx|QD1xx d|0~~999|
1386 |Word|QD2xx|QD2xx|QD2xx d|0~~299|
1387 |Word|SD|SD|SD d|0~~4999|
1388 |Word|TD|TD|TD d|0~~575|
1389 |Word|CD|CD|CD d|0~~575|
1390 |Word|ETD|ETD|ETD d|0~~31|
1391 |Word|HD|HD|HD d|0~~24999|
1392 |Word|HSD|HSD|HSD d|0~~1023|
1393 |Word|HTD|HTD|HTD d|0~~95|
1394 |Word|HCD|HCD|HCD d|0~~95|
1395 |Word|HSCD|HSCD|HSCD d|0~~31|
1396 |Word|FD|FD|FD d|0~~8191|
1397 |Word|SFD|SFD|SFD d|0~~5999|
1398 |Word|FS|FS|FS d|0~~47|
1399
1400 **3)Configure the communication protocol**
1401
1402 [[image:image-20220831163923-7.png]]
1403
1404
1405
1406 **4)Cable Wiring**
1407
1408 Figure
1409
1410 [[image:image-20220831163406-2.png]][[image:image-20220831163553-6.png]]
1411
1412 Pin Definition Diagram
1413
1414 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830160232-3.png?rev=1.1||alt="image-20220830160232-3.png"]]
1415
1416
1417 = Create communication with **Schneider PLC** =
1418
1419 == **Schneider MODBUS RTU** ==
1420
1421 **1)V-BOX Setting**
1422
1423 |=**Parameters**|=**Recommended**|=**Notes**
1424 |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
1425 |**Connection**|RS485|
1426 |**Baud rate**|19200|
1427 |**Data bit**|8|
1428 |**Parity**|Even|
1429 |**Stop bit**|1|
1430 |**PLC station No.**|1|
1431
1432 **2)Address List**
1433
1434 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
1435 |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
1436 |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
1437 |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
1438 |W|MW|DDDDDD|0 ~~ 999999|Output register
1439 |DW|MD|DDDDDD|0 ~~ 999999|Output register
1440
1441 **3)Configure the communication protocol**
1442
1443 [[image:image-20220902104329-1.png]]
1444
1445 **4)Cable Wiring**
1446
1447 **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
1448
1449 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220817154212-1.jpeg?width=554&height=315&rev=1.1||alt="image-20220817154212-1.jpeg" height="315" width="554"]]
1450
1451 = Create communication with Inovance** PLC** =
1452
1453 == **H3U serial protocol** ==
1454
1455 **1)V-BOX Settings**
1456
1457 |**Item**|**Settings**|**Note**
1458 |Protocol|INOVANCE H3U PLC|
1459 |Connection|RS422|
1460 |Baud rate|9600|
1461 |Data bit|7|
1462 |Parity|EVEN|
1463 |Stop bit|1|
1464 |PLC station No.|0|
1465
1466 **2)Address List**
1467
1468 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1469 |Bit|X|X|X o|0~~303237|
1470 |Bit|Y|Y|Y o|0~~303237|
1471 |Bit|M|M|M d|0~~99999|
1472 |Bit|T|T|T d|0~~99999|
1473 |Bit|C|C|C d|0~~99999|
1474 |Bit|SM|SM|SM d|8000~~999|
1475 |Bit|S|T|S d|0~~99999|
1476 |Bit|Lamp|Lamp|Lamp d|0~~0|
1477 |Word|X|X|X o|0~~303237|
1478 |Word|Y|Y|Y o|0~~303237|
1479 |Word|M|M|M d|0~~99999|
1480 |Word|T|T|T d|0~~99999|
1481 |Word|C|C|C d|0~~199|
1482 |Word|D|D|D d|0~~7999|
1483 |Word|S|S|S d|0~~99999|
1484 |Word|SD|SD|SD d|8000~~9999|
1485 |Word|R|R|R d|0~~32767|
1486
1487 **3)Configure the communication protocol**
1488
1489 [[image:image-20220831164626-1.png]]
1490
1491
1492
1493 **4)Cable Wiring**
1494
1495 Figure
1496
1497 [[image:image-20220831164646-2.png]][[image:image-20220831164700-3.png]]
1498
1499 Pin Definition Diagram
1500
1501 [[image:image-20220831164731-4.png]]
1502
1503 = Create communication with Panasonic** PLC** =
1504
1505 == **FP serial protocol** ==
1506
1507 **1)V-BOX Settings**
1508
1509 |**Item**|**Settings**|**Note**
1510 |Protocol|Panasonic FP MFWTOCOL|
1511 |Connection|RS232|
1512 |Baud rate|9600|
