1 = Create communication with WECON PLC =
2
3 == **LX3V Serial Protocol** ==
4
5 Supported series: Wecon LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
6
7 **1)V-BOX setting**
8
9 |**Item**|**Settings**|**Note**
10 |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
11 |Connection|RS422/RS485|
12 |Baud rate|9600|
13 |Data bit|7|
14 |Parity|EVEN|
15 |Stop bit|1|
16 |PLC station No.|1|
17
18 **2)Address List**
19
20
21 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
22 |(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
23 |Y|Y|Y o|0~~303237|
24 |M|M|M d|0~~99999|
25 |T|T|T d|0~~99999|
26 |C|C|C d|0~~99999|
27 |S|S|S d|0~~99999|
28 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
29 |Y|Y|Y o|0~~303237|
30 |M|M|M d|0~~99999|
31 |T|T|T d|0~~99999|
32 |C|C|C d|0~~199|
33 |D|D|D d|0~~7999|
34 |S|S|S d|0~~99999|
35 |SD|SD|SD d|8000~~9999|
36
37 **3)Configure the communication protocol**
38
39 [[image:image-20220824152217-1.png||alt="图片-20220824152217-1.png"]]
40
41 **4)Cable Wiring**
42
43 * **RS422**
44
45 [[image:image-20220824120614-5.png]]
46
47 * **RS485**
48
49 [[image:image-20220824120524-3.png]]
50
51 == **LX5V Serial Protocol** ==
52
53 This example introduces the establishment of serial port communication between V-BOX and LX5V. It is introduced through three parts: PLC software configuration, V-BOX software configuration, and hardware wiring.
54
55 **Software configuration of PLC**
56
57 **1)PLC programming software**
58
59 [[image:image-20220824142722-1.png]]
60
61 **2)New PLC project**
62
63 Click New Project and select the PLC model.
64
65 [[image:image-20220822172623-2.png]]
66
67 **3)Set Serial port parameters**
68
69 Follow the steps below to configure Serial port parameters
70
71 Baud rate:115200
72
73 Data bit:8
74
75 Stop bit:1
76
77 Parity:No verification
78
79 [[image:image-20220822172657-3.png]]
80
81 **4)Registers list**
82
83 [[image:image-20220822172730-4.png]]
84
85 **V-BOX software configuration**
86
87 **1)V-BOX programming software**
88
89 [[image:image-20220824104124-1.png]]
90
91 **2)V-NET add device**
92
93 Open V-NET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the access key, password and remark, to add the device.
94
95 [[image:image-20220824104909-2.png]]
96
97 **3)Set communication port parameters**
98
99 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
100
101 Baud rate:115200
102
103 Data bit:8
104
105 Stop bit:1
106
107 Parity:No verification
108
109 [[image:image-20220824142130-1.png]]
110
111 **hardware connection**
112
113 **1)Hardware wiring diagram**
114
115 [[image:image-20220824142546-2.png]]
116
117 [[image:image-20220824142643-3.png]]
118
119 The above are all the steps for establishing serial port communication between V-BOX with LX5V PLC.
120
121 == **LX5V-N Ethernet protocol** ==
122
123 This example introduces the establishment of Ethernet communication between V-BOX and LX5V-N. It is introduced through three parts: PLC software configuration, V-BOX software configuration, and hardware wiring.
124
125 **Software configuration of PLC**
126
127 **1)PLC programming software**
128
129 [[image:image-20220824142722-1.png]]
130
131 **2)New PLC project**
132
133 Click New Project and select the PLC model.
134
135 [[image:image-20220824143613-1.png]]
136
137 **3)Set Ethernet port parameters**
138
139 Follow the steps below to configure Ethernet parameters
140
141 PLC IP address:192.168.39.200
142
143 default gateway:192.168.39.1
144
145 subnet mask:255.255.255.0
146
147 [[image:image-20220824143744-2.png]]
148
149 **4)Registers list**
150
151 [[image:image-20220822172730-4.png]]
152
153 (% id="cke_bm_22473S" style="display:none" %)** **(%%)**V-BOX software configuration**
154
155 **1)V-BOX programming software**
156
157 [[image:image-20220824104124-1.png]]
158
159 **2)V-NET add device**
160
161 Open V-NET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the access key, password and remark, to add the device.
162
163 [[image:image-20220824104909-2.png]]
164
165 **3)Set communication Protocol**
166
167 Click Communication to configure the LX5V plc protocol and IP address.
168
169 [[image:image-20220824144619-1.png]]
170
171 **hardware connection**
172
173 **1)Hardware wiring diagram**
174
175 [[image:image-20220824151127-2.png]]
176
177 The above are all the steps for establishing ethernet communication between V-BOX with LX5V PLC.
178
179 = Create communication with **Rockwell PLC** =
180
181 == **DF1 Advanced Protocol** ==
182
183 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
184
185 **1) V-Box Settings**
186
187 |=Item|=Recommended |=Note
188 |=Protocol|Allen Bradley DF1 Advanced|
189 |=Connection|RS232|
190 |=Baud rate|19200|
191 |=Stop bits|1|
192 |=Data bits|8|
193 |=Parity|None|
194 |=PLC Station No.|1|
195 |=HMI Station No.|0|
196
197 **2) Address List**
198
199 |=**Type**|=**Device registers**|=**Format**|=**Range**|=Note
200 |(% colspan="1" rowspan="7" %)Bit|I1|I1ddd.dd|0.0~~255.15|Only able to communicate with file number I1
201 |O0|O0ddd.dd|0.0~~255.15|Only able to communicate with file number O0
202 |S2|S2ddd.dd|0.0~~255.15|Only able to communicate with file number S2
203 |B3|B3ddd.dd|0.0~~255.15|Only able to communicate with file number B3
204 |BN|BNddddd.dd|0.0~~99255.15|(((
205 Bit data file B0~~B99
206
207 First two digits is for file number
208
209 For example, BN13001.00 represents file number B13, address 001, the 0th bit.
210 )))
211 |N7|N7ddd.dd|0.0~~255.15|Only able to communicate with file number N7
212 |NN|NNddddd.dd|0.0~~99255.15|(((
213 Integer data file bit format N0~~N99
214
215 First two digits is for file number
216
217 For example, NN13001.00 represents file number N13, address 001, the 0th bit.
218 )))
219 |(% rowspan="11" %)Word|S2|S2ddd|0~~255|Only able to communicate with file number S2
220 |T4S|T4Sddd|0~~255|Only able to communicate with file number T4 (Timer Preset Value)
221 |T4P|T4Pddd|0~~255|Only able to communicate with file number T4 (Timer Accumulator Value)
222 |TNS|TNSddddd|0~~99255|(((
223 Timer Preset Value
224
225 First two digits is for file number
226
227 For example, TNS99255 represents file number T99, address 255.
228 )))
229 |TNP|TNPddddd|0~~99255|(((
230 Timer Accumulator Value
231
232 First two digits is for file number
233
234 For example, TNP99255 represents file number T99, address 255.
235 )))
236 |C5S|C5Sddd|0~~255|Only able to communicate with file number C5 (Counter Preset Value)
237 |C5P|C5Pddd|0~~255|Only able to communicate with file number C5 (Counter Accumulator Value)
238 |CNS|CNSddddd|0~~99255|(((
239 Counter Preset Value
240
241 First two digits is for file number
242
243 For example, CNS99255 represents file number C99, address 255.
244 )))
245 |CNP|CNPddddd|0~~99255|(((
246 Counter Accumulator Value
247
248 First two digits is for file number
249
250 For example, CNP99255 represents file number C99, address 255.
251 )))
252 |N7|N7ddd|0~~255|Only able to communicate with file number N7
253 |NN|NNddd|0~~99255|(((
254 Integer data file
255
256 First two digits is for file number
257
258 For example, NN99255 represents file number N99, address 255.
259 )))
260 |(% colspan="1" rowspan="3" %)Double Word|F8|F8ddd|0~~255|(((
261 Only able to communicate with file number N7
262 )))
263 |FN|FNddddd|0~~99255|(((
264 Floating point data file
265
266 First two digits is for file number
267
268 For example, FN99255 represents file number F99, address 255.
269 )))
270 |LN|LNddddd|0~~99255|Long
271
272 **3) Cable Wiring**
273
274 (% style="text-align:center" %)
275 [[image:ABRS232.gif]]
276
277 == (% id="cke_bm_5621S" style="display:none" %)** **(%%)**MicroLogix Protocol** ==
278
279 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
280
281 **1)V-BOX setting**
282
283 |**Item**|**Settings**|**Note**
284 |Protocol|Allen-Bradley DF1 Advanced|
285 |Connection|RS232|
286 |Baud rate|19200|
287 |Data bit|8|
288 |Parity|None|
289 |Stop bit|1|
290 |PLC station No.|1|
291
292 **2)Address List**
293
294 |**Type**|**Device registers**|**Format**|**Range**|**Note**
295 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
296 |O|O d.d|0.0~~255.15|
297 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
298 |S|S d.d|0.0~~255.15|
299 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
300 |(% rowspan="9" %)Word|S|S d|0~~255|
301 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
302 |TP|TP nnhh|0~~ffff
303 |CS|CS nnhh|0~~ffff
304 |CP|CP nnhh|0~~ffff
305 |N|N nnhh|0~~ffff
306 |C|C nnhh|0~~ffff
307 |T|T nnhh|0~~ffff
308 |R|R nnhh|0~~ffff
309
310 **3)Configure the communication protocol**[[image:image-20220824152928-1.png]]
311
312 **4)Configure the communication protocol**
313
314 [[image:image-20220824110724-1.png]]
315
316 == **Micro850_FreeTag Protocol** ==
317
318 (((
319 (((
320 This example introduces the establishment of Ethernet communication between Wecon V-box and CompactLogix L1769. It is introduced through three parts: PLC software configuration, V-box software configuration, and hardware wiring.
