Wiki source code of 1 Communication

Version 219.1 by Hunter on 2023/03/18 16:04

Show last authors
1 = Create communication with WECON PLC =
2
3 == **LX3V Serial Protocol** ==
4
5 Supported series: Wecon LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
6
7 **1)V-BOX setting**
8
9 |**Item**|**Settings**|**Note**
10 |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
11 |Connection|RS422/RS485|
12 |Baud rate|9600|
13 |Data bit|7|
14 |Parity|EVEN|
15 |Stop bit|1|
16 |PLC station No.|1|
17
18 **2)Address List**
19
20
21 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
22 |(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
23 |Y|Y|Y o|0~~303237|
24 |M|M|M d|0~~99999|
25 |T|T|T d|0~~99999|
26 |C|C|C d|0~~99999|
27 |S|S|S d|0~~99999|
28 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
29 |Y|Y|Y o|0~~303237|
30 |M|M|M d|0~~99999|
31 |T|T|T d|0~~99999|
32 |C|C|C d|0~~199|
33 |D|D|D d|0~~7999|
34 |S|S|S d|0~~99999|
35 |SD|SD|SD d|8000~~9999|
36
37 **3)Configure the communication protocol**
38
39 [[image:image-20220824152217-1.png||alt="图片-20220824152217-1.png"]]
40
41 **4)Cable Wiring**
42
43 * **RS422**
44
45 [[image:image-20220824120614-5.png]]
46
47 * **RS485**
48
49 [[image:image-20220824120524-3.png]]
50
51 == **LX5V Serial Protocol** ==
52
53 This example introduces the establishment of serial port communication between V-BOX and LX5V. It is introduced through three parts: PLC software configuration, V-BOX software configuration, and hardware wiring.
54
55 **Software configuration of PLC**
56
57 **1)PLC programming software**
58
59 [[image:image-20220824142722-1.png]]
60
61 **2)New PLC project**
62
63 Click New Project and select the PLC model.
64
65 [[image:image-20220822172623-2.png]]
66
67 **3)Set Serial port parameters**
68
69 Follow the steps below to configure Serial port parameters
70
71 Baud rate:115200
72
73 Data bit:8
74
75 Stop bit:1
76
77 Parity:No verification
78
79 [[image:image-20220822172657-3.png]]
80
81 **4)Registers list**
82
83 [[image:image-20220822172730-4.png]]
84
85 **V-BOX software configuration**
86
87 **1)V-BOX programming software**
88
89 [[image:image-20220824104124-1.png]]
90
91 **2)V-NET add device**
92
93 Open V-NET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the access key, password and remark, to add the device.
94
95 [[image:image-20220824104909-2.png]]
96
97 **3)Set communication port parameters**
98
99 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
100
101 Baud rate:115200
102
103 Data bit:8
104
105 Stop bit:1
106
107 Parity:No verification
108
109 [[image:image-20220824142130-1.png]]
110
111 **hardware connection**
112
113 **1)Hardware wiring diagram**
114
115 [[image:image-20220824142546-2.png]]
116
117 [[image:image-20220824142643-3.png]]
118
119 The above are all the steps for establishing serial port communication between V-BOX with LX5V PLC.
120
121 == **LX5V-N Ethernet protocol** ==
122
123 This example introduces the establishment of Ethernet communication between V-BOX and LX5V-N. It is introduced through three parts: PLC software configuration, V-BOX software configuration, and hardware wiring.
124
125 **Software configuration of PLC**
126
127 **1)PLC programming software**
128
129 [[image:image-20220824142722-1.png]]
130
131 **2)New PLC project**
132
133 Click New Project and select the PLC model.
134
135 [[image:image-20220824143613-1.png]]
136
137 **3)Set Ethernet port parameters**
138
139 Follow the steps below to configure Ethernet parameters
140
141 PLC IP address:192.168.39.200
142
143 default gateway:192.168.39.1
144
145 subnet mask:255.255.255.0
146
147 [[image:image-20220824143744-2.png]]
148
149 **4)Registers list**
150
151 [[image:image-20220822172730-4.png]]
152
153 (% id="cke_bm_22473S" style="display:none" %)** **(%%)**V-BOX software configuration**
154
155 **1)V-BOX programming software**
156
157 [[image:image-20220824104124-1.png]]
158
159 **2)V-NET add device**
160
161 Open V-NET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the access key, password and remark, to add the device.
162
163 [[image:image-20220824104909-2.png]]
164
165 **3)Set communication Protocol**
166
167 Click Communication to configure the LX5V plc protocol and IP address.
168
169 [[image:image-20220824144619-1.png]]
170
171 **hardware connection**
172
173 **1)Hardware wiring diagram**
174
175 [[image:image-20220824151127-2.png]]
176
177 The above are all the steps for establishing ethernet communication between V-BOX with LX5V PLC.
178
179 = Create communication with Allen-Bradley(**Rockwell**)** PLC** =
180
181 == **DF1 Advanced Protocol** ==
182
183 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
184
185 **1) V-Box Settings**
186
187 |=Item|=Recommended |=Note
188 |=Protocol|Allen Bradley DF1 Advanced|
189 |=Connection|RS232|
190 |=Baud rate|19200|
191 |=Stop bits|1|
192 |=Data bits|8|
193 |=Parity|None|
194 |=PLC Station No.|1|
195 |=HMI Station No.|0|
196
197 **2) Address List**
198
199 |=**Type**|=**Device registers**|=**Format**|=**Range**|=Note
200 |(% colspan="1" rowspan="7" %)Bit|I1|I1ddd.dd|0.0~~255.15|Only able to communicate with file number I1
201 |O0|O0ddd.dd|0.0~~255.15|Only able to communicate with file number O0
202 |S2|S2ddd.dd|0.0~~255.15|Only able to communicate with file number S2
203 |B3|B3ddd.dd|0.0~~255.15|Only able to communicate with file number B3
204 |BN|BNddddd.dd|0.0~~99255.15|(((
205 Bit data file B0~~B99
206
207 First two digits is for file number
208
209 For example, BN13001.00 represents file number B13, address 001, the 0th bit.
210 )))
211 |N7|N7ddd.dd|0.0~~255.15|Only able to communicate with file number N7
212 |NN|NNddddd.dd|0.0~~99255.15|(((
213 Integer data file bit format N0~~N99
214
215 First two digits is for file number
216
217 For example, NN13001.00 represents file number N13, address 001, the 0th bit.
218 )))
219 |(% rowspan="11" %)Word|S2|S2ddd|0~~255|Only able to communicate with file number S2
220 |T4S|T4Sddd|0~~255|Only able to communicate with file number T4 (Timer Preset Value)
221 |T4P|T4Pddd|0~~255|Only able to communicate with file number T4 (Timer Accumulator Value)
222 |TNS|TNSddddd|0~~99255|(((
223 Timer Preset Value
224
225 First two digits is for file number
226
227 For example, TNS99255 represents file number T99, address 255.
228 )))
229 |TNP|TNPddddd|0~~99255|(((
230 Timer Accumulator Value
231
232 First two digits is for file number
233
234 For example, TNP99255 represents file number T99, address 255.
235 )))
236 |C5S|C5Sddd|0~~255|Only able to communicate with file number C5 (Counter Preset Value)
237 |C5P|C5Pddd|0~~255|Only able to communicate with file number C5 (Counter Accumulator Value)
238 |CNS|CNSddddd|0~~99255|(((
239 Counter Preset Value
240
241 First two digits is for file number
242
243 For example, CNS99255 represents file number C99, address 255.
244 )))
245 |CNP|CNPddddd|0~~99255|(((
246 Counter Accumulator Value
247
248 First two digits is for file number
249
250 For example, CNP99255 represents file number C99, address 255.
251 )))
252 |N7|N7ddd|0~~255|Only able to communicate with file number N7
253 |NN|NNddd|0~~99255|(((
254 Integer data file
255
256 First two digits is for file number
257
258 For example, NN99255 represents file number N99, address 255.
259 )))
260 |(% colspan="1" rowspan="3" %)Double Word|F8|F8ddd|0~~255|(((
261 Only able to communicate with file number N7
262 )))
263 |FN|FNddddd|0~~99255|(((
264 Floating point data file
265
266 First two digits is for file number
267
268 For example, FN99255 represents file number F99, address 255.
269 )))
270 |LN|LNddddd|0~~99255|Long
271
272 **3) Cable Wiring**
273
274 (% style="text-align:center" %)
275 [[image:ABRS232.gif]]
276
277 (% class="wikigeneratedid" id="HMicroLogixA0Protocol" %)
278 (% id="cke_bm_5621S" style="display:none" %)** **
279
280 == **MicroLogix Protocol** ==
281
282 (% class="wikigeneratedid" %)
283 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
284
285 **1)V-BOX setting**
286
287 |**Item**|**Settings**|**Note**
288 |Protocol|Allen-Bradley DF1 Advanced|
289 |Connection|RS232|
290 |Baud rate|19200|
291 |Data bit|8|
292 |Parity|None|
293 |Stop bit|1|
294 |PLC station No.|1|
295
296 **2)Address List**
297
298 |**Type**|**Device registers**|**Format**|**Range**|**Note**
299 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
300 |O|O d.d|0.0~~255.15|
301 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
302 |S|S d.d|0.0~~255.15|
303 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
304 |(% rowspan="9" %)Word|S|S d|0~~255|
305 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
306 |TP|TP nnhh|0~~ffff
307 |CS|CS nnhh|0~~ffff
308 |CP|CP nnhh|0~~ffff
309 |N|N nnhh|0~~ffff
310 |C|C nnhh|0~~ffff
311 |T|T nnhh|0~~ffff
312 |R|R nnhh|0~~ffff
313
314 **3)Configure the communication protocol**[[image:image-20220824152928-1.png]]
315
316 **4)Configure the communication protocol**
317
318 [[image:image-20220824110724-1.png]]
319
320 == **Micro850_FreeTag Protocol** ==
321
322 (((
323 (((
324 This example introduces the establishment of Ethernet communication between Wecon V-box and CompactLogix L1769. It is introduced through three parts: PLC software configuration, V-box software configuration, and hardware wiring.