1513 |Data bit|8|
1514 |Parity|ODD|
1515 |Stop bit|1|
1516 |PLC station No.|1|
1517
1518 **2)Address List**
1519
1520 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1521 |Bit|X|X|X d|0~~9999|
1522 |Bit|Y|Y|Y d|0~~9999|
1523 |Bit|R|R|R d|0~~9999|
1524 |Bit|T|T|T d|0~~9999|
1525 |Bit|C|C|C d|0~~9999|
1526 |Bit|L|L|L d|0~~9999|
1527 |Word|WX|WX|WX d|0~~9999|
1528 |Word|WY|WY|WY d|0~~9999|
1529 |Word|WR|WR|WR d|0~~9999|
1530 |Word|WL|WL|WL d|0~~9999|
1531 |Word|LD|LD|LD d|0~~9999|
1532 |Word|DT|DT|DT d|0~~65535|
1533 |Word|FL|FL|FL d|0~~9999|
1534 |Word|EV|EV|EV d|0~~9999|
1535 |Word|SV|SV|SV d|0~~9999|
1536
1537 **3)Configure the communication protocol**
1538
1539 [[image:image-20220831165238-4.png]]
1540
1541
1542
1543 **4)Cable Wiring**
1544
1545 Figure
1546
1547 [[image:image-20220831165031-3.png]][[image:image-20220831165017-2.png]]
1548
1549 Pin Definition Diagram
1550
1551 [[image:image-20220831165008-1.png]]
1552
1553 = Create communication with LS** PLC** =
1554
1555 == **XBC serial protocol** ==
1556
1557 **1)V-BOX Settings**
1558
1559 |**Item**|**Settings**|**Note**
1560 |Protocol|LS XBC CNet|
1561 |Connection|RS232|
1562 |Baud rate|115200|
1563 |Data bit|8|
1564 |Parity|NONE|
1565 |Stop bit|1|
1566 |PLC station No.|1|
1567
1568 **2)Address List**
1569
1570 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1571 |Bit|P|P|P d|0~~2047|
1572 |Bit|M|M|M d|0~~2047|
1573 |Bit|L|L|L d|0~~11263|
1574 |Bit|K|K|K d|0~~16183|
1575 |Bit|F|F|F d|0~~2047|
1576 |Bit|D|D|D d|0~~32767|
1577 |Bit|R|R|R d|0~~32767|
1578 |Bit|U|U|U d|0~~4095|
1579 |Word|P|P|P d|0~~2047|
1580 |Word|M|M|M d|0~~2047|
1581 |Word|L|L|L d|0~~11263|
1582 |Word|K|K|K d|0~~16183|
1583 |Word|F|F|F d|0~~2047|
1584 |Word|C|C|C d|0~~2047|
1585 |Word|T|T|T d|0~~2047|
1586 |Word|D|D|D d|0~~32767|
1587 |Word|N|N|N d|0~~21503|
1588 |Word|R|R|R d|0~~32767|
1589 |Word|U|U|U d|0~~4095|
1590 |Word|Z|Z|Z d|0~~127|
1591 |Word|S|S|S d|0~~127|
1592
1593 **3)Configure the communication protocol**
1594
1595 [[image:image-20220831170147-1.png]]
1596
1597 **4)Cable Wiring**
1598
1599 Figure
1600
1601 [[image:image-20220831170306-4.png]][[image:image-20220831170254-3.png]]
1602
1603 Pin Definition Diagram
1604
1605 [[image:image-20220831170215-2.png]]
1606
1607 == **XGK FEnet Ethernet protocol** ==
1608
1609 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
1610
1611 **1)V-BOX Settings**
1612
1613 |**Items**|**Settings**|**Note**
1614 |Protocol|LG XGK FEnet(Ethernet)|
1615 |Connection|Ethernet|
1616 |Port No.|2004|
1617
1618 **2)Address List**
1619
1620 |**Type**|**Register**|**Range**|**Format**|**Note**
1621 |(% rowspan="14" %)Word|P|0~~2047|P d|
1622 |M|0~~2047|M d|
1623 |K|0~~2047|K d|
1624 |F|0~~2047|F d|
1625 |T|0~~2047|T d|
1626 |C|0~~2047|C d|
1627 |Z|0~~127|Z d|
1628 |S|0~~127|S d|
1629 |L|0~~11263|L d|
1630 |N|0~~21503|N d|
1631 |D|0~~32767|D d|
1632 |R|0~~32767|R d|
1633 |ZR|0~~65535|ZR d|
1634 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
1635
1636 **✎Note:**
1637
1638 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
1639 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
1640 * All bit registers are in the form of bits in word, and the range is the same as the word register;
1641
1642 **3)Communication Settings**
1643
1644 [[image:image-20220831171127-1.png]]
1645
1646 **4)Cable Wiring**
1647
1648 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1649
1650 = Create communication with **Modbus ** =
1651
1652 == **MODBUS RTU Slave (All function)** ==
