Wiki source code of 1 Communication

Version 204.1 by Bob on 2023/02/02 11:19

Show last authors
1 = Create communication with WECON PLC =
2
3 == **LX3V Serial Protocol** ==
4
5 Supported series: Wecon LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
6
7 **1)V-BOX setting**
8
9 |**Item**|**Settings**|**Note**
10 |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
11 |Connection|RS422/RS485|
12 |Baud rate|9600|
13 |Data bit|7|
14 |Parity|EVEN|
15 |Stop bit|1|
16 |PLC station No.|1|
17
18 **2)Address List**
19
20
21 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
22 |(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
23 |Y|Y|Y o|0~~303237|
24 |M|M|M d|0~~99999|
25 |T|T|T d|0~~99999|
26 |C|C|C d|0~~99999|
27 |S|S|S d|0~~99999|
28 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
29 |Y|Y|Y o|0~~303237|
30 |M|M|M d|0~~99999|
31 |T|T|T d|0~~99999|
32 |C|C|C d|0~~199|
33 |D|D|D d|0~~7999|
34 |S|S|S d|0~~99999|
35 |SD|SD|SD d|8000~~9999|
36
37 **3)Configure the communication protocol**
38
39 [[image:image-20220824152217-1.png||alt="图片-20220824152217-1.png"]]
40
41 **4)Cable Wiring**
42
43 * **RS422**
44
45 [[image:image-20220824120614-5.png]]
46
47 * **RS485**
48
49 [[image:image-20220824120524-3.png]]
50
51 == **LX5V Serial Protocol** ==
52
53 This example introduces the establishment of serial port communication between V-BOX and LX5V. It is introduced through three parts: PLC software configuration, V-BOX software configuration, and hardware wiring.
54
55 **Software configuration of PLC**
56
57 **1)PLC programming software**
58
59 [[image:image-20220824142722-1.png]]
60
61 **2)New PLC project**
62
63 Click New Project and select the PLC model.
64
65 [[image:image-20220822172623-2.png]]
66
67 **3)Set Serial port parameters**
68
69 Follow the steps below to configure Serial port parameters
70
71 Baud rate:115200
72
73 Data bit:8
74
75 Stop bit:1
76
77 Parity:No verification
78
79 [[image:image-20220822172657-3.png]]
80
81 **4)Registers list**
82
83 [[image:image-20220822172730-4.png]]
84
85 **V-BOX software configuration**
86
87 **1)V-BOX programming software**
88
89 [[image:image-20220824104124-1.png]]
90
91 **2)V-NET add device**
92
93 Open V-NET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the access key, password and remark, to add the device.
94
95 [[image:image-20220824104909-2.png]]
96
97 **3)Set communication port parameters**
98
99 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
100
101 Baud rate:115200
102
103 Data bit:8
104
105 Stop bit:1
106
107 Parity:No verification
108
109 [[image:image-20220824142130-1.png]]
110
111 **hardware connection**
112
113 **1)Hardware wiring diagram**
114
115 [[image:image-20220824142546-2.png]]
116
117 [[image:image-20220824142643-3.png]]
118
119 The above are all the steps for establishing serial port communication between V-BOX with LX5V PLC.
120
121 == **LX5V-N Ethernet protocol** ==
122
123 This example introduces the establishment of Ethernet communication between V-BOX and LX5V-N. It is introduced through three parts: PLC software configuration, V-BOX software configuration, and hardware wiring.
124
125 **Software configuration of PLC**
126
127 **1)PLC programming software**
128
129 [[image:image-20220824142722-1.png]]
130
131 **2)New PLC project**
132
133 Click New Project and select the PLC model.
134
135 [[image:image-20220824143613-1.png]]
136
137 **3)Set Ethernet port parameters**
138
139 Follow the steps below to configure Ethernet parameters
140
141 PLC IP address:192.168.39.200
142
143 default gateway:192.168.39.1
144
145 subnet mask:255.255.255.0
146
147 [[image:image-20220824143744-2.png]]
148
149 **4)Registers list**
150
151 [[image:image-20220822172730-4.png]]
152
153 (% id="cke_bm_22473S" style="display:none" %)** **(%%)**V-BOX software configuration**
154
155 **1)V-BOX programming software**
156
157 [[image:image-20220824104124-1.png]]
158
159 **2)V-NET add device**
160
161 Open V-NET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the access key, password and remark, to add the device.
162
163 [[image:image-20220824104909-2.png]]
164
165 **3)Set communication Protocol**
166
167 Click Communication to configure the LX5V plc protocol and IP address.
168
169 [[image:image-20220824144619-1.png]]
170
171 **hardware connection**
172
173 **1)Hardware wiring diagram**
174
175 [[image:image-20220824151127-2.png]]
176
177 The above are all the steps for establishing ethernet communication between V-BOX with LX5V PLC.
178
179 = Create communication with **Rockwell PLC** =
180
181 == **DF1 Advanced Protocol** ==
182
183 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
184
185 **1) V-Box Settings**
186
187 |=Item|=Recommended |=Note
188 |=Protocol|Allen Bradley DF1 Advanced|
189 |=Connection|RS232|
190 |=Baud rate|19200|
191 |=Stop bits|1|
192 |=Data bits|8|
193 |=Parity|None|
194 |=PLC Station No.|1|
195 |=HMI Station No.|0|
196
197 **2) Address List**
198
199 |=**Type**|=**Device registers**|=**Format**|=**Range**|=Note
200 |(% colspan="1" rowspan="7" %)Bit|I1|I1ddd.dd|0.0~~255.15|Only able to communicate with file number I1
201 |O0|O0ddd.dd|0.0~~255.15|Only able to communicate with file number O0
202 |S2|S2ddd.dd|0.0~~255.15|Only able to communicate with file number S2
203 |B3|B3ddd.dd|0.0~~255.15|Only able to communicate with file number B3
204 |BN|BNddddd.dd|0.0~~99255.15|(((
205 Bit data file B0~~B99
206
207 First two digits is for file number
208
209 For example, BN13001.00 represents file number B13, address 001, the 0th bit.
210 )))
211 |N7|N7ddd.dd|0.0~~255.15|Only able to communicate with file number N7
212 |NN|NNddddd.dd|0.0~~99255.15|(((
213 Integer data file bit format N0~~N99
214
215 First two digits is for file number
216
217 For example, NN13001.00 represents file number N13, address 001, the 0th bit.
218 )))
219 |(% rowspan="11" %)Word|S2|S2ddd|0~~255|Only able to communicate with file number S2
220 |T4S|T4Sddd|0~~255|Only able to communicate with file number T4 (Timer Preset Value)
221 |T4P|T4Pddd|0~~255|Only able to communicate with file number T4 (Timer Accumulator Value)
222 |TNS|TNSddddd|0~~99255|(((
223 Timer Preset Value
224
225 First two digits is for file number
226
227 For example, TNS99255 represents file number T99, address 255.
228 )))
229 |TNP|TNPddddd|0~~99255|(((
230 Timer Accumulator Value
231
232 First two digits is for file number
233
234 For example, TNP99255 represents file number T99, address 255.
235 )))
236 |C5S|C5Sddd|0~~255|Only able to communicate with file number C5 (Counter Preset Value)
237 |C5P|C5Pddd|0~~255|Only able to communicate with file number C5 (Counter Accumulator Value)
238 |CNS|CNSddddd|0~~99255|(((
239 Counter Preset Value
240
241 First two digits is for file number
242
243 For example, CNS99255 represents file number C99, address 255.
244 )))
245 |CNP|CNPddddd|0~~99255|(((
246 Counter Accumulator Value
247
248 First two digits is for file number
249
250 For example, CNP99255 represents file number C99, address 255.
251 )))
252 |N7|N7ddd|0~~255|Only able to communicate with file number N7
253 |NN|NNddd|0~~99255|(((
254 Integer data file
255
256 First two digits is for file number
257
258 For example, NN99255 represents file number N99, address 255.
259 )))
260 |(% colspan="1" rowspan="3" %)Double Word|F8|F8ddd|0~~255|(((
261 Only able to communicate with file number N7
262 )))
263 |FN|FNddddd|0~~99255|(((
264 Floating point data file
265
266 First two digits is for file number
267
268 For example, FN99255 represents file number F99, address 255.
269 )))
270 |LN|LNddddd|0~~99255|Long
271
272 **3) Cable Wiring**
273
274 (% style="text-align:center" %)
275 [[image:ABRS232.gif]]
276
277 == (% id="cke_bm_5621S" style="display:none" %)** **(%%)**MicroLogix Protocol** ==
278
279 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
280
281 **1)V-BOX setting**
282
283 |**Item**|**Settings**|**Note**
284 |Protocol|Allen-Bradley DF1 Advanced|
285 |Connection|RS232|
286 |Baud rate|19200|
287 |Data bit|8|
288 |Parity|None|
289 |Stop bit|1|
290 |PLC station No.|1|
291
292 **2)Address List**
293
294 |**Type**|**Device registers**|**Format**|**Range**|**Note**
295 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
296 |O|O d.d|0.0~~255.15|
297 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
298 |S|S d.d|0.0~~255.15|
299 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
300 |(% rowspan="9" %)Word|S|S d|0~~255|
301 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
302 |TP|TP nnhh|0~~ffff
303 |CS|CS nnhh|0~~ffff
304 |CP|CP nnhh|0~~ffff
305 |N|N nnhh|0~~ffff
306 |C|C nnhh|0~~ffff
307 |T|T nnhh|0~~ffff
308 |R|R nnhh|0~~ffff
309
310 **3)Configure the communication protocol**[[image:image-20220824152928-1.png]]
311
312 **4)Configure the communication protocol**
313
314 [[image:image-20220824110724-1.png]]
315
316 == **Micro850_FreeTag Protocol** ==
317
318 (((
319 (((
320 This example introduces the establishment of Ethernet communication between Wecon V-box and CompactLogix L1769. It is introduced through three parts: PLC software configuration, V-box software configuration, and hardware wiring.
