Wiki source code of 1 Communication

Version 239.1 by Hunter on 2023/05/06 15:33

Show last authors
1 = Create communication with WECON PLC =
2
3 == **LX3V Serial Protocol** ==
4
5 Supported series: Wecon LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
6
7 **1)V-BOX setting**
8
9 |**Item**|**Settings**|**Note**
10 |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
11 |Connection|RS422/RS485|
12 |Baud rate|9600|
13 |Data bit|7|
14 |Parity|EVEN|
15 |Stop bit|1|
16 |PLC station No.|1|
17
18 **2)Address List**
19
20
21 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
22 |(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
23 |Y|Y|Y o|0~~303237|
24 |M|M|M d|0~~99999|
25 |T|T|T d|0~~99999|
26 |C|C|C d|0~~99999|
27 |S|S|S d|0~~99999|
28 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
29 |Y|Y|Y o|0~~303237|
30 |M|M|M d|0~~99999|
31 |T|T|T d|0~~99999|
32 |C|C|C d|0~~199|
33 |D|D|D d|0~~7999|
34 |S|S|S d|0~~99999|
35 |SD|SD|SD d|8000~~9999|
36
37 **3)Configure the communication protocol**
38
39 [[image:image-20220824152217-1.png||alt="图片-20220824152217-1.png"]]
40
41 **4)Cable Wiring**
42
43 * **RS422**
44
45 [[image:image-20220824120614-5.png]]
46
47 * **RS485**
48
49 [[image:image-20220824120524-3.png]]
50
51 == **LX5V Serial Protocol** ==
52
53 This example introduces the establishment of serial port communication between V-BOX and LX5V. It is introduced through three parts: PLC software configuration, V-BOX software configuration, and hardware wiring.
54
55 **Software configuration of PLC**
56
57 **1)PLC programming software**
58
59 [[image:image-20220824142722-1.png]]
60
61 **2)New PLC project**
62
63 Click New Project and select the PLC model.
64
65 [[image:image-20220822172623-2.png]]
66
67 **3)Set Serial port parameters**
68
69 Follow the steps below to configure Serial port parameters
70
71 Baud rate:115200
72
73 Data bit:8
74
75 Stop bit:1
76
77 Parity:No verification
78
79 [[image:image-20220822172657-3.png]]
80
81 **4)Registers list**
82
83 [[image:image-20220822172730-4.png]]
84
85 **V-BOX software configuration**
86
87 **1)V-BOX programming software**
88
89 [[image:image-20220824104124-1.png]]
90
91 **2)V-NET add device**
92
93 Open V-NET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the access key, password and remark, to add the device.
94
95 [[image:image-20220824104909-2.png]]
96
97 **3)Set communication port parameters**
98
99 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
100
101 Baud rate:115200
102
103 Data bit:8
104
105 Stop bit:1
106
107 Parity:No verification
108
109 [[image:image-20220824142130-1.png]]
110
111 **hardware connection**
112
113 **1)Hardware wiring diagram**
114
115 [[image:image-20220824142546-2.png]]
116
117 [[image:image-20220824142643-3.png]]
118
119 The above are all the steps for establishing serial port communication between V-BOX with LX5V PLC.
120
121 == **LX5V-N Ethernet protocol** ==
122
123 This example introduces the establishment of Ethernet communication between V-BOX and LX5V-N. It is introduced through three parts: PLC software configuration, V-BOX software configuration, and hardware wiring.
124
125 **Software configuration of PLC**
126
127 **1)PLC programming software**
128
129 [[image:image-20220824142722-1.png]]
130
131 **2)New PLC project**
132
133 Click New Project and select the PLC model.
134
135 [[image:image-20220824143613-1.png]]
136
137 **3)Set Ethernet port parameters**
138
139 Follow the steps below to configure Ethernet parameters
140
141 PLC IP address:192.168.39.200
142
143 default gateway:192.168.39.1
144
145 subnet mask:255.255.255.0
146
147 [[image:image-20220824143744-2.png]]
148
149 **4)Registers list**
150
151 [[image:image-20220822172730-4.png]]
152
153 (% id="cke_bm_22473S" style="display:none" %)** **(%%)**V-BOX software configuration**
154
155 **1)V-BOX programming software**
156
157 [[image:image-20220824104124-1.png]]
158
159 **2)V-NET add device**
160
161 Open V-NET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the access key, password and remark, to add the device.
162
163 [[image:image-20220824104909-2.png]]
164
165 **3)Set communication Protocol**
166
167 Click Communication to configure the LX5V plc protocol and IP address.
168
169 [[image:image-20220824144619-1.png]]
170
171 **hardware connection**
172
173 **1)Hardware wiring diagram**
174
175 [[image:image-20220824151127-2.png]]
176
177 The above are all the steps for establishing ethernet communication between V-BOX with LX5V PLC.
178
179 = Create communication with Allen-Bradley(**Rockwell**)** PLC** =
180
181 == **DF1 Advanced Protocol** ==
182
183 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
184
185 **1) V-Box Settings**
186
187 |=Item|=Recommended |=Note
188 |=Protocol|Allen Bradley DF1 Advanced|
189 |=Connection|RS232|
190 |=Baud rate|19200|
191 |=Stop bits|1|
192 |=Data bits|8|
193 |=Parity|None|
194 |=PLC Station No.|1|
195 |=HMI Station No.|0|
196
197 **2) Address List**
198
199 |=**Type**|=**Device registers**|=**Format**|=**Range**|=Note
200 |(% colspan="1" rowspan="7" %)Bit|I1|I1ddd.dd|0.0~~255.15|Only able to communicate with file number I1
201 |O0|O0ddd.dd|0.0~~255.15|Only able to communicate with file number O0
202 |S2|S2ddd.dd|0.0~~255.15|Only able to communicate with file number S2
203 |B3|B3ddd.dd|0.0~~255.15|Only able to communicate with file number B3
204 |BN|BNddddd.dd|0.0~~99255.15|(((
205 Bit data file B0~~B99
206
207 First two digits is for file number
208
209 For example, BN13001.00 represents file number B13, address 001, the 0th bit.
210 )))
211 |N7|N7ddd.dd|0.0~~255.15|Only able to communicate with file number N7
212 |NN|NNddddd.dd|0.0~~99255.15|(((
213 Integer data file bit format N0~~N99
214
215 First two digits is for file number
216
217 For example, NN13001.00 represents file number N13, address 001, the 0th bit.
218 )))
219 |(% rowspan="11" %)Word|S2|S2ddd|0~~255|Only able to communicate with file number S2
220 |T4S|T4Sddd|0~~255|Only able to communicate with file number T4 (Timer Preset Value)
221 |T4P|T4Pddd|0~~255|Only able to communicate with file number T4 (Timer Accumulator Value)
222 |TNS|TNSddddd|0~~99255|(((
223 Timer Preset Value
224
225 First two digits is for file number
226
227 For example, TNS99255 represents file number T99, address 255.
228 )))
229 |TNP|TNPddddd|0~~99255|(((
230 Timer Accumulator Value
231
232 First two digits is for file number
233
234 For example, TNP99255 represents file number T99, address 255.
235 )))
236 |C5S|C5Sddd|0~~255|Only able to communicate with file number C5 (Counter Preset Value)
237 |C5P|C5Pddd|0~~255|Only able to communicate with file number C5 (Counter Accumulator Value)
238 |CNS|CNSddddd|0~~99255|(((
239 Counter Preset Value
240
241 First two digits is for file number
242
243 For example, CNS99255 represents file number C99, address 255.
244 )))
245 |CNP|CNPddddd|0~~99255|(((
246 Counter Accumulator Value
247
248 First two digits is for file number
249
250 For example, CNP99255 represents file number C99, address 255.
251 )))
252 |N7|N7ddd|0~~255|Only able to communicate with file number N7
253 |NN|NNddd|0~~99255|(((
254 Integer data file
255
256 First two digits is for file number
257
258 For example, NN99255 represents file number N99, address 255.
259 )))
260 |(% colspan="1" rowspan="3" %)Double Word|F8|F8ddd|0~~255|(((
261 Only able to communicate with file number N7
262 )))
263 |FN|FNddddd|0~~99255|(((
264 Floating point data file
265
266 First two digits is for file number
267
268 For example, FN99255 represents file number F99, address 255.
269 )))
270 |LN|LNddddd|0~~99255|Long
271
272 **3) Cable Wiring**
273
274 (% style="text-align:center" %)
275 [[image:ABRS232.gif]]
276
277 (% class="wikigeneratedid" id="HMicroLogixA0Protocol" %)
278 (% id="cke_bm_5621S" style="display:none" %)** **
279
280 == **MicroLogix Protocol** ==
281
282 (% class="wikigeneratedid" %)
283 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
284
285 **1)V-BOX setting**
286
287 |**Item**|**Settings**|**Note**
288 |Protocol|Allen-Bradley DF1 Advanced|
289 |Connection|RS232|
290 |Baud rate|19200|
291 |Data bit|8|
292 |Parity|None|
293 |Stop bit|1|
294 |PLC station No.|1|
295
296 **2)Address List**
297
298 |**Type**|**Device registers**|**Format**|**Range**|**Note**
299 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
300 |O|O d.d|0.0~~255.15|
301 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
302 |S|S d.d|0.0~~255.15|
303 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
304 |(% rowspan="9" %)Word|S|S d|0~~255|
305 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
306 |TP|TP nnhh|0~~ffff
307 |CS|CS nnhh|0~~ffff
308 |CP|CP nnhh|0~~ffff
309 |N|N nnhh|0~~ffff
310 |C|C nnhh|0~~ffff
311 |T|T nnhh|0~~ffff
312 |R|R nnhh|0~~ffff
313
314 **3)Configure the communication protocol**[[image:image-20220824152928-1.png]]
315
316 **4)Configure the communication protocol**
317
318 [[image:image-20220824110724-1.png]]
319
320 == **Micro850_FreeTag Protocol** ==
321
322 (((
323 (((
324 This example introduces the establishment of Ethernet communication between Wecon V-box and CompactLogix L1769. It is introduced through three parts: PLC software configuration, V-box software configuration, and hardware wiring.