1653
1654 Select the protocol "Modbus RTU Slave (All Fuction)",
1655
1656 Then set baud rate, port, stop bits, data bits, parity.
1657
1658 (% style="text-align:center" %)
1659 [[image:1624342015914-382.png||height="486" width="800" class="img-thumbnail"]]
1660
1661 == **MODBUS RTU Master** ==
1662
1663 Select the protocol "Modbus RTU Master",
1664
1665 Then set baud rate, port, stop bits, data bits, parity
1666
1667 (% style="text-align:center" %)
1668 [[image:1624348709622-711.png||queryString="width=809&height=493" height="488" width="800" class="img-thumbnail"]]
1669
1670 **address list**
1671
1672 (% class="table-bordered" %)
1673 |**type**|**register**|**Function code and description**
1674 |(% rowspan="11" %)词|(% rowspan="3" %)3|04 (Read Input Registers: Read the current binary value in one or more input registers)
1675 |06 (write single register: write a binary value to a holding register)
1676 |10 (write values to multiple addresses )
1677 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1678 |06 (write single register: write a binary value to a holding register)
1679 |10 (write values to multiple addresses )
1680 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1681 |06 (write single register: write a binary value to a holding register)
1682 |10 (write values to multiple addresses )
1683 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1684 |10 (write values to multiple addresses )
1685 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1686 |05 (Force a single coil to force the on/off state of a logic coil)
1687 |0F (Write multiple bits, ie write continuously)
1688 |(% rowspan="3" %)1|02 (Read the input state)
1689 |05 (Force a single coil to force the on/off state of a logic coil)
1690 |0F (Write multiple bits)
1691 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1692 |05 (Force a single coil to force the on/off state of a logic coil)
1693 |0F (Write multiple bits)
1694 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1695 |0F (Write multiple bits)
1696
1697 == **MODBUS TCP Slave (All function)** ==
1698
1699 Supported series: MODBUS TCP controller
1700
1701 V-B0X works as MODBUS TCP MASTER connecting with TCP SLAVE
1702
1703 **1)V-BOX Setting**
1704
1705 |**Items**|**Settings**|**Note**
1706 |Protocol|MODBUS TCP Slave (All function)|
1707 |Connection|Ethernet|
1708 |Port No.|502|
1709 |PLC station No.|1
1710
1711 **2)Address List**
1712
1713 |**Type**|**Register**|**Function code & Description**
1714 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
1715 |06 (write single register: write a binary value to a holding register)
1716 |10 (write values to multiple addresses )
1717 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1718 |06 (write single register: write a binary value to a holding register)
1719 |10 (write values to multiple addresses )
1720 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1721 |06 (write single register: write a binary value to a holding register)
1722 |10 (write values to multiple addresses )
1723 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1724 |10 (write values to multiple addresses )
1725 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1726 |05 (Force a single coil to force the on/off state of a logic coil)
1727 |0F (Write multiple bits, ie write continuously)
1728 |(% rowspan="3" %)1|02 (Read the input state)
1729 |05 (Force a single coil to force the on/off state of a logic coil)
1730 |0F (Write multiple bits)