321 )))
322 )))
323
324 (((
325 (% class="wikigeneratedid" id="HSoftwareconfigurationofPLC" %)
326 (((
327 **Software configuration of PLC**
328 )))
329
330 (% class="wikigeneratedid" id="HPLCprogrammingsoftware" %)
331 (((
332 **1)PLC programming software**
333 )))
334
335 [[image:image-20220714162600-1.png]]
336
337 (% class="wikigeneratedid" id="HNewPLCproject" %)
338 (((
339 **2)New PLC project**
340 )))
341
342 (((
343 (((
344 Click New Project and select the PLC model.
345 )))
346 )))
347
348 (((
349 [[image:image-20220714162617-2.png]]
350 )))
351
352 (((
353
354
355 [[image:image-20220714162652-4.png]]
356 )))
357
358 (((
359 (% class="wikigeneratedid" id="HSetEthernetparameters" %)
360 (((
361 **3)Set Ethernet parameters**
362 )))
363
364 (((
365 (((
366 (((
367 Follow the steps below to configure Ethernet parameters
368 )))
369 )))
370 )))
371
372 (((
373 (((
374 (((
375 PLC IP address:192.168.40.101
376 )))
377 )))
378 )))
379
380 (((
381 (((
382 (((
383 default gateway:192.168.40.1
384 )))
385 )))
386 )))
387
388 (((
389 (((
390 (((
391 subnet mask:255.255.255.0
392 )))
393 )))
394 )))
395
396 (((
397 [[image:image-20220714162713-5.png]]
398 )))
399
400 (((
401
402 )))
403
404 (((
405 (% class="wikigeneratedid" id="HV-boxsoftwareconfiguration" %)
406 (((
407 **V-box software configuration**
408 )))
409
410 (% class="wikigeneratedid" id="HV-boxprogrammingsoftware" %)
411 (((
412 **1)V-box programming software**
413 )))
414
415 (% class="wikigeneratedid" %)
416 (((
417 [[image:image-20220714162725-6.png]]
418 )))
419
420 (% class="wikigeneratedid" id="HConfiguredevicenetwork" %)
421 (((
422 **2)Configure device network**
423 )))
424
425 (((
426 (((
427 (((
428 Click the Configuration Download button[[image:image-20220714115308-8.png||height="22" width="15"]], It is used to configure the device network, update the device time, obtain the device machine code, check the device network, etc.
429 )))
430
431 (((
432 In the example below, the IP address of V-Box is configured as 192.168.40.66, and the networking method is 4G connection
433 )))
434 )))
435 )))
436
437 (((
438 (((
439 [[image:image-20220714162737-7.png]]
440
441
442 )))
443 )))
444 )))
445 )))
446
447 (% class="wikigeneratedid" id="HV-netadddevice" %)
448 (((
449 **3)V-net add device**
450 )))
451 )))
452
453 (((
454 (((
455 Open VNET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the device machine code/product code, device password, and device alias to add the device.   [[image:image-20220714162752-8.png]]
456 )))
457
458
459 )))
460
461 (((
462 (% class="wikigeneratedid" id="HSetcommunicationportparameters" %)
463 (((
464 **4)Set communication port parameters**
465 )))
466
467 (((
468 In the device list on the left, find the Vbox that communicates with the L1769, click it and select configuration,communication port configuration in the main interface to add a communication protocol.
469 )))
470
471 [[image:image-20220714162805-9.png]]
472 )))
473
474 (((
475 The communication port is selected as Ethernet, the device type is selected as Allen-Bradley, the protocol is Allen-BradleyMicro850_FreeTag EthemetIP, and the IP is the internal IP address of the L1769 PLC. The port number is 44818.
476 )))
477
478 [[image:image-20220824164346-1.png]]
479
480
481 (((
482 After adding the protocol Allen-BradleyMicro850_FreeTag, click[[image:image-20220714143838-2.png]]icon add label.[[image:image-20220714162827-11.png]]
483 )))
484
485 (% class="wikigeneratedid" id="HEngineeringproduction" %)
486 (((
487 **5)Engineering production**
488 )))
489
490 (% class="wikigeneratedid" %)
491 (((
492 (((
493 According to your own needs, use the V-NET client software to edit the required data monitoring points.
494 )))
495
496 [[image:image-20220714162841-12.png]]
497
498
499 (((
500 **hardware connection**
501 )))
502 )))
503
504 (((
505 **1)Hardware wiring diagram**
506 )))
507
508 (((
509 (((
510 This example introduces Wecon V-box with Allen-Bradley L1769 PLC to establish communication through Ethernet. The connection diagram is as follows:
511 )))
512
513 [[image:image-20220714162856-13.png]]
514
515 (((
516 The above are all the steps for establishing Ethernet communication between Wecon V-box with CompactLogix L1769 PLC.
517
518
519 = **Allen-Bradley Ethernet DF1** =
520
521 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Allen-Bradley%20Ethernet%20DF1.zip]]
522
523
524 = Create communication with **Siemens PLC** =
525
526 == **S7-200 Smart Ethernet Protocol** ==
527
528 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20S7-200%20Smart.zip]]
529
530
531 == **S7-300 Ethernet Protocol** ==
532
533 Supported Series: Siemens S7-300 series PLC
534
535 **1)V-BOX setting**
536
537 |**Items**|**Settings**|**Note**
538 |Protocol|Simens S7-300 Ethernet|
539 |Connection|Ethernet|
540 |Port No.|102|
541 |PLC station No.|2|Need to be same as the PLC setting
542
543 **2)Address List**
544
545 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
546 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
547 |Q|Q|Q ddddd.o|0.0~~99999.7|
548 |M|M|M ddddd.o|0.0~~99999.7|
549 |DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
550 nn: block number;
551
552 dddd: address;
553 )))
554 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
555 |Q|QW|QW ddddd|0~~99999|
556 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
557 |MW|MW ddddd|0~~99999|(((
558 MW0=MB(0~~1)
559
560 MW2=MB(2~~3)
561
562 Address value is a multiple of 2
563 )))
564 |MD|MD ddddd|0~~99999|(((
565 MD0=MB(0~~3)
566
567 MD4=MB(4~~7)
568
569 Address value is a multiple of 4
570 )))
571 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
572 nn: block number;
573
574 dddd: address
575 )))
576 |DBxDBW|DBxDBW nndddd|0~~99999999
577 |DBxDBD|DBxDBD nndddd|0~~99999999
578
579 **3)Configure the communication protocol**
580
581 [[image:image-20220824161345-1.png]]
582
583 **4)Cable Wiring**
584
585 [[image:image-20220824161450-2.png]]
586 )))
587 )))
588
589 == **S7-1200 Ethernet Protocol** ==
590
591 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]]
592
593 == **S7-XXX Ethernet Protocol** ==
594
595 Supported Series: Siemens S7-400, S7-1200 and S7-1500
596
597 **1)V-BOX setting**
598
599 |=**Items**|=**Settings**|=**Note**
600 |Protocol|Siemens S7-XXX|
601 |Connection|Ethernet|
602 |Port No.|102|
603 |Device No.|Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|
604 |HMI No.|Rack (Default as 0)|
605
606 Slot from TIA Portal is equal to Device No. of V-net
607
608 Rack from TIA Portal is equal to HMI No. of V-net
609
610 [[image:image-20220824162459-3.png]]
611
612 [[image:image-20220824163305-2.png]]
613
614 **2)Address List**
615
616 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
617 |(% rowspan="4" %)Bit|I|I|M d.o|(((
618 d:0~-~-9999
619
620 o:0-7
621 )))|
622 |Q|Q|Q d.o|(((
623 d:0~-~-9999
624
625 o:0-7
626 )))|
627 |M|M|M d.o|(((
628 d:0~-~-9999
629
630 o:0-7
631 )))|
632 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
633 nn:0-9999,
634
635 dddd:0-9999,
636
637 o:0-7
638 )))|(((
639 nn:DB No.