321 )))
322 )))
323
324 (((
325 (% class="wikigeneratedid" id="HSoftwareconfigurationofPLC" %)
326 (((
327 **Software configuration of PLC**
328 )))
329
330 (% class="wikigeneratedid" id="HPLCprogrammingsoftware" %)
331 (((
332 **1)PLC programming software**
333 )))
334
335 [[image:image-20220714162600-1.png]]
336
337 (% class="wikigeneratedid" id="HNewPLCproject" %)
338 (((
339 **2)New PLC project**
340 )))
341
342 (((
343 (((
344 Click New Project and select the PLC model.
345 )))
346 )))
347
348 (((
349 [[image:image-20220714162617-2.png]]
350 )))
351
352 (((
353
354
355 [[image:image-20220714162652-4.png]]
356 )))
357
358 (((
359 (% class="wikigeneratedid" id="HSetEthernetparameters" %)
360 (((
361 **3)Set Ethernet parameters**
362 )))
363
364 (((
365 (((
366 (((
367 Follow the steps below to configure Ethernet parameters
368 )))
369 )))
370 )))
371
372 (((
373 (((
374 (((
375 PLC IP address:192.168.40.101
376 )))
377 )))
378 )))
379
380 (((
381 (((
382 (((
383 default gateway:192.168.40.1
384 )))
385 )))
386 )))
387
388 (((
389 (((
390 (((
391 subnet mask:255.255.255.0
392 )))
393 )))
394 )))
395
396 (((
397 [[image:image-20220714162713-5.png]]
398 )))
399
400 (((
401
402 )))
403
404 (((
405 (% class="wikigeneratedid" id="HV-boxsoftwareconfiguration" %)
406 (((
407 **V-box software configuration**
408 )))
409
410 (% class="wikigeneratedid" id="HV-boxprogrammingsoftware" %)
411 (((
412 **1)V-box programming software**
413 )))
414
415 (% class="wikigeneratedid" %)
416 (((
417 [[image:image-20220714162725-6.png]]
418 )))
419
420 (% class="wikigeneratedid" id="HConfiguredevicenetwork" %)
421 (((
422 **2)Configure device network**
423 )))
424
425 (((
426 (((
427 (((
428 Click the Configuration Download button[[image:image-20220714115308-8.png||height="22" width="15"]], It is used to configure the device network, update the device time, obtain the device machine code, check the device network, etc.
429 )))
430
431 (((
432 In the example below, the IP address of V-Box is configured as 192.168.40.66, and the networking method is 4G connection
433 )))
434 )))
435 )))
436
437 (((
438 (((
439 [[image:image-20220714162737-7.png]]
440
441
442 )))
443 )))
444 )))
445 )))
446
447 (% class="wikigeneratedid" id="HV-netadddevice" %)
448 (((
449 **3)V-net add device**
450 )))
451 )))
452
453 (((
454 (((
455 Open VNET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the device machine code/product code, device password, and device alias to add the device.   [[image:image-20220714162752-8.png]]
456 )))
457
458
459 )))
460
461 (((
462 (% class="wikigeneratedid" id="HSetcommunicationportparameters" %)
463 (((
464 **4)Set communication port parameters**
465 )))
466
467 (((
468 In the device list on the left, find the Vbox that communicates with the L1769, click it and select configuration,communication port configuration in the main interface to add a communication protocol.
469 )))
470
471 [[image:image-20220714162805-9.png]]
472 )))
473
474 (((
475 The communication port is selected as Ethernet, the device type is selected as Allen-Bradley, the protocol is Allen-BradleyMicro850_FreeTag EthemetIP, and the IP is the internal IP address of the L1769 PLC. The port number is 44818.
476 )))
477
478 [[image:image-20220824164346-1.png]]
479
480
481 (((
482 After adding the protocol Allen-BradleyMicro850_FreeTag, click[[image:image-20220714143838-2.png]]icon add label.[[image:image-20220714162827-11.png]]
483 )))
484
485 (% class="wikigeneratedid" id="HEngineeringproduction" %)
486 (((
487 **5)Engineering production**
488 )))
489
490 (% class="wikigeneratedid" %)
491 (((
492 (((
493 According to your own needs, use the V-NET client software to edit the required data monitoring points.
494 )))
495
496 [[image:image-20220714162841-12.png]]
497
498
499 (((
500 **hardware connection**
501 )))
502 )))
503
504 (((
505 **1)Hardware wiring diagram**
506 )))
507
508 (((
509 (((
510 This example introduces Wecon V-box with Allen-Bradley L1769 PLC to establish communication through Ethernet. The connection diagram is as follows:
511 )))
512
513 [[image:image-20220714162856-13.png]]
514
515 (((
516 The above are all the steps for establishing Ethernet communication between Wecon V-box with CompactLogix L1769 PLC.
517
518
519 = **Allen-Bradley Ethernet DF1** =
520
521 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Allen-Bradley%20Ethernet%20DF1.zip]]
522
523
524 = Create communication with **Siemens PLC** =
525
526 == **S7-200 Smart Ethernet Protocol** ==
527
528 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20S7-200%20Smart.zip]]
529
530
531 == **S7-300 Ethernet Protocol** ==
532
533 Supported Series: Siemens S7-300 series PLC
534
535 **1)V-BOX setting**
536
537 |**Items**|**Settings**|**Note**
538 |Protocol|Simens S7-300 Ethernet|
539 |Connection|Ethernet|
540 |Port No.|102|
541 |PLC station No.|2|Need to be same as the PLC setting
542
543 **2)Address List**
544
545 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
546 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
547 |Q|Q|Q ddddd.o|0.0~~99999.7|
548 |M|M|M ddddd.o|0.0~~99999.7|
549 |DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
550 nn: block number;
551
552 dddd: address;
553 )))
554 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
555 |Q|QW|QW ddddd|0~~99999|
556 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
557 |MW|MW ddddd|0~~99999|(((
558 MW0=MB(0~~1)
559
560 MW2=MB(2~~3)
561
562 Address value is a multiple of 2
563 )))
564 |MD|MD ddddd|0~~99999|(((
565 MD0=MB(0~~3)
566
567 MD4=MB(4~~7)
568
569 Address value is a multiple of 4
570 )))
571 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
572 nn: block number;
573
574 dddd: address
575 )))
576 |DBxDBW|DBxDBW nndddd|0~~99999999
577 |DBxDBD|DBxDBD nndddd|0~~99999999
578
579 **3)Configure the communication protocol**
580
581 [[image:image-20220824161345-1.png]]
582
583 **4)Cable Wiring**
584
585 [[image:image-20220824161450-2.png]]
586 )))
587 )))
588
589 == **S7-1200 Ethernet Protocol** ==
590
591 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]]
592
593 == **S7-XXX Ethernet Protocol** ==
594
595 Supported Series: Siemens S7-400, S7-1200 and S7-1500
596
597 **1)V-BOX setting**
598
599 |=**Items**|=**Settings**|=**Note**
600 |Protocol|Siemens S7-XXX|
601 |Connection|Ethernet|
602 |Port No.|102|
603 |Device No.|Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|
604 |HMI No.|Rack (Default as 0)|
605
606 Slot from TIA Portal is equal to Device No. of V-net
607
608 Rack from TIA Portal is equal to HMI No. of V-net
609
610 [[image:image-20220824162459-3.png]]
611
612 [[image:image-20220824163305-2.png]]
613
614 **2)Address List**
615
616 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
617 |(% rowspan="4" %)Bit|I|I|M d.o|(((
618 d:0~-~-9999
619
620 o:0-7
621 )))|
622 |Q|Q|Q d.o|(((
623 d:0~-~-9999
624
625 o:0-7
626 )))|
627 |M|M|M d.o|(((
628 d:0~-~-9999
629
630 o:0-7
631 )))|
632 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
633 nn:0-9999,
634
635 dddd:0-9999,
636
637 o:0-7
638 )))|(((
639 nn:DB No.
640
641 dddd:address value
642
643 o: digit address
644 )))
645 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
646 |M|MW|MW d|d:0-99999|(((
647 MW0=MB(0~~1)
648
649 MW2=MB(2~~3)
650
651 Address value is a multiple of 2
652 )))
653 |M|MD|MD d|d:0-99999|(((
654 MD0=MB(0~~3)
655
656 MD4=MB(4~~7)
657
658 Address value is a multiple of 4
659 )))
660 |I|IW|IW d|d:0-99999|
661 |Q|QW|QW d|d:0-99999|
662 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
663 nn:0-9999
664
665 dddd:0-9999
666 )))|(((
667 nn:DB No.