325 )))
326 )))
327
328 (((
329 (% class="wikigeneratedid" id="HSoftwareconfigurationofPLC" %)
330 (((
331 **Software configuration of PLC**
332 )))
333
334 (% class="wikigeneratedid" id="HPLCprogrammingsoftware" %)
335 (((
336 **1)PLC programming software**
337 )))
338
339 [[image:image-20220714162600-1.png]]
340
341 (% class="wikigeneratedid" id="HNewPLCproject" %)
342 (((
343 **2)New PLC project**
344 )))
345
346 (((
347 (((
348 Click New Project and select the PLC model.
349 )))
350 )))
351
352 (((
353 [[image:image-20220714162617-2.png]]
354 )))
355
356 (((
357
358
359 [[image:image-20220714162652-4.png]]
360 )))
361
362 (((
363 (% class="wikigeneratedid" id="HSetEthernetparameters" %)
364 (((
365 **3)Set Ethernet parameters**
366 )))
367
368 (((
369 (((
370 (((
371 Follow the steps below to configure Ethernet parameters
372 )))
373 )))
374 )))
375
376 (((
377 (((
378 (((
379 PLC IP address:192.168.40.101
380 )))
381 )))
382 )))
383
384 (((
385 (((
386 (((
387 default gateway:192.168.40.1
388 )))
389 )))
390 )))
391
392 (((
393 (((
394 (((
395 subnet mask:255.255.255.0
396 )))
397 )))
398 )))
399
400 (((
401 [[image:image-20220714162713-5.png]]
402 )))
403
404 (((
405
406 )))
407
408 (((
409 (% class="wikigeneratedid" id="HV-boxsoftwareconfiguration" %)
410 (((
411 **V-box software configuration**
412 )))
413
414 (% class="wikigeneratedid" id="HV-boxprogrammingsoftware" %)
415 (((
416 **1)V-box programming software**
417 )))
418
419 (% class="wikigeneratedid" %)
420 (((
421 [[image:image-20220714162725-6.png]]
422 )))
423
424 (% class="wikigeneratedid" id="HConfiguredevicenetwork" %)
425 (((
426 **2)Configure device network**
427 )))
428
429 (((
430 (((
431 (((
432 Click the Configuration Download button[[image:image-20220714115308-8.png||height="22" width="15"]], It is used to configure the device network, update the device time, obtain the device machine code, check the device network, etc.
433 )))
434
435 (((
436 In the example below, the IP address of V-Box is configured as 192.168.40.66, and the networking method is 4G connection
437 )))
438 )))
439 )))
440
441 (((
442 (((
443 [[image:image-20220714162737-7.png]]
444
445
446 )))
447 )))
448 )))
449 )))
450
451 (% class="wikigeneratedid" id="HV-netadddevice" %)
452 (((
453 **3)V-net add device**
454 )))
455 )))
456
457 (((
458 (((
459 Open VNET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the device machine code/product code, device password, and device alias to add the device.   [[image:image-20220714162752-8.png]]
460 )))
461
462
463 )))
464
465 (((
466 (% class="wikigeneratedid" id="HSetcommunicationportparameters" %)
467 (((
468 **4)Set communication port parameters**
469 )))
470
471 (((
472 In the device list on the left, find the Vbox that communicates with the L1769, click it and select configuration,communication port configuration in the main interface to add a communication protocol.
473 )))
474
475 [[image:image-20220714162805-9.png]]
476 )))
477
478 (((
479 The communication port is selected as Ethernet, the device type is selected as Allen-Bradley, the protocol is Allen-BradleyMicro850_FreeTag EthemetIP, and the IP is the internal IP address of the L1769 PLC. The port number is 44818.
480 )))
481
482 [[image:image-20220824164346-1.png]]
483
484
485 (((
486 After adding the protocol Allen-BradleyMicro850_FreeTag, click[[image:image-20220714143838-2.png]]icon add label.[[image:image-20220714162827-11.png]]
487 )))
488
489 (% class="wikigeneratedid" id="HEngineeringproduction" %)
490 (((
491 **5)Engineering production**
492 )))
493
494 (% class="wikigeneratedid" %)
495 (((
496 (((
497 According to your own needs, use the V-NET client software to edit the required data monitoring points.
498 )))
499
500 [[image:image-20220714162841-12.png]]
501
502
503 (((
504 **hardware connection**
505 )))
506 )))
507
508 (((
509 **1)Hardware wiring diagram**
510 )))
511
512 (((
513 (((
514 This example introduces Wecon V-box with Allen-Bradley L1769 PLC to establish communication through Ethernet. The connection diagram is as follows:
515 )))
516
517 [[image:image-20220714162856-13.png]]
518
519 (((
520 The above are all the steps for establishing Ethernet communication between Wecon V-box with CompactLogix L1769 PLC.
521
522 == **Ethernet DF1 Protocol** ==
523
524 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Allen-Bradley%20Ethernet%20DF1.zip]]
525
526 = Create communication with **Crouzet PLC** =
527
528 == **CROUZET M3 (FBD)** ==
529
530 **1)V-BOX setting**
531
532 |=Item|=Recommended |=Note
533 |=Protocol|CROUZET M3 (FBD)|
534 |=Connection|RS232|
535 |=Baud rate|115200|
536 |=Stop bits|1|
537 |=Data bits|7|
538 |=Parity|EVEN|
539
540 **2)Address List**
541
542 |=**Type**|=**Device registers**|=**Format**|=**Range**|=Note
543 |(% rowspan="4" %)Bit|I|I DD|1~~99|Input
544 |SLIBit|SLIBit DD.dd|1.0~~24.15|Serial Link Input
545 |SLOBit|SLOBit DD.dd|25.0~~48.15|Serial Link Output(Read only)
546 |State|State D|1~~1|PLC state(Read only)
547 |(% rowspan="5" %)Word|AI|AI DD|1~~99|Analog Input
548 |SLIn|SLIn DD|1~~24|Serial Link Input
549 |SLOut|SLOut DD|25~~48|Serial Link Output(Read only)
550 |Time|Time D|1~~6|(((
551 Time1: Second
552
553 Time2: Minute
554
555 Time3: Hour
556
557 Time4: Day
558
559 Time5: Month
560
561 Time6: Year
562 )))
563 |Order|Order D|1~~1|(((
564 Running command(Write only)
565
566 ~=2: Run mode; =1: Stop mode;
567 )))
568
569 **3)Cable Wiring**
570
571 (% style="text-align:center" %)
572 [[image:CrouzetRS232 VBox.png]]
573
574 {{info}}
575 **✎Note: **As the wiring diagram indicated, this protocol requires the DB9 serial port pin 4. But pin 4 is undefined for all V-Box, so it need the user to solder a Pull-up resistor to make the pin 4 working. As for how to solder the resistor on the motherboard, please contact with Wecon technical support for the details.
576 {{/info}}
577
578 = Create communication with **Siemens PLC** =
579
580 == **S7-200 Smart Ethernet Protocol** ==
581
582 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20S7-200%20Smart.zip]]
583
584
585 == **S7-300 Ethernet Protocol** ==
586
587 Supported Series: Siemens S7-300 series PLC
588
589 **1)V-BOX setting**
590
591 |**Items**|**Settings**|**Note**
592 |Protocol|Simens S7-300 Ethernet|
593 |Connection|Ethernet|
594 |Port No.|102|
595 |PLC station No.|2|Need to be same as the PLC setting
596
597 **2)Address List**
598
599 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
600 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
601 |Q|Q|Q ddddd.o|0.0~~99999.7|
602 |M|M|M ddddd.o|0.0~~99999.7|
603 |DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
604 nn: block number;
605
606 dddd: address;
607 )))
608 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
609 |Q|QW|QW ddddd|0~~99999|
610 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
611 |MW|MW ddddd|0~~99999|(((
612 MW0=MB(0~~1)
613
614 MW2=MB(2~~3)
615
616 Address value is a multiple of 2
617 )))
618 |MD|MD ddddd|0~~99999|(((
619 MD0=MB(0~~3)
620
621 MD4=MB(4~~7)
622
623 Address value is a multiple of 4
624 )))
625 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
626 nn: block number;
627
628 dddd: address
629 )))
630 |DBxDBW|DBxDBW nndddd|0~~99999999
631 |DBxDBD|DBxDBD nndddd|0~~99999999
632
633 **3)Configure the communication protocol**
634
635 [[image:image-20220824161345-1.png]]
636
637 **4)Cable Wiring**
638
639 [[image:image-20220824161450-2.png]]
640 )))
641 )))
642
643 == **S7-1200 Ethernet Protocol** ==
644
645 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]]
646
647 == **S7-XXX Ethernet Protocol** ==
648
649 Supported Series: Siemens S7-400, S7-1200 and S7-1500
650
651 **1)V-BOX setting**
652
653 |=**Items**|=**Settings**|=**Note**
654 |Protocol|Siemens S7-XXX|
655 |Connection|Ethernet|
656 |Port No.|102|
657 |Device No.|Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|
658 |HMI No.|Rack (Default as 0)|
659
660 Slot from TIA Portal is equal to Device No. of V-net
661
662 Rack from TIA Portal is equal to HMI No. of V-net
663
664 [[image:image-20220824162459-3.png]]
665
666 [[image:image-20220824163305-2.png]]
667
668 **2)Address List**
669
670 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
671 |(% rowspan="4" %)Bit|I|I|M d.o|(((
672 d:0~-~-9999
673
674 o:0-7
675 )))|
676 |Q|Q|Q d.o|(((
677 d:0~-~-9999
678
679 o:0-7
680 )))|
681 |M|M|M d.o|(((
682 d:0~-~-9999
683
684 o:0-7
685 )))|
686 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
687 nn:0-9999,
688
689 dddd:0-9999,
690
691 o:0-7
692 )))|(((
693 nn:DB No.