325 )))
326 )))
327
328 (((
329 (% class="wikigeneratedid" id="HSoftwareconfigurationofPLC" %)
330 (((
331 **Software configuration of PLC**
332 )))
333
334 (% class="wikigeneratedid" id="HPLCprogrammingsoftware" %)
335 (((
336 **1)PLC programming software**
337 )))
338
339 [[image:image-20220714162600-1.png]]
340
341 (% class="wikigeneratedid" id="HNewPLCproject" %)
342 (((
343 **2)New PLC project**
344 )))
345
346 (((
347 (((
348 Click New Project and select the PLC model.
349 )))
350 )))
351
352 (((
353 [[image:image-20220714162617-2.png]]
354 )))
355
356 (((
357
358
359 [[image:image-20220714162652-4.png]]
360 )))
361
362 (((
363 (% class="wikigeneratedid" id="HSetEthernetparameters" %)
364 (((
365 **3)Set Ethernet parameters**
366 )))
367
368 (((
369 (((
370 (((
371 Follow the steps below to configure Ethernet parameters
372 )))
373 )))
374 )))
375
376 (((
377 (((
378 (((
379 PLC IP address:192.168.40.101
380 )))
381 )))
382 )))
383
384 (((
385 (((
386 (((
387 default gateway:192.168.40.1
388 )))
389 )))
390 )))
391
392 (((
393 (((
394 (((
395 subnet mask:255.255.255.0
396 )))
397 )))
398 )))
399
400 (((
401 [[image:image-20220714162713-5.png]]
402 )))
403
404 (((
405
406 )))
407
408 (((
409 (% class="wikigeneratedid" id="HV-boxsoftwareconfiguration" %)
410 (((
411 **V-box software configuration**
412 )))
413
414 (% class="wikigeneratedid" id="HV-boxprogrammingsoftware" %)
415 (((
416 **1)V-box programming software**
417 )))
418
419 (% class="wikigeneratedid" %)
420 (((
421 [[image:image-20220714162725-6.png]]
422 )))
423
424 (% class="wikigeneratedid" id="HConfiguredevicenetwork" %)
425 (((
426 **2)Configure device network**
427 )))
428
429 (((
430 (((
431 (((
432 Click the Configuration Download button[[image:image-20220714115308-8.png||height="22" width="15"]], It is used to configure the device network, update the device time, obtain the device machine code, check the device network, etc.
433 )))
434
435 (((
436 In the example below, the IP address of V-Box is configured as 192.168.40.66, and the networking method is 4G connection
437 )))
438 )))
439 )))
440
441 (((
442 (((
443 [[image:image-20220714162737-7.png]]
444
445
446 )))
447 )))
448 )))
449 )))
450
451 (% class="wikigeneratedid" id="HV-netadddevice" %)
452 (((
453 **3)V-net add device**
454 )))
455 )))
456
457 (((
458 (((
459 Open VNET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the device machine code/product code, device password, and device alias to add the device.   [[image:image-20220714162752-8.png]]
460 )))
461
462
463 )))
464
465 (((
466 (% class="wikigeneratedid" id="HSetcommunicationportparameters" %)
467 (((
468 **4)Set communication port parameters**
469 )))
470
471 (((
472 In the device list on the left, find the Vbox that communicates with the L1769, click it and select configuration,communication port configuration in the main interface to add a communication protocol.
473 )))
474
475 [[image:image-20220714162805-9.png]]
476 )))
477
478 (((
479 The communication port is selected as Ethernet, the device type is selected as Allen-Bradley, the protocol is Allen-BradleyMicro850_FreeTag EthemetIP, and the IP is the internal IP address of the L1769 PLC. The port number is 44818.
480 )))
481
482 [[image:image-20220824164346-1.png]]
483
484
485 (((
486 After adding the protocol Allen-BradleyMicro850_FreeTag, click[[image:image-20220714143838-2.png]]icon add label.[[image:image-20220714162827-11.png]]
487 )))
488
489 (% class="wikigeneratedid" id="HEngineeringproduction" %)
490 (((
491 **5)Engineering production**
492 )))
493
494 (% class="wikigeneratedid" %)
495 (((
496 (((
497 According to your own needs, use the V-NET client software to edit the required data monitoring points.
498 )))
499
500 [[image:image-20220714162841-12.png]]
501
502
503 (((
504 **hardware connection**
505 )))
506 )))
507
508 (((
509 **1)Hardware wiring diagram**
510 )))
511
512 (((
513 (((
514 This example introduces Wecon V-box with Allen-Bradley L1769 PLC to establish communication through Ethernet. The connection diagram is as follows:
515 )))
516
517 [[image:image-20220714162856-13.png]]
518
519 (((
520 The above are all the steps for establishing Ethernet communication between Wecon V-box with CompactLogix L1769 PLC.
521
522
523 == **Micro850_FreeTag Protocol(new)** ==
524
525 This example introduces the establishment of Ethernet communication between Wecon V-box and 2080-LC50-48QWB,Micro850. It is introduced through three parts: PLC software configuration, V-box software configuration.
526
527 (% class="wikigeneratedid" id="HSoftwareconfigurationofPLC" %)
528 (((
529 **Software configuration of PLC**
530 )))
531
532 (% class="wikigeneratedid" id="HPLCprogrammingsoftware" %)
533 (((
534 **1)PLC programming software:Connected Components Workbench™**
535
536 (% style="text-align:center" %)
537 [[image:software.png]]
538
539 **2)New PLC project**
540
541 Click New Project and select the PLC model.
542
543 (% style="text-align:center" %)
544 [[image:project create.png]]
545
546 **3)Set Ethernet parameters**
547
548 Follow the steps below to configure Ethernet parameters
549
550 PLC IP address:192.168.39.56
551
552 default gateway:192.168.39.1
553
554 subnet mask:255.255.255.0
555
556 (% style="text-align:center" %)
557 [[image:Ethernet.png]]
558
559 **4)connect PLC**
560
561 **When downloading the setting, need to change the status of the PLC to PRG**
562
563 (% style="text-align:center" %)
564 [[image:conne ab plc.png]]
565
566 **V-box software configuration**
567
568 **1)V-box programming software**
569
570 (% style="text-align:center" %)
571 [[image:v-net client vers.png]]
572
573 **2)Set communication port parameters**
574
575 In the device list on the left, find the Vbox that communicates with the L1769, click it and select configuration,communication port configuration in the main interface to add a communication protocol.
576
577 (% style="text-align:center" %)
578 [[image:V-NET_Client_t2Rg2wpSoY.png]]
579
580 The communication port is selected as Ethernet, the device type is selected as Allen-Bradley, the protocol is Allen-BradleyMicro850_FreeTag EthemetIP, and the IP is the internal IP address of the L1769 PLC. The port number is 44818.
581
582 (% style="text-align:center" %)
583 [[image:V-NET_Client_communication.png]]
584
585 Export variables from PLC, select CSV file, comma delimited.(% id="cke_bm_1950S" style="display:none" %)
586
587 (% style="text-align:center" %)
588 [[image:export1.png]]
589
590 (% style="text-align:center" %)
591 [[image:CCW.Shell_E5Cwj4tUL3.png]]
592
593 After adding the protocol Allen-BradleyMicro850_FreeTag, click[[image:https://docs.we-con.com.cn/bin/download/V-BOX/V-Net/Training/1%20Communication/WebHome/image-20220714143838-2.png?rev=1.1||alt="image-20220714143838-2.png"]]icon add label.
594
595 (% style="text-align:center" %)
596 [[image:V-NET_Client_TNBuqy7T5r.png]]
597
598 **3)Engineering production**
599
600 According to your own needs, use the V-NET client software to edit the required data monitoring points.
601
602 (% style="text-align:center" %)
603 [[image:V-NET_Client_KOR0AHEA4M.png]]
604
605
606 )))
607
608 == **Ethernet DF1 Protocol** ==
609
610 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Allen-Bradley%20Ethernet%20DF1.zip]]
611
612 = Create communication with **Crouzet PLC** =
613
614 == **CROUZET M3 (FBD)** ==
615
616 Support Series: Crouzet Millenium 3 CD12/CB12
617
618 **1)V-BOX setting**
619
620 |=Item|=Recommended |=Note
621 |=Protocol|CROUZET M3 (FBD)|
622 |=Connection|RS232|
623 |=Baud rate|115200|
624 |=Stop bits|1|
625 |=Data bits|7|
626 |=Parity|EVEN|
627
628 **2)Address List**
629
630 |=**Type**|=**Device registers**|=**Format**|=**Range**|=Note
631 |(% rowspan="4" %)Bit|I|I DD|1~~99|Input
632 |SLIBit|SLIBit DD.dd|1.0~~24.15|Serial Link Input
633 |SLOBit|SLOBit DD.dd|25.0~~48.15|Serial Link Output(Read only)
634 |State|State D|1~~1|PLC state(Read only)
635 |(% rowspan="5" %)Word|AI|AI DD|1~~99|Analog Input
636 |SLIn|SLIn DD|1~~24|Serial Link Input
637 |SLOut|SLOut DD|25~~48|Serial Link Output(Read only)
638 |Time|Time D|1~~6|(((
639 Time1: Second
640
641 Time2: Minute
642
643 Time3: Hour
644
645 Time4: Day
646
647 Time5: Month
648
649 Time6: Year
650 )))
651 |Order|Order D|1~~1|(((
652 Running command(Write only)
653
654 ~=2: Run mode; =1: Stop mode;
655 )))
656
657 **3)Cable Wiring**
658
659 (% style="text-align:center" %)
660 [[image:CrouzetRS232 VBox.png]]
661
662 {{info}}
663 **✎Note: **As the wiring diagram indicated, this protocol requires the DB9 serial port pin 4. But pin 4 is undefined for all V-Box, so it need the user to solder a Pull-up resistor to make the pin 4 working. As for how to solder the resistor on the motherboard, please contact with Wecon technical support for the details.
664 {{/info}}
665
666 = Create communication with EMERSON PLC =
667
668 == **RTU Slave Protocol** ==
669
670 Supported series: EC10 series
671
672 **1)V-BOX setting**
673
674 |**Items**|**Settings**|**Note**
675 |Protocol|Emerson 984 RTU Slave MODBUS|
676 |Connection|RS485|
677 |Baud rate|19200|
678 |Data bit|8|
679 |Parity|EVEN|
680 |Stop bit|1|
681 |Device station No.|1|Need to be same as the PLC setting
682
683 (% class="wikigeneratedid" %)
684 **2)PLC Setting**
685
686 (% class="wikigeneratedid" %)
687 Remember to use the Control Star to enable the Modbus RTU communication for port 1 in system block before dowload into PLC.