640
641 dddd:address value
642
643 o: digit address
644 )))
645 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
646 |M|MW|MW d|d:0-99999|(((
647 MW0=MB(0~~1)
648
649 MW2=MB(2~~3)
650
651 Address value is a multiple of 2
652 )))
653 |M|MD|MD d|d:0-99999|(((
654 MD0=MB(0~~3)
655
656 MD4=MB(4~~7)
657
658 Address value is a multiple of 4
659 )))
660 |I|IW|IW d|d:0-99999|
661 |Q|QW|QW d|d:0-99999|
662 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
663 nn:0-9999
664
665 dddd:0-9999
666 )))|(((
667 nn:DB No.
668
669 dddd:address value
670 )))
671 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
672 nn:0-9999
673
674 dddd:0-9999
675 )))|(((
676 nn:DB No.
677
678 dddd:address value
679
680 Address value is a multiple of 2
681 )))
682 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
683 nn:0-9999
684
685 dddd:0-9999
686 )))|(((
687 nn:DB No.
688
689 dddd:address value
690
691 Address value is a multiple of 4
692 )))
693
694 **3)Configure the communication protocol**
695
696 [[image:image-20220824163448-3.png]]
697
698 **✎Note:**
699
700 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three V-BOX.
701 * V-BOX access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
702
703 **4)Cable Wiring**
704
705 [[image:image-20220824162342-2.png]]
706
707 == **LOGO Ethernet Protocol** ==
708
709 = Create communication with **Mitsubishi PLC** =
710
711 == **FX1S,1N,2N Serial Protocol** ==
712
713 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
714
715 **1)V-BOX Settings**
716
717 |**Item**|**Settings**|**Note**
718 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
719 |Connection|RS422/RS485/RS232|
720 |Baud rate|9600~~115200|
721 |Data bit|7/8|
722 |Parity|EVEN/Odd/None|
723 |Stop bit|1/2|
724 |PLC station No.|1~~255|
725
726 **2)Address List**
727
728 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
729 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
730 |Y|Y|Y o|0~~303237|
731 |M|M|M d|0~~99999|
732 |T|T|T d|0~~99999|
733 |C|C|C d|0~~99999|
734 |S|S|S d|0~~99999|
735 |SM|SM|SM d|8000~~9999|
736 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
737 |Y|Y|Y o|0~~303237|
738 |M|M|M d|0~~99999|
739 |T|T|T d|0~~99999|
740 |C|C|C d|0~~199|
741 |D|D|D d|0~~7999|
742 |S|S|S d|0~~99999|
743 |SD|SD|SD d|8000~~9999|
744
745 **3)Configure the communication protocol**
746
747 [[image:image-20220825102844-3.png]]
748
749 **4)Cable Wiring**
750
751 * **RS422**
752
753 [[image:image-20220825103350-4.png]]
754
755 [[image:image-20220825100845-4.png]]
756
757
758 == **FX3U,3G,3GA Serial Protocol** ==
759
760 Supported Series: Mitsubishi FX3U, FX3G, FX3GA series
761
762 **1)V-BOX Settings**
763
764 |**Item**|**Settings**|**Note**
765 |Protocol|Mitsubishi FX3U/3G/3GA|
766 |Connection|RS422/RS485/RS232|
767 |Baud rate|9600~~115200|
768 |Data bit|7/8|
769 |Parity|EVEN/Odd/None|
770 |Stop bit|1/2|
771 |PLC station No.|1~~255|
772
773 **2)Address List**
774
775 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
776 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
777 |Y|Y|Y o|0~~303237|
778 |M|M|M d|0~~99999|
779 |T|T|T d|0~~99999|
780 |C|C|C d|0~~99999|
781 |S|S|S d|0~~99999|
782 |SM|SM|SM d|8000~~9999|
783 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
784 |Y|Y|Y o|0~~303237|
785 |M|M|M d|0~~99999|
786 |T|T|T d|0~~99999|
787 |C|C|C d|0~~199|
788 |D|D|D d|0~~7999|
789 |S|S|S d|0~~99999|
790 |SD|SD|SD d|8000~~9999|
791
792 **3)Configure the communication protocol**
793
794 [[image:image-20220825102649-2.png]]
795
796 **4)Cable Wiring**
797
798 * **RS422**
799
800 [[image:image-20220825103421-5.png]]
801
802 [[image:image-20220825100845-4.png]]
803
804
805 == **FX3U Ethernet Protocol** ==
806
807 Supported Modules: FX3U-ENET-ADP, FX3U-ENET-L
808
809 **1)V-BOX Settings**
810
811 |Items|Settings|Note
812 |Protocol|Mitsubishi FX3U|
813 |Connection|Ethernet|
814 |Port No.|5009|Must be the same as the PLC setting
815 |PLC station No.|0|
816
817 **2)Address List**
818
819 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
820 |(% colspan="1" rowspan="7" %)Bit|X|X|X OOO|0~~377|
821 |Y|Y|Y OOO|0~~377|
822 |M|M|M DDDD|0~~7679|
823 |SM|SM|SM DDDD|8000~~8511|
824 |S|S|S DDDD|0~~4095|
825 |TS|TS|TS DDD|0~~511|
826 |CS|CS|CS DDD|0~~255|
827 |(% colspan="1" rowspan="9" %)Word|CN|CN|CN DDD|0~~199|
828 |TN|TN|TN DDD|0~~511|
829 |D|D|D DDDD|0~~7999|
830 |SD|SD|SD DDDD|8000~~8511|
831 |R|R|R DDDDD|0~~32767|
832
833 **3)Ethernet Module Settings**
834
835 FX3U-ENET-L module configuration
836 Set up the FX3U-ENET-L Ethernet module settings as follows.
837 Select the module location, which in this document is Module 0.
838
839 [[image:image-20221116105850-1.png]]
840
841 Select "Operational setting" to enter the following screen.
842
843 The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default.
844
845 [[image:image-20221116105947-1.png]]
846
847 Select "Open setting" to enter the setting interface, the settings are as follows.
848
849 The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the
850
851 Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module.
852
853 [[image:image-20221116110802-1.png]]
854
855 Click on "transter setup" - "PC side I/F setting", see the following figure.
856
857 After setting, the first download must use the programming cable, as shown in the figure; after that, can
858
859 use the IP set in the "Ethernet board" to communicate directly with the network cable.
860
861 [[image:image-20221116110832-2.png||height="423" width="708"]]
862
863 Read and write data from the Ethernet module
864
865 [[image:image-20221116110907-3.png]]
866
867 Set "Transter setup" to COM communication, and read or write operation as shown below
868
869 [[image:image-20221116110917-4.png]]
870
871 **4)PLC Settings (GX Works 2)**
872
873 Create a blank FX5U project
874
875 Find Current Connection in the navigation
876
877 [[image:image-20221116111427-1.png||height="421" width="705"]]
878
879 Select Connection Channel List
880
881 Select Ethernet board communication
882
883 [[image:image-20221116111451-2.png||height="421" width="705"]]
884
885 Select Ethernet Module
886 Set the IP address of the PLC
887
888 [[image:image-20221116111509-3.png||height="666" width="699"]]
889
890 Read or write PLC data, in this document is read
891
892 [[image:image-20221116111651-4.png||height="416" width="697"]]
893
894 [[image:image-20221116111727-5.png||height="416" width="697"]]
895
896 **4)Configure the communication protocol**
897
898 [[image:image-20221119101946-2.png||height="395" width="695"]]
899
900 == **FX5U Serial Protocol** ==
901
902 Mitsubishi FX5U series PLC
903
904 **1)V-BOX Settings**
905
906 |**Item**|**Settings**|**Note**
907 |Protocol|Mitsubishi FX5U|
908 |Connection|RS422/RS485|
909 |Baud rate|9600|
910 |Data bit|7|
911 |Parity|Odd|
912 |Stop bit|1|
913 |PLC station No.|1~~255|Need to be the same as PLC settings
914
915 **2)Address List**
916
917 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
918 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
919 |Y|Y|Y o|0~~303237|
920 |M|M|M d|0~~99999|
921 |B|B|B h|0~~7FFF|
922 |F|F|F d|0~~32767|
923 |SB|SB|SB h|0~~7FFF|
924 |TS|TS|TS d|0~~1023|
925 |TC|TC|TC d|0~~1023|
926 |STS|STS|STS d|0~~1023|
927 |STC|STC|STS d|0~~1023|
928 |CS|CS|CS d|0~~1023|
929 |CC|CC|CC d|0~~1023|
930 |SM|SM|SM d|0~~9999|
931 |L|L|L d|0~~32767|
932 |S|S|S d|0~~4095|
933 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
934 |TN|TN|TN d|0~~1023|
935 |STN|STN|STN d|0~~1023|
936 |CN|CN|CN d|0~~1023|
937 |R|R|R d|0~~32767|
938 |SW|SW|SW h|0~~7FFF|
939 |Z|Z|Z d|0~~23|
940 |D|D|D d|0~~7999|
941 |SD|SD|SD d|0~~11999|
942
943 **3)PLC Settings (GX Works 3)**
944
945 Create a blank FX5U project
946
947 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
948
949 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5c9cb13fac1e6c93.png?width=200&height=462&rev=1.1||alt="12.PLC Protocol_html_5c9cb13fac1e6c93.png" height="462" width="200"]]