668
669 dddd:address value
670 )))
671 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
672 nn:0-9999
673
674 dddd:0-9999
675 )))|(((
676 nn:DB No.
677
678 dddd:address value
679
680 Address value is a multiple of 2
681 )))
682 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
683 nn:0-9999
684
685 dddd:0-9999
686 )))|(((
687 nn:DB No.
688
689 dddd:address value
690
691 Address value is a multiple of 4
692 )))
693
694 **3)Configure the communication protocol**
695
696 [[image:image-20220824163448-3.png]]
697
698 **✎Note:**
699
700 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three V-BOX.
701 * V-BOX access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
702
703 **4)Cable Wiring**
704
705 [[image:image-20220824162342-2.png]]
706
707 == **LOGO Ethernet Protocol** ==
708
709 Supported Series: Siemens Logo 0BA0, 0BA1 series
710
711 **V-BOX Settings**
712
713
714 |**Items**|**Settings**|**Note**
715 |Protocol|Siemens LOGO|
716 |Connection|Ethernet|
717 |Port No.|102|
718 |PLC station No.|2|
719
720 **Address List**
721
722
723 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
724 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
725 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
726 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
727 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
728 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
729 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
730 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
731 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
732 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
733 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
734 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
735 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
736 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
737 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
738 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
739
740 **PLC Settings in LOGO Software:**
741
742 Click [Tools]~-~-[Ethernet Connections],shown as below.
743
744 (% style="text-align:center" %)
745 [[image:PIStudio.12\.PLC protocols.WebHome@12.PLC Protocol_html_8b9d2322edf89519.png]]
746
747 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
748
749 (% style="text-align:center" %)
750 [[image:PIStudio.12\.PLC protocols.WebHome@image-20221228142937-4.png]]
751
752 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
753
754 (% style="text-align:center" %)
755 [[image:PIStudio.12\.PLC protocols.WebHome@image-20221228143047-5.png]]
756
757 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
758
759 (% style="text-align:center" %)
760 [[image:PIStudio.12\.PLC protocols.WebHome@image-20221228143246-6.png]]
761
762 **V-BOX Communication Settings**
763
764 Set PLC IP in [IP Address] settings;
765
766 (% style="text-align:center" %)
767 [[image:LldwDGntf4.png]]
768
769 Enable V-BOX Ethernet in [Network];
770
771 (% style="text-align:center" %)
772 [[image:WgvjfWbQif.png]]
773
774 TSAP setting
775
776 * The initialization script needs to set the source TSAP address and the target TSAP address, otherwise the communication will not be successful.
777
778 {{code language="LUA"}}
779 function init.main()
780    addr_setword("@W_0#HSW1200",8192) -- Set the source TSAP address
781
782    addr_setword("@W_0#HSW1201",4096) -- Set the destination TSAP address
783
784 end
785 {{/code}}
786
787 = Create communication with **Mitsubishi PLC** =
788
789 == **FX1S,1N,2N Serial Protocol** ==
790
791 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
792
793 **1)V-BOX Settings**
794
795 |**Item**|**Settings**|**Note**
796 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
797 |Connection|RS422/RS485/RS232|
798 |Baud rate|9600~~115200|
799 |Data bit|7/8|
800 |Parity|EVEN/Odd/None|
801 |Stop bit|1/2|
802 |PLC station No.|1~~255|
803
804 **2)Address List**
805
806 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
807 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
808 |Y|Y|Y o|0~~303237|
809 |M|M|M d|0~~99999|
810 |T|T|T d|0~~99999|
811 |C|C|C d|0~~99999|
812 |S|S|S d|0~~99999|
813 |SM|SM|SM d|8000~~9999|
814 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
815 |Y|Y|Y o|0~~303237|
816 |M|M|M d|0~~99999|
817 |T|T|T d|0~~99999|
818 |C|C|C d|0~~199|
819 |D|D|D d|0~~7999|
820 |S|S|S d|0~~99999|
821 |SD|SD|SD d|8000~~9999|
822
823 **3)Configure the communication protocol**
824
825 [[image:image-20220825102844-3.png]]
826
827 **4)Cable Wiring**
828
829 * **RS422**
830
831 [[image:image-20220825103350-4.png]]
832
833 [[image:image-20220825100845-4.png]]
834
835
836 == **FX3U,3G,3GA Serial Protocol** ==
837
838 Supported Series: Mitsubishi FX3U, FX3G, FX3GA series
839
840 **1)V-BOX Settings**
841
842 |**Item**|**Settings**|**Note**
843 |Protocol|Mitsubishi FX3U/3G/3GA|
844 |Connection|RS422/RS485/RS232|
845 |Baud rate|9600~~115200|
846 |Data bit|7/8|
847 |Parity|EVEN/Odd/None|
848 |Stop bit|1/2|
849 |PLC station No.|1~~255|
850
851 **2)Address List**
852
853 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
854 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
855 |Y|Y|Y o|0~~303237|
856 |M|M|M d|0~~99999|
857 |T|T|T d|0~~99999|
858 |C|C|C d|0~~99999|
859 |S|S|S d|0~~99999|
860 |SM|SM|SM d|8000~~9999|
861 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
862 |Y|Y|Y o|0~~303237|
863 |M|M|M d|0~~99999|
864 |T|T|T d|0~~99999|
865 |C|C|C d|0~~199|
866 |D|D|D d|0~~7999|
867 |S|S|S d|0~~99999|
868 |SD|SD|SD d|8000~~9999|
869
870 **3)Configure the communication protocol**
871
872 [[image:image-20220825102649-2.png]]
873
874 **4)Cable Wiring**
875
876 * **RS422**
877
878 [[image:image-20220825103421-5.png]]
879
880 [[image:image-20220825100845-4.png]]
881
882
883 == **FX3U Ethernet Protocol** ==
884
885 Supported Modules: FX3U-ENET-ADP, FX3U-ENET-L
886
887 **1)V-BOX Settings**
888
889 |Items|Settings|Note
890 |Protocol|Mitsubishi FX3U|
891 |Connection|Ethernet|
892 |Port No.|5009|Must be the same as the PLC setting
893 |PLC station No.|0|
894
895 **2)Address List**
896
897 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
898 |(% colspan="1" rowspan="7" %)Bit|X|X|X OOO|0~~377|
899 |Y|Y|Y OOO|0~~377|
900 |M|M|M DDDD|0~~7679|
901 |SM|SM|SM DDDD|8000~~8511|
902 |S|S|S DDDD|0~~4095|
903 |TS|TS|TS DDD|0~~511|
904 |CS|CS|CS DDD|0~~255|
905 |(% colspan="1" rowspan="9" %)Word|CN|CN|CN DDD|0~~199|
906 |TN|TN|TN DDD|0~~511|
907 |D|D|D DDDD|0~~7999|
908 |SD|SD|SD DDDD|8000~~8511|
909 |R|R|R DDDDD|0~~32767|
910
911 **3)Ethernet Module Settings**
912
913 FX3U-ENET-L module configuration
914 Set up the FX3U-ENET-L Ethernet module settings as follows.
915 Select the module location, which in this document is Module 0.
916
917 [[image:image-20221116105850-1.png]]
918
919 Select "Operational setting" to enter the following screen.
920
921 The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default.
922
923 [[image:image-20221116105947-1.png]]
924
925 Select "Open setting" to enter the setting interface, the settings are as follows.
926
927 The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the
928
929 Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module.
930
931 [[image:image-20221116110802-1.png]]
932
933 Click on "transter setup" - "PC side I/F setting", see the following figure.
934
935 After setting, the first download must use the programming cable, as shown in the figure; after that, can
936
937 use the IP set in the "Ethernet board" to communicate directly with the network cable.