688
689 (% style="text-align:center" %)
690 [[image:ControlStarSystemBlock.png]]
691
692 (% style="text-align:center" %)
693 [[image:ControlStarCommunicate.png]]
694
695 (% style="text-align:center" %)
696 [[image:ControlStarModbus.png]]
697
698 (% class="wikigeneratedid" %)
699 **3)Address List**
700
701 |**Type**|**Device registers**|**Format**|**Range**|**Note**
702 |(% colspan="1" rowspan="12" %)Bit|Y|YOOO|0~~377|
703 |X|XOOO|0~~377|
704 |M0|M0DDDD|0~~2047|
705 |M1|M1DDDDD|2048~~10239|
706 |SM0|SM0DDD|0~~255|
707 |SM1|SM1DDD|256~~511|
708 |S0|S0DDDD|0~~1023|
709 |S1|S1DDDD|1024~~4095|
710 |T0|T0DDD|0~~255|
711 |T1|T1DDD|256~~511|
712 |C0|C0DDD|0~~255|
713 |C1|C1DDD|256~~306|
714 |(% colspan="1" rowspan="7" %)Word|D|DDDDD|0~~7999|
715 |Z|ZDD|0~~15|
716 |TW0|TW0DDD|0~~255|
717 |TW1|TW1DDD|256~~511|
718 |SD0|SD0DDD|0~~255|
719 |SD1|SD1DDD|256~~511|
720 |CW|CWDDD|0~~306|
721 |(% colspan="1" rowspan="2" %)Double Word|CW0|CW0DDD|200~~255|
722 |CW1|CW1DDDDD|256~~99999|
723
724 **4) Cable Wiring**
725
726 (% style="text-align:center" %)
727 [[image:Emerson.png]]
728
729 = Create communication with **Siemens PLC** =
730
731 == **S7-200 Smart Ethernet Protocol** ==
732
733 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20S7-200%20Smart.zip]]
734
735
736 == **S7-300 Ethernet Protocol** ==
737
738 Supported Series: Siemens S7-300 series PLC
739
740 **1)V-BOX setting**
741
742 |**Items**|**Settings**|**Note**
743 |Protocol|Simens S7-300 Ethernet|
744 |Connection|Ethernet|
745 |Port No.|102|
746 |PLC station No.|2|Need to be same as the PLC setting
747
748 **2)Address List**
749
750 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
751 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
752 |Q|Q|Q ddddd.o|0.0~~99999.7|
753 |M|M|M ddddd.o|0.0~~99999.7|
754 |DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
755 nn: block number;
756
757 dddd: address;
758 )))
759 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
760 |Q|QW|QW ddddd|0~~99999|
761 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
762 |MW|MW ddddd|0~~99999|(((
763 MW0=MB(0~~1)
764
765 MW2=MB(2~~3)
766
767 Address value is a multiple of 2
768 )))
769 |MD|MD ddddd|0~~99999|(((
770 MD0=MB(0~~3)
771
772 MD4=MB(4~~7)
773
774 Address value is a multiple of 4
775 )))
776 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
777 nn: block number;
778
779 dddd: address
780 )))
781 |DBxDBW|DBxDBW nndddd|0~~99999999
782 |DBxDBD|DBxDBD nndddd|0~~99999999
783
784 **3)Configure the communication protocol**
785
786 [[image:image-20220824161345-1.png]]
787
788 **4)Cable Wiring**
789
790 [[image:image-20220824161450-2.png]]
791 )))
792 )))
793
794 == **S7-1200 Ethernet Protocol** ==
795
796 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]]
797
798 == **S7-XXX Ethernet Protocol** ==
799
800 Supported Series: Siemens S7-400, S7-1200 and S7-1500
801
802 **1)V-BOX setting**
803
804 |=**Items**|=**Settings**|=**Note**
805 |Protocol|Siemens S7-XXX|
806 |Connection|Ethernet|
807 |Port No.|102|
808 |Device No.|Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|
809 |HMI No.|Rack (Default as 0)|
810
811 Slot from TIA Portal is equal to Device No. of V-net
812
813 Rack from TIA Portal is equal to HMI No. of V-net
814
815 [[image:image-20220824162459-3.png]]
816
817 [[image:image-20220824163305-2.png]]
818
819 **2)Address List**
820
821 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
822 |(% rowspan="4" %)Bit|I|I|M d.o|(((
823 d:0~-~-9999
824
825 o:0-7
826 )))|
827 |Q|Q|Q d.o|(((
828 d:0~-~-9999
829
830 o:0-7
831 )))|
832 |M|M|M d.o|(((
833 d:0~-~-9999
834
835 o:0-7
836 )))|
837 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
838 nn:0-9999,
839
840 dddd:0-9999,
841
842 o:0-7
843 )))|(((
844 nn:DB No.
845
846 dddd:address value
847
848 o: digit address
849 )))
850 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
851 |M|MW|MW d|d:0-99999|(((
852 MW0=MB(0~~1)
853
854 MW2=MB(2~~3)
855
856 Address value is a multiple of 2
857 )))
858 |M|MD|MD d|d:0-99999|(((
859 MD0=MB(0~~3)
860
861 MD4=MB(4~~7)
862
863 Address value is a multiple of 4
864 )))
865 |I|IW|IW d|d:0-99999|
866 |Q|QW|QW d|d:0-99999|
867 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
868 nn:0-9999
869
870 dddd:0-9999
871 )))|(((
872 nn:DB No.
873
874 dddd:address value
875 )))
876 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
877 nn:0-9999
878
879 dddd:0-9999
880 )))|(((
881 nn:DB No.
882
883 dddd:address value
884
885 Address value is a multiple of 2
886 )))
887 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
888 nn:0-9999
889
890 dddd:0-9999
891 )))|(((
892 nn:DB No.
893
894 dddd:address value
895
896 Address value is a multiple of 4
897 )))
898
899 **3)Configure the communication protocol**
900
901 [[image:image-20220824163448-3.png]]
902
903 **✎Note:**
904
905 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three V-BOX.
906 * V-BOX access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
907
908 **4)Cable Wiring**
909
910 [[image:image-20220824162342-2.png]]
911
912 == **LOGO Ethernet Protocol** ==
913
914 Supported Series: Siemens Logo 0BA0, 0BA1 series
915
916 **V-BOX Settings**
917
918
919 |**Items**|**Settings**|**Note**
920 |Protocol|Siemens LOGO|
921 |Connection|Ethernet|
922 |Port No.|102|
923 |PLC station No.|2|
924
925 **Address List**
926
927
928 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
929 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
930 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
931 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
932 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
933 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
934 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
935 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
936 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
937 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
938 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
939 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
940 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
941 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
942 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
943 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
944
945 **PLC Settings in LOGO Software:**
946
947 Click [Tools]~-~-[Ethernet Connections],shown as below.
948
949 (% style="text-align:center" %)
950 [[image:PIStudio.12\.PLC protocols.WebHome@12.PLC Protocol_html_8b9d2322edf89519.png]]
951
952 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
953
954 (% style="text-align:center" %)
955 [[image:PIStudio.12\.PLC protocols.WebHome@image-20221228142937-4.png]]
956
957 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
958
959 (% style="text-align:center" %)
960 [[image:PIStudio.12\.PLC protocols.WebHome@image-20221228143047-5.png]]
961
962 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
963
964 (% style="text-align:center" %)
965 [[image:PIStudio.12\.PLC protocols.WebHome@image-20221228143246-6.png]]
966
967 **V-BOX Communication Settings**
968
969 Set PLC IP in [IP Address] settings;
970
971 (% style="text-align:center" %)
972 [[image:LldwDGntf4.png]]
973
974 Enable V-BOX Ethernet in [Network];
975
976 (% style="text-align:center" %)
977 [[image:WgvjfWbQif.png]]
978
979 TSAP setting
980
981 * The initialization script needs to set the source TSAP address and the target TSAP address, otherwise the communication will not be successful.
982
983 {{code language="LUA"}}
984 function init.main()
985 addr_setword("@W_0#HSW1200",8192) -- Set the source TSAP address
986 addr_setword("@W_0#HSW1201",4096) -- Set the destination TSAP address
987 end
988 {{/code}}
989
990 Note: The name of the test script is init, 8192 and 4096 are the data used for the test, there is no HSW address in the register option, but you can directly set the value of the corresponding address through the code.
991
992 **✎Note:**
993
994 * **Communication port configuration: **
995 ** Continuous length needs to be set to 0.
996 ** Integration interval needs to be set to 1. (no change may result in data errors)
997 ** Set Port and Device Station NO.
998 ** Other set as defaulted.
999 * **Notes on the use of registers:**
1000 ** Register VD: Use only registers that are multiples of 4, such as 0, 4, 8, etc.
1001 ** Register VW: Use only registers thay are multiples of 2, such as 0, 2, 4 etc. (Using an odd-length register may result in data errors, such as 2 3 4 )
1002
1003 = Create communication with **Mitsubishi PLC** =
1004
1005 == **FX1S,1N,2N Serial Protocol** ==
1006
1007 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
1008
1009 **1)V-BOX Settings**
1010
1011 |**Item**|**Settings**|**Note**
1012 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
1013 |Connection|RS422/RS485/RS232|
1014 |Baud rate|9600~~115200|
1015 |Data bit|7/8|
1016 |Parity|EVEN/Odd/None|
1017 |Stop bit|1/2|
1018 |PLC station No.|1~~255|
1019
1020 **2)Address List**
1021
1022 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1023 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1024 |Y|Y|Y o|0~~303237|
1025 |M|M|M d|0~~99999|
1026 |T|T|T d|0~~99999|
1027 |C|C|C d|0~~99999|
1028 |S|S|S d|0~~99999|
1029 |SM|SM|SM d|8000~~9999|
1030 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1031 |Y|Y|Y o|0~~303237|
1032 |M|M|M d|0~~99999|
1033 |T|T|T d|0~~99999|
1034 |C|C|C d|0~~199|
1035 |D|D|D d|0~~7999|
1036 |S|S|S d|0~~99999|
1037 |SD|SD|SD d|8000~~9999|
1038
1039 **3)Configure the communication protocol**
1040
1041 [[image:image-20220825102844-3.png]]
1042
1043 **4)Cable Wiring**
1044
1045 * **RS422**
1046
1047 [[image:image-20220825103350-4.png]]
1048
1049 [[image:image-20220825100845-4.png]]
1050
1051
1052 == **FX3U,3G,3GA Serial Protocol** ==
1053
1054 Supported Series: Mitsubishi FX3U, FX3G, FX3GA series
1055
1056 **1)V-BOX Settings**
1057
1058 |**Item**|**Settings**|**Note**
1059 |Protocol|Mitsubishi FX3U/3G/3GA|
1060 |Connection|RS422/RS485/RS232|
1061 |Baud rate|9600~~115200|
1062 |Data bit|7/8|
1063 |Parity|EVEN/Odd/None|
1064 |Stop bit|1/2|
1065 |PLC station No.|1~~255|
1066
1067 **2)Address List**
1068
1069 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1070 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1071 |Y|Y|Y o|0~~303237|
1072 |M|M|M d|0~~99999|
1073 |T|T|T d|0~~99999|
1074 |C|C|C d|0~~99999|
1075 |S|S|S d|0~~99999|
1076 |SM|SM|SM d|8000~~9999|
1077 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1078 |Y|Y|Y o|0~~303237|
1079 |M|M|M d|0~~99999|
1080 |T|T|T d|0~~99999|
1081 |C|C|C d|0~~199|
1082 |D|D|D d|0~~7999|
1083 |S|S|S d|0~~99999|
1084 |SD|SD|SD d|8000~~9999|
1085
1086 **3)Configure the communication protocol**
1087
1088 [[image:image-20220825102649-2.png]]
1089
1090 **4)Cable Wiring**
1091
1092 * **RS422**
1093
1094 [[image:image-20220825103421-5.png]]
1095
1096 [[image:image-20220825100845-4.png]]
1097
1098
1099 == **FX3U Ethernet Protocol** ==
1100
1101 Supported Modules: FX3U-ENET-ADP, FX3U-ENET-L
1102
1103 **1)V-BOX Settings**
1104
1105 |Items|Settings|Note
1106 |Protocol|Mitsubishi FX3U|
1107 |Connection|Ethernet|
1108 |Port No.|5009|Must be the same as the PLC setting
1109 |PLC station No.|0|
1110
1111 **2)Address List**
1112
1113 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1114 |(% colspan="1" rowspan="7" %)Bit|X|X|X OOO|0~~377|