950
951 Select protocol in the setting item, and set parameters.
952
953 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_de942589ca070228.png?width=600&height=324&rev=1.1||alt="12.PLC Protocol_html_de942589ca070228.png" height="324" width="600"]]
954
955 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
956
957 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_387ec7d00b5feb59.png?width=600&height=323&rev=1.1||alt="12.PLC Protocol_html_387ec7d00b5feb59.png" height="323" width="600"]]
958
959 Click the [Apply] button to finish the setting.
960
961 Click download and select the items as below, then click [execute] to download the configuration to PLC.
962
963 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_cdef1c5ec8cc2105.png?width=600&height=434&rev=1.1||alt="12.PLC Protocol_html_cdef1c5ec8cc2105.png" height="434" width="600"]]
964
965 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
966
967 Done.
968
969 **4)Configure the communication protocol**
970
971 [[image:image-20220825104904-1.png]]
972
973 **5)Cable Wiring**
974
975
976 * **RS422**
977
978 [[image:image-20220825105105-2.png]]
979
980 [[image:image-20220825105533-3.png]]
981
982 == **FX5U Ethernet Protocol** ==
983
984 Mitsubishi FX5U series PLC
985
986 **1)V-BOX Settings**
987
988 |**Items**|**Settings**|**Note**
989 |Protocol|Mitsubishi FX5U|
990 |Connection|Ethernet|
991 |Port No.|5002|Must be the same as the PLC setting
992 |PLC station No.|0|
993
994 **2)Address List**
995
996 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
997 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
998 |Y|Y|Y o|0~~303237|
999 |M|M|M d|0~~99999|
1000 |B|B|B h|0~~7FFF|
1001 |F|F|F d|0~~32767|
1002 |SB|SB|SB h|0~~7FFF|
1003 |TS|TS|TS d|0~~1023|
1004 |TC|TC|TC d|0~~1023|
1005 |STS|STS|STS d|0~~1023|
1006 |STC|STC|STS d|0~~1023|
1007 |CS|CS|CS d|0~~1023|
1008 |CC|CC|CC d|0~~1023|
1009 |SM|SM|SM d|0~~9999|
1010 |L|L|L d|0~~32767|
1011 |S|S|S d|0~~4095|
1012 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1013 |TN|TN|TN d|0~~1023|
1014 |STN|STN|STN d|0~~1023|
1015 |CN|CN|CN d|0~~1023|
1016 |R|R|R d|0~~32767|
1017 |SW|SW|SW h|0~~7FFF|
1018 |Z|Z|Z d|0~~23|
1019 |D|D|D d|0~~7999|
1020 |SD|SD|SD d|0~~11999|
1021
1022 **3)PLC Settings (GX Works 3)**
1023
1024 Find the [Ethernet port] in the navigation area.
1025
1026 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_8e8f85ace087346c.png?width=300&height=593&rev=1.1||alt="12.PLC Protocol_html_8e8f85ace087346c.png" height="593" width="300"]]
1027
1028 Select [Own Node Settings] in the [Setting Item List];
1029
1030 Set [IP Address], [Subnet Mask], [Default Gateway];
1031
1032 Click [Detailed Settings] into [Ethernet Configuration (Built-in Ethernet Port)] windows;
1033
1034 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5d98495052c8c10e.png?width=600&height=339&rev=1.1||alt="12.PLC Protocol_html_5d98495052c8c10e.png" height="339" width="600"]]
1035
1036 Select [SLMP Connection Module] and add into host station as below picture shows;
1037
1038 Set Port number as 5002 (this is necessary settings);
1039
1040 Click [Close with Reflecting the Setting] to save and close window;
1041
1042 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_14b489fdc6c6589d.png?width=600&height=350&rev=1.1||alt="12.PLC Protocol_html_14b489fdc6c6589d.png" height="350" width="600"]]
1043
1044 Click [Apply] to completed Etherenet settings;
1045
1046 Switch to the [On line data operation] interface as below, check the item and click [Execute] to download.
1047
1048 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_c93025a968a8a9e7.png?width=600&height=434&rev=1.1||alt="12.PLC Protocol_html_c93025a968a8a9e7.png" height="434" width="600"]]
1049
1050 **4)Configure the communication protocol**
1051
1052 [[image:image-20220825112403-1.png||alt="图片-20220825112403-1.png"]]
1053
1054 **5)Cable Wiring**
1055
1056 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1057
1058 == **L02 Serial Protocol** ==
1059
1060 Mitsubishi L02 series CPU built-in serial port.
1061
1062 **1)V-BOX Settings**
1063
1064 |**Item**|**Settings**|**Note**
1065 |Protocol|Mitsubishi L02|
1066 |Connection|RS422|
1067 |Baud rate|115200|
1068 |Data bit|8|
1069 |Parity|Odd|
1070 |Stop bit|1|
1071 |PLC station No.|1~~255|Need to be the same as PLC settings
1072
1073 **2)Address List**
1074
1075 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1076 |Bit|X|X|X h|0~~FFFF|
1077 |Bit|Y|Y|Y h|0~~FFFF|
1078 |Bit|M|M|M d|0~~9999|
1079 |Bit|L|L|L d|0~~9999|
1080 |Bit|F|F|F d|0~~9999|
1081 |Bit|B|B|B h|0~~FFFF|
1082 |Bit|V|V|V d|0~~2047|
1083 |Bit|TC|TC|TC d|0~~9999|
1084 |Bit|SS|SS|SS d|0~~9999|
1085 |Bit|SC|SC|SC d|0~~9999|
1086 |Bit|CS|CS|CS d|0~~9999|
1087 |Bit|CC|CC|CC d|0~~9999|
1088 |Bit|SB|SB|SB h|0~~FFFF|
1089 |Bit|SM|SM|SM d|0~~2047|
1090 |Bit|STS|STS|STS d|0~~1023|
1091 |Bit|S|S|S d|0~~9999|
1092 |Bit|DX|DX|DX h|0~~FFFF|
1093 |Bit|DY|DY|DY h|0~~FFFF|
1094 |Bit|TS|TS|TS d|0~~9999|
1095 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1096 |Word|W|W|W h|0~~FFFF|
1097 |Word|TN|TN|TN d|0~~99999|
1098 |Word|SN|SN|SN d|0~~99999|
1099 |Word|CN|CN|CN d|0~~99999|
1100 |Word|R|R|R d|0~~99999|
1101 |Word|SW|SW|SW h|0~~FFFF|
1102 |Word|Z|Z|Z d|0~~99999|
1103 |Word|ZR|ZR|ZR h|0~~FFFF|
1104 |Word|D|D|D d|0~~99999|
1105
1106 **3)Communication Settings**
1107
1108 [[image:image-20220825160648-3.png]]
1109
1110 **4)Cable Wiring**
1111
1112 * **RS422**
1113
1114 [[image:image-20220825161612-8.png]]
1115
1116 [[image:image-20220825160820-4.png]]