938
939 [[image:image-20221116110832-2.png||height="423" width="708"]]
940
941 Read and write data from the Ethernet module
942
943 [[image:image-20221116110907-3.png]]
944
945 Set "Transter setup" to COM communication, and read or write operation as shown below
946
947 [[image:image-20221116110917-4.png]]
948
949 **4)PLC Settings (GX Works 2)**
950
951 Create a blank FX5U project
952
953 Find Current Connection in the navigation
954
955 [[image:image-20221116111427-1.png||height="421" width="705"]]
956
957 Select Connection Channel List
958
959 Select Ethernet board communication
960
961 [[image:image-20221116111451-2.png||height="421" width="705"]]
962
963 Select Ethernet Module
964 Set the IP address of the PLC
965
966 [[image:image-20221116111509-3.png||height="666" width="699"]]
967
968 Read or write PLC data, in this document is read
969
970 [[image:image-20221116111651-4.png||height="416" width="697"]]
971
972 [[image:image-20221116111727-5.png||height="416" width="697"]]
973
974 **4)Configure the communication protocol**
975
976 [[image:image-20221119101946-2.png||height="395" width="695"]]
977
978 == **FX5U Serial Protocol** ==
979
980 Mitsubishi FX5U series PLC
981
982 **1)V-BOX Settings**
983
984 |**Item**|**Settings**|**Note**
985 |Protocol|Mitsubishi FX5U|
986 |Connection|RS422/RS485|
987 |Baud rate|9600|
988 |Data bit|7|
989 |Parity|Odd|
990 |Stop bit|1|
991 |PLC station No.|1~~255|Need to be the same as PLC settings
992
993 **2)Address List**
994
995 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
996 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
997 |Y|Y|Y o|0~~303237|
998 |M|M|M d|0~~99999|
999 |B|B|B h|0~~7FFF|
1000 |F|F|F d|0~~32767|
1001 |SB|SB|SB h|0~~7FFF|
1002 |TS|TS|TS d|0~~1023|
1003 |TC|TC|TC d|0~~1023|
1004 |STS|STS|STS d|0~~1023|
1005 |STC|STC|STS d|0~~1023|
1006 |CS|CS|CS d|0~~1023|
1007 |CC|CC|CC d|0~~1023|
1008 |SM|SM|SM d|0~~9999|
1009 |L|L|L d|0~~32767|
1010 |S|S|S d|0~~4095|
1011 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1012 |TN|TN|TN d|0~~1023|
1013 |STN|STN|STN d|0~~1023|
1014 |CN|CN|CN d|0~~1023|
1015 |R|R|R d|0~~32767|
1016 |SW|SW|SW h|0~~7FFF|
1017 |Z|Z|Z d|0~~23|
1018 |D|D|D d|0~~7999|
1019 |SD|SD|SD d|0~~11999|
1020
1021 **3)PLC Settings (GX Works 3)**
1022
1023 Create a blank FX5U project
1024
1025 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
1026
1027 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5c9cb13fac1e6c93.png?width=200&height=462&rev=1.1||alt="12.PLC Protocol_html_5c9cb13fac1e6c93.png" height="462" width="200"]]
1028
1029 Select protocol in the setting item, and set parameters.
1030
1031 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_de942589ca070228.png?width=600&height=324&rev=1.1||alt="12.PLC Protocol_html_de942589ca070228.png" height="324" width="600"]]
1032
1033 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
1034
1035 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_387ec7d00b5feb59.png?width=600&height=323&rev=1.1||alt="12.PLC Protocol_html_387ec7d00b5feb59.png" height="323" width="600"]]
1036
1037 Click the [Apply] button to finish the setting.
1038
1039 Click download and select the items as below, then click [execute] to download the configuration to PLC.
1040
1041 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_cdef1c5ec8cc2105.png?width=600&height=434&rev=1.1||alt="12.PLC Protocol_html_cdef1c5ec8cc2105.png" height="434" width="600"]]
1042
1043 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
1044
1045 Done.
1046
1047 **4)Configure the communication protocol**
1048
1049 [[image:image-20220825104904-1.png]]
1050
1051 **5)Cable Wiring**
1052
1053
1054 * **RS422**
1055
1056 [[image:image-20220825105105-2.png]]
1057
1058 [[image:image-20220825105533-3.png]]
1059
1060 == **FX5U Ethernet Protocol** ==
1061
1062 Mitsubishi FX5U series PLC
1063
1064 **1)V-BOX Settings**
1065
1066 |**Items**|**Settings**|**Note**
1067 |Protocol|Mitsubishi FX5U|
1068 |Connection|Ethernet|
1069 |Port No.|5002|Must be the same as the PLC setting
1070 |PLC station No.|0|
1071
1072 **2)Address List**
1073
1074 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1075 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1076 |Y|Y|Y o|0~~303237|
1077 |M|M|M d|0~~99999|
1078 |B|B|B h|0~~7FFF|
1079 |F|F|F d|0~~32767|
1080 |SB|SB|SB h|0~~7FFF|
1081 |TS|TS|TS d|0~~1023|
1082 |TC|TC|TC d|0~~1023|
1083 |STS|STS|STS d|0~~1023|
1084 |STC|STC|STS d|0~~1023|
1085 |CS|CS|CS d|0~~1023|
1086 |CC|CC|CC d|0~~1023|
1087 |SM|SM|SM d|0~~9999|
1088 |L|L|L d|0~~32767|
1089 |S|S|S d|0~~4095|
1090 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1091 |TN|TN|TN d|0~~1023|
1092 |STN|STN|STN d|0~~1023|
1093 |CN|CN|CN d|0~~1023|
1094 |R|R|R d|0~~32767|
1095 |SW|SW|SW h|0~~7FFF|
1096 |Z|Z|Z d|0~~23|
1097 |D|D|D d|0~~7999|
1098 |SD|SD|SD d|0~~11999|
1099
1100 **3)PLC Settings (GX Works 3)**
1101
1102 Find the [Ethernet port] in the navigation area.
1103
1104 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_8e8f85ace087346c.png?width=300&height=593&rev=1.1||alt="12.PLC Protocol_html_8e8f85ace087346c.png" height="593" width="300"]]
1105
1106 Select [Own Node Settings] in the [Setting Item List];
1107
1108 Set [IP Address], [Subnet Mask], [Default Gateway];
1109
1110 Click [Detailed Settings] into [Ethernet Configuration (Built-in Ethernet Port)] windows;
1111
1112 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5d98495052c8c10e.png?width=600&height=339&rev=1.1||alt="12.PLC Protocol_html_5d98495052c8c10e.png" height="339" width="600"]]
1113
1114 Select [SLMP Connection Module] and add into host station as below picture shows;
1115
1116 Set Port number as 5002 (this is necessary settings);
1117
1118 Click [Close with Reflecting the Setting] to save and close window;
1119
1120 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_14b489fdc6c6589d.png?width=600&height=350&rev=1.1||alt="12.PLC Protocol_html_14b489fdc6c6589d.png" height="350" width="600"]]
1121
1122 Click [Apply] to completed Etherenet settings;
1123
1124 Switch to the [On line data operation] interface as below, check the item and click [Execute] to download.
1125
1126 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_c93025a968a8a9e7.png?width=600&height=434&rev=1.1||alt="12.PLC Protocol_html_c93025a968a8a9e7.png" height="434" width="600"]]
1127
1128 **4)Configure the communication protocol**
1129
1130 [[image:image-20220825112403-1.png||alt="图片-20220825112403-1.png"]]
1131
1132 **5)Cable Wiring**
1133
1134 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1135
1136 == **L02 Serial Protocol** ==
1137
1138 Mitsubishi L02 series CPU built-in serial port.
1139
1140 **1)V-BOX Settings**
1141
1142 |**Item**|**Settings**|**Note**
1143 |Protocol|Mitsubishi L02|
1144 |Connection|RS422|
1145 |Baud rate|115200|
1146 |Data bit|8|
1147 |Parity|Odd|
1148 |Stop bit|1|
1149 |PLC station No.|1~~255|Need to be the same as PLC settings
1150
1151 **2)Address List**
1152
1153 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1154 |Bit|X|X|X h|0~~FFFF|
1155 |Bit|Y|Y|Y h|0~~FFFF|
1156 |Bit|M|M|M d|0~~9999|
1157 |Bit|L|L|L d|0~~9999|
1158 |Bit|F|F|F d|0~~9999|
1159 |Bit|B|B|B h|0~~FFFF|
1160 |Bit|V|V|V d|0~~2047|
1161 |Bit|TC|TC|TC d|0~~9999|
1162 |Bit|SS|SS|SS d|0~~9999|
1163 |Bit|SC|SC|SC d|0~~9999|
1164 |Bit|CS|CS|CS d|0~~9999|
1165 |Bit|CC|CC|CC d|0~~9999|
1166 |Bit|SB|SB|SB h|0~~FFFF|
1167 |Bit|SM|SM|SM d|0~~2047|
1168 |Bit|STS|STS|STS d|0~~1023|
1169 |Bit|S|S|S d|0~~9999|
1170 |Bit|DX|DX|DX h|0~~FFFF|
1171 |Bit|DY|DY|DY h|0~~FFFF|
1172 |Bit|TS|TS|TS d|0~~9999|
1173 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1174 |Word|W|W|W h|0~~FFFF|
1175 |Word|TN|TN|TN d|0~~99999|
1176 |Word|SN|SN|SN d|0~~99999|
1177 |Word|CN|CN|CN d|0~~99999|
1178 |Word|R|R|R d|0~~99999|
1179 |Word|SW|SW|SW h|0~~FFFF|
1180 |Word|Z|Z|Z d|0~~99999|
1181 |Word|ZR|ZR|ZR h|0~~FFFF|
1182 |Word|D|D|D d|0~~99999|
1183
1184 **3)Communication Settings**
1185
1186 [[image:image-20220825160648-3.png]]
1187
1188 **4)Cable Wiring**
1189
1190 * **RS422**
1191
1192 [[image:image-20220825161612-8.png]]
1193
1194 [[image:image-20220825160820-4.png]]