694
695 dddd:address value
696
697 o: digit address
698 )))
699 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
700 |M|MW|MW d|d:0-99999|(((
701 MW0=MB(0~~1)
702
703 MW2=MB(2~~3)
704
705 Address value is a multiple of 2
706 )))
707 |M|MD|MD d|d:0-99999|(((
708 MD0=MB(0~~3)
709
710 MD4=MB(4~~7)
711
712 Address value is a multiple of 4
713 )))
714 |I|IW|IW d|d:0-99999|
715 |Q|QW|QW d|d:0-99999|
716 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
717 nn:0-9999
718
719 dddd:0-9999
720 )))|(((
721 nn:DB No.
722
723 dddd:address value
724 )))
725 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
726 nn:0-9999
727
728 dddd:0-9999
729 )))|(((
730 nn:DB No.
731
732 dddd:address value
733
734 Address value is a multiple of 2
735 )))
736 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
737 nn:0-9999
738
739 dddd:0-9999
740 )))|(((
741 nn:DB No.
742
743 dddd:address value
744
745 Address value is a multiple of 4
746 )))
747
748 **3)Configure the communication protocol**
749
750 [[image:image-20220824163448-3.png]]
751
752 **✎Note:**
753
754 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three V-BOX.
755 * V-BOX access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
756
757 **4)Cable Wiring**
758
759 [[image:image-20220824162342-2.png]]
760
761 == **LOGO Ethernet Protocol** ==
762
763 Supported Series: Siemens Logo 0BA0, 0BA1 series
764
765 **V-BOX Settings**
766
767
768 |**Items**|**Settings**|**Note**
769 |Protocol|Siemens LOGO|
770 |Connection|Ethernet|
771 |Port No.|102|
772 |PLC station No.|2|
773
774 **Address List**
775
776
777 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
778 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
779 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
780 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
781 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
782 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
783 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
784 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
785 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
786 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
787 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
788 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
789 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
790 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
791 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
792 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
793
794 **PLC Settings in LOGO Software:**
795
796 Click [Tools]~-~-[Ethernet Connections],shown as below.
797
798 (% style="text-align:center" %)
799 [[image:PIStudio.12\.PLC protocols.WebHome@12.PLC Protocol_html_8b9d2322edf89519.png]]
800
801 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
802
803 (% style="text-align:center" %)
804 [[image:PIStudio.12\.PLC protocols.WebHome@image-20221228142937-4.png]]
805
806 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
807
808 (% style="text-align:center" %)
809 [[image:PIStudio.12\.PLC protocols.WebHome@image-20221228143047-5.png]]
810
811 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
812
813 (% style="text-align:center" %)
814 [[image:PIStudio.12\.PLC protocols.WebHome@image-20221228143246-6.png]]
815
816 **V-BOX Communication Settings**
817
818 Set PLC IP in [IP Address] settings;
819
820 (% style="text-align:center" %)
821 [[image:LldwDGntf4.png]]
822
823 Enable V-BOX Ethernet in [Network];
824
825 (% style="text-align:center" %)
826 [[image:WgvjfWbQif.png]]
827
828 TSAP setting
829
830 * The initialization script needs to set the source TSAP address and the target TSAP address, otherwise the communication will not be successful.
831
832 {{code language="LUA"}}
833 function init.main()
834 addr_setword("@W_0#HSW1200",8192) -- Set the source TSAP address
835 addr_setword("@W_0#HSW1201",4096) -- Set the destination TSAP address
836 end
837 {{/code}}
838
839 Note: The name of the test script is init, 8192 and 4096 are the data used for the test, there is no HSW address in the register option, but you can directly set the value of the corresponding address through the code.
840
841 **✎Note:**
842
843 * **Communication port configuration: **
844 ** Continuous length needs to be set to 0.
845 ** Integration interval needs to be set to 1. (no change may result in data errors)
846 ** Set Port and Device Station NO.
847 ** Other set as defaulted.
848 * **Notes on the use of registers:**
849 ** Register VD: Use only registers that are multiples of 4, such as 0, 4, 8, etc.
850 ** Register VW: Use only registers thay are multiples of 2, such as 0, 2, 4 etc. (Using an odd-length register may result in data errors, such as 2 3 4 )
851
852 = Create communication with **Mitsubishi PLC** =
853
854 == **FX1S,1N,2N Serial Protocol** ==
855
856 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
857
858 **1)V-BOX Settings**
859
860 |**Item**|**Settings**|**Note**
861 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
862 |Connection|RS422/RS485/RS232|
863 |Baud rate|9600~~115200|
864 |Data bit|7/8|
865 |Parity|EVEN/Odd/None|
866 |Stop bit|1/2|
867 |PLC station No.|1~~255|
868
869 **2)Address List**
870
871 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
872 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
873 |Y|Y|Y o|0~~303237|
874 |M|M|M d|0~~99999|
875 |T|T|T d|0~~99999|
876 |C|C|C d|0~~99999|
877 |S|S|S d|0~~99999|
878 |SM|SM|SM d|8000~~9999|
879 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
880 |Y|Y|Y o|0~~303237|
881 |M|M|M d|0~~99999|
882 |T|T|T d|0~~99999|
883 |C|C|C d|0~~199|
884 |D|D|D d|0~~7999|
885 |S|S|S d|0~~99999|
886 |SD|SD|SD d|8000~~9999|
887
888 **3)Configure the communication protocol**
889
890 [[image:image-20220825102844-3.png]]
891
892 **4)Cable Wiring**
893
894 * **RS422**
895
896 [[image:image-20220825103350-4.png]]
897
898 [[image:image-20220825100845-4.png]]
899
900
901 == **FX3U,3G,3GA Serial Protocol** ==
902
903 Supported Series: Mitsubishi FX3U, FX3G, FX3GA series
904
905 **1)V-BOX Settings**
906
907 |**Item**|**Settings**|**Note**
908 |Protocol|Mitsubishi FX3U/3G/3GA|
909 |Connection|RS422/RS485/RS232|
910 |Baud rate|9600~~115200|
911 |Data bit|7/8|
912 |Parity|EVEN/Odd/None|
913 |Stop bit|1/2|
914 |PLC station No.|1~~255|
915
916 **2)Address List**
917
918 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
919 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
920 |Y|Y|Y o|0~~303237|
921 |M|M|M d|0~~99999|
922 |T|T|T d|0~~99999|
923 |C|C|C d|0~~99999|
924 |S|S|S d|0~~99999|
925 |SM|SM|SM d|8000~~9999|
926 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
927 |Y|Y|Y o|0~~303237|
928 |M|M|M d|0~~99999|
929 |T|T|T d|0~~99999|
930 |C|C|C d|0~~199|
931 |D|D|D d|0~~7999|
932 |S|S|S d|0~~99999|
933 |SD|SD|SD d|8000~~9999|
934
935 **3)Configure the communication protocol**
936
937 [[image:image-20220825102649-2.png]]
938
939 **4)Cable Wiring**
940
941 * **RS422**
942
943 [[image:image-20220825103421-5.png]]
944
945 [[image:image-20220825100845-4.png]]
946
947
948 == **FX3U Ethernet Protocol** ==
949
950 Supported Modules: FX3U-ENET-ADP, FX3U-ENET-L
951
952 **1)V-BOX Settings**
953
954 |Items|Settings|Note
955 |Protocol|Mitsubishi FX3U|
956 |Connection|Ethernet|
957 |Port No.|5009|Must be the same as the PLC setting
958 |PLC station No.|0|
959
960 **2)Address List**
961
962 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
963 |(% colspan="1" rowspan="7" %)Bit|X|X|X OOO|0~~377|
964 |Y|Y|Y OOO|0~~377|
965 |M|M|M DDDD|0~~7679|
966 |SM|SM|SM DDDD|8000~~8511|
967 |S|S|S DDDD|0~~4095|
968 |TS|TS|TS DDD|0~~511|
969 |CS|CS|CS DDD|0~~255|
970 |(% colspan="1" rowspan="9" %)Word|CN|CN|CN DDD|0~~199|
971 |TN|TN|TN DDD|0~~511|
972 |D|D|D DDDD|0~~7999|
973 |SD|SD|SD DDDD|8000~~8511|
974 |R|R|R DDDDD|0~~32767|
975
976 **3)Ethernet Module Settings**
977
978 FX3U-ENET-L module configuration
979 Set up the FX3U-ENET-L Ethernet module settings as follows.
980 Select the module location, which in this document is Module 0.
981
982 [[image:image-20221116105850-1.png]]
983
984 Select "Operational setting" to enter the following screen.
985
986 The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default.
987
988 [[image:image-20221116105947-1.png]]
989
990 Select "Open setting" to enter the setting interface, the settings are as follows.
991
992 The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the
993
994 Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module.