1117
1118 == **L02 Ethernet Protocol** ==
1119
1120 Mitsubishi L series CPU built-in Ethernet port.
1121
1122 **1)V-BOX Settings**
1123
1124 |**Items**|**Settings**|**Note**
1125 |Protocol|MIT L02 CPU MELSEC|
1126 |Connection|Ethernet|
1127 |Port No.|1025|Must be the same as the PLC setting
1128 |PLC station No.|0|Must be the same as the PLC setting
1129
1130 **2)Address List**
1131
1132 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1133 |Bit|X|X|X h|0~~FFFF|
1134 |Bit|Y|Y|Y h|0~~FFFF|
1135 |Bit|M|M|M d|0~~9999|
1136 |Bit|L|L|L d|0~~9999|
1137 |Bit|F|F|F d|0~~9999|
1138 |Bit|B|B|B h|0~~FFFF|
1139 |Bit|V|V|V d|0~~2047|
1140 |Bit|TC|TC|TC d|0~~9999|
1141 |Bit|SS|SS|SS d|0~~9999|
1142 |Bit|SC|SC|SC d|0~~9999|
1143 |Bit|CS|CS|CS d|0~~9999|
1144 |Bit|CC|CC|CC d|0~~9999|
1145 |Bit|SB|SB|SB h|0~~FFFF|
1146 |Bit|SM|SM|SM d|0~~2047|
1147 |Bit|STS|STS|STS d|0~~1023|
1148 |Bit|S|S|S d|0~~9999|
1149 |Bit|DX|DX|DX h|0~~FFFF|
1150 |Bit|DY|DY|DY h|0~~FFFF|
1151 |Bit|TS|TS|TS d|0~~9999|
1152 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1153 |Word|W|W|W h|0~~FFFF|
1154 |Word|TN|TN|TN d|0~~99999|
1155 |Word|SN|SN|SN d|0~~99999|
1156 |Word|CN|CN|CN d|0~~99999|
1157 |Word|R|R|R d|0~~99999|
1158 |Word|SW|SW|SW h|0~~FFFF|
1159 |Word|Z|Z|Z d|0~~99999|
1160 |Word|ZR|ZR|ZR h|0~~FFFF|
1161 |Word|D|D|D d|0~~99999|
1162
1163 **3)PLC Settings (GX Works2 )**
1164
1165 Create a project
1166
1167 Set PLC IP, subnet mask and gateway;
1168
1169 Select [Binary Code] as communication data code;
1170
1171 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_776e17505f3fc6c0.png?width=600&height=524&rev=1.1||alt="12.PLC Protocol_html_776e17505f3fc6c0.png" height="524" width="600"]]
1172
1173 Set PLC port number, for example 1025
1174
1175 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_8d0d1a22d388f70b.png?width=600&height=524&rev=1.1||alt="12.PLC Protocol_html_8d0d1a22d388f70b.png" height="524" width="600"]]
1176
1177 Save settings;
1178
1179 Download project into PLC device;
1180
1181 Restart PLC device;
1182
1183 **4)Configure the communication protocol**
1184
1185 [[image:image-20220825142659-1.png]]
1186
1187 **5)Cable Wiring**
1188
1189 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1190
1191 == **Q12H Serial Protocol** ==
1192
1193 This Demo shows V-BOX communicate with Q12H PLC by Q02H serial Protocol
1194
1195 [[**Download link**>>https://ftp.we-con.com.cn/Download/WIKI/PI%20HMI/Demo/Communication/V-Box%20connect%20PLC%20Q12H.rar]]
1196
1197 == **QJ71E71 Ethernet Protocol** ==
1198
1199 Mitsubishi QJ71E71 Ethernet communication module;
1200
1201 **1)V-BOX Settings**
1202
1203 |**Items**|**Settings**|**Note**
1204 |Protocol|MIT QJ71E71 MELSEC|
1205 |Connection|Ethernet|
1206 |Port No.|1025|Must be the same as the PLC setting
1207 |PLC station No.|0|Must be the same as the PLC setting
1208
1209 **2)Address List**
1210
1211 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1212 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1213 |Y|Y|Y h|0~~1FFF|
1214 |M|M|M d|0~~99999|
1215 |L|L|L d|0~~8191|
1216 |F|F|F d|0~~2047|
1217 |B|B|B h|0~~1FFF|
1218 |V|V|V d|0~~2047|
1219 |TS|TS|TS d|0~~2047|
1220 |TC|TC|TC d|0~~2047|
1221 |SS|SS|SS d|0~~2047|
1222 |SC|SC|SC d|0~~2047|
1223 |CS|CS|CS d|0~~1023|
1224 |CC|CC|CC d|0~~1023|
1225 |SB|SB|SB h|0~~7FF|
1226 |S|S|S d|0~~8191|
1227 |DX|DX|DX h|0~~1FFF|
1228 |DY|DY|DY h|0~~1FFF|
1229 |SM|SM|SM d|8000~~9999|
1230 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1231 |D|D|D d|0~~12287|
1232 |W|W|W h|0~~1FFF|
1233 |TN|TN|TN d|0~~2047|
1234 |SN|SN|SN d|0~~2047|
1235 |CN|CN|CN d|0~~1023|
1236 |R|R|R d|0~~32767|
1237 |SW|SW|SW h|0~~7FF|
1238 |Z|Z|Z d|0~~15|
1239 |ZR|ZR|ZR h|0~~FE7FF|
1240
1241 **3)PLC Settings(GX Works2)**
1242
1243 * Click [Ethernet/CC IE/MELSECNET];
1244 * Please select [Ethernet] as network type;
1245 * Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order);
1246 * Select [Online] as Mode;
1247 * [[image:image-20221119171343-2.png||height="341" width="587"]]
1248 * Click [Operation setting] to set IP;
1249 * Select [Binary Code] as [Communication Data Code];
1250 * [[image:image-20221119171436-3.png||height="354" width="588"]]
1251 * Click [Open setting]
1252 * Set protocol: TCP;
1253 * Set [unpassive] in [Open system];
1254 * Set [receive] in [Fixed buffer];
1255 * Set [procedure Exist] in [Fixed buffer communication];
1256 * Disable [Pairing open];
1257 * Set [No confirm] in [Existence confirmation];
1258 * Host station port number: 5009;
1259 * Save settings;
1260 * [[image:image-20221119171611-4.png||height="354" width="588"]]
1261 * Download project into PLC and restart it
1262
1263 **4)Configure the communication protocol**
1264
1265 [[image:image-20221119171832-5.png||height="354" width="625"]]
1266
1267
1268 **5)Cable Wiring**
1269
1270 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png"]]
1271
1272 = Create communication with **Delta PLC** =
1273
1274 == **DVP Ethernet Protocol** ==
1275
1276 Supoort Series: DELTA DVP20/32/40/60ES200RE/200TE or any DVP models with built-in Ethernet port, DELTA DVPEN01-SL module
1277
1278 **1)V-BOX Settings**
1279
1280 |=**Items**|=**Settings**|=**Note**
1281 |Protocol|DELTA DVP MODBUS TCP|
1282 |Connection|Ethernet|
1283 |Port No.|502|
1284 |Device No.|1|
1285 |VBox Device No.|0|
1286
1287 **2)Address List **
1288
1289 |=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 217px;" %)**VBox registers**|=(% style="width: 168px;" %)**Format**|=(% style="width: 225px;" %)**Range**|=**Note**
1290 |Bit|(% style="width:191px" %)X|(% style="width:217px" %)X|(% style="width:168px" %)X OOO|(% style="width:225px" %)0~~377|
1291 |Bit|(% style="width:191px" %)Y|(% style="width:217px" %)Y|(% style="width:168px" %)Y OOO|(% style="width:225px" %)0~~377|
1292 |Bit|(% style="width:191px" %)M0|(% style="width:217px" %)M0|(% style="width:168px" %)M0DDDD|(% style="width:225px" %)0~~1535|
1293 |Bit|(% style="width:191px" %)M1|(% style="width:217px" %)M1|(% style="width:168px" %)M1DDDD|(% style="width:225px" %)1536~~4096|
1294 |Bit|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDD|(% style="width:225px" %)0~~255|
1295 |Bit|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~255|
1296 |Bit|(% style="width:191px" %)S|(% style="width:217px" %)S|(% style="width:168px" %)SDDDD|(% style="width:225px" %)0~~1023|
1297 |Word|(% style="width:191px" %)D0|(% style="width:217px" %)D0|(% style="width:168px" %)D0DDDD|(% style="width:225px" %)0~~4095|
1298 |Word|(% style="width:191px" %)D1|(% style="width:217px" %)D1|(% style="width:168px" %)D1DDDD|(% style="width:225px" %)4096~~11999|
1299 |Word|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDD|(% style="width:225px" %)0~~255|
1300 |Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~199|