1195
1196 == **L02 Ethernet Protocol** ==
1197
1198 Mitsubishi L series CPU built-in Ethernet port.
1199
1200 **1)V-BOX Settings**
1201
1202 |**Items**|**Settings**|**Note**
1203 |Protocol|MIT L02 CPU MELSEC|
1204 |Connection|Ethernet|
1205 |Port No.|1025|Must be the same as the PLC setting
1206 |PLC station No.|0|Must be the same as the PLC setting
1207
1208 **2)Address List**
1209
1210 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1211 |Bit|X|X|X h|0~~FFFF|
1212 |Bit|Y|Y|Y h|0~~FFFF|
1213 |Bit|M|M|M d|0~~9999|
1214 |Bit|L|L|L d|0~~9999|
1215 |Bit|F|F|F d|0~~9999|
1216 |Bit|B|B|B h|0~~FFFF|
1217 |Bit|V|V|V d|0~~2047|
1218 |Bit|TC|TC|TC d|0~~9999|
1219 |Bit|SS|SS|SS d|0~~9999|
1220 |Bit|SC|SC|SC d|0~~9999|
1221 |Bit|CS|CS|CS d|0~~9999|
1222 |Bit|CC|CC|CC d|0~~9999|
1223 |Bit|SB|SB|SB h|0~~FFFF|
1224 |Bit|SM|SM|SM d|0~~2047|
1225 |Bit|STS|STS|STS d|0~~1023|
1226 |Bit|S|S|S d|0~~9999|
1227 |Bit|DX|DX|DX h|0~~FFFF|
1228 |Bit|DY|DY|DY h|0~~FFFF|
1229 |Bit|TS|TS|TS d|0~~9999|
1230 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1231 |Word|W|W|W h|0~~FFFF|
1232 |Word|TN|TN|TN d|0~~99999|
1233 |Word|SN|SN|SN d|0~~99999|
1234 |Word|CN|CN|CN d|0~~99999|
1235 |Word|R|R|R d|0~~99999|
1236 |Word|SW|SW|SW h|0~~FFFF|
1237 |Word|Z|Z|Z d|0~~99999|
1238 |Word|ZR|ZR|ZR h|0~~FFFF|
1239 |Word|D|D|D d|0~~99999|
1240
1241 **3)PLC Settings (GX Works2 )**
1242
1243 Create a project
1244
1245 Set PLC IP, subnet mask and gateway;
1246
1247 Select [Binary Code] as communication data code;
1248
1249 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_776e17505f3fc6c0.png?width=600&height=524&rev=1.1||alt="12.PLC Protocol_html_776e17505f3fc6c0.png" height="524" width="600"]]
1250
1251 Set PLC port number, for example 1025
1252
1253 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_8d0d1a22d388f70b.png?width=600&height=524&rev=1.1||alt="12.PLC Protocol_html_8d0d1a22d388f70b.png" height="524" width="600"]]
1254
1255 Save settings;
1256
1257 Download project into PLC device;
1258
1259 Restart PLC device;
1260
1261 **4)Configure the communication protocol**
1262
1263 [[image:image-20220825142659-1.png]]
1264
1265 **5)Cable Wiring**
1266
1267 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1268
1269 == **Q12H Serial Protocol** ==
1270
1271 This Demo shows V-BOX communicate with Q12H PLC by Q02H serial Protocol
1272
1273 [[**Download link**>>https://ftp.we-con.com.cn/Download/WIKI/PI%20HMI/Demo/Communication/V-Box%20connect%20PLC%20Q12H.rar]]
1274
1275 == **QJ71E71 Ethernet Protocol** ==
1276
1277 Mitsubishi QJ71E71 Ethernet communication module;
1278
1279 **1)V-BOX Settings**
1280
1281 |**Items**|**Settings**|**Note**
1282 |Protocol|MIT QJ71E71 MELSEC|
1283 |Connection|Ethernet|
1284 |Port No.|1025|Must be the same as the PLC setting
1285 |PLC station No.|0|Must be the same as the PLC setting
1286
1287 **2)Address List**
1288
1289 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1290 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1291 |Y|Y|Y h|0~~1FFF|
1292 |M|M|M d|0~~99999|
1293 |L|L|L d|0~~8191|
1294 |F|F|F d|0~~2047|
1295 |B|B|B h|0~~1FFF|
1296 |V|V|V d|0~~2047|
1297 |TS|TS|TS d|0~~2047|
1298 |TC|TC|TC d|0~~2047|
1299 |SS|SS|SS d|0~~2047|
1300 |SC|SC|SC d|0~~2047|
1301 |CS|CS|CS d|0~~1023|
1302 |CC|CC|CC d|0~~1023|
1303 |SB|SB|SB h|0~~7FF|
1304 |S|S|S d|0~~8191|
1305 |DX|DX|DX h|0~~1FFF|
1306 |DY|DY|DY h|0~~1FFF|
1307 |SM|SM|SM d|8000~~9999|
1308 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1309 |D|D|D d|0~~12287|
1310 |W|W|W h|0~~1FFF|
1311 |TN|TN|TN d|0~~2047|
1312 |SN|SN|SN d|0~~2047|
1313 |CN|CN|CN d|0~~1023|
1314 |R|R|R d|0~~32767|
1315 |SW|SW|SW h|0~~7FF|
1316 |Z|Z|Z d|0~~15|
1317 |ZR|ZR|ZR h|0~~FE7FF|
1318
1319 **3)PLC Settings(GX Works2)**
1320
1321 * Click [Ethernet/CC IE/MELSECNET];
1322 * Please select [Ethernet] as network type;
1323 * Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order);
1324 * Select [Online] as Mode;
1325 * [[image:image-20221119171343-2.png||height="341" width="587"]]
1326 * Click [Operation setting] to set IP;
1327 * Select [Binary Code] as [Communication Data Code];
1328 * [[image:image-20221119171436-3.png||height="354" width="588"]]
1329 * Click [Open setting]
1330 * Set protocol: TCP;
1331 * Set [unpassive] in [Open system];
1332 * Set [receive] in [Fixed buffer];
1333 * Set [procedure Exist] in [Fixed buffer communication];
1334 * Disable [Pairing open];
1335 * Set [No confirm] in [Existence confirmation];
1336 * Host station port number: 5009;
1337 * Save settings;
1338 * [[image:image-20221119171611-4.png||height="354" width="588"]]
1339 * Download project into PLC and restart it
1340
1341 **4)Configure the communication protocol**
1342
1343 [[image:image-20221119171832-5.png||height="354" width="625"]]
1344
1345
1346 **5)Cable Wiring**
1347
1348 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png"]]
1349
1350 = Create communication with **Delta PLC** =
1351
1352 == **DVP Ethernet Protocol** ==
1353
1354 Supoort Series: DELTA DVP20/32/40/60ES200RE/200TE or any DVP models with built-in Ethernet port, DELTA DVPEN01-SL module
1355
1356 **1)V-BOX Settings**
1357
1358 |=**Items**|=**Settings**|=**Note**
1359 |Protocol|DELTA DVP MODBUS TCP|
1360 |Connection|Ethernet|
1361 |Port No.|502|
1362 |Device No.|1|
1363 |VBox Device No.|0|
1364
1365 **2)Address List **
1366
1367 |=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 217px;" %)**VBox registers**|=(% style="width: 168px;" %)**Format**|=(% style="width: 225px;" %)**Range**|=**Note**
1368 |Bit|(% style="width:191px" %)X|(% style="width:217px" %)X|(% style="width:168px" %)X OOO|(% style="width:225px" %)0~~377|
1369 |Bit|(% style="width:191px" %)Y|(% style="width:217px" %)Y|(% style="width:168px" %)Y OOO|(% style="width:225px" %)0~~377|
1370 |Bit|(% style="width:191px" %)M0|(% style="width:217px" %)M0|(% style="width:168px" %)M0DDDD|(% style="width:225px" %)0~~1535|
1371 |Bit|(% style="width:191px" %)M1|(% style="width:217px" %)M1|(% style="width:168px" %)M1DDDD|(% style="width:225px" %)1536~~4096|
1372 |Bit|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDD|(% style="width:225px" %)0~~255|
1373 |Bit|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~255|
1374 |Bit|(% style="width:191px" %)S|(% style="width:217px" %)S|(% style="width:168px" %)SDDDD|(% style="width:225px" %)0~~1023|
1375 |Word|(% style="width:191px" %)D0|(% style="width:217px" %)D0|(% style="width:168px" %)D0DDDD|(% style="width:225px" %)0~~4095|
1376 |Word|(% style="width:191px" %)D1|(% style="width:217px" %)D1|(% style="width:168px" %)D1DDDD|(% style="width:225px" %)4096~~11999|
1377 |Word|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDD|(% style="width:225px" %)0~~255|
1378 |Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~199|