995
996 [[image:image-20221116110802-1.png]]
997
998 Click on "transter setup" - "PC side I/F setting", see the following figure.
999
1000 After setting, the first download must use the programming cable, as shown in the figure; after that, can
1001
1002 use the IP set in the "Ethernet board" to communicate directly with the network cable.
1003
1004 [[image:image-20221116110832-2.png||height="423" width="708"]]
1005
1006 Read and write data from the Ethernet module
1007
1008 [[image:image-20221116110907-3.png]]
1009
1010 Set "Transter setup" to COM communication, and read or write operation as shown below
1011
1012 [[image:image-20221116110917-4.png]]
1013
1014 **4)PLC Settings (GX Works 2)**
1015
1016 Create a blank FX5U project
1017
1018 Find Current Connection in the navigation
1019
1020 [[image:image-20221116111427-1.png||height="421" width="705"]]
1021
1022 Select Connection Channel List
1023
1024 Select Ethernet board communication
1025
1026 [[image:image-20221116111451-2.png||height="421" width="705"]]
1027
1028 Select Ethernet Module
1029 Set the IP address of the PLC
1030
1031 [[image:image-20221116111509-3.png||height="666" width="699"]]
1032
1033 Read or write PLC data, in this document is read
1034
1035 [[image:image-20221116111651-4.png||height="416" width="697"]]
1036
1037 [[image:image-20221116111727-5.png||height="416" width="697"]]
1038
1039 **4)Configure the communication protocol**
1040
1041 [[image:image-20221119101946-2.png||height="395" width="695"]]
1042
1043 == **FX5U Serial Protocol** ==
1044
1045 Mitsubishi FX5U series PLC
1046
1047 **1)V-BOX Settings**
1048
1049 |**Item**|**Settings**|**Note**
1050 |Protocol|Mitsubishi FX5U|
1051 |Connection|RS422/RS485|
1052 |Baud rate|9600|
1053 |Data bit|7|
1054 |Parity|Odd|
1055 |Stop bit|1|
1056 |PLC station No.|1~~255|Need to be the same as PLC settings
1057
1058 **2)Address List**
1059
1060 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1061 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1062 |Y|Y|Y o|0~~303237|
1063 |M|M|M d|0~~99999|
1064 |B|B|B h|0~~7FFF|
1065 |F|F|F d|0~~32767|
1066 |SB|SB|SB h|0~~7FFF|
1067 |TS|TS|TS d|0~~1023|
1068 |TC|TC|TC d|0~~1023|
1069 |STS|STS|STS d|0~~1023|
1070 |STC|STC|STS d|0~~1023|
1071 |CS|CS|CS d|0~~1023|
1072 |CC|CC|CC d|0~~1023|
1073 |SM|SM|SM d|0~~9999|
1074 |L|L|L d|0~~32767|
1075 |S|S|S d|0~~4095|
1076 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1077 |TN|TN|TN d|0~~1023|
1078 |STN|STN|STN d|0~~1023|
1079 |CN|CN|CN d|0~~1023|
1080 |R|R|R d|0~~32767|
1081 |SW|SW|SW h|0~~7FFF|
1082 |Z|Z|Z d|0~~23|
1083 |D|D|D d|0~~7999|
1084 |SD|SD|SD d|0~~11999|
1085
1086 **3)PLC Settings (GX Works 3)**
1087
1088 Create a blank FX5U project
1089
1090 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
1091
1092 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5c9cb13fac1e6c93.png?width=200&height=462&rev=1.1||alt="12.PLC Protocol_html_5c9cb13fac1e6c93.png" height="462" width="200"]]
1093
1094 Select protocol in the setting item, and set parameters.
1095
1096 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_de942589ca070228.png?width=600&height=324&rev=1.1||alt="12.PLC Protocol_html_de942589ca070228.png" height="324" width="600"]]
1097
1098 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
1099
1100 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_387ec7d00b5feb59.png?width=600&height=323&rev=1.1||alt="12.PLC Protocol_html_387ec7d00b5feb59.png" height="323" width="600"]]
1101
1102 Click the [Apply] button to finish the setting.
1103
1104 Click download and select the items as below, then click [execute] to download the configuration to PLC.
1105
1106 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_cdef1c5ec8cc2105.png?width=600&height=434&rev=1.1||alt="12.PLC Protocol_html_cdef1c5ec8cc2105.png" height="434" width="600"]]
1107
1108 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
1109
1110 Done.
1111
1112 **4)Configure the communication protocol**
1113
1114 [[image:image-20220825104904-1.png]]
1115
1116 **5)Cable Wiring**
1117
1118
1119 * **RS422**
1120
1121 [[image:image-20220825105105-2.png]]
1122
1123 [[image:image-20220825105533-3.png]]
1124
1125 == **FX5U Ethernet Protocol** ==
1126
1127 Mitsubishi FX5U series PLC
1128
1129 **1)V-BOX Settings**
1130
1131 |**Items**|**Settings**|**Note**
1132 |Protocol|Mitsubishi FX5U|
1133 |Connection|Ethernet|
1134 |Port No.|5002|Must be the same as the PLC setting
1135 |PLC station No.|0|
1136
1137 **2)Address List**
1138
1139 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1140 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1141 |Y|Y|Y o|0~~303237|
1142 |M|M|M d|0~~99999|
1143 |B|B|B h|0~~7FFF|
1144 |F|F|F d|0~~32767|
1145 |SB|SB|SB h|0~~7FFF|
1146 |TS|TS|TS d|0~~1023|
1147 |TC|TC|TC d|0~~1023|
1148 |STS|STS|STS d|0~~1023|
1149 |STC|STC|STS d|0~~1023|
1150 |CS|CS|CS d|0~~1023|
1151 |CC|CC|CC d|0~~1023|
1152 |SM|SM|SM d|0~~9999|
1153 |L|L|L d|0~~32767|
1154 |S|S|S d|0~~4095|
1155 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1156 |TN|TN|TN d|0~~1023|
1157 |STN|STN|STN d|0~~1023|
1158 |CN|CN|CN d|0~~1023|
1159 |R|R|R d|0~~32767|
1160 |SW|SW|SW h|0~~7FFF|
1161 |Z|Z|Z d|0~~23|
1162 |D|D|D d|0~~7999|
1163 |SD|SD|SD d|0~~11999|
1164
1165 **3)PLC Settings (GX Works 3)**
1166
1167 Find the [Ethernet port] in the navigation area.
1168
1169 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_8e8f85ace087346c.png?width=300&height=593&rev=1.1||alt="12.PLC Protocol_html_8e8f85ace087346c.png" height="593" width="300"]]
1170
1171 Select [Own Node Settings] in the [Setting Item List];
1172
1173 Set [IP Address], [Subnet Mask], [Default Gateway];
1174
1175 Click [Detailed Settings] into [Ethernet Configuration (Built-in Ethernet Port)] windows;
1176
1177 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5d98495052c8c10e.png?width=600&height=339&rev=1.1||alt="12.PLC Protocol_html_5d98495052c8c10e.png" height="339" width="600"]]
1178
1179 Select [SLMP Connection Module] and add into host station as below picture shows;
1180
1181 Set Port number as 5002 (this is necessary settings);
1182
1183 Click [Close with Reflecting the Setting] to save and close window;
1184
1185 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_14b489fdc6c6589d.png?width=600&height=350&rev=1.1||alt="12.PLC Protocol_html_14b489fdc6c6589d.png" height="350" width="600"]]
1186
1187 Click [Apply] to completed Etherenet settings;
1188
1189 Switch to the [On line data operation] interface as below, check the item and click [Execute] to download.
1190
1191 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_c93025a968a8a9e7.png?width=600&height=434&rev=1.1||alt="12.PLC Protocol_html_c93025a968a8a9e7.png" height="434" width="600"]]
1192
1193 **4)Configure the communication protocol**
1194
1195 [[image:image-20220825112403-1.png||alt="图片-20220825112403-1.png"]]