1301 |Double Word|(% style="width:191px" %)HC|(% style="width:217px" %)HC|(% style="width:168px" %)HCDDD|(% style="width:225px" %)200~~255|
1302
1303 **3) PLC Setting:**
1304
1305 ~1. Create new project in Delta WPL Soft, and click Setting to open the communication settings:
1306
1307 (% style="text-align:center" %)
1308 [[image:DVPEthernetWPLSoft2.png]]
1309
1310 2. Set up the communication type and PLC IP:
1311
1312 (% style="text-align:center" %)
1313 [[image:DVPEthernetSetup.png]]
1314
1315 (% class="wikigeneratedid" %)
1316 3. Click OK and save the settings. Then click Communication on toolbar, then click Transfer Setup to open new window:
1317
1318 (% style="text-align:center" %)
1319 [[image:DVPEthernetTransfer.png]]
1320
1321 (% class="wikigeneratedid" %)
1322 4. Select Communication Mode as PC => PLC to download or select PC <=PLC to upload:
1323
1324 (% style="text-align:center" %)
1325 [[image:DVPEthernetPLCtoPC.png]]
1326
1327 5. Click Auto-Search Ethernet Module to find the PLC on the same LAN network:
1328
1329 (% style="text-align:center" %)
1330 [[image:DVPEthernetAutoSearch.png]]
1331
1332 **4) V-BOX Setting:**
1333
1334 Set the same IP address according to the setting from WPL Soft:
1335
1336 (% style="text-align:center" %)
1337 [[image:DVPEthernetVNETPortocol.png]]
1338
1339 == **DVP serial protocol** ==
1340
1341 Supoort Series: DELTA DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX
1342
1343 **1)V-BOX Settings**
1344
1345 |=**Items**|=**Settings**|=**Note**
1346 |Protocol|DELTA DVP PROTOCOL|
1347 |Connection|RS232|
1348 |Baud Rate|9600|
1349 |Stop Bit|1|
1350 |Data Bit|7|
1351 |Parity|EVEN|
1352 |Device No.|1|
1353
1354 (% class="wikigeneratedid" %)
1355 **2)Address List**
1356
1357 |=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 217px;" %)**VBox registers**|=(% style="width: 168px;" %)**Format**|=(% style="width: 225px;" %)**Range**|=**Note**
1358 |Bit|(% style="width:191px" %)X|(% style="width:217px" %)X|(% style="width:168px" %)X OOOOOO|(% style="width:225px" %)0~~303237|
1359 |Bit|(% style="width:191px" %)Y|(% style="width:217px" %)Y|(% style="width:168px" %)Y OOOOOO|(% style="width:225px" %)0~~303237|
1360 |Bit|(% style="width:191px" %)M|(% style="width:217px" %)M|(% style="width:168px" %)MDDDDD|(% style="width:225px" %)0~~99999|
1361 |Bit|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDDDD|(% style="width:225px" %)0~~99999|
1362 |Bit|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDDDD|(% style="width:225px" %)0~~99999|
1363 |Bit|(% style="width:191px" %)S|(% style="width:217px" %)S|(% style="width:168px" %)SDDDDD|(% style="width:225px" %)0~~99999|
1364 |Word|(% style="width:191px" %)D|(% style="width:217px" %)D|(% style="width:168px" %)D DDDDD|(% style="width:225px" %)0~~99999|
1365 |Word|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDDDD|(% style="width:225px" %)0~~99999|
1366 |Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~199|
1367 |Double Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDDDD|(% style="width:225px" %)200~~99999|
1368
1369 (% class="wikigeneratedid" %)
1370 **3)Wiring Diagram**
1371
1372 (% style="text-align:center" %)
1373 [[image:Delta DVP PROTOCOLSerial232.png]]
1374
1375 == **AS Ethernet Protocol** ==
1376
1377 **1)V-BOX Settings**
1378
1379 |=**Items**|=**Settings**|=**Note**
1380 |Protocol|DELTA AS300 MODBUS TCP|
1381 |Connection|Ethernet|
1382 |Port No.|502|
1383 |Device No.|1|
1384 |HMI No.|0|
1385
1386 **2)Address List**
1387
1388 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1389 |Bit|X|X|X d|0~~63|
1390 |Bit|Y|Y|Y d|0~~63|
1391 |Bit|D|D|D d|0~~29999|
1392 |Bit|M|M|M d|0~~8191|
1393 |Bit|SM|SM|SM d|0~~4095|
1394 |Bit|S|S|S h|0~~2047|
1395 |Bit|T|T|T d|0~~511|
1396 |Bit|C|C|C d|0~~511|
1397 |Bit|HC|HC|HC d|0~~255|
1398 |Word|X|X|X h|0~~63|
1399 |Word|Y|Y|Y d|0~~63|
1400 |Word|SR|SR|SR d|0~~2047|
1401 |Word|D|D|D d|0~~29999|
1402 |Word|T|T|T d|0~~511|
1403 |Word|C|C|C h|0~~511|
1404 |Word|E|E|E d|0~~9|
1405
1406 **3)Configure the communication protocol**
1407
1408 [[image:image-20220831160010-4.png]]
1409
1410 **4)Cable Wiring**
1411
1412 Figure
1413
1414 [[image:image-20220831155101-1.png]][[image:image-20220831160055-5.png]]
1415
1416 Pin Definition Diagram
1417
1418 [[image:image-20220831155157-3.png]]
1419
1420 = Create communication with **Omron PLC** =
1421
1422 == **CP1 Series Protocol ** ==
1423
1424 [[下载链接>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CP1%20Series.zip]]
1425
1426 == **CP2M Series Protocol** ==
1427
1428 [[下载链接>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CJ2M.zip]]
1429
1430
1431 == **EC55 Series Protocol** ==
1432
1433 Supported device: EC55 temperature instrument
1434
1435 **1)V-BOX Settings**
1436
1437 |**Items**|**Settings**|**Note**
1438 |Protocol|Omron EC55|
1439 |Connection|RS485 (9600, 2, 7, EVEN)|
1440 |Port No.|None|
1441 |PLC station No.|0|
1442
1443 **2)Address List**
1444
1445 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
1446 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
1447 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
1448 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
1449 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
1450 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
1451 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
1452 |CP|-|0-6|Read controller intrinsic property
1453 |CS|-|0-2|Read controller states
1454 |CA|-|0-17|Action command
1455
1456 **3)Device Settings**
1457
1458 Omron E5CC PLC configuration
1459
1460 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
1461
1462 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_3d95e093792ba98a.png?width=550&height=229&rev=1.1||alt="12.PLC Protocol_html_3d95e093792ba98a.png" height="229" width="550"]]
1463
1464 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
1465
1466 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_be583aa69dd6cf4c.png?width=550&height=242&rev=1.1||alt="12.PLC Protocol_html_be583aa69dd6cf4c.png" height="242" width="550"]]
1467
1468 **✎Note:** The communication settings for HMI should be consistent with this setting.
1469
1470 **4)Configure the communication protocol**
1471
1472 [[image:image-20220831161041-1.png]]
1473
1474 **5)Cable Wiring**
1475
1476 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5e9a81a14106da9e.png?width=392&height=223&rev=1.1||alt="12.PLC Protocol_html_5e9a81a14106da9e.png" height="223" width="392"]]
1477
1478 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_1897d92be6948d58.png?width=393&height=223&rev=1.1||alt="12.PLC Protocol_html_1897d92be6948d58.png" height="223" width="393"]]
1479
1480 **✎Note:**
1481
1482 * COM3 only available in PI8000/PI9000 series.