1379 |Double Word|(% style="width:191px" %)HC|(% style="width:217px" %)HC|(% style="width:168px" %)HCDDD|(% style="width:225px" %)200~~255|
1380
1381 **3) PLC Setting:**
1382
1383 ~1. Create new project in Delta WPL Soft, and click Setting to open the communication settings:
1384
1385 (% style="text-align:center" %)
1386 [[image:DVPEthernetWPLSoft2.png]]
1387
1388 2. Set up the communication type and PLC IP:
1389
1390 (% style="text-align:center" %)
1391 [[image:DVPEthernetSetup.png]]
1392
1393 (% class="wikigeneratedid" %)
1394 3. Click OK and save the settings. Then click Communication on toolbar, then click Transfer Setup to open new window:
1395
1396 (% style="text-align:center" %)
1397 [[image:DVPEthernetTransfer.png]]
1398
1399 (% class="wikigeneratedid" %)
1400 4. Select Communication Mode as PC => PLC to download or select PC <=PLC to upload:
1401
1402 (% style="text-align:center" %)
1403 [[image:DVPEthernetPLCtoPC.png]]
1404
1405 5. Click Auto-Search Ethernet Module to find the PLC on the same LAN network:
1406
1407 (% style="text-align:center" %)
1408 [[image:DVPEthernetAutoSearch.png]]
1409
1410 **4) V-BOX Setting:**
1411
1412 Set the same IP address according to the setting from WPL Soft:
1413
1414 (% style="text-align:center" %)
1415 [[image:DVPEthernetVNETPortocol.png]]
1416
1417 == **DVP serial protocol** ==
1418
1419 Supoort Series: DELTA DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX
1420
1421 **1)V-BOX Settings**
1422
1423 |=**Items**|=**Settings**|=**Note**
1424 |Protocol|DELTA DVP PROTOCOL|
1425 |Connection|RS232|
1426 |Baud Rate|9600|
1427 |Stop Bit|1|
1428 |Data Bit|7|
1429 |Parity|EVEN|
1430 |Device No.|1|
1431
1432 (% class="wikigeneratedid" %)
1433 **2)Address List**
1434
1435 |=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 217px;" %)**VBox registers**|=(% style="width: 168px;" %)**Format**|=(% style="width: 225px;" %)**Range**|=**Note**
1436 |Bit|(% style="width:191px" %)X|(% style="width:217px" %)X|(% style="width:168px" %)X OOOOOO|(% style="width:225px" %)0~~303237|
1437 |Bit|(% style="width:191px" %)Y|(% style="width:217px" %)Y|(% style="width:168px" %)Y OOOOOO|(% style="width:225px" %)0~~303237|
1438 |Bit|(% style="width:191px" %)M|(% style="width:217px" %)M|(% style="width:168px" %)MDDDDD|(% style="width:225px" %)0~~99999|
1439 |Bit|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDDDD|(% style="width:225px" %)0~~99999|
1440 |Bit|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDDDD|(% style="width:225px" %)0~~99999|
1441 |Bit|(% style="width:191px" %)S|(% style="width:217px" %)S|(% style="width:168px" %)SDDDDD|(% style="width:225px" %)0~~99999|
1442 |Word|(% style="width:191px" %)D|(% style="width:217px" %)D|(% style="width:168px" %)D DDDDD|(% style="width:225px" %)0~~99999|
1443 |Word|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDDDD|(% style="width:225px" %)0~~99999|
1444 |Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~199|
1445 |Double Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDDDD|(% style="width:225px" %)200~~99999|
1446
1447 (% class="wikigeneratedid" %)
1448 **3)Wiring Diagram**
1449
1450 (% style="text-align:center" %)
1451 [[image:Delta DVP PROTOCOLSerial232.png]]
1452
1453 == **AS Ethernet Protocol** ==
1454
1455 **1)V-BOX Settings**
1456
1457 |=**Items**|=**Settings**|=**Note**
1458 |Protocol|DELTA AS300 MODBUS TCP|
1459 |Connection|Ethernet|
1460 |Port No.|502|
1461 |Device No.|1|
1462 |HMI No.|0|
1463
1464 **2)Address List**
1465
1466 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1467 |Bit|X|X|X d|0~~63|
1468 |Bit|Y|Y|Y d|0~~63|
1469 |Bit|D|D|D d|0~~29999|
1470 |Bit|M|M|M d|0~~8191|
1471 |Bit|SM|SM|SM d|0~~4095|
1472 |Bit|S|S|S h|0~~2047|
1473 |Bit|T|T|T d|0~~511|
1474 |Bit|C|C|C d|0~~511|
1475 |Bit|HC|HC|HC d|0~~255|
1476 |Word|X|X|X h|0~~63|
1477 |Word|Y|Y|Y d|0~~63|
1478 |Word|SR|SR|SR d|0~~2047|
1479 |Word|D|D|D d|0~~29999|
1480 |Word|T|T|T d|0~~511|
1481 |Word|C|C|C h|0~~511|
1482 |Word|E|E|E d|0~~9|
1483
1484 **3)Configure the communication protocol**
1485
1486 [[image:image-20220831160010-4.png]]
1487
1488 **4)Cable Wiring**
1489
1490 Figure
1491
1492 [[image:image-20220831155101-1.png]][[image:image-20220831160055-5.png]]
1493
1494 Pin Definition Diagram
1495
1496 [[image:image-20220831155157-3.png]]
1497
1498 = Create communication with **Omron PLC** =
1499
1500 == **CP1 Series Protocol ** ==
1501
1502 [[下载链接>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CP1%20Series.zip]]
1503
1504 == **CP2M Series Protocol** ==
1505
1506 [[下载链接>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CJ2M.zip]]
1507
1508
1509 == **EC55 Series Protocol** ==
1510
1511 Supported device: EC55 temperature instrument
1512
1513 **1)V-BOX Settings**
1514
1515 |**Items**|**Settings**|**Note**
1516 |Protocol|Omron EC55|
1517 |Connection|RS485 (9600, 2, 7, EVEN)|
1518 |Port No.|None|
1519 |PLC station No.|0|
1520
1521 **2)Address List**
1522
1523 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
1524 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
1525 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
1526 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
1527 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
1528 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
1529 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
1530 |CP|-|0-6|Read controller intrinsic property
1531 |CS|-|0-2|Read controller states
1532 |CA|-|0-17|Action command
1533
1534 **3)Device Settings**
1535
1536 Omron E5CC PLC configuration
1537
1538 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
1539
1540 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_3d95e093792ba98a.png?width=550&height=229&rev=1.1||alt="12.PLC Protocol_html_3d95e093792ba98a.png" height="229" width="550"]]
1541
1542 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
1543
1544 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_be583aa69dd6cf4c.png?width=550&height=242&rev=1.1||alt="12.PLC Protocol_html_be583aa69dd6cf4c.png" height="242" width="550"]]
1545
1546 **✎Note:** The communication settings for HMI should be consistent with this setting.
1547
1548 **4)Configure the communication protocol**
1549
1550 [[image:image-20220831161041-1.png]]
1551
1552 **5)Cable Wiring**
1553
1554 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5e9a81a14106da9e.png?width=392&height=223&rev=1.1||alt="12.PLC Protocol_html_5e9a81a14106da9e.png" height="223" width="392"]]
1555
1556 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_1897d92be6948d58.png?width=393&height=223&rev=1.1||alt="12.PLC Protocol_html_1897d92be6948d58.png" height="223" width="393"]]
1557
1558 **✎Note:**
1559
1560 * COM3 only available in PI8000/PI9000 series.