1196
1197 **5)Cable Wiring**
1198
1199 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1200
1201 == **L02 Serial Protocol** ==
1202
1203 Mitsubishi L02 series CPU built-in serial port.
1204
1205 **1)V-BOX Settings**
1206
1207 |**Item**|**Settings**|**Note**
1208 |Protocol|Mitsubishi L02|
1209 |Connection|RS422|
1210 |Baud rate|115200|
1211 |Data bit|8|
1212 |Parity|Odd|
1213 |Stop bit|1|
1214 |PLC station No.|1~~255|Need to be the same as PLC settings
1215
1216 **2)Address List**
1217
1218 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1219 |Bit|X|X|X h|0~~FFFF|
1220 |Bit|Y|Y|Y h|0~~FFFF|
1221 |Bit|M|M|M d|0~~9999|
1222 |Bit|L|L|L d|0~~9999|
1223 |Bit|F|F|F d|0~~9999|
1224 |Bit|B|B|B h|0~~FFFF|
1225 |Bit|V|V|V d|0~~2047|
1226 |Bit|TC|TC|TC d|0~~9999|
1227 |Bit|SS|SS|SS d|0~~9999|
1228 |Bit|SC|SC|SC d|0~~9999|
1229 |Bit|CS|CS|CS d|0~~9999|
1230 |Bit|CC|CC|CC d|0~~9999|
1231 |Bit|SB|SB|SB h|0~~FFFF|
1232 |Bit|SM|SM|SM d|0~~2047|
1233 |Bit|STS|STS|STS d|0~~1023|
1234 |Bit|S|S|S d|0~~9999|
1235 |Bit|DX|DX|DX h|0~~FFFF|
1236 |Bit|DY|DY|DY h|0~~FFFF|
1237 |Bit|TS|TS|TS d|0~~9999|
1238 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1239 |Word|W|W|W h|0~~FFFF|
1240 |Word|TN|TN|TN d|0~~99999|
1241 |Word|SN|SN|SN d|0~~99999|
1242 |Word|CN|CN|CN d|0~~99999|
1243 |Word|R|R|R d|0~~99999|
1244 |Word|SW|SW|SW h|0~~FFFF|
1245 |Word|Z|Z|Z d|0~~99999|
1246 |Word|ZR|ZR|ZR h|0~~FFFF|
1247 |Word|D|D|D d|0~~99999|
1248
1249 **3)Communication Settings**
1250
1251 [[image:image-20220825160648-3.png]]
1252
1253 **4)Cable Wiring**
1254
1255 * **RS422**
1256
1257 [[image:image-20220825161612-8.png]]
1258
1259 [[image:image-20220825160820-4.png]]
1260
1261 == **L02 Ethernet Protocol** ==
1262
1263 Mitsubishi L series CPU built-in Ethernet port.
1264
1265 **1)V-BOX Settings**
1266
1267 |**Items**|**Settings**|**Note**
1268 |Protocol|MIT L02 CPU MELSEC|
1269 |Connection|Ethernet|
1270 |Port No.|1025|Must be the same as the PLC setting
1271 |PLC station No.|0|Must be the same as the PLC setting
1272
1273 **2)Address List**
1274
1275 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1276 |Bit|X|X|X h|0~~FFFF|
1277 |Bit|Y|Y|Y h|0~~FFFF|
1278 |Bit|M|M|M d|0~~9999|
1279 |Bit|L|L|L d|0~~9999|
1280 |Bit|F|F|F d|0~~9999|
1281 |Bit|B|B|B h|0~~FFFF|
1282 |Bit|V|V|V d|0~~2047|
1283 |Bit|TC|TC|TC d|0~~9999|
1284 |Bit|SS|SS|SS d|0~~9999|
1285 |Bit|SC|SC|SC d|0~~9999|
1286 |Bit|CS|CS|CS d|0~~9999|
1287 |Bit|CC|CC|CC d|0~~9999|
1288 |Bit|SB|SB|SB h|0~~FFFF|
1289 |Bit|SM|SM|SM d|0~~2047|
1290 |Bit|STS|STS|STS d|0~~1023|
1291 |Bit|S|S|S d|0~~9999|
1292 |Bit|DX|DX|DX h|0~~FFFF|
1293 |Bit|DY|DY|DY h|0~~FFFF|
1294 |Bit|TS|TS|TS d|0~~9999|
1295 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1296 |Word|W|W|W h|0~~FFFF|
1297 |Word|TN|TN|TN d|0~~99999|
1298 |Word|SN|SN|SN d|0~~99999|
1299 |Word|CN|CN|CN d|0~~99999|
1300 |Word|R|R|R d|0~~99999|
1301 |Word|SW|SW|SW h|0~~FFFF|
1302 |Word|Z|Z|Z d|0~~99999|
1303 |Word|ZR|ZR|ZR h|0~~FFFF|
1304 |Word|D|D|D d|0~~99999|
1305
1306 **3)PLC Settings (GX Works2 )**
1307
1308 Create a project
1309
1310 Set PLC IP, subnet mask and gateway;
1311
1312 Select [Binary Code] as communication data code;
1313
1314 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_776e17505f3fc6c0.png?width=600&height=524&rev=1.1||alt="12.PLC Protocol_html_776e17505f3fc6c0.png" height="524" width="600"]]
1315
1316 Set PLC port number, for example 1025
1317
1318 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_8d0d1a22d388f70b.png?width=600&height=524&rev=1.1||alt="12.PLC Protocol_html_8d0d1a22d388f70b.png" height="524" width="600"]]
1319
1320 Save settings;
1321
1322 Download project into PLC device;
1323
1324 Restart PLC device;
1325
1326 **4)Configure the communication protocol**
1327
1328 [[image:image-20220825142659-1.png]]
1329
1330 **5)Cable Wiring**
1331
1332 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1333
1334 == **Q12H Serial Protocol** ==
1335
1336 This Demo shows V-BOX communicate with Q12H PLC by Q02H serial Protocol
1337
1338 [[**Download link**>>https://ftp.we-con.com.cn/Download/WIKI/PI%20HMI/Demo/Communication/V-Box%20connect%20PLC%20Q12H.rar]]
1339
1340 == **QJ71E71 Ethernet Protocol** ==
1341
1342 Mitsubishi QJ71E71 Ethernet communication module;
1343
1344 **1)V-BOX Settings**
1345
1346 |**Items**|**Settings**|**Note**
1347 |Protocol|MIT QJ71E71 MELSEC|
1348 |Connection|Ethernet|
1349 |Port No.|1025|Must be the same as the PLC setting
1350 |PLC station No.|0|Must be the same as the PLC setting
1351
1352 **2)Address List**
1353
1354 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1355 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1356 |Y|Y|Y h|0~~1FFF|
1357 |M|M|M d|0~~99999|
1358 |L|L|L d|0~~8191|
1359 |F|F|F d|0~~2047|
1360 |B|B|B h|0~~1FFF|
1361 |V|V|V d|0~~2047|
1362 |TS|TS|TS d|0~~2047|
1363 |TC|TC|TC d|0~~2047|
1364 |SS|SS|SS d|0~~2047|
1365 |SC|SC|SC d|0~~2047|
1366 |CS|CS|CS d|0~~1023|
1367 |CC|CC|CC d|0~~1023|
1368 |SB|SB|SB h|0~~7FF|
1369 |S|S|S d|0~~8191|
1370 |DX|DX|DX h|0~~1FFF|
1371 |DY|DY|DY h|0~~1FFF|
1372 |SM|SM|SM d|8000~~9999|
1373 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1374 |D|D|D d|0~~12287|
1375 |W|W|W h|0~~1FFF|
1376 |TN|TN|TN d|0~~2047|
1377 |SN|SN|SN d|0~~2047|
1378 |CN|CN|CN d|0~~1023|
1379 |R|R|R d|0~~32767|
1380 |SW|SW|SW h|0~~7FF|
1381 |Z|Z|Z d|0~~15|
1382 |ZR|ZR|ZR h|0~~FE7FF|
1383
1384 **3)PLC Settings(GX Works2)**
1385
1386 * Click [Ethernet/CC IE/MELSECNET];
1387 * Please select [Ethernet] as network type;
1388 * Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order);
1389 * Select [Online] as Mode;
1390 * [[image:image-20221119171343-2.png||height="341" width="587"]]
1391 * Click [Operation setting] to set IP;
1392 * Select [Binary Code] as [Communication Data Code];
1393 * [[image:image-20221119171436-3.png||height="354" width="588"]]
1394 * Click [Open setting]
1395 * Set protocol: TCP;
1396 * Set [unpassive] in [Open system];
1397 * Set [receive] in [Fixed buffer];
1398 * Set [procedure Exist] in [Fixed buffer communication];
1399 * Disable [Pairing open];
1400 * Set [No confirm] in [Existence confirmation];
1401 * Host station port number: 5009;
1402 * Save settings;
1403 * [[image:image-20221119171611-4.png||height="354" width="588"]]
1404 * Download project into PLC and restart it
1405
1406 **4)Configure the communication protocol**
1407
1408 [[image:image-20221119171832-5.png||height="354" width="625"]]
1409
1410
1411 **5)Cable Wiring**
1412
1413 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png"]]
1414
1415 = Create communication with **Delta PLC** =
1416
1417 == **DVP Ethernet Protocol** ==
1418
1419 Supoort Series: DELTA DVP20/32/40/60ES200RE/200TE or any DVP models with built-in Ethernet port, DELTA DVPEN01-SL module
1420
1421 **1)V-BOX Settings**
1422
1423 |=**Items**|=**Settings**|=**Note**
1424 |Protocol|DELTA DVP MODBUS TCP|
1425 |Connection|Ethernet|
1426 |Port No.|502|
1427 |Device No.|1|
1428 |VBox Device No.|0|
1429
1430 **2)Address List **
1431
1432 |=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 217px;" %)**VBox registers**|=(% style="width: 168px;" %)**Format**|=(% style="width: 225px;" %)**Range**|=**Note**
1433 |Bit|(% style="width:191px" %)X|(% style="width:217px" %)X|(% style="width:168px" %)X OOO|(% style="width:225px" %)0~~377|
1434 |Bit|(% style="width:191px" %)Y|(% style="width:217px" %)Y|(% style="width:168px" %)Y OOO|(% style="width:225px" %)0~~377|
1435 |Bit|(% style="width:191px" %)M0|(% style="width:217px" %)M0|(% style="width:168px" %)M0DDDD|(% style="width:225px" %)0~~1535|