1483 * CA address could not support continuous writing function;
1484 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
1485 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
1486 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
1487 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
1488 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
1489 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
1490 * [[image:image-20220831161356-1.png]]Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
1491
1492 = Create communication with Xinje** PLC** =
1493
1494 == **XC serial protocol** ==
1495
1496 **1)V-BOX Settings**
1497
1498 |**Item**|**Settings**|**Note**
1499 |Protocol|XINJE XC MODBUS|
1500 |Connection|RS232|
1501 |Baud rate|19200|
1502 |Data bit|8|
1503 |Parity|EVEN|
1504 |Stop bit|1|
1505 |PLC station No.|1|
1506
1507 **2)Address List**
1508
1509 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1510 |Bit|M|M|M d|0~~8511|
1511 |Bit|X|X|X o|0~~1747|
1512 |Bit|Y|Y|Y o|0~~1747|
1513 |Bit|S|S|S d|0~~1023|
1514 |Bit|T|T|T d|0~~4095|
1515 |Bit|C|C|C d|0~~634|
1516 |Word|D|D|D d|0~~8511|
1517 |Word|TD|TD|TD d|0~~618|
1518 |Word|CD|CD|CD d|0~~634|
1519 |Word|FD|FD|FD d|0~~8511|
1520
1521 **3)Configure the communication protocol**
1522
1523
1524 [[image:image-20220831163041-1.png]]
1525
1526 **4)Cable Wiring**
1527
1528 Figure
1529
1530 [[image:image-20220831163406-2.png]][[image:image-20220831163422-3.png]]
1531
1532 Pin Definition Diagram
1533
1534 [[image:image-20220831163441-4.png]]
1535
1536 == **XD serial protocol** ==
1537
1538 **1)V-BOX Settings**
1539
1540 Supported Series: Xinjie XD/XE Series PLC
1541
1542 |**Item**|**Settings**|**Note**
1543 |Protocol|XINJE XD/XC MODBUS|
1544 |Connection|RS232|
1545 |Baud rate|19200|
1546 |Data bit|8|
1547 |Parity|EVEN|
1548 |Stop bit|1|
1549 |PLC station No.|1|
1550
1551 **2)Address List**
1552
1553 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1554 |Bit|M|M|M d|0~~74999|
1555 |Bit|X1xx|X1xx|X1xx o|0~~1177|
1556 |Bit|X2xx|X2xx|X2xx o|0~~277|
1557 |Bit|X|X|X o|0~~77|
1558 |Bit|Y1xx|Y1xx|Y1xx o|0~~1177|
1559 |Bit|Y2xx|Y2xx|Y2xx o|0~~277|
1560 |Bit|Y|Y|Y o|0~~4095|
1561 |Bit|SM|SM|SM d|0~~4999|(((
1562
1563 )))
1564 |Bit|T|T|T d|0~~4999|
1565 |Bit|C|C|C d|0~~4999|
1566 |Bit|ET|ET|ET d|0~~31|
1567 |Bit|SE|SE|SE d|0~~31|
1568 |Bit|HM|HM|HM d|0~~11999|
1569 |Bit|HSC|HSC|HSC d|0~~39|
1570 |Bit|HS|HS|HS d|0~~999|
1571 |Bit|HT|HT|HT d|0~~1999|
1572 |Bit|HC|HC|HC d|0~~1999|
1573 |Bit|S|S|S d|0~~7999|
1574 |Word|D|D|D d|0~~69999|
1575 |Word|ID|ID|ID d|0~~99|
1576 |Word|ID1xx|ID1xx|ID1xx d|0~~999|
1577 |Word|ID2xx|ID2xx|ID2xx d|0~~299|
1578 |Word|QD|QD|QD d|0~~99|
1579 |Word|QD1xx|QD1xx|QD1xx d|0~~999|
1580 |Word|QD2xx|QD2xx|QD2xx d|0~~299|
1581 |Word|SD|SD|SD d|0~~4999|
1582 |Word|TD|TD|TD d|0~~575|
1583 |Word|CD|CD|CD d|0~~575|
1584 |Word|ETD|ETD|ETD d|0~~31|
1585 |Word|HD|HD|HD d|0~~24999|
1586 |Word|HSD|HSD|HSD d|0~~1023|
1587 |Word|HTD|HTD|HTD d|0~~95|
1588 |Word|HCD|HCD|HCD d|0~~95|
1589 |Word|HSCD|HSCD|HSCD d|0~~31|
1590 |Word|FD|FD|FD d|0~~8191|
1591 |Word|SFD|SFD|SFD d|0~~5999|
1592 |Word|FS|FS|FS d|0~~47|
1593
1594 **3)Configure the communication protocol**
1595
1596 [[image:image-20220831163923-7.png]]
1597
1598
1599
1600 **4)Cable Wiring**
1601
1602 Figure
1603
1604 [[image:image-20220831163406-2.png]][[image:image-20220831163553-6.png]]
1605
1606 Pin Definition Diagram
1607
1608 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830160232-3.png?rev=1.1||alt="image-20220830160232-3.png"]]
1609
1610 = Create communication with **Schneider PLC** =
1611
1612 == **Schneider MODBUS RTU** ==
1613
1614 **1)V-BOX Setting**
1615
1616 |=**Parameters**|=**Recommended**|=**Notes**
1617 |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
1618 |**Connection**|RS485|
1619 |**Baud rate**|19200|
1620 |**Data bit**|8|
1621 |**Parity**|Even|
1622 |**Stop bit**|1|
1623 |**PLC station No.**|1|
1624
1625 **2)Address List**
1626
1627 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
1628 |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
1629 |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
1630 |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
1631 |W|MW|DDDDDD|0 ~~ 999999|Output register
1632 |DW|MD|DDDDDD|0 ~~ 999999|Output register
1633
1634 **3)Configure the communication protocol**
1635
1636 [[image:image-20220902104329-1.png]]
1637
1638 **4)Cable Wiring**
1639
1640 **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
1641
1642 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220817154212-1.jpeg?width=554&height=315&rev=1.1||alt="image-20220817154212-1.jpeg" height="315" width="554"]]
1643
1644 = Create communication with Inovance** PLC** =
1645
1646 == **H3U serial protocol** ==
1647
1648 **1)V-BOX Settings**
1649
1650 |**Item**|**Settings**|**Note**
1651 |Protocol|INOVANCE H3U PLC|
1652 |Connection|RS422|
1653 |Baud rate|9600|
1654 |Data bit|7|
1655 |Parity|EVEN|
1656 |Stop bit|1|
1657 |PLC station No.|0|
1658
1659 **2)Address List**
1660
1661 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1662 |Bit|X|X|X o|0~~303237|
1663 |Bit|Y|Y|Y o|0~~303237|
1664 |Bit|M|M|M d|0~~99999|
1665 |Bit|T|T|T d|0~~99999|
1666 |Bit|C|C|C d|0~~99999|
1667 |Bit|SM|SM|SM d|8000~~999|
1668 |Bit|S|T|S d|0~~99999|
1669 |Bit|Lamp|Lamp|Lamp d|0~~0|
1670 |Word|X|X|X o|0~~303237|
1671 |Word|Y|Y|Y o|0~~303237|
1672 |Word|M|M|M d|0~~99999|
1673 |Word|T|T|T d|0~~99999|
1674 |Word|C|C|C d|0~~199|
1675 |Word|D|D|D d|0~~7999|
1676 |Word|S|S|S d|0~~99999|
1677 |Word|SD|SD|SD d|8000~~9999|
1678 |Word|R|R|R d|0~~32767|
1679
1680 **3)Configure the communication protocol**
1681
1682 [[image:image-20220831164626-1.png]]
1683
1684
1685
1686 **4)Cable Wiring**
1687
1688 Figure
1689
1690 [[image:image-20220831164646-2.png]][[image:image-20220831164700-3.png]]
1691
1692 Pin Definition Diagram
1693
1694 [[image:image-20220831164731-4.png]]
1695
1696 = Create communication with Panasonic** PLC** =
1697
1698 == **FP serial protocol** ==
1699
1700 **1)V-BOX Settings**
1701
1702 |**Item**|**Settings**|**Note**
1703 |Protocol|Panasonic FP MFWTOCOL|
1704 |Connection|RS232|
1705 |Baud rate|9600|
1706 |Data bit|8|
1707 |Parity|ODD|
1708 |Stop bit|1|
1709 |PLC station No.|1|
1710
1711 **2)Address List**
1712
1713 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1714 |Bit|X|X|X d|0~~9999|
1715 |Bit|Y|Y|Y d|0~~9999|
1716 |Bit|R|R|R d|0~~9999|
1717 |Bit|T|T|T d|0~~9999|
1718 |Bit|C|C|C d|0~~9999|
1719 |Bit|L|L|L d|0~~9999|
1720 |Word|WX|WX|WX d|0~~9999|
1721 |Word|WY|WY|WY d|0~~9999|
1722 |Word|WR|WR|WR d|0~~9999|
1723 |Word|WL|WL|WL d|0~~9999|
1724 |Word|LD|LD|LD d|0~~9999|
1725 |Word|DT|DT|DT d|0~~65535|
1726 |Word|FL|FL|FL d|0~~9999|
1727 |Word|EV|EV|EV d|0~~9999|
1728 |Word|SV|SV|SV d|0~~9999|
1729
1730 **3)Configure the communication protocol**
1731
1732 [[image:image-20220831165238-4.png]]
1733
1734
1735
1736 **4)Cable Wiring**
1737
1738 Figure
1739
1740 [[image:image-20220831165031-3.png]][[image:image-20220831165017-2.png]]
1741
1742 Pin Definition Diagram
1743
1744 [[image:image-20220831165008-1.png]]
1745
1746 = Create communication with LS** PLC** =
1747
1748 == **XBC serial protocol** ==
1749
1750 **1)V-BOX Settings**
1751
1752 |**Item**|**Settings**|**Note**
1753 |Protocol|LS XBC CNet|
1754 |Connection|RS232|
1755 |Baud rate|115200|
1756 |Data bit|8|
1757 |Parity|NONE|
1758 |Stop bit|1|
1759 |PLC station No.|1|
1760
1761 **2)Address List**
1762
1763 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1764 |Bit|P|P|P d|0~~2047|
1765 |Bit|M|M|M d|0~~2047|
1766 |Bit|L|L|L d|0~~11263|
1767 |Bit|K|K|K d|0~~16183|
1768 |Bit|F|F|F d|0~~2047|
1769 |Bit|D|D|D d|0~~32767|
1770 |Bit|R|R|R d|0~~32767|
1771 |Bit|U|U|U d|0~~4095|
1772 |Word|P|P|P d|0~~2047|
1773 |Word|M|M|M d|0~~2047|
1774 |Word|L|L|L d|0~~11263|
1775 |Word|K|K|K d|0~~16183|
1776 |Word|F|F|F d|0~~2047|
1777 |Word|C|C|C d|0~~2047|
1778 |Word|T|T|T d|0~~2047|
1779 |Word|D|D|D d|0~~32767|
1780 |Word|N|N|N d|0~~21503|
1781 |Word|R|R|R d|0~~32767|
1782 |Word|U|U|U d|0~~4095|
1783 |Word|Z|Z|Z d|0~~127|
1784 |Word|S|S|S d|0~~127|
1785
1786 **3)Configure the communication protocol**
1787
1788 [[image:image-20220831170147-1.png]]
1789
1790 **4)Cable Wiring**
1791
1792 Figure
1793
1794 [[image:image-20220831170306-4.png]][[image:image-20220831170254-3.png]]
1795
1796 Pin Definition Diagram
1797
1798 [[image:image-20220831170215-2.png]]
1799
1800 == **XGK FEnet Ethernet protocol** ==
1801
1802 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
1803
1804 **1)V-BOX Settings**
1805
1806 |**Items**|**Settings**|**Note**
1807 |Protocol|LG XGK FEnet(Ethernet)|
1808 |Connection|Ethernet|
1809 |Port No.|2004|
1810
1811 **2)Address List**
1812
1813 |**Type**|**Register**|**Range**|**Format**|**Note**
1814 |(% rowspan="14" %)Word|P|0~~2047|P d|
1815 |M|0~~2047|M d|
1816 |K|0~~2047|K d|
1817 |F|0~~2047|F d|
1818 |T|0~~2047|T d|
1819 |C|0~~2047|C d|
1820 |Z|0~~127|Z d|
1821 |S|0~~127|S d|
1822 |L|0~~11263|L d|
1823 |N|0~~21503|N d|
1824 |D|0~~32767|D d|
1825 |R|0~~32767|R d|
1826 |ZR|0~~65535|ZR d|
1827 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
1828
1829 **✎Note:**
1830
1831 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
1832 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
1833 * All bit registers are in the form of bits in word, and the range is the same as the word register;
1834
1835 **3)Communication Settings**
1836
1837 [[image:image-20220831171127-1.png]]