1561 * CA address could not support continuous writing function;
1562 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
1563 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
1564 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
1565 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
1566 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
1567 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
1568 * [[image:image-20220831161356-1.png]]Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
1569
1570 = Create communication with Xinje** PLC** =
1571
1572 == **XC serial protocol** ==
1573
1574 **1)V-BOX Settings**
1575
1576 |**Item**|**Settings**|**Note**
1577 |Protocol|XINJE XC MODBUS|
1578 |Connection|RS232|
1579 |Baud rate|19200|
1580 |Data bit|8|
1581 |Parity|EVEN|
1582 |Stop bit|1|
1583 |PLC station No.|1|
1584
1585 **2)Address List**
1586
1587 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1588 |Bit|M|M|M d|0~~8511|
1589 |Bit|X|X|X o|0~~1747|
1590 |Bit|Y|Y|Y o|0~~1747|
1591 |Bit|S|S|S d|0~~1023|
1592 |Bit|T|T|T d|0~~4095|
1593 |Bit|C|C|C d|0~~634|
1594 |Word|D|D|D d|0~~8511|
1595 |Word|TD|TD|TD d|0~~618|
1596 |Word|CD|CD|CD d|0~~634|
1597 |Word|FD|FD|FD d|0~~8511|
1598
1599 **3)Configure the communication protocol**
1600
1601
1602 [[image:image-20220831163041-1.png]]
1603
1604 **4)Cable Wiring**
1605
1606 Figure
1607
1608 [[image:image-20220831163406-2.png]][[image:image-20220831163422-3.png]]
1609
1610 Pin Definition Diagram
1611
1612 [[image:image-20220831163441-4.png]]
1613
1614 == **XD serial protocol** ==
1615
1616 **1)V-BOX Settings**
1617
1618 Supported Series: Xinjie XD/XE Series PLC
1619
1620 |**Item**|**Settings**|**Note**
1621 |Protocol|XINJE XD/XC MODBUS|
1622 |Connection|RS232|
1623 |Baud rate|19200|
1624 |Data bit|8|
1625 |Parity|EVEN|
1626 |Stop bit|1|
1627 |PLC station No.|1|
1628
1629 **2)Address List**
1630
1631 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1632 |Bit|M|M|M d|0~~74999|
1633 |Bit|X1xx|X1xx|X1xx o|0~~1177|
1634 |Bit|X2xx|X2xx|X2xx o|0~~277|
1635 |Bit|X|X|X o|0~~77|
1636 |Bit|Y1xx|Y1xx|Y1xx o|0~~1177|
1637 |Bit|Y2xx|Y2xx|Y2xx o|0~~277|
1638 |Bit|Y|Y|Y o|0~~4095|
1639 |Bit|SM|SM|SM d|0~~4999|(((
1640
1641 )))
1642 |Bit|T|T|T d|0~~4999|
1643 |Bit|C|C|C d|0~~4999|
1644 |Bit|ET|ET|ET d|0~~31|
1645 |Bit|SE|SE|SE d|0~~31|
1646 |Bit|HM|HM|HM d|0~~11999|
1647 |Bit|HSC|HSC|HSC d|0~~39|
1648 |Bit|HS|HS|HS d|0~~999|
1649 |Bit|HT|HT|HT d|0~~1999|
1650 |Bit|HC|HC|HC d|0~~1999|
1651 |Bit|S|S|S d|0~~7999|
1652 |Word|D|D|D d|0~~69999|
1653 |Word|ID|ID|ID d|0~~99|
1654 |Word|ID1xx|ID1xx|ID1xx d|0~~999|
1655 |Word|ID2xx|ID2xx|ID2xx d|0~~299|
1656 |Word|QD|QD|QD d|0~~99|
1657 |Word|QD1xx|QD1xx|QD1xx d|0~~999|
1658 |Word|QD2xx|QD2xx|QD2xx d|0~~299|
1659 |Word|SD|SD|SD d|0~~4999|
1660 |Word|TD|TD|TD d|0~~575|
1661 |Word|CD|CD|CD d|0~~575|
1662 |Word|ETD|ETD|ETD d|0~~31|
1663 |Word|HD|HD|HD d|0~~24999|
1664 |Word|HSD|HSD|HSD d|0~~1023|
1665 |Word|HTD|HTD|HTD d|0~~95|
1666 |Word|HCD|HCD|HCD d|0~~95|
1667 |Word|HSCD|HSCD|HSCD d|0~~31|
1668 |Word|FD|FD|FD d|0~~8191|
1669 |Word|SFD|SFD|SFD d|0~~5999|
1670 |Word|FS|FS|FS d|0~~47|
1671
1672 **3)Configure the communication protocol**
1673
1674 [[image:image-20220831163923-7.png]]
1675
1676
1677
1678 **4)Cable Wiring**
1679
1680 Figure
1681
1682 [[image:image-20220831163406-2.png]][[image:image-20220831163553-6.png]]
1683
1684 Pin Definition Diagram
1685
1686 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830160232-3.png?rev=1.1||alt="image-20220830160232-3.png"]]
1687
1688 = Create communication with **Schneider PLC** =
1689
1690 == **Schneider MODBUS RTU** ==
1691
1692 **1)V-BOX Setting**
1693
1694 |=**Parameters**|=**Recommended**|=**Notes**
1695 |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
1696 |**Connection**|RS485|
1697 |**Baud rate**|19200|
1698 |**Data bit**|8|
1699 |**Parity**|Even|
1700 |**Stop bit**|1|
1701 |**PLC station No.**|1|
1702
1703 **2)Address List**
1704
1705 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
1706 |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
1707 |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
1708 |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
1709 |W|MW|DDDDDD|0 ~~ 999999|Output register
1710 |DW|MD|DDDDDD|0 ~~ 999999|Output register
1711
1712 **3)Configure the communication protocol**
1713
1714 [[image:image-20220902104329-1.png]]
1715
1716 **4)Cable Wiring**
1717
1718 **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
1719
1720 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220817154212-1.jpeg?width=554&height=315&rev=1.1||alt="image-20220817154212-1.jpeg" height="315" width="554"]]
1721
1722 = Create communication with Inovance** PLC** =
1723
1724 == **H3U serial protocol** ==
1725
1726 **1)V-BOX Settings**
1727
1728 |**Item**|**Settings**|**Note**
1729 |Protocol|INOVANCE H3U PLC|
1730 |Connection|RS422|
1731 |Baud rate|9600|
1732 |Data bit|7|
1733 |Parity|EVEN|
1734 |Stop bit|1|
1735 |PLC station No.|0|
1736
1737 **2)Address List**
1738
1739 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1740 |Bit|X|X|X o|0~~303237|
1741 |Bit|Y|Y|Y o|0~~303237|
1742 |Bit|M|M|M d|0~~99999|
1743 |Bit|T|T|T d|0~~99999|
1744 |Bit|C|C|C d|0~~99999|
1745 |Bit|SM|SM|SM d|8000~~999|
1746 |Bit|S|T|S d|0~~99999|
1747 |Bit|Lamp|Lamp|Lamp d|0~~0|
1748 |Word|X|X|X o|0~~303237|
1749 |Word|Y|Y|Y o|0~~303237|
1750 |Word|M|M|M d|0~~99999|
1751 |Word|T|T|T d|0~~99999|
1752 |Word|C|C|C d|0~~199|
1753 |Word|D|D|D d|0~~7999|
1754 |Word|S|S|S d|0~~99999|
1755 |Word|SD|SD|SD d|8000~~9999|
1756 |Word|R|R|R d|0~~32767|
1757
1758 **3)Configure the communication protocol**
1759
1760 [[image:image-20220831164626-1.png]]
1761
1762
1763
1764 **4)Cable Wiring**
1765
1766 Figure
1767
1768 [[image:image-20220831164646-2.png]][[image:image-20220831164700-3.png]]
1769
1770 Pin Definition Diagram
1771
1772 [[image:image-20220831164731-4.png]]
1773
1774 = Create communication with Panasonic** PLC** =
1775
1776 == **FP serial protocol** ==
1777
1778 **1)V-BOX Settings**
1779
1780 |**Item**|**Settings**|**Note**
1781 |Protocol|Panasonic FP MFWTOCOL|
1782 |Connection|RS232|
1783 |Baud rate|9600|
1784 |Data bit|8|
1785 |Parity|ODD|
1786 |Stop bit|1|
1787 |PLC station No.|1|
1788
1789 **2)Address List**
1790
1791 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1792 |Bit|X|X|X d|0~~9999|
1793 |Bit|Y|Y|Y d|0~~9999|
1794 |Bit|R|R|R d|0~~9999|
1795 |Bit|T|T|T d|0~~9999|
1796 |Bit|C|C|C d|0~~9999|
1797 |Bit|L|L|L d|0~~9999|
1798 |Word|WX|WX|WX d|0~~9999|
1799 |Word|WY|WY|WY d|0~~9999|
1800 |Word|WR|WR|WR d|0~~9999|
1801 |Word|WL|WL|WL d|0~~9999|
1802 |Word|LD|LD|LD d|0~~9999|
1803 |Word|DT|DT|DT d|0~~65535|
1804 |Word|FL|FL|FL d|0~~9999|
1805 |Word|EV|EV|EV d|0~~9999|
1806 |Word|SV|SV|SV d|0~~9999|
1807
1808 **3)Configure the communication protocol**
1809
1810 [[image:image-20220831165238-4.png]]
1811
1812
1813
1814 **4)Cable Wiring**
1815
1816 Figure
1817
1818 [[image:image-20220831165031-3.png]][[image:image-20220831165017-2.png]]
1819
1820 Pin Definition Diagram
1821
1822 [[image:image-20220831165008-1.png]]
1823
1824 = Create communication with LS** PLC** =
1825
1826 == **XBC serial protocol** ==
1827
1828 **1)V-BOX Settings**
1829
1830 |**Item**|**Settings**|**Note**
1831 |Protocol|LS XBC CNet|
1832 |Connection|RS232|
1833 |Baud rate|115200|
1834 |Data bit|8|
1835 |Parity|NONE|
1836 |Stop bit|1|
1837 |PLC station No.|1|
1838
1839 **2)Address List**
1840
1841 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1842 |Bit|P|P|P d|0~~2047|
1843 |Bit|M|M|M d|0~~2047|
1844 |Bit|L|L|L d|0~~11263|
1845 |Bit|K|K|K d|0~~16183|
1846 |Bit|F|F|F d|0~~2047|
1847 |Bit|D|D|D d|0~~32767|
1848 |Bit|R|R|R d|0~~32767|
1849 |Bit|U|U|U d|0~~4095|
1850 |Word|P|P|P d|0~~2047|
1851 |Word|M|M|M d|0~~2047|
1852 |Word|L|L|L d|0~~11263|
1853 |Word|K|K|K d|0~~16183|
1854 |Word|F|F|F d|0~~2047|
1855 |Word|C|C|C d|0~~2047|
1856 |Word|T|T|T d|0~~2047|
1857 |Word|D|D|D d|0~~32767|
1858 |Word|N|N|N d|0~~21503|
1859 |Word|R|R|R d|0~~32767|
1860 |Word|U|U|U d|0~~4095|
1861 |Word|Z|Z|Z d|0~~127|
1862 |Word|S|S|S d|0~~127|
1863
1864 **3)Configure the communication protocol**
1865
1866 [[image:image-20220831170147-1.png]]
1867
1868 **4)Cable Wiring**
1869
1870 Figure
1871
1872 [[image:image-20220831170306-4.png]][[image:image-20220831170254-3.png]]
1873
1874 Pin Definition Diagram
1875
1876 [[image:image-20220831170215-2.png]]
1877
1878 == **XGK FEnet Ethernet protocol** ==
1879
1880 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
1881
1882 **1)V-BOX Settings**
1883
1884 |**Items**|**Settings**|**Note**
1885 |Protocol|LG XGK FEnet(Ethernet)|
1886 |Connection|Ethernet|
1887 |Port No.|2004|
1888
1889 **2)Address List**
1890
1891 |**Type**|**Register**|**Range**|**Format**|**Note**
1892 |(% rowspan="14" %)Word|P|0~~2047|P d|
1893 |M|0~~2047|M d|
1894 |K|0~~2047|K d|
1895 |F|0~~2047|F d|
1896 |T|0~~2047|T d|
1897 |C|0~~2047|C d|
1898 |Z|0~~127|Z d|
1899 |S|0~~127|S d|
1900 |L|0~~11263|L d|
1901 |N|0~~21503|N d|
1902 |D|0~~32767|D d|
1903 |R|0~~32767|R d|
1904 |ZR|0~~65535|ZR d|
1905 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
1906
1907 **✎Note:**
1908
1909 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
1910 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
1911 * All bit registers are in the form of bits in word, and the range is the same as the word register;
1912
1913 **3)Communication Settings**
1914
1915 [[image:image-20220831171127-1.png]]