1115 |Y|Y|Y OOO|0~~377|
1116 |M|M|M DDDD|0~~7679|
1117 |SM|SM|SM DDDD|8000~~8511|
1118 |S|S|S DDDD|0~~4095|
1119 |TS|TS|TS DDD|0~~511|
1120 |CS|CS|CS DDD|0~~255|
1121 |(% colspan="1" rowspan="9" %)Word|CN|CN|CN DDD|0~~199|
1122 |TN|TN|TN DDD|0~~511|
1123 |D|D|D DDDD|0~~7999|
1124 |SD|SD|SD DDDD|8000~~8511|
1125 |R|R|R DDDDD|0~~32767|
1126
1127 **3)Ethernet Module Settings**
1128
1129 FX3U-ENET-L module configuration
1130 Set up the FX3U-ENET-L Ethernet module settings as follows.
1131 Select the module location, which in this document is Module 0.
1132
1133 [[image:image-20221116105850-1.png]]
1134
1135 Select "Operational setting" to enter the following screen.
1136
1137 The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default.
1138
1139 [[image:image-20221116105947-1.png]]
1140
1141 Select "Open setting" to enter the setting interface, the settings are as follows.
1142
1143 The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the
1144
1145 Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module.
1146
1147 [[image:image-20221116110802-1.png]]
1148
1149 Click on "transter setup" - "PC side I/F setting", see the following figure.
1150
1151 After setting, the first download must use the programming cable, as shown in the figure; after that, can
1152
1153 use the IP set in the "Ethernet board" to communicate directly with the network cable.
1154
1155 [[image:image-20221116110832-2.png||height="423" width="708"]]
1156
1157 Read and write data from the Ethernet module
1158
1159 [[image:image-20221116110907-3.png]]
1160
1161 Set "Transter setup" to COM communication, and read or write operation as shown below
1162
1163 [[image:image-20221116110917-4.png]]
1164
1165 **4)PLC Settings (GX Works 2)**
1166
1167 Create a blank FX5U project
1168
1169 Find Current Connection in the navigation
1170
1171 [[image:image-20221116111427-1.png||height="421" width="705"]]
1172
1173 Select Connection Channel List
1174
1175 Select Ethernet board communication
1176
1177 [[image:image-20221116111451-2.png||height="421" width="705"]]
1178
1179 Select Ethernet Module
1180 Set the IP address of the PLC
1181
1182 [[image:image-20221116111509-3.png||height="666" width="699"]]
1183
1184 Read or write PLC data, in this document is read
1185
1186 [[image:image-20221116111651-4.png||height="416" width="697"]]
1187
1188 [[image:image-20221116111727-5.png||height="416" width="697"]]
1189
1190 **4)Configure the communication protocol**
1191
1192 [[image:image-20221119101946-2.png||height="395" width="695"]]
1193
1194 == **FX5U Serial Protocol** ==
1195
1196 Mitsubishi FX5U series PLC
1197
1198 **1)V-BOX Settings**
1199
1200 |**Item**|**Settings**|**Note**
1201 |Protocol|Mitsubishi FX5U|
1202 |Connection|RS422/RS485|
1203 |Baud rate|9600|
1204 |Data bit|7|
1205 |Parity|Odd|
1206 |Stop bit|1|
1207 |PLC station No.|1~~255|Need to be the same as PLC settings
1208
1209 **2)Address List**
1210
1211 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1212 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1213 |Y|Y|Y o|0~~303237|
1214 |M|M|M d|0~~99999|
1215 |B|B|B h|0~~7FFF|
1216 |F|F|F d|0~~32767|
1217 |SB|SB|SB h|0~~7FFF|
1218 |TS|TS|TS d|0~~1023|
1219 |TC|TC|TC d|0~~1023|
1220 |STS|STS|STS d|0~~1023|
1221 |STC|STC|STS d|0~~1023|
1222 |CS|CS|CS d|0~~1023|
1223 |CC|CC|CC d|0~~1023|
1224 |SM|SM|SM d|0~~9999|
1225 |L|L|L d|0~~32767|
1226 |S|S|S d|0~~4095|
1227 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1228 |TN|TN|TN d|0~~1023|
1229 |STN|STN|STN d|0~~1023|
1230 |CN|CN|CN d|0~~1023|
1231 |R|R|R d|0~~32767|
1232 |SW|SW|SW h|0~~7FFF|
1233 |Z|Z|Z d|0~~23|
1234 |D|D|D d|0~~7999|
1235 |SD|SD|SD d|0~~11999|
1236
1237 **3)PLC Settings (GX Works 3)**
1238
1239 Create a blank FX5U project
1240
1241 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
1242
1243 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5c9cb13fac1e6c93.png?width=200&height=462&rev=1.1||alt="12.PLC Protocol_html_5c9cb13fac1e6c93.png" height="462" width="200"]]
1244
1245 Select protocol in the setting item, and set parameters.
1246
1247 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_de942589ca070228.png?width=600&height=324&rev=1.1||alt="12.PLC Protocol_html_de942589ca070228.png" height="324" width="600"]]
1248
1249 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
1250
1251 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_387ec7d00b5feb59.png?width=600&height=323&rev=1.1||alt="12.PLC Protocol_html_387ec7d00b5feb59.png" height="323" width="600"]]
1252
1253 Click the [Apply] button to finish the setting.
1254
1255 Click download and select the items as below, then click [execute] to download the configuration to PLC.
1256
1257 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_cdef1c5ec8cc2105.png?width=600&height=434&rev=1.1||alt="12.PLC Protocol_html_cdef1c5ec8cc2105.png" height="434" width="600"]]
1258
1259 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
1260
1261 Done.
1262
1263 **4)Configure the communication protocol**
1264
1265 [[image:image-20220825104904-1.png]]
1266
1267 **5)Cable Wiring**
1268
1269
1270 * **RS422**
1271
1272 [[image:image-20220825105105-2.png]]
1273
1274 [[image:image-20220825105533-3.png]]
1275
1276 == **FX5U Ethernet Protocol** ==
1277
1278 Mitsubishi FX5U series PLC
1279
1280 **1)V-BOX Settings**
1281
1282 |**Items**|**Settings**|**Note**
1283 |Protocol|Mitsubishi FX5U|
1284 |Connection|Ethernet|
1285 |Port No.|5002|Must be the same as the PLC setting
1286 |PLC station No.|0|
1287
1288 **2)Address List**
1289
1290 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1291 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1292 |Y|Y|Y o|0~~303237|
1293 |M|M|M d|0~~99999|
1294 |B|B|B h|0~~7FFF|
1295 |F|F|F d|0~~32767|
1296 |SB|SB|SB h|0~~7FFF|
1297 |TS|TS|TS d|0~~1023|
1298 |TC|TC|TC d|0~~1023|
1299 |STS|STS|STS d|0~~1023|
1300 |STC|STC|STS d|0~~1023|
1301 |CS|CS|CS d|0~~1023|
1302 |CC|CC|CC d|0~~1023|
1303 |SM|SM|SM d|0~~9999|
1304 |L|L|L d|0~~32767|
1305 |S|S|S d|0~~4095|
1306 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1307 |TN|TN|TN d|0~~1023|
1308 |STN|STN|STN d|0~~1023|
1309 |CN|CN|CN d|0~~1023|
1310 |R|R|R d|0~~32767|
1311 |SW|SW|SW h|0~~7FFF|
1312 |Z|Z|Z d|0~~23|
1313 |D|D|D d|0~~7999|
1314 |SD|SD|SD d|0~~11999|
1315
1316 **3)PLC Settings (GX Works 3)**
1317
1318 Find the [Ethernet port] in the navigation area.
1319
1320 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_8e8f85ace087346c.png?width=300&height=593&rev=1.1||alt="12.PLC Protocol_html_8e8f85ace087346c.png" height="593" width="300"]]
1321
1322 Select [Own Node Settings] in the [Setting Item List];
1323
1324 Set [IP Address], [Subnet Mask], [Default Gateway];
1325
1326 Click [Detailed Settings] into [Ethernet Configuration (Built-in Ethernet Port)] windows;
1327
1328 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5d98495052c8c10e.png?width=600&height=339&rev=1.1||alt="12.PLC Protocol_html_5d98495052c8c10e.png" height="339" width="600"]]
1329
1330 Select [SLMP Connection Module] and add into host station as below picture shows;
1331
1332 Set Port number as 5002 (this is necessary settings);
1333
1334 Click [Close with Reflecting the Setting] to save and close window;
1335
1336 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_14b489fdc6c6589d.png?width=600&height=350&rev=1.1||alt="12.PLC Protocol_html_14b489fdc6c6589d.png" height="350" width="600"]]
1337
1338 Click [Apply] to completed Etherenet settings;
1339
1340 Switch to the [On line data operation] interface as below, check the item and click [Execute] to download.
1341
1342 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_c93025a968a8a9e7.png?width=600&height=434&rev=1.1||alt="12.PLC Protocol_html_c93025a968a8a9e7.png" height="434" width="600"]]
1343
1344 **4)Configure the communication protocol**
1345
1346 [[image:image-20220825112403-1.png||alt="图片-20220825112403-1.png"]]