1731 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1732 |05 (Force a single coil to force the on/off state of a logic coil)
1733 |0F (Write multiple bits)
1734 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1735 |0F (Write multiple bits)
1736
1737 **3)Communication Settings**
1738
1739 Configure V-BOX Ethernet IP in Networking Settings
1740
1741 [[image:image-20220902111833-3.png]]
1742
1743
1744 Configure PLC Ethernet IP in Communication;
1745
1746 [[image:image-20220902111121-1.png]]
1747
1748 **4)Cable Wiring**
1749
1750 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1751
1752 == **communicate with VB inverter** ==
1753
1754 [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20VB%20inverter.zip]]
1755
1756 = **User define protocol** =
1757
1758 More serial port script instruction,please refer manual:[[Lua script function>>doc:V-BOX.V-Net.Manual.04 Lua Script.01 Lua Functions.WebHome]]~-~-->[[3.Serial port operation>>url:http://docs.we-con.com.cn/wiki/vbox/view/HMI/04.Lua%20script%20%20function%20and%20operation/01.Lua%20script%20function/#H3.Serialportoperation]]
1759
1760 == **Read the temperature sensor.** ==
1761
1762 the commond format is as beliow:
1763
1764 Send commond:01 03 02 00 00 03 04 73
1765
1766 Feedback commond:01 03 06 07 F7 0E 7E B7 35
1767
1768 Temperature data:07 F7,desimal = 2039,it means temperature is 20.39℃.
1769
1770 Humidity data:0E 7E,desimal = 3710, it mean humidity is 37.10%RH.
1771
1772 Script Demo:
1773
1774 ~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~--
1775
1776 function com.main()
1777 ~-~-dosomething
1778 openPlc()
1779 end
1780 function openPlc()
1781 if obj then
1782 ~-~- If the serial port opened,then read/write data by timing
1783
1784 local wri = string.pack(">HHHH",0X0103,0X0200,0X0003,0X0473)
1785 local arr = reading(wri)
1786 ~-~- if arr ~~=nil then
1787 ~-~- if arr[1] ==33 and arr[2] ==v[2][2] and arr[3] ==v[2][3] then
1788 ~-~- local A = arr[4]*256
1789 ~-~- local B = A+arr[5]
1790 ~-~- addr_setword(v[1],B)
1791 ~-~- end
1792 ~-~- end
1793
1794 else
1795 ~-~-judge if there is a serial object, then initialize and open the serial port
1796 local configs = {
1797 name = 'COM1', ~-~-Select serial port COM1
1798 mode = 485, ~-~-Communication mode RS485
1799 baud_rate = 9600, ~-~-Baud rate 9600
1800 stop_bit = 1, ~-~-stop bit 1
1801 data_len = 8, ~-~-data length 8
1802 check_bit = 'NONE', ~-~-no parity
1803
1804 }
1805 obj,err = serial.open(configs) ~-~-Open serial port
1806 if not obj then
1807 print("serial open :failed", err) ~-~- Open serial port failed
1808 end
1809 end
1810 end
1811
1812 function reading(wri)
1813 obj:flush() ~-~- Clear serial port
1814 obj:write(wri) ~-~- Write serial port
1815 print(string.byte(wri,1,#wri))
1816 obj:flush() ~-~- Clear serial port 
1817 local readed =obj:read(9,1000) ~-~- Read 9 bytes, timeout 1 second
1818 if readed and readed ~~= "" then 
1819 ~-~- judge that a non-empty string is read
1820 print(string.byte(readed,1,#readed))
1821 a={string.byte(readed, 1, #readed)}
1822 if nil ~~= a[4] and nil ~~= a[5] and nil ~~= a[6] and nil ~~= a[7] then
1823 a1=a[4]*256+a[5]
1824 a2=a[6]*256+a[7]
1825 addr_setword("@HDW0",a1)
1826 addr_setword("@HDW1",a2)
1827 end
1828 return {string.byte(readed, 1, #readed)}
1829 elseif readed == nil then
1830 print("serial read err:", err or "")
1831 return nil
1832 end
1833 return nil
1834 end
1835
1836 ~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-