1436 |Bit|(% style="width:191px" %)M1|(% style="width:217px" %)M1|(% style="width:168px" %)M1DDDD|(% style="width:225px" %)1536~~4096|
1437 |Bit|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDD|(% style="width:225px" %)0~~255|
1438 |Bit|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~255|
1439 |Bit|(% style="width:191px" %)S|(% style="width:217px" %)S|(% style="width:168px" %)SDDDD|(% style="width:225px" %)0~~1023|
1440 |Word|(% style="width:191px" %)D0|(% style="width:217px" %)D0|(% style="width:168px" %)D0DDDD|(% style="width:225px" %)0~~4095|
1441 |Word|(% style="width:191px" %)D1|(% style="width:217px" %)D1|(% style="width:168px" %)D1DDDD|(% style="width:225px" %)4096~~11999|
1442 |Word|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDD|(% style="width:225px" %)0~~255|
1443 |Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~199|
1444 |Double Word|(% style="width:191px" %)HC|(% style="width:217px" %)HC|(% style="width:168px" %)HCDDD|(% style="width:225px" %)200~~255|
1445
1446 **3) PLC Setting:**
1447
1448 ~1. Create new project in Delta WPL Soft, and click Setting to open the communication settings:
1449
1450 (% style="text-align:center" %)
1451 [[image:DVPEthernetWPLSoft2.png]]
1452
1453 2. Set up the communication type and PLC IP:
1454
1455 (% style="text-align:center" %)
1456 [[image:DVPEthernetSetup.png]]
1457
1458 (% class="wikigeneratedid" %)
1459 3. Click OK and save the settings. Then click Communication on toolbar, then click Transfer Setup to open new window:
1460
1461 (% style="text-align:center" %)
1462 [[image:DVPEthernetTransfer.png]]
1463
1464 (% class="wikigeneratedid" %)
1465 4. Select Communication Mode as PC => PLC to download or select PC <=PLC to upload:
1466
1467 (% style="text-align:center" %)
1468 [[image:DVPEthernetPLCtoPC.png]]
1469
1470 5. Click Auto-Search Ethernet Module to find the PLC on the same LAN network:
1471
1472 (% style="text-align:center" %)
1473 [[image:DVPEthernetAutoSearch.png]]
1474
1475 **4) V-BOX Setting:**
1476
1477 Set the same IP address according to the setting from WPL Soft:
1478
1479 (% style="text-align:center" %)
1480 [[image:DVPEthernetVNETPortocol.png]]
1481
1482 == **DVP serial protocol** ==
1483
1484 Supoort Series: DELTA DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX
1485
1486 **1)V-BOX Settings**
1487
1488 |=**Items**|=**Settings**|=**Note**
1489 |Protocol|DELTA DVP PROTOCOL|
1490 |Connection|RS232|
1491 |Baud Rate|9600|
1492 |Stop Bit|1|
1493 |Data Bit|7|
1494 |Parity|EVEN|
1495 |Device No.|1|
1496
1497 (% class="wikigeneratedid" %)
1498 **2)Address List**
1499
1500 |=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 217px;" %)**VBox registers**|=(% style="width: 168px;" %)**Format**|=(% style="width: 225px;" %)**Range**|=**Note**
1501 |Bit|(% style="width:191px" %)X|(% style="width:217px" %)X|(% style="width:168px" %)X OOOOOO|(% style="width:225px" %)0~~303237|
1502 |Bit|(% style="width:191px" %)Y|(% style="width:217px" %)Y|(% style="width:168px" %)Y OOOOOO|(% style="width:225px" %)0~~303237|
1503 |Bit|(% style="width:191px" %)M|(% style="width:217px" %)M|(% style="width:168px" %)MDDDDD|(% style="width:225px" %)0~~99999|
1504 |Bit|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDDDD|(% style="width:225px" %)0~~99999|
1505 |Bit|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDDDD|(% style="width:225px" %)0~~99999|
1506 |Bit|(% style="width:191px" %)S|(% style="width:217px" %)S|(% style="width:168px" %)SDDDDD|(% style="width:225px" %)0~~99999|
1507 |Word|(% style="width:191px" %)D|(% style="width:217px" %)D|(% style="width:168px" %)D DDDDD|(% style="width:225px" %)0~~99999|
1508 |Word|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDDDD|(% style="width:225px" %)0~~99999|
1509 |Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~199|
1510 |Double Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDDDD|(% style="width:225px" %)200~~99999|
1511
1512 (% class="wikigeneratedid" %)
1513 **3)Wiring Diagram**
1514
1515 (% style="text-align:center" %)
1516 [[image:Delta DVP PROTOCOLSerial232.png]]
1517
1518 == **AS Ethernet Protocol** ==
1519
1520 **1)V-BOX Settings**
1521
1522 |=**Items**|=**Settings**|=**Note**
1523 |Protocol|DELTA AS300 MODBUS TCP|
1524 |Connection|Ethernet|
1525 |Port No.|502|
1526 |Device No.|1|
1527 |HMI No.|0|
1528
1529 **2)Address List**
1530
1531 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1532 |Bit|X|X|X d|0~~63|
1533 |Bit|Y|Y|Y d|0~~63|
1534 |Bit|D|D|D d|0~~29999|
1535 |Bit|M|M|M d|0~~8191|
1536 |Bit|SM|SM|SM d|0~~4095|
1537 |Bit|S|S|S h|0~~2047|
1538 |Bit|T|T|T d|0~~511|
1539 |Bit|C|C|C d|0~~511|
1540 |Bit|HC|HC|HC d|0~~255|
1541 |Word|X|X|X h|0~~63|
1542 |Word|Y|Y|Y d|0~~63|
1543 |Word|SR|SR|SR d|0~~2047|
1544 |Word|D|D|D d|0~~29999|
1545 |Word|T|T|T d|0~~511|
1546 |Word|C|C|C h|0~~511|
1547 |Word|E|E|E d|0~~9|
1548
1549 **3)Configure the communication protocol**
1550
1551 [[image:image-20220831160010-4.png]]
1552
1553 **4)Cable Wiring**
1554
1555 Figure
1556
1557 [[image:image-20220831155101-1.png]][[image:image-20220831160055-5.png]]
1558
1559 Pin Definition Diagram
1560
1561 [[image:image-20220831155157-3.png]]
1562
1563 = Create communication with **Omron PLC** =
1564
1565 == **CP1 Series Protocol ** ==
1566
1567 [[下载链接>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CP1%20Series.zip]]
1568
1569 == **CP2M Series Protocol** ==
1570
1571 [[下载链接>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CJ2M.zip]]
1572
1573
1574 == **EC55 Series Protocol** ==
1575
1576 Supported device: EC55 temperature instrument
1577
1578 **1)V-BOX Settings**
1579
1580 |**Items**|**Settings**|**Note**
1581 |Protocol|Omron EC55|
1582 |Connection|RS485 (9600, 2, 7, EVEN)|
1583 |Port No.|None|
1584 |PLC station No.|0|
1585
1586 **2)Address List**
1587
1588 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
1589 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
1590 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
1591 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
1592 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
1593 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
1594 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
1595 |CP|-|0-6|Read controller intrinsic property
1596 |CS|-|0-2|Read controller states
1597 |CA|-|0-17|Action command
1598
1599 **3)Device Settings**
1600
1601 Omron E5CC PLC configuration
1602
1603 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
1604
1605 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_3d95e093792ba98a.png?width=550&height=229&rev=1.1||alt="12.PLC Protocol_html_3d95e093792ba98a.png" height="229" width="550"]]
1606
1607 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
1608
1609 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_be583aa69dd6cf4c.png?width=550&height=242&rev=1.1||alt="12.PLC Protocol_html_be583aa69dd6cf4c.png" height="242" width="550"]]
1610
1611 **✎Note:** The communication settings for HMI should be consistent with this setting.
1612
1613 **4)Configure the communication protocol**
1614
1615 [[image:image-20220831161041-1.png]]
1616
1617 **5)Cable Wiring**
1618
1619 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5e9a81a14106da9e.png?width=392&height=223&rev=1.1||alt="12.PLC Protocol_html_5e9a81a14106da9e.png" height="223" width="392"]]
1620
1621 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_1897d92be6948d58.png?width=393&height=223&rev=1.1||alt="12.PLC Protocol_html_1897d92be6948d58.png" height="223" width="393"]]
1622
1623 **✎Note:**
1624
1625 * COM3 only available in PI8000/PI9000 series.