1347
1348 **5)Cable Wiring**
1349
1350 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1351
1352 == **L02 Serial Protocol** ==
1353
1354 Mitsubishi L02 series CPU built-in serial port.
1355
1356 **1)V-BOX Settings**
1357
1358 |**Item**|**Settings**|**Note**
1359 |Protocol|Mitsubishi L02|
1360 |Connection|RS422|
1361 |Baud rate|115200|
1362 |Data bit|8|
1363 |Parity|Odd|
1364 |Stop bit|1|
1365 |PLC station No.|1~~255|Need to be the same as PLC settings
1366
1367 **2)Address List**
1368
1369 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1370 |Bit|X|X|X h|0~~FFFF|
1371 |Bit|Y|Y|Y h|0~~FFFF|
1372 |Bit|M|M|M d|0~~9999|
1373 |Bit|L|L|L d|0~~9999|
1374 |Bit|F|F|F d|0~~9999|
1375 |Bit|B|B|B h|0~~FFFF|
1376 |Bit|V|V|V d|0~~2047|
1377 |Bit|TC|TC|TC d|0~~9999|
1378 |Bit|SS|SS|SS d|0~~9999|
1379 |Bit|SC|SC|SC d|0~~9999|
1380 |Bit|CS|CS|CS d|0~~9999|
1381 |Bit|CC|CC|CC d|0~~9999|
1382 |Bit|SB|SB|SB h|0~~FFFF|
1383 |Bit|SM|SM|SM d|0~~2047|
1384 |Bit|STS|STS|STS d|0~~1023|
1385 |Bit|S|S|S d|0~~9999|
1386 |Bit|DX|DX|DX h|0~~FFFF|
1387 |Bit|DY|DY|DY h|0~~FFFF|
1388 |Bit|TS|TS|TS d|0~~9999|
1389 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1390 |Word|W|W|W h|0~~FFFF|
1391 |Word|TN|TN|TN d|0~~99999|
1392 |Word|SN|SN|SN d|0~~99999|
1393 |Word|CN|CN|CN d|0~~99999|
1394 |Word|R|R|R d|0~~99999|
1395 |Word|SW|SW|SW h|0~~FFFF|
1396 |Word|Z|Z|Z d|0~~99999|
1397 |Word|ZR|ZR|ZR h|0~~FFFF|
1398 |Word|D|D|D d|0~~99999|
1399
1400 **3)Communication Settings**
1401
1402 [[image:image-20220825160648-3.png]]
1403
1404 **4)Cable Wiring**
1405
1406 * **RS422**
1407
1408 [[image:image-20220825161612-8.png]]
1409
1410 [[image:image-20220825160820-4.png]]
1411
1412 == **L02 Ethernet Protocol** ==
1413
1414 Mitsubishi L series CPU built-in Ethernet port.
1415
1416 **1)V-BOX Settings**
1417
1418 |**Items**|**Settings**|**Note**
1419 |Protocol|MIT L02 CPU MELSEC|
1420 |Connection|Ethernet|
1421 |Port No.|1025|Must be the same as the PLC setting
1422 |PLC station No.|0|Must be the same as the PLC setting
1423
1424 **2)Address List**
1425
1426 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1427 |Bit|X|X|X h|0~~FFFF|
1428 |Bit|Y|Y|Y h|0~~FFFF|
1429 |Bit|M|M|M d|0~~9999|
1430 |Bit|L|L|L d|0~~9999|
1431 |Bit|F|F|F d|0~~9999|
1432 |Bit|B|B|B h|0~~FFFF|
1433 |Bit|V|V|V d|0~~2047|
1434 |Bit|TC|TC|TC d|0~~9999|
1435 |Bit|SS|SS|SS d|0~~9999|
1436 |Bit|SC|SC|SC d|0~~9999|
1437 |Bit|CS|CS|CS d|0~~9999|
1438 |Bit|CC|CC|CC d|0~~9999|
1439 |Bit|SB|SB|SB h|0~~FFFF|
1440 |Bit|SM|SM|SM d|0~~2047|
1441 |Bit|STS|STS|STS d|0~~1023|
1442 |Bit|S|S|S d|0~~9999|
1443 |Bit|DX|DX|DX h|0~~FFFF|
1444 |Bit|DY|DY|DY h|0~~FFFF|
1445 |Bit|TS|TS|TS d|0~~9999|
1446 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1447 |Word|W|W|W h|0~~FFFF|
1448 |Word|TN|TN|TN d|0~~99999|
1449 |Word|SN|SN|SN d|0~~99999|
1450 |Word|CN|CN|CN d|0~~99999|
1451 |Word|R|R|R d|0~~99999|
1452 |Word|SW|SW|SW h|0~~FFFF|
1453 |Word|Z|Z|Z d|0~~99999|
1454 |Word|ZR|ZR|ZR h|0~~FFFF|
1455 |Word|D|D|D d|0~~99999|
1456
1457 **3)PLC Settings (GX Works2 )**
1458
1459 Create a project
1460
1461 Set PLC IP, subnet mask and gateway;
1462
1463 Select [Binary Code] as communication data code;
1464
1465 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_776e17505f3fc6c0.png?width=600&height=524&rev=1.1||alt="12.PLC Protocol_html_776e17505f3fc6c0.png" height="524" width="600"]]
1466
1467 Set PLC port number, for example 1025
1468
1469 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_8d0d1a22d388f70b.png?width=600&height=524&rev=1.1||alt="12.PLC Protocol_html_8d0d1a22d388f70b.png" height="524" width="600"]]
1470
1471 Save settings;
1472
1473 Download project into PLC device;
1474
1475 Restart PLC device;
1476
1477 **4)Configure the communication protocol**
1478
1479 [[image:image-20220825142659-1.png]]
1480
1481 **5)Cable Wiring**
1482
1483 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1484
1485 == **Q12H Serial Protocol** ==
1486
1487 This Demo shows V-BOX communicate with Q12H PLC by Q02H serial Protocol
1488
1489 [[**Download link**>>https://ftp.we-con.com.cn/Download/WIKI/PI%20HMI/Demo/Communication/V-Box%20connect%20PLC%20Q12H.rar]]
1490
1491 == **QJ71E71 Ethernet Protocol** ==
1492
1493 Mitsubishi QJ71E71 Ethernet communication module;
1494
1495 **1)V-BOX Settings**
1496
1497 |**Items**|**Settings**|**Note**
1498 |Protocol|MIT QJ71E71 MELSEC|
1499 |Connection|Ethernet|
1500 |Port No.|1025|Must be the same as the PLC setting
1501 |PLC station No.|0|Must be the same as the PLC setting
1502
1503 **2)Address List**
1504
1505 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1506 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1507 |Y|Y|Y h|0~~1FFF|
1508 |M|M|M d|0~~99999|
1509 |L|L|L d|0~~8191|
1510 |F|F|F d|0~~2047|
1511 |B|B|B h|0~~1FFF|
1512 |V|V|V d|0~~2047|
1513 |TS|TS|TS d|0~~2047|
1514 |TC|TC|TC d|0~~2047|
1515 |SS|SS|SS d|0~~2047|
1516 |SC|SC|SC d|0~~2047|
1517 |CS|CS|CS d|0~~1023|
1518 |CC|CC|CC d|0~~1023|
1519 |SB|SB|SB h|0~~7FF|
1520 |S|S|S d|0~~8191|
1521 |DX|DX|DX h|0~~1FFF|
1522 |DY|DY|DY h|0~~1FFF|
1523 |SM|SM|SM d|8000~~9999|
1524 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1525 |D|D|D d|0~~12287|
1526 |W|W|W h|0~~1FFF|
1527 |TN|TN|TN d|0~~2047|
1528 |SN|SN|SN d|0~~2047|
1529 |CN|CN|CN d|0~~1023|
1530 |R|R|R d|0~~32767|
1531 |SW|SW|SW h|0~~7FF|
1532 |Z|Z|Z d|0~~15|
1533 |ZR|ZR|ZR h|0~~FE7FF|
1534
1535 **3)PLC Settings(GX Works2)**
1536
1537 * Click [Ethernet/CC IE/MELSECNET];
1538 * Please select [Ethernet] as network type;
1539 * Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order);
1540 * Select [Online] as Mode;
1541 * [[image:image-20221119171343-2.png||height="341" width="587"]]
1542 * Click [Operation setting] to set IP;
1543 * Select [Binary Code] as [Communication Data Code];
1544 * [[image:image-20221119171436-3.png||height="354" width="588"]]
1545 * Click [Open setting]
1546 * Set protocol: TCP;
1547 * Set [unpassive] in [Open system];
1548 * Set [receive] in [Fixed buffer];
1549 * Set [procedure Exist] in [Fixed buffer communication];
1550 * Disable [Pairing open];
1551 * Set [No confirm] in [Existence confirmation];
1552 * Host station port number: 5009;
1553 * Save settings;
1554 * [[image:image-20221119171611-4.png||height="354" width="588"]]
1555 * Download project into PLC and restart it
1556
1557 **4)Configure the communication protocol**
1558
1559 [[image:image-20221119171832-5.png||height="354" width="625"]]
1560
1561
1562 **5)Cable Wiring**
1563
1564 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png"]]
1565
1566 = Create communication with **Delta PLC** =
1567
1568 == **DVP Ethernet Protocol** ==
1569
1570 Supoort Series: DELTA DVP20/32/40/60ES200RE/200TE or any DVP models with built-in Ethernet port, DELTA DVPEN01-SL module
1571
1572 **1)V-BOX Settings**
1573
1574 |=**Items**|=**Settings**|=**Note**
1575 |Protocol|DELTA DVP MODBUS TCP|
1576 |Connection|Ethernet|
1577 |Port No.|502|
1578 |Device No.|1|
1579 |VBox Device No.|0|
1580
1581 **2)Address List **
1582
1583 |=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 217px;" %)**VBox registers**|=(% style="width: 168px;" %)**Format**|=(% style="width: 225px;" %)**Range**|=**Note**
1584 |Bit|(% style="width:191px" %)X|(% style="width:217px" %)X|(% style="width:168px" %)X OOO|(% style="width:225px" %)0~~377|
1585 |Bit|(% style="width:191px" %)Y|(% style="width:217px" %)Y|(% style="width:168px" %)Y OOO|(% style="width:225px" %)0~~377|
1586 |Bit|(% style="width:191px" %)M0|(% style="width:217px" %)M0|(% style="width:168px" %)M0DDDD|(% style="width:225px" %)0~~1535|
1587 |Bit|(% style="width:191px" %)M1|(% style="width:217px" %)M1|(% style="width:168px" %)M1DDDD|(% style="width:225px" %)1536~~4096|
1588 |Bit|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDD|(% style="width:225px" %)0~~255|
1589 |Bit|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~255|
1590 |Bit|(% style="width:191px" %)S|(% style="width:217px" %)S|(% style="width:168px" %)SDDDD|(% style="width:225px" %)0~~1023|
1591 |Word|(% style="width:191px" %)D0|(% style="width:217px" %)D0|(% style="width:168px" %)D0DDDD|(% style="width:225px" %)0~~4095|
1592 |Word|(% style="width:191px" %)D1|(% style="width:217px" %)D1|(% style="width:168px" %)D1DDDD|(% style="width:225px" %)4096~~11999|
1593 |Word|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDD|(% style="width:225px" %)0~~255|
1594 |Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~199|
1595 |Double Word|(% style="width:191px" %)HC|(% style="width:217px" %)HC|(% style="width:168px" %)HCDDD|(% style="width:225px" %)200~~255|
1596
1597 **3) PLC Setting:**
1598
1599 ~1. Create new project in Delta WPL Soft, and click Setting to open the communication settings:
1600
1601 (% style="text-align:center" %)
1602 [[image:DVPEthernetWPLSoft2.png]]
1603
1604 2. Set up the communication type and PLC IP:
1605
1606 (% style="text-align:center" %)
1607 [[image:DVPEthernetSetup.png]]
1608
1609 (% class="wikigeneratedid" %)
1610 3. Click OK and save the settings. Then click Communication on toolbar, then click Transfer Setup to open new window:
1611
1612 (% style="text-align:center" %)
1613 [[image:DVPEthernetTransfer.png]]
1614
1615 (% class="wikigeneratedid" %)
1616 4. Select Communication Mode as PC => PLC to download or select PC <=PLC to upload:
1617
1618 (% style="text-align:center" %)
1619 [[image:DVPEthernetPLCtoPC.png]]
1620
1621 5. Click Auto-Search Ethernet Module to find the PLC on the same LAN network:
1622
1623 (% style="text-align:center" %)
1624 [[image:DVPEthernetAutoSearch.png]]
1625
1626 **4) V-BOX Setting:**
1627
1628 Set the same IP address according to the setting from WPL Soft:
1629
1630 (% style="text-align:center" %)
1631 [[image:DVPEthernetVNETPortocol.png]]
1632
1633 == **DVP serial protocol** ==
1634
1635 Supoort Series: DELTA DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX
1636
1637 **1)V-BOX Settings**
1638
1639 |=**Items**|=**Settings**|=**Note**
1640 |Protocol|DELTA DVP PROTOCOL|
1641 |Connection|RS232|
1642 |Baud Rate|9600|
1643 |Stop Bit|1|
1644 |Data Bit|7|
1645 |Parity|EVEN|
1646 |Device No.|1|
1647
1648 (% class="wikigeneratedid" %)
1649 **2)Address List**
1650
1651 |=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 217px;" %)**VBox registers**|=(% style="width: 168px;" %)**Format**|=(% style="width: 225px;" %)**Range**|=**Note**
1652 |Bit|(% style="width:191px" %)X|(% style="width:217px" %)X|(% style="width:168px" %)X OOOOOO|(% style="width:225px" %)0~~303237|
1653 |Bit|(% style="width:191px" %)Y|(% style="width:217px" %)Y|(% style="width:168px" %)Y OOOOOO|(% style="width:225px" %)0~~303237|
1654 |Bit|(% style="width:191px" %)M|(% style="width:217px" %)M|(% style="width:168px" %)MDDDDD|(% style="width:225px" %)0~~99999|
1655 |Bit|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDDDD|(% style="width:225px" %)0~~99999|
1656 |Bit|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDDDD|(% style="width:225px" %)0~~99999|
1657 |Bit|(% style="width:191px" %)S|(% style="width:217px" %)S|(% style="width:168px" %)SDDDDD|(% style="width:225px" %)0~~99999|
1658 |Word|(% style="width:191px" %)D|(% style="width:217px" %)D|(% style="width:168px" %)D DDDDD|(% style="width:225px" %)0~~99999|
1659 |Word|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDDDD|(% style="width:225px" %)0~~99999|
1660 |Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~199|
1661 |Double Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDDDD|(% style="width:225px" %)200~~99999|
1662
1663 (% class="wikigeneratedid" %)
1664 **3)Wiring Diagram**
1665
1666 (% style="text-align:center" %)
1667 [[image:Delta DVP PROTOCOLSerial232.png]]
1668
1669 == **AS Ethernet Protocol** ==
1670
1671 **1)V-BOX Settings**
1672
1673 |=**Items**|=**Settings**|=**Note**
1674 |Protocol|DELTA AS300 MODBUS TCP|
1675 |Connection|Ethernet|
1676 |Port No.|502|
1677 |Device No.|1|
1678 |HMI No.|0|
1679
1680 **2)Address List**
1681
1682 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1683 |Bit|X|X|X d|0~~63|
1684 |Bit|Y|Y|Y d|0~~63|
1685 |Bit|D|D|D d|0~~29999|
1686 |Bit|M|M|M d|0~~8191|
1687 |Bit|SM|SM|SM d|0~~4095|
1688 |Bit|S|S|S h|0~~2047|
1689 |Bit|T|T|T d|0~~511|
1690 |Bit|C|C|C d|0~~511|
1691 |Bit|HC|HC|HC d|0~~255|
1692 |Word|X|X|X h|0~~63|
1693 |Word|Y|Y|Y d|0~~63|
1694 |Word|SR|SR|SR d|0~~2047|
1695 |Word|D|D|D d|0~~29999|
1696 |Word|T|T|T d|0~~511|
1697 |Word|C|C|C h|0~~511|
1698 |Word|E|E|E d|0~~9|
1699
1700 **3)Configure the communication protocol**
1701
1702 [[image:image-20220831160010-4.png]]
1703
1704 **4)Cable Wiring**
1705
1706 Figure
1707
1708 [[image:image-20220831155101-1.png]][[image:image-20220831160055-5.png]]
1709
1710 Pin Definition Diagram
1711
1712 [[image:image-20220831155157-3.png]]
1713
1714 = Create communication with **Omron PLC** =
1715
1716 == **CP1 Series Protocol ** ==
1717
1718 [[下载链接>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CP1%20Series.zip]]
1719
1720 == **CP2M Series Protocol** ==
1721
1722 [[下载链接>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CJ2M.zip]]
1723
1724
1725 == **EC55 Series Protocol** ==
1726
1727 Supported device: EC55 temperature instrument
1728
1729 **1)V-BOX Settings**
1730
1731 |**Items**|**Settings**|**Note**
1732 |Protocol|Omron EC55|
1733 |Connection|RS485 (9600, 2, 7, EVEN)|
1734 |Port No.|None|
1735 |PLC station No.|0|
1736
1737 **2)Address List**
1738
1739 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
1740 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
1741 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
1742 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
1743 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
1744 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
1745 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
1746 |CP|-|0-6|Read controller intrinsic property
1747 |CS|-|0-2|Read controller states
1748 |CA|-|0-17|Action command
1749
1750 **3)Device Settings**
1751
1752 Omron E5CC PLC configuration
1753
1754 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
1755
1756 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_3d95e093792ba98a.png?width=550&height=229&rev=1.1||alt="12.PLC Protocol_html_3d95e093792ba98a.png" height="229" width="550"]]
1757
1758 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
1759
1760 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_be583aa69dd6cf4c.png?width=550&height=242&rev=1.1||alt="12.PLC Protocol_html_be583aa69dd6cf4c.png" height="242" width="550"]]
1761
1762 **✎Note:** The communication settings for HMI should be consistent with this setting.
1763
1764 **4)Configure the communication protocol**
1765
1766 [[image:image-20220831161041-1.png]]
1767
1768 **5)Cable Wiring**
1769
1770 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5e9a81a14106da9e.png?width=392&height=223&rev=1.1||alt="12.PLC Protocol_html_5e9a81a14106da9e.png" height="223" width="392"]]
1771
1772 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_1897d92be6948d58.png?width=393&height=223&rev=1.1||alt="12.PLC Protocol_html_1897d92be6948d58.png" height="223" width="393"]]
1773
1774 **✎Note:**
1775
1776 * COM3 only available in PI8000/PI9000 series.
1777 * CA address could not support continuous writing function;
1778 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
1779 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
1780 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
1781 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
1782 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
1783 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
1784 * [[image:image-20220831161356-1.png]]Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
1785
1786 = Create communication with Xinje** PLC** =
1787
1788 == **XC serial protocol** ==
1789
1790 **1)V-BOX Settings**
1791
1792 |**Item**|**Settings**|**Note**
1793 |Protocol|XINJE XC MODBUS|
1794 |Connection|RS232|
1795 |Baud rate|19200|
1796 |Data bit|8|
1797 |Parity|EVEN|
1798 |Stop bit|1|
1799 |PLC station No.|1|
1800
1801 **2)Address List**
1802
1803 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1804 |Bit|M|M|M d|0~~8511|
1805 |Bit|X|X|X o|0~~1747|
1806 |Bit|Y|Y|Y o|0~~1747|
1807 |Bit|S|S|S d|0~~1023|
1808 |Bit|T|T|T d|0~~4095|
1809 |Bit|C|C|C d|0~~634|
1810 |Word|D|D|D d|0~~8511|
1811 |Word|TD|TD|TD d|0~~618|
1812 |Word|CD|CD|CD d|0~~634|
1813 |Word|FD|FD|FD d|0~~8511|
1814
1815 **3)Configure the communication protocol**
1816
1817
1818 [[image:image-20220831163041-1.png]]
1819
1820 **4)Cable Wiring**
1821
1822 Figure
1823
1824 [[image:image-20220831163406-2.png]][[image:image-20220831163422-3.png]]
1825
1826 Pin Definition Diagram
1827
1828 [[image:image-20220831163441-4.png]]
1829
1830 == **XD serial protocol** ==
1831
1832 **1)V-BOX Settings**
1833
1834 Supported Series: Xinjie XD/XE Series PLC
1835
1836 |**Item**|**Settings**|**Note**
1837 |Protocol|XINJE XD/XC MODBUS|
1838 |Connection|RS232|
1839 |Baud rate|19200|
1840 |Data bit|8|
1841 |Parity|EVEN|
1842 |Stop bit|1|
1843 |PLC station No.|1|
1844
1845 **2)Address List**
1846
1847 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1848 |Bit|M|M|M d|0~~74999|
1849 |Bit|X1xx|X1xx|X1xx o|0~~1177|
1850 |Bit|X2xx|X2xx|X2xx o|0~~277|
1851 |Bit|X|X|X o|0~~77|
1852 |Bit|Y1xx|Y1xx|Y1xx o|0~~1177|
1853 |Bit|Y2xx|Y2xx|Y2xx o|0~~277|
1854 |Bit|Y|Y|Y o|0~~4095|
1855 |Bit|SM|SM|SM d|0~~4999|(((