1838
1839 **4)Cable Wiring**
1840
1841 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1842
1843 = Create communication with **Modbus ** =
1844
1845 == **MODBUS RTU Slave (All function)** ==
1846
1847 Select the protocol "Modbus RTU Slave (All Fuction)",
1848
1849 Then set baud rate, port, stop bits, data bits, parity.
1850
1851 (% style="text-align:center" %)
1852 [[image:1624342015914-382.png||height="486" width="800" class="img-thumbnail"]]
1853
1854 == **MODBUS RTU Master** ==
1855
1856 Select the protocol "Modbus RTU Master",
1857
1858 Then set baud rate, port, stop bits, data bits, parity
1859
1860 (% style="text-align:center" %)
1861 [[image:1624348709622-711.png||queryString="width=809&height=493" height="488" width="800" class="img-thumbnail"]]
1862
1863 **address list**
1864
1865 (% class="table-bordered" %)
1866 |=(% scope="row" %)**Type**|=**Data Type**|=**Function code and description**
1867 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (Read Input Registers: Read the current binary value in one or more input registers)
1868 |06 (write single register: write a binary value to a holding register)
1869 |10 (write values to multiple addresses )
1870 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1871 |06 (write single register: write a binary value to a holding register)
1872 |10 (write values to multiple addresses )
1873 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1874 |06 (write single register: write a binary value to a holding register)
1875 |10 (write values to multiple addresses )
1876 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1877 |10 (write values to multiple addresses )
1878 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1879 |05 (Force a single coil to force the on/off state of a logic coil)
1880 |0F (Write multiple bits, ie write continuously)
1881 |(% rowspan="3" %)1|02 (Read the input state)
1882 |05 (Force a single coil to force the on/off state of a logic coil)
1883 |0F (Write multiple bits)
1884 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1885 |05 (Force a single coil to force the on/off state of a logic coil)
1886 |0F (Write multiple bits)
1887 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1888 |0F (Write multiple bits)
1889
1890 == **MODBUS TCP Slave (All function)** ==
1891
1892 Supported series: MODBUS TCP controller
1893
1894 V-B0X works as MODBUS TCP MASTER connecting with TCP SLAVE
1895
1896 **1)V-BOX Setting**
1897
1898 |**Items**|**Settings**|**Note**
1899 |Protocol|MODBUS TCP Slave (All function)|
1900 |Connection|Ethernet|
1901 |Port No.|502|
1902 |PLC station No.|1
1903
1904 **2)Address List**
1905
1906 |=**Type**|=**Data Type**|=**Function code & Description**
1907 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
1908 |06 (write single register: write a binary value to a holding register)
1909 |10 (write values to multiple addresses )
1910 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1911 |06 (write single register: write a binary value to a holding register)
1912 |10 (write values to multiple addresses )
1913 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1914 |06 (write single register: write a binary value to a holding register)
1915 |10 (write values to multiple addresses )
1916 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1917 |10 (write values to multiple addresses )
1918 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1919 |05 (Force a single coil to force the on/off state of a logic coil)
1920 |0F (Write multiple bits, ie write continuously)
1921 |(% rowspan="3" %)1|02 (Read the input state)
1922 |05 (Force a single coil to force the on/off state of a logic coil)
1923 |0F (Write multiple bits)
1924 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1925 |05 (Force a single coil to force the on/off state of a logic coil)
1926 |0F (Write multiple bits)
1927 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1928 |0F (Write multiple bits)
1929
1930 **3)Communication Settings**
1931
1932 Configure V-BOX Ethernet IP in Networking Settings
1933
1934 [[image:image-20220902111833-3.png]]
1935
1936
1937 Configure PLC Ethernet IP in Communication;
1938
1939 [[image:image-20220902111121-1.png]]
1940
1941 **4)Cable Wiring**
1942
1943 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1944
1945 == **communicate with VB inverter** ==
1946
1947 [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20VB%20inverter.zip]]
1948
1949 = **User define protocol** =
1950
1951 More serial port script instruction,please refer manual:[[Lua script function>>doc:V-BOX.V-Net.Manual.04 Lua Script.01 Lua Functions.WebHome]]~-~-->[[3.Serial port operation>>url:http://docs.we-con.com.cn/wiki/vbox/view/HMI/04.Lua%20script%20%20function%20and%20operation/01.Lua%20script%20function/#H3.Serialportoperation]]
1952
1953 == **Read the temperature sensor.** ==
1954
1955 the commond format is as beliow:
1956
1957 Send commond:01 03 02 00 00 03 04 73
1958
1959 Feedback commond:01 03 06 07 F7 0E 7E B7 35
1960
1961 Temperature data:07 F7,desimal = 2039,it means temperature is 20.39℃.
1962
1963 Humidity data:0E 7E,desimal = 3710, it mean humidity is 37.10%RH.
1964
1965 Script Demo:
1966
1967 ~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~--
1968
1969 function com.main()
1970 ~-~-dosomething
1971 openPlc()
1972 end
1973 function openPlc()
1974 if obj then
1975 ~-~- If the serial port opened,then read/write data by timing
1976
1977 local wri = string.pack(">HHHH",0X0103,0X0200,0X0003,0X0473)
1978 local arr = reading(wri)
1979 ~-~- if arr ~~=nil then
1980 ~-~- if arr[1] ==33 and arr[2] ==v[2][2] and arr[3] ==v[2][3] then
1981 ~-~- local A = arr[4]*256
1982 ~-~- local B = A+arr[5]
1983 ~-~- addr_setword(v[1],B)
1984 ~-~- end
1985 ~-~- end
1986
1987 else
1988 ~-~-judge if there is a serial object, then initialize and open the serial port
1989 local configs = {
1990 name = 'COM1', ~-~-Select serial port COM1
1991 mode = 485, ~-~-Communication mode RS485
1992 baud_rate = 9600, ~-~-Baud rate 9600
1993 stop_bit = 1, ~-~-stop bit 1
1994 data_len = 8, ~-~-data length 8
1995 check_bit = 'NONE', ~-~-no parity
1996
1997 }
1998 obj,err = serial.open(configs) ~-~-Open serial port
1999 if not obj then
2000 print("serial open :failed", err) ~-~- Open serial port failed
2001 end
2002 end
2003 end
2004
2005 function reading(wri)
2006 obj:flush() ~-~- Clear serial port
2007 obj:write(wri) ~-~- Write serial port
2008 print(string.byte(wri,1,#wri))
2009 obj:flush() ~-~- Clear serial port 
2010 local readed =obj:read(9,1000) ~-~- Read 9 bytes, timeout 1 second
2011 if readed and readed ~~= "" then 
2012 ~-~- judge that a non-empty string is read
2013 print(string.byte(readed,1,#readed))
2014 a={string.byte(readed, 1, #readed)}
2015 if nil ~~= a[4] and nil ~~= a[5] and nil ~~= a[6] and nil ~~= a[7] then
2016 a1=a[4]*256+a[5]
2017 a2=a[6]*256+a[7]
2018 addr_setword("@HDW0",a1)
2019 addr_setword("@HDW1",a2)
2020 end
2021 return {string.byte(readed, 1, #readed)}
2022 elseif readed == nil then
2023 print("serial read err:", err or "")
2024 return nil
2025 end
2026 return nil
2027 end
2028
2029 ~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-