1626 * CA address could not support continuous writing function;
1627 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
1628 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
1629 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
1630 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
1631 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
1632 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
1633 * [[image:image-20220831161356-1.png]]Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
1634
1635 = Create communication with Xinje** PLC** =
1636
1637 == **XC serial protocol** ==
1638
1639 **1)V-BOX Settings**
1640
1641 |**Item**|**Settings**|**Note**
1642 |Protocol|XINJE XC MODBUS|
1643 |Connection|RS232|
1644 |Baud rate|19200|
1645 |Data bit|8|
1646 |Parity|EVEN|
1647 |Stop bit|1|
1648 |PLC station No.|1|
1649
1650 **2)Address List**
1651
1652 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1653 |Bit|M|M|M d|0~~8511|
1654 |Bit|X|X|X o|0~~1747|
1655 |Bit|Y|Y|Y o|0~~1747|
1656 |Bit|S|S|S d|0~~1023|
1657 |Bit|T|T|T d|0~~4095|
1658 |Bit|C|C|C d|0~~634|
1659 |Word|D|D|D d|0~~8511|
1660 |Word|TD|TD|TD d|0~~618|
1661 |Word|CD|CD|CD d|0~~634|
1662 |Word|FD|FD|FD d|0~~8511|
1663
1664 **3)Configure the communication protocol**
1665
1666
1667 [[image:image-20220831163041-1.png]]
1668
1669 **4)Cable Wiring**
1670
1671 Figure
1672
1673 [[image:image-20220831163406-2.png]][[image:image-20220831163422-3.png]]
1674
1675 Pin Definition Diagram
1676
1677 [[image:image-20220831163441-4.png]]
1678
1679 == **XD serial protocol** ==
1680
1681 **1)V-BOX Settings**
1682
1683 Supported Series: Xinjie XD/XE Series PLC
1684
1685 |**Item**|**Settings**|**Note**
1686 |Protocol|XINJE XD/XC MODBUS|
1687 |Connection|RS232|
1688 |Baud rate|19200|
1689 |Data bit|8|
1690 |Parity|EVEN|
1691 |Stop bit|1|
1692 |PLC station No.|1|
1693
1694 **2)Address List**
1695
1696 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1697 |Bit|M|M|M d|0~~74999|
1698 |Bit|X1xx|X1xx|X1xx o|0~~1177|
1699 |Bit|X2xx|X2xx|X2xx o|0~~277|
1700 |Bit|X|X|X o|0~~77|
1701 |Bit|Y1xx|Y1xx|Y1xx o|0~~1177|
1702 |Bit|Y2xx|Y2xx|Y2xx o|0~~277|
1703 |Bit|Y|Y|Y o|0~~4095|
1704 |Bit|SM|SM|SM d|0~~4999|(((
1705
1706 )))
1707 |Bit|T|T|T d|0~~4999|
1708 |Bit|C|C|C d|0~~4999|
1709 |Bit|ET|ET|ET d|0~~31|
1710 |Bit|SE|SE|SE d|0~~31|
1711 |Bit|HM|HM|HM d|0~~11999|
1712 |Bit|HSC|HSC|HSC d|0~~39|
1713 |Bit|HS|HS|HS d|0~~999|
1714 |Bit|HT|HT|HT d|0~~1999|
1715 |Bit|HC|HC|HC d|0~~1999|
1716 |Bit|S|S|S d|0~~7999|
1717 |Word|D|D|D d|0~~69999|
1718 |Word|ID|ID|ID d|0~~99|
1719 |Word|ID1xx|ID1xx|ID1xx d|0~~999|
1720 |Word|ID2xx|ID2xx|ID2xx d|0~~299|
1721 |Word|QD|QD|QD d|0~~99|
1722 |Word|QD1xx|QD1xx|QD1xx d|0~~999|
1723 |Word|QD2xx|QD2xx|QD2xx d|0~~299|
1724 |Word|SD|SD|SD d|0~~4999|
1725 |Word|TD|TD|TD d|0~~575|
1726 |Word|CD|CD|CD d|0~~575|
1727 |Word|ETD|ETD|ETD d|0~~31|
1728 |Word|HD|HD|HD d|0~~24999|
1729 |Word|HSD|HSD|HSD d|0~~1023|
1730 |Word|HTD|HTD|HTD d|0~~95|
1731 |Word|HCD|HCD|HCD d|0~~95|
1732 |Word|HSCD|HSCD|HSCD d|0~~31|
1733 |Word|FD|FD|FD d|0~~8191|
1734 |Word|SFD|SFD|SFD d|0~~5999|
1735 |Word|FS|FS|FS d|0~~47|
1736
1737 **3)Configure the communication protocol**
1738
1739 [[image:image-20220831163923-7.png]]
1740
1741
1742
1743 **4)Cable Wiring**
1744
1745 Figure
1746
1747 [[image:image-20220831163406-2.png]][[image:image-20220831163553-6.png]]
1748
1749 Pin Definition Diagram
1750
1751 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830160232-3.png?rev=1.1||alt="image-20220830160232-3.png"]]
1752
1753 = Create communication with **Schneider PLC** =
1754
1755 == **Schneider MODBUS RTU** ==
1756
1757 **1)V-BOX Setting**
1758
1759 |=**Parameters**|=**Recommended**|=**Notes**
1760 |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
1761 |**Connection**|RS485|
1762 |**Baud rate**|19200|
1763 |**Data bit**|8|
1764 |**Parity**|Even|
1765 |**Stop bit**|1|
1766 |**PLC station No.**|1|
1767
1768 **2)Address List**
1769
1770 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
1771 |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
1772 |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
1773 |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
1774 |W|MW|DDDDDD|0 ~~ 999999|Output register
1775 |DW|MD|DDDDDD|0 ~~ 999999|Output register
1776
1777 **3)Configure the communication protocol**
1778
1779 [[image:image-20220902104329-1.png]]
1780
1781 **4)Cable Wiring**
1782
1783 **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
1784
1785 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220817154212-1.jpeg?width=554&height=315&rev=1.1||alt="image-20220817154212-1.jpeg" height="315" width="554"]]
1786
1787 = Create communication with Inovance** PLC** =
1788
1789 == **H3U serial protocol** ==
1790
1791 **1)V-BOX Settings**
1792
1793 |**Item**|**Settings**|**Note**
1794 |Protocol|INOVANCE H3U PLC|
1795 |Connection|RS422|
1796 |Baud rate|9600|
1797 |Data bit|7|
1798 |Parity|EVEN|
1799 |Stop bit|1|
1800 |PLC station No.|0|
1801
1802 **2)Address List**
1803
1804 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1805 |Bit|X|X|X o|0~~303237|
1806 |Bit|Y|Y|Y o|0~~303237|
1807 |Bit|M|M|M d|0~~99999|
1808 |Bit|T|T|T d|0~~99999|
1809 |Bit|C|C|C d|0~~99999|
1810 |Bit|SM|SM|SM d|8000~~999|
1811 |Bit|S|T|S d|0~~99999|
1812 |Bit|Lamp|Lamp|Lamp d|0~~0|
1813 |Word|X|X|X o|0~~303237|
1814 |Word|Y|Y|Y o|0~~303237|
1815 |Word|M|M|M d|0~~99999|
1816 |Word|T|T|T d|0~~99999|
1817 |Word|C|C|C d|0~~199|
1818 |Word|D|D|D d|0~~7999|
1819 |Word|S|S|S d|0~~99999|
1820 |Word|SD|SD|SD d|8000~~9999|
1821 |Word|R|R|R d|0~~32767|
1822
1823 **3)Configure the communication protocol**
1824
1825 [[image:image-20220831164626-1.png]]
1826
1827
1828
1829 **4)Cable Wiring**
1830
1831 Figure
1832
1833 [[image:image-20220831164646-2.png]][[image:image-20220831164700-3.png]]
1834
1835 Pin Definition Diagram
1836
1837 [[image:image-20220831164731-4.png]]
1838
1839 = Create communication with Panasonic** PLC** =
1840
1841 == **FP serial protocol** ==
1842
1843 **1)V-BOX Settings**
1844
1845 |**Item**|**Settings**|**Note**
1846 |Protocol|Panasonic FP MFWTOCOL|
1847 |Connection|RS232|
1848 |Baud rate|9600|
1849 |Data bit|8|
1850 |Parity|ODD|
1851 |Stop bit|1|
1852 |PLC station No.|1|
1853
1854 **2)Address List**
1855
1856 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1857 |Bit|X|X|X d|0~~9999|
1858 |Bit|Y|Y|Y d|0~~9999|
1859 |Bit|R|R|R d|0~~9999|
1860 |Bit|T|T|T d|0~~9999|
1861 |Bit|C|C|C d|0~~9999|
1862 |Bit|L|L|L d|0~~9999|
1863 |Word|WX|WX|WX d|0~~9999|
1864 |Word|WY|WY|WY d|0~~9999|
1865 |Word|WR|WR|WR d|0~~9999|
1866 |Word|WL|WL|WL d|0~~9999|
1867 |Word|LD|LD|LD d|0~~9999|
1868 |Word|DT|DT|DT d|0~~65535|
1869 |Word|FL|FL|FL d|0~~9999|
1870 |Word|EV|EV|EV d|0~~9999|
1871 |Word|SV|SV|SV d|0~~9999|
1872
1873 **3)Configure the communication protocol**
1874
1875 [[image:image-20220831165238-4.png]]
1876
1877
1878
1879 **4)Cable Wiring**
1880
1881 Figure
1882
1883 [[image:image-20220831165031-3.png]][[image:image-20220831165017-2.png]]
1884
1885 Pin Definition Diagram
1886
1887 [[image:image-20220831165008-1.png]]
1888
1889 = Create communication with LS** PLC** =
1890
1891 == **XBC serial protocol** ==
1892
1893 **1)V-BOX Settings**
1894
1895 |**Item**|**Settings**|**Note**
1896 |Protocol|LS XBC CNet|
1897 |Connection|RS232|
1898 |Baud rate|115200|
1899 |Data bit|8|
1900 |Parity|NONE|
1901 |Stop bit|1|
1902 |PLC station No.|1|
1903
1904 **2)Address List**
1905
1906 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1907 |Bit|P|P|P d|0~~2047|
1908 |Bit|M|M|M d|0~~2047|
1909 |Bit|L|L|L d|0~~11263|
1910 |Bit|K|K|K d|0~~16183|
1911 |Bit|F|F|F d|0~~2047|
1912 |Bit|D|D|D d|0~~32767|
1913 |Bit|R|R|R d|0~~32767|
1914 |Bit|U|U|U d|0~~4095|
1915 |Word|P|P|P d|0~~2047|
1916 |Word|M|M|M d|0~~2047|
1917 |Word|L|L|L d|0~~11263|
1918 |Word|K|K|K d|0~~16183|
1919 |Word|F|F|F d|0~~2047|
1920 |Word|C|C|C d|0~~2047|
1921 |Word|T|T|T d|0~~2047|
1922 |Word|D|D|D d|0~~32767|
1923 |Word|N|N|N d|0~~21503|
1924 |Word|R|R|R d|0~~32767|
1925 |Word|U|U|U d|0~~4095|
1926 |Word|Z|Z|Z d|0~~127|
1927 |Word|S|S|S d|0~~127|
1928
1929 **3)Configure the communication protocol**
1930
1931 [[image:image-20220831170147-1.png]]
1932
1933 **4)Cable Wiring**
1934
1935 Figure
1936
1937 [[image:image-20220831170306-4.png]][[image:image-20220831170254-3.png]]
1938
1939 Pin Definition Diagram
1940
1941 [[image:image-20220831170215-2.png]]
1942
1943 == **XGK FEnet Ethernet protocol** ==
1944
1945 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
1946
1947 **1)V-BOX Settings**
1948
1949 |**Items**|**Settings**|**Note**
1950 |Protocol|LG XGK FEnet(Ethernet)|
1951 |Connection|Ethernet|
1952 |Port No.|2004|
1953
1954 **2)Address List**
1955
1956 |**Type**|**Register**|**Range**|**Format**|**Note**
1957 |(% rowspan="14" %)Word|P|0~~2047|P d|
1958 |M|0~~2047|M d|
1959 |K|0~~2047|K d|
1960 |F|0~~2047|F d|
1961 |T|0~~2047|T d|
1962 |C|0~~2047|C d|
1963 |Z|0~~127|Z d|
1964 |S|0~~127|S d|
1965 |L|0~~11263|L d|
1966 |N|0~~21503|N d|
1967 |D|0~~32767|D d|
1968 |R|0~~32767|R d|
1969 |ZR|0~~65535|ZR d|
1970 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
1971
1972 **✎Note:**
1973
1974 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
1975 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
1976 * All bit registers are in the form of bits in word, and the range is the same as the word register;
1977
1978 **3)Communication Settings**
1979
1980 [[image:image-20220831171127-1.png]]