1856
1857 )))
1858 |Bit|T|T|T d|0~~4999|
1859 |Bit|C|C|C d|0~~4999|
1860 |Bit|ET|ET|ET d|0~~31|
1861 |Bit|SE|SE|SE d|0~~31|
1862 |Bit|HM|HM|HM d|0~~11999|
1863 |Bit|HSC|HSC|HSC d|0~~39|
1864 |Bit|HS|HS|HS d|0~~999|
1865 |Bit|HT|HT|HT d|0~~1999|
1866 |Bit|HC|HC|HC d|0~~1999|
1867 |Bit|S|S|S d|0~~7999|
1868 |Word|D|D|D d|0~~69999|
1869 |Word|ID|ID|ID d|0~~99|
1870 |Word|ID1xx|ID1xx|ID1xx d|0~~999|
1871 |Word|ID2xx|ID2xx|ID2xx d|0~~299|
1872 |Word|QD|QD|QD d|0~~99|
1873 |Word|QD1xx|QD1xx|QD1xx d|0~~999|
1874 |Word|QD2xx|QD2xx|QD2xx d|0~~299|
1875 |Word|SD|SD|SD d|0~~4999|
1876 |Word|TD|TD|TD d|0~~575|
1877 |Word|CD|CD|CD d|0~~575|
1878 |Word|ETD|ETD|ETD d|0~~31|
1879 |Word|HD|HD|HD d|0~~24999|
1880 |Word|HSD|HSD|HSD d|0~~1023|
1881 |Word|HTD|HTD|HTD d|0~~95|
1882 |Word|HCD|HCD|HCD d|0~~95|
1883 |Word|HSCD|HSCD|HSCD d|0~~31|
1884 |Word|FD|FD|FD d|0~~8191|
1885 |Word|SFD|SFD|SFD d|0~~5999|
1886 |Word|FS|FS|FS d|0~~47|
1887
1888 **3)Configure the communication protocol**
1889
1890 [[image:image-20220831163923-7.png]]
1891
1892
1893
1894 **4)Cable Wiring**
1895
1896 Figure
1897
1898 [[image:image-20220831163406-2.png]][[image:image-20220831163553-6.png]]
1899
1900 Pin Definition Diagram
1901
1902 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830160232-3.png?rev=1.1||alt="image-20220830160232-3.png"]]
1903
1904 = Create communication with **Schneider PLC** =
1905
1906 == **Schneider MODBUS RTU** ==
1907
1908 **1)V-BOX Setting**
1909
1910 |=**Parameters**|=**Recommended**|=**Notes**
1911 |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
1912 |**Connection**|RS485|
1913 |**Baud rate**|19200|
1914 |**Data bit**|8|
1915 |**Parity**|Even|
1916 |**Stop bit**|1|
1917 |**PLC station No.**|1|
1918
1919 **2)Address List**
1920
1921 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
1922 |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
1923 |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
1924 |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
1925 |W|MW|DDDDDD|0 ~~ 999999|Output register
1926 |DW|MD|DDDDDD|0 ~~ 999999|Output register
1927
1928 **3)Configure the communication protocol**
1929
1930 [[image:image-20220902104329-1.png]]
1931
1932 **4)Cable Wiring**
1933
1934 **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
1935
1936 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220817154212-1.jpeg?width=554&height=315&rev=1.1||alt="image-20220817154212-1.jpeg" height="315" width="554"]]
1937
1938 = Create communication with Inovance** PLC** =
1939
1940 == **H3U serial protocol** ==
1941
1942 **1)V-BOX Settings**
1943
1944 |**Item**|**Settings**|**Note**
1945 |Protocol|INOVANCE H3U PLC|
1946 |Connection|RS422|
1947 |Baud rate|9600|
1948 |Data bit|7|
1949 |Parity|EVEN|
1950 |Stop bit|1|
1951 |PLC station No.|0|
1952
1953 **2)Address List**
1954
1955 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1956 |Bit|X|X|X o|0~~303237|
1957 |Bit|Y|Y|Y o|0~~303237|
1958 |Bit|M|M|M d|0~~99999|
1959 |Bit|T|T|T d|0~~99999|
1960 |Bit|C|C|C d|0~~99999|
1961 |Bit|SM|SM|SM d|8000~~999|
1962 |Bit|S|T|S d|0~~99999|
1963 |Bit|Lamp|Lamp|Lamp d|0~~0|
1964 |Word|X|X|X o|0~~303237|
1965 |Word|Y|Y|Y o|0~~303237|
1966 |Word|M|M|M d|0~~99999|
1967 |Word|T|T|T d|0~~99999|
1968 |Word|C|C|C d|0~~199|
1969 |Word|D|D|D d|0~~7999|
1970 |Word|S|S|S d|0~~99999|
1971 |Word|SD|SD|SD d|8000~~9999|
1972 |Word|R|R|R d|0~~32767|
1973
1974 **3)Configure the communication protocol**
1975
1976 [[image:image-20220831164626-1.png]]
1977
1978
1979
1980 **4)Cable Wiring**
1981
1982 Figure
1983
1984 [[image:image-20220831164646-2.png]][[image:image-20220831164700-3.png]]
1985
1986 Pin Definition Diagram
1987
1988 [[image:image-20220831164731-4.png]]
1989
1990 = Create communication with Panasonic** PLC** =
1991
1992 == **FP serial protocol** ==
1993
1994 **1)V-BOX Settings**
1995
1996 |**Item**|**Settings**|**Note**
1997 |Protocol|Panasonic FP MFWTOCOL|
1998 |Connection|RS232|
1999 |Baud rate|9600|
2000 |Data bit|8|
2001 |Parity|ODD|
2002 |Stop bit|1|
2003 |PLC station No.|1|
2004
2005 **2)Address List**
2006
2007 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
2008 |Bit|X|X|X d|0~~9999|
2009 |Bit|Y|Y|Y d|0~~9999|
2010 |Bit|R|R|R d|0~~9999|
2011 |Bit|T|T|T d|0~~9999|
2012 |Bit|C|C|C d|0~~9999|
2013 |Bit|L|L|L d|0~~9999|
2014 |Word|WX|WX|WX d|0~~9999|
2015 |Word|WY|WY|WY d|0~~9999|
2016 |Word|WR|WR|WR d|0~~9999|
2017 |Word|WL|WL|WL d|0~~9999|
2018 |Word|LD|LD|LD d|0~~9999|
2019 |Word|DT|DT|DT d|0~~65535|
2020 |Word|FL|FL|FL d|0~~9999|
2021 |Word|EV|EV|EV d|0~~9999|
2022 |Word|SV|SV|SV d|0~~9999|
2023
2024 **3)Configure the communication protocol**
2025
2026 [[image:image-20220831165238-4.png]]
2027
2028
2029
2030 **4)Cable Wiring**
2031
2032 Figure
2033
2034 [[image:image-20220831165031-3.png]][[image:image-20220831165017-2.png]]
2035
2036 Pin Definition Diagram
2037
2038 [[image:image-20220831165008-1.png]]
2039
2040 = Create communication with LS** PLC** =
2041
2042 == **XBC serial protocol** ==
2043
2044 **1)V-BOX Settings**
2045
2046 |**Item**|**Settings**|**Note**
2047 |Protocol|LS XBC CNet|
2048 |Connection|RS232|
2049 |Baud rate|115200|
2050 |Data bit|8|
2051 |Parity|NONE|
2052 |Stop bit|1|
2053 |PLC station No.|1|
2054
2055 **2)Address List**
2056
2057 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
2058 |Bit|P|P|P d|0~~2047|
2059 |Bit|M|M|M d|0~~2047|
2060 |Bit|L|L|L d|0~~11263|
2061 |Bit|K|K|K d|0~~16183|
2062 |Bit|F|F|F d|0~~2047|
2063 |Bit|D|D|D d|0~~32767|
2064 |Bit|R|R|R d|0~~32767|
2065 |Bit|U|U|U d|0~~4095|
2066 |Word|P|P|P d|0~~2047|
2067 |Word|M|M|M d|0~~2047|
2068 |Word|L|L|L d|0~~11263|
2069 |Word|K|K|K d|0~~16183|
2070 |Word|F|F|F d|0~~2047|
2071 |Word|C|C|C d|0~~2047|
2072 |Word|T|T|T d|0~~2047|
2073 |Word|D|D|D d|0~~32767|
2074 |Word|N|N|N d|0~~21503|
2075 |Word|R|R|R d|0~~32767|
2076 |Word|U|U|U d|0~~4095|
2077 |Word|Z|Z|Z d|0~~127|
2078 |Word|S|S|S d|0~~127|
2079
2080 **3)Configure the communication protocol**
2081
2082 [[image:image-20220831170147-1.png]]
2083
2084 **4)Cable Wiring**
2085
2086 Figure
2087
2088 [[image:image-20220831170306-4.png]][[image:image-20220831170254-3.png]]
2089
2090 Pin Definition Diagram
2091
2092 [[image:image-20220831170215-2.png]]
2093
2094 == **XGK FEnet Ethernet protocol** ==
2095
2096 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
2097
2098 **1)V-BOX Settings**
2099
2100 |**Items**|**Settings**|**Note**
2101 |Protocol|LG XGK FEnet(Ethernet)|
2102 |Connection|Ethernet|
2103 |Port No.|2004|
2104
2105 **2)Address List**
2106
2107 |**Type**|**Register**|**Range**|**Format**|**Note**
2108 |(% rowspan="14" %)Word|P|0~~2047|P d|
2109 |M|0~~2047|M d|
2110 |K|0~~2047|K d|
2111 |F|0~~2047|F d|
2112 |T|0~~2047|T d|
2113 |C|0~~2047|C d|
2114 |Z|0~~127|Z d|
2115 |S|0~~127|S d|
2116 |L|0~~11263|L d|
2117 |N|0~~21503|N d|
2118 |D|0~~32767|D d|
2119 |R|0~~32767|R d|
2120 |ZR|0~~65535|ZR d|
2121 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
2122
2123 **✎Note:**
2124
2125 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
2126 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
2127 * All bit registers are in the form of bits in word, and the range is the same as the word register;
2128
2129 **3)Communication Settings**
2130
2131 [[image:image-20220831171127-1.png]]
2132
2133 **4)Cable Wiring**
2134
2135 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2136
2137 = Create communication with **Modbus ** =
2138
2139 == **MODBUS RTU Slave (All function)** ==
2140
2141 Select the protocol "Modbus RTU Slave (All Fuction)",
2142
2143 Then set baud rate, port, stop bits, data bits, parity.
2144
2145 (% style="text-align:center" %)
2146 [[image:1624342015914-382.png||height="486" width="800" class="img-thumbnail"]]
2147
2148 == **Communicate with Modbus Meter** ==
2149
2150 The following example is using the Linfee meter LNF96EY to demonstrate how to set up the Modbus communication.
2151
2152 ~1. Wiring the RS485 cable first. Because the pin 58 is A, the pin 59 is B for meter. Here we use the COM1 to connect. So the diagram like follows:
2153
2154 (% style="text-align:center" %)
2155 [[image:LinfeeTerminalDiagram.png]]
2156
2157 2. Check the specific Modbus parameter in the communication menu from LED display.
2158
2159 So from the following pictures, we can know the Meter Address is 85, Baud rate is 9600, CRC None.
2160
2161 {{info}}
2162 **✎Note: **Meter address usually corresponding to the Modbus Slave Station No. on the Modbus communication.
2163 {{/info}}
2164
2165 (% style="text-align:center" %)
2166 [[image:MeterModbusAllView.png]]
2167
2168 (% class="wikigeneratedid" %)
2169 3. Set up the communication in the Configuration tab.