1916
1917 **4)Cable Wiring**
1918
1919 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1920
1921 = Create communication with **Modbus ** =
1922
1923 == **MODBUS RTU Slave (All function)** ==
1924
1925 Select the protocol "Modbus RTU Slave (All Fuction)",
1926
1927 Then set baud rate, port, stop bits, data bits, parity.
1928
1929 (% style="text-align:center" %)
1930 [[image:1624342015914-382.png||height="486" width="800" class="img-thumbnail"]]
1931
1932 == **MODBUS RTU Master** ==
1933
1934 Select the protocol "Modbus RTU Master",
1935
1936 Then set baud rate, port, stop bits, data bits, parity
1937
1938 (% style="text-align:center" %)
1939 [[image:1624348709622-711.png||queryString="width=809&height=493" height="488" width="800" class="img-thumbnail"]]
1940
1941 **address list**
1942
1943 (% class="table-bordered" %)
1944 |=(% scope="row" %)**Type**|=**Data Type**|=**Function code and description**
1945 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (Read Input Registers: Read the current binary value in one or more input registers)
1946 |06 (write single register: write a binary value to a holding register)
1947 |10 (write values to multiple addresses )
1948 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1949 |06 (write single register: write a binary value to a holding register)
1950 |10 (write values to multiple addresses )
1951 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1952 |06 (write single register: write a binary value to a holding register)
1953 |10 (write values to multiple addresses )
1954 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1955 |10 (write values to multiple addresses )
1956 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1957 |05 (Force a single coil to force the on/off state of a logic coil)
1958 |0F (Write multiple bits, ie write continuously)
1959 |(% rowspan="3" %)1|02 (Read the input state)
1960 |05 (Force a single coil to force the on/off state of a logic coil)
1961 |0F (Write multiple bits)
1962 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1963 |05 (Force a single coil to force the on/off state of a logic coil)
1964 |0F (Write multiple bits)
1965 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1966 |0F (Write multiple bits)
1967
1968 == **MODBUS TCP Slave (All function)** ==
1969
1970 Supported series: MODBUS TCP controller
1971
1972 V-B0X works as MODBUS TCP MASTER connecting with TCP SLAVE
1973
1974 **1)V-BOX Setting**
1975
1976 |**Items**|**Settings**|**Note**
1977 |Protocol|MODBUS TCP Slave (All function)|
1978 |Connection|Ethernet|
1979 |Port No.|502|
1980 |PLC station No.|1
1981
1982 **2)Address List**
1983
1984 |=**Type**|=**Data Type**|=**Function code & Description**
1985 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
1986 |06 (write single register: write a binary value to a holding register)
1987 |10 (write values to multiple addresses )
1988 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1989 |06 (write single register: write a binary value to a holding register)
1990 |10 (write values to multiple addresses )
1991 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1992 |06 (write single register: write a binary value to a holding register)
1993 |10 (write values to multiple addresses )
1994 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1995 |10 (write values to multiple addresses )
1996 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1997 |05 (Force a single coil to force the on/off state of a logic coil)
1998 |0F (Write multiple bits, ie write continuously)
1999 |(% rowspan="3" %)1|02 (Read the input state)
2000 |05 (Force a single coil to force the on/off state of a logic coil)
2001 |0F (Write multiple bits)
2002 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
2003 |05 (Force a single coil to force the on/off state of a logic coil)
2004 |0F (Write multiple bits)
2005 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
2006 |0F (Write multiple bits)
2007
2008 **3)Communication Settings**
2009
2010 Configure V-BOX Ethernet IP in Networking Settings
2011
2012 [[image:image-20220902111833-3.png]]
2013
2014
2015 Configure PLC Ethernet IP in Communication;
2016
2017 [[image:image-20220902111121-1.png]]
2018
2019 **4)Cable Wiring**
2020
2021 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2022
2023 == **communicate with VB inverter** ==
2024
2025 [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20VB%20inverter.zip]]
2026
2027 = **User define protocol** =
2028
2029 More serial port script instruction,please refer manual:[[Lua script function>>doc:V-BOX.V-Net.Manual.04 Lua Script.01 Lua Functions.WebHome]]~-~-->[[3.Serial port operation>>url:http://docs.we-con.com.cn/wiki/vbox/view/HMI/04.Lua%20script%20%20function%20and%20operation/01.Lua%20script%20function/#H3.Serialportoperation]]
2030
2031 == **Read the temperature sensor.** ==
2032
2033 the commond format is as beliow:
2034
2035 Send commond:01 03 02 00 00 03 04 73
2036
2037 Feedback commond:01 03 06 07 F7 0E 7E B7 35
2038
2039 Temperature data:07 F7,desimal = 2039,it means temperature is 20.39℃.
2040
2041 Humidity data:0E 7E,desimal = 3710, it mean humidity is 37.10%RH.
2042
2043 Script Demo:
2044
2045 ~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~--
2046
2047 function com.main()
2048 ~-~-dosomething
2049 openPlc()
2050 end
2051 function openPlc()
2052 if obj then
2053 ~-~- If the serial port opened,then read/write data by timing
2054
2055 local wri = string.pack(">HHHH",0X0103,0X0200,0X0003,0X0473)
2056 local arr = reading(wri)
2057 ~-~- if arr ~~=nil then
2058 ~-~- if arr[1] ==33 and arr[2] ==v[2][2] and arr[3] ==v[2][3] then
2059 ~-~- local A = arr[4]*256
2060 ~-~- local B = A+arr[5]
2061 ~-~- addr_setword(v[1],B)
2062 ~-~- end
2063 ~-~- end
2064
2065 else
2066 ~-~-judge if there is a serial object, then initialize and open the serial port
2067 local configs = {
2068 name = 'COM1', ~-~-Select serial port COM1
2069 mode = 485, ~-~-Communication mode RS485
2070 baud_rate = 9600, ~-~-Baud rate 9600
2071 stop_bit = 1, ~-~-stop bit 1
2072 data_len = 8, ~-~-data length 8
2073 check_bit = 'NONE', ~-~-no parity
2074
2075 }
2076 obj,err = serial.open(configs) ~-~-Open serial port
2077 if not obj then
2078 print("serial open :failed", err) ~-~- Open serial port failed
2079 end
2080 end
2081 end
2082
2083 function reading(wri)
2084 obj:flush() ~-~- Clear serial port
2085 obj:write(wri) ~-~- Write serial port
2086 print(string.byte(wri,1,#wri))
2087 obj:flush() ~-~- Clear serial port 
2088 local readed =obj:read(9,1000) ~-~- Read 9 bytes, timeout 1 second
2089 if readed and readed ~~= "" then 
2090 ~-~- judge that a non-empty string is read
2091 print(string.byte(readed,1,#readed))
2092 a={string.byte(readed, 1, #readed)}
2093 if nil ~~= a[4] and nil ~~= a[5] and nil ~~= a[6] and nil ~~= a[7] then
2094 a1=a[4]*256+a[5]
2095 a2=a[6]*256+a[7]
2096 addr_setword("@HDW0",a1)
2097 addr_setword("@HDW1",a2)
2098 end
2099 return {string.byte(readed, 1, #readed)}
2100 elseif readed == nil then
2101 print("serial read err:", err or "")
2102 return nil
2103 end
2104 return nil
2105 end
2106
2107 ~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-