1981
1982 **4)Cable Wiring**
1983
1984 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1985
1986 = Create communication with **Modbus ** =
1987
1988 == **MODBUS RTU Slave (All function)** ==
1989
1990 Select the protocol "Modbus RTU Slave (All Fuction)",
1991
1992 Then set baud rate, port, stop bits, data bits, parity.
1993
1994 (% style="text-align:center" %)
1995 [[image:1624342015914-382.png||height="486" width="800" class="img-thumbnail"]]
1996
1997 == **MODBUS RTU Master** ==
1998
1999 Select the protocol "Modbus RTU Master",
2000
2001 Then set baud rate, port, stop bits, data bits, parity
2002
2003 (% style="text-align:center" %)
2004 [[image:1624348709622-711.png||queryString="width=809&height=493" height="488" width="800" class="img-thumbnail"]]
2005
2006 **address list**
2007
2008 (% class="table-bordered" %)
2009 |=(% scope="row" %)**Type**|=**Data Type**|=**Function code and description**
2010 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (Read Input Registers: Read the current binary value in one or more input registers)
2011 |06 (write single register: write a binary value to a holding register)
2012 |10 (write values to multiple addresses )
2013 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
2014 |06 (write single register: write a binary value to a holding register)
2015 |10 (write values to multiple addresses )
2016 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
2017 |06 (write single register: write a binary value to a holding register)
2018 |10 (write values to multiple addresses )
2019 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
2020 |10 (write values to multiple addresses )
2021 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
2022 |05 (Force a single coil to force the on/off state of a logic coil)
2023 |0F (Write multiple bits, ie write continuously)
2024 |(% rowspan="3" %)1|02 (Read the input state)
2025 |05 (Force a single coil to force the on/off state of a logic coil)
2026 |0F (Write multiple bits)
2027 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
2028 |05 (Force a single coil to force the on/off state of a logic coil)
2029 |0F (Write multiple bits)
2030 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
2031 |0F (Write multiple bits)
2032
2033 == **MODBUS TCP Slave (All function)** ==
2034
2035 Supported series: MODBUS TCP controller
2036
2037 V-B0X works as MODBUS TCP MASTER connecting with TCP SLAVE
2038
2039 **1)V-BOX Setting**
2040
2041 |**Items**|**Settings**|**Note**
2042 |Protocol|MODBUS TCP Slave (All function)|
2043 |Connection|Ethernet|
2044 |Port No.|502|
2045 |PLC station No.|1
2046
2047 **2)Address List**
2048
2049 |=**Type**|=**Data Type**|=**Function code & Description**
2050 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
2051 |06 (write single register: write a binary value to a holding register)
2052 |10 (write values to multiple addresses )
2053 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
2054 |06 (write single register: write a binary value to a holding register)
2055 |10 (write values to multiple addresses )
2056 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
2057 |06 (write single register: write a binary value to a holding register)
2058 |10 (write values to multiple addresses )
2059 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
2060 |10 (write values to multiple addresses )
2061 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
2062 |05 (Force a single coil to force the on/off state of a logic coil)
2063 |0F (Write multiple bits, ie write continuously)
2064 |(% rowspan="3" %)1|02 (Read the input state)
2065 |05 (Force a single coil to force the on/off state of a logic coil)
2066 |0F (Write multiple bits)
2067 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
2068 |05 (Force a single coil to force the on/off state of a logic coil)
2069 |0F (Write multiple bits)
2070 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
2071 |0F (Write multiple bits)
2072
2073 **3)Communication Settings**
2074
2075 Configure V-BOX Ethernet IP in Networking Settings
2076
2077 [[image:image-20220902111833-3.png]]
2078
2079
2080 Configure PLC Ethernet IP in Communication;
2081
2082 [[image:image-20220902111121-1.png]]
2083
2084 **4)Cable Wiring**
2085
2086 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2087
2088 == **communicate with VB inverter** ==
2089
2090 [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20VB%20inverter.zip]]
2091
2092 = **User define protocol** =
2093
2094 More serial port script instruction,please refer manual:[[Lua script function>>doc:V-BOX.V-Net.Manual.04 Lua Script.01 Lua Functions.WebHome]]~-~-->[[3.Serial port operation>>url:http://docs.we-con.com.cn/wiki/vbox/view/HMI/04.Lua%20script%20%20function%20and%20operation/01.Lua%20script%20function/#H3.Serialportoperation]]
2095
2096 == **Read the temperature sensor.** ==
2097
2098 the commond format is as beliow:
2099
2100 Send commond:01 03 02 00 00 03 04 73
2101
2102 Feedback commond:01 03 06 07 F7 0E 7E B7 35
2103
2104 Temperature data:07 F7,desimal = 2039,it means temperature is 20.39℃.
2105
2106 Humidity data:0E 7E,desimal = 3710, it mean humidity is 37.10%RH.
2107
2108 Script Demo:
2109
2110 ~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~--
2111
2112 function com.main()
2113 ~-~-dosomething
2114 openPlc()
2115 end
2116 function openPlc()
2117 if obj then
2118 ~-~- If the serial port opened,then read/write data by timing
2119
2120 local wri = string.pack(">HHHH",0X0103,0X0200,0X0003,0X0473)
2121 local arr = reading(wri)
2122 ~-~- if arr ~~=nil then
2123 ~-~- if arr[1] ==33 and arr[2] ==v[2][2] and arr[3] ==v[2][3] then
2124 ~-~- local A = arr[4]*256
2125 ~-~- local B = A+arr[5]
2126 ~-~- addr_setword(v[1],B)
2127 ~-~- end
2128 ~-~- end
2129
2130 else
2131 ~-~-judge if there is a serial object, then initialize and open the serial port
2132 local configs = {
2133 name = 'COM1', ~-~-Select serial port COM1
2134 mode = 485, ~-~-Communication mode RS485
2135 baud_rate = 9600, ~-~-Baud rate 9600
2136 stop_bit = 1, ~-~-stop bit 1
2137 data_len = 8, ~-~-data length 8
2138 check_bit = 'NONE', ~-~-no parity
2139
2140 }
2141 obj,err = serial.open(configs) ~-~-Open serial port
2142 if not obj then
2143 print("serial open :failed", err) ~-~- Open serial port failed
2144 end
2145 end
2146 end
2147
2148 function reading(wri)
2149 obj:flush() ~-~- Clear serial port
2150 obj:write(wri) ~-~- Write serial port
2151 print(string.byte(wri,1,#wri))
2152 obj:flush() ~-~- Clear serial port 
2153 local readed =obj:read(9,1000) ~-~- Read 9 bytes, timeout 1 second
2154 if readed and readed ~~= "" then 
2155 ~-~- judge that a non-empty string is read
2156 print(string.byte(readed,1,#readed))
2157 a={string.byte(readed, 1, #readed)}
2158 if nil ~~= a[4] and nil ~~= a[5] and nil ~~= a[6] and nil ~~= a[7] then
2159 a1=a[4]*256+a[5]
2160 a2=a[6]*256+a[7]
2161 addr_setword("@HDW0",a1)
2162 addr_setword("@HDW1",a2)
2163 end
2164 return {string.byte(readed, 1, #readed)}
2165 elseif readed == nil then
2166 print("serial read err:", err or "")
2167 return nil
2168 end
2169 return nil
2170 end
2171
2172 ~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-