2170
2171 (% class="wikigeneratedid" %)
2172 Select the protocol as **ModBus RTU Slave (All Function)**. And set the communication parameters like below.
2173
2174 (% style="text-align:center" %)
2175 [[image:VNETCommunicationtabmeter.png]]
2176
2177 (% class="wikigeneratedid" %)
2178 4. Create new real-time monitoring tag accroding to Modbus manual
2179
2180 (% class="wikigeneratedid" %)
2181 Enter the address we want to read from the meter. The following table is intercept part of the manual for Linfee Modbus manual.
2182
2183 (% class="wikigeneratedid" %)
2184 **0x03/0x04 command data register address**:
2185
2186 (% style="width:1142.22px" %)
2187 |(% style="display:none" %) |=(% colspan="2" rowspan="1" style="width: 165px;" %)Address(% style="display:none" %) |=Description|=Data Format|=(% style="width: 254px;" %)Data Length(Word)|=(% style="width: 282px;" %)Remark
2188 |(%%)(% style="display:none" %) (%%) HEX|(% style="width:107px" %)DEC|(%%)(% style="display:none" %) (%%) |(% style="width:100px" %) |(%%)(% style="display:none" %) (%%) |(% style="width:318px" %)
2189 |(% style="width:107px" %)0x00|(% style="width:100px" %)0|Reserved| | |(% style="width:318px" %)
2190 |(% style="width:107px" %)0x02|(% style="width:100px" %)2|Reserved| | |(% style="width:318px" %)
2191 |(% style="width:107px" %)0x04|(% style="width:100px" %)4|Reserved| | |(% style="width:318px" %)
2192 |(% style="width:107px" %)0x06|(% style="width:100px" %)6|Ua|float|2|(% style="width:318px" %)Phase Voltage data, Unit V
2193 |(% style="width:107px" %)0x08|(% style="width:100px" %)8|Ub|float|2|(% style="width:318px" %)Phase Voltage data, Unit V
2194 |(% style="width:107px" %)0x0A|(% style="width:100px" %)10|Uc|float|2|(% style="width:318px" %)Phase Voltage data, Unit V
2195 |(% style="width:107px" %)0x0C|(% style="width:100px" %)12|Uab|float|2|(% style="width:318px" %)Line Voltage data, Unit V
2196 |(% style="width:107px" %)0x0E|(% style="width:100px" %)14|Ubc|float|2|(% style="width:318px" %)Line Voltage data, Unit V
2197 |(% style="width:107px" %)0x10|(% style="width:100px" %)16|Uca|float|2|(% style="width:318px" %)Line Voltage data, Unit V
2198 |(% style="width:107px" %)0x12|(% style="width:100px" %)18|Ia|float|2|(% style="width:318px" %)Phase Current data, Unit A
2199 |(% style="width:107px" %)0x14|(% style="width:100px" %)20|Ib|float|2|(% style="width:318px" %)Phase Current data, Unit A
2200 |(% style="width:107px" %)0x16|(% style="width:100px" %)22|Ic|float|2|(% style="width:318px" %)Phase Current data, Unit A
2201
2202 {{info}}
2203 **✎Note: **We usually use the Data Type 4 for read the Modbus registers(Function Code 03)
2204 {{/info}}
2205
2206 For example, here we want to read the Phase Voltage Ua (Modbus offset 0006), the Modbus register main No. requires input decimal number, and check whether the actual address has one address offset, so the tag configured like the following screenshot:
2207
2208 (% style="text-align:center" %)
2209 [[image:VNETModbusTagSettings.png]]
2210
2211 (% style="text-align:center" %)
2212 [[image:VNETModbusTagByteSettings.png]]
2213
2214 {{info}}
2215 **✎Note: **If the read value is incorrect, please check whether need to change the Byte order.
2216 {{/info}}
2217
2218 Set the Modbus Slave Station No.
2219
2220 (% style="text-align:center" %)
2221 [[image:ModbusStationSettings.png]]
2222
2223 If the communication is setup successfully, the tag will show green light.
2224
2225 (% style="text-align:center" %)
2226 [[image:Monitoringtaggreenlight.png]]
2227
2228 == **MODBUS RTU Master** ==
2229
2230 Select the protocol "Modbus RTU Master",
2231
2232 Then set baud rate, port, stop bits, data bits, parity
2233
2234 (% style="text-align:center" %)
2235 [[image:1624348709622-711.png||queryString="width=809&height=493" height="488" width="800" class="img-thumbnail"]]
2236
2237 **address list**
2238
2239 (% class="table-bordered" %)
2240 |=(% scope="row" %)**Type**|=**Data Type**|=**Function code and description**
2241 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (Read Input Registers: Read the current binary value in one or more input registers)
2242 |06 (write single register: write a binary value to a holding register)
2243 |10 (write values to multiple addresses )
2244 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
2245 |06 (write single register: write a binary value to a holding register)
2246 |10 (write values to multiple addresses )
2247 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
2248 |06 (write single register: write a binary value to a holding register)
2249 |10 (write values to multiple addresses )
2250 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
2251 |10 (write values to multiple addresses )
2252 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
2253 |05 (Force a single coil to force the on/off state of a logic coil)
2254 |0F (Write multiple bits, ie write continuously)
2255 |(% rowspan="3" %)1|02 (Read the input state)
2256 |05 (Force a single coil to force the on/off state of a logic coil)
2257 |0F (Write multiple bits)
2258 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
2259 |05 (Force a single coil to force the on/off state of a logic coil)
2260 |0F (Write multiple bits)
2261 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
2262 |0F (Write multiple bits)
2263
2264 == **MODBUS TCP Slave (All function)** ==
2265
2266 Supported series: MODBUS TCP controller
2267
2268 V-B0X works as MODBUS TCP MASTER connecting with TCP SLAVE
2269
2270 **1)V-BOX Setting**
2271
2272 |**Items**|**Settings**|**Note**
2273 |Protocol|MODBUS TCP Slave (All function)|
2274 |Connection|Ethernet|
2275 |Port No.|502|
2276 |PLC station No.|1
2277
2278 **2)Address List**
2279
2280 |=**Type**|=**Data Type**|=**Function code & Description**
2281 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
2282 |06 (write single register: write a binary value to a holding register)
2283 |10 (write values to multiple addresses )
2284 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
2285 |06 (write single register: write a binary value to a holding register)
2286 |10 (write values to multiple addresses )
2287 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
2288 |06 (write single register: write a binary value to a holding register)
2289 |10 (write values to multiple addresses )
2290 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
2291 |10 (write values to multiple addresses )
2292 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
2293 |05 (Force a single coil to force the on/off state of a logic coil)
2294 |0F (Write multiple bits, ie write continuously)
2295 |(% rowspan="3" %)1|02 (Read the input state)
2296 |05 (Force a single coil to force the on/off state of a logic coil)
2297 |0F (Write multiple bits)
2298 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
2299 |05 (Force a single coil to force the on/off state of a logic coil)
2300 |0F (Write multiple bits)
2301 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
2302 |0F (Write multiple bits)
2303
2304 **3)Communication Settings**
2305
2306 Configure V-BOX Ethernet IP in Networking Settings
2307
2308 [[image:image-20220902111833-3.png]]
2309
2310
2311 Configure PLC Ethernet IP in Communication;
2312
2313 [[image:image-20220902111121-1.png]]
2314
2315 **4)Cable Wiring**
2316
2317 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2318
2319 == **communicate with VB inverter** ==
2320
2321 [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20VB%20inverter.zip]]
2322
2323 = **User define protocol** =
2324
2325 More serial port script instruction,please refer manual:[[Lua script function>>doc:V-BOX.V-Net.Manual.04 Lua Script.01 Lua Functions.WebHome]]~-~-->[[3.Serial port operation>>url:http://docs.we-con.com.cn/wiki/vbox/view/HMI/04.Lua%20script%20%20function%20and%20operation/01.Lua%20script%20function/#H3.Serialportoperation]]
2326
2327 == **Read the temperature sensor.** ==
2328
2329 the commond format is as beliow:
2330
2331 Send commond:01 03 02 00 00 03 04 73
2332
2333 Feedback commond:01 03 06 07 F7 0E 7E B7 35
2334
2335 Temperature data:07 F7,desimal = 2039,it means temperature is 20.39℃.
2336
2337 Humidity data:0E 7E,desimal = 3710, it mean humidity is 37.10%RH.
2338
2339 Script Demo:
2340
2341 ~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~--
2342
2343 function com.main()
2344 ~-~-dosomething
2345 openPlc()
2346 end
2347 function openPlc()
2348 if obj then
2349 ~-~- If the serial port opened,then read/write data by timing
2350
2351 local wri = string.pack(">HHHH",0X0103,0X0200,0X0003,0X0473)
2352 local arr = reading(wri)
2353 ~-~- if arr ~~=nil then
2354 ~-~- if arr[1] ==33 and arr[2] ==v[2][2] and arr[3] ==v[2][3] then
2355 ~-~- local A = arr[4]*256
2356 ~-~- local B = A+arr[5]
2357 ~-~- addr_setword(v[1],B)
2358 ~-~- end
2359 ~-~- end
2360
2361 else
2362 ~-~-judge if there is a serial object, then initialize and open the serial port
2363 local configs = {
2364 name = 'COM1', ~-~-Select serial port COM1
2365 mode = 485, ~-~-Communication mode RS485
2366 baud_rate = 9600, ~-~-Baud rate 9600
2367 stop_bit = 1, ~-~-stop bit 1
2368 data_len = 8, ~-~-data length 8
2369 check_bit = 'NONE', ~-~-no parity
2370
2371 }
2372 obj,err = serial.open(configs) ~-~-Open serial port
2373 if not obj then
2374 print("serial open :failed", err) ~-~- Open serial port failed
2375 end
2376 end
2377 end
2378
2379 function reading(wri)
2380 obj:flush() ~-~- Clear serial port
2381 obj:write(wri) ~-~- Write serial port
2382 print(string.byte(wri,1,#wri))
2383 obj:flush() ~-~- Clear serial port 
2384 local readed =obj:read(9,1000) ~-~- Read 9 bytes, timeout 1 second
2385 if readed and readed ~~= "" then 
2386 ~-~- judge that a non-empty string is read
2387 print(string.byte(readed,1,#readed))
2388 a={string.byte(readed, 1, #readed)}
2389 if nil ~~= a[4] and nil ~~= a[5] and nil ~~= a[6] and nil ~~= a[7] then
2390 a1=a[4]*256+a[5]
2391 a2=a[6]*256+a[7]
2392 addr_setword("@HDW0",a1)
2393 addr_setword("@HDW1",a2)
2394 end
2395 return {string.byte(readed, 1, #readed)}
2396 elseif readed == nil then
2397 print("serial read err:", err or "")
2398 return nil
2399 end
2400 return nil
2401 end
2402
2403 ~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-