Wiki source code of 1 Communication

Version 240.1 by Hunter on 2023/05/19 18:13

Show last authors
1 = Create communication with WECON PLC =
2
3 == **LX3V Serial Protocol** ==
4
5 Supported series: Wecon LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
6
7 **1)V-BOX setting**
8
9 |**Item**|**Settings**|**Note**
10 |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
11 |Connection|RS422/RS485|
12 |Baud rate|9600|
13 |Data bit|7|
14 |Parity|EVEN|
15 |Stop bit|1|
16 |PLC station No.|1|
17
18 **2)Address List**
19
20
21 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
22 |(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
23 |Y|Y|Y o|0~~303237|
24 |M|M|M d|0~~99999|
25 |T|T|T d|0~~99999|
26 |C|C|C d|0~~99999|
27 |S|S|S d|0~~99999|
28 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
29 |Y|Y|Y o|0~~303237|
30 |M|M|M d|0~~99999|
31 |T|T|T d|0~~99999|
32 |C|C|C d|0~~199|
33 |D|D|D d|0~~7999|
34 |S|S|S d|0~~99999|
35 |SD|SD|SD d|8000~~9999|
36
37 **3)Configure the communication protocol**
38
39 [[image:image-20220824152217-1.png||alt="图片-20220824152217-1.png"]]
40
41 **4)Cable Wiring**
42
43 * **RS422**
44
45 [[image:image-20220824120614-5.png]]
46
47 * **RS485**
48
49 [[image:image-20220824120524-3.png]]
50
51 == **LX5V Serial Protocol** ==
52
53 This example introduces the establishment of serial port communication between V-BOX and LX5V. It is introduced through three parts: PLC software configuration, V-BOX software configuration, and hardware wiring.
54
55 **Software configuration of PLC**
56
57 **1)PLC programming software**
58
59 [[image:image-20220824142722-1.png]]
60
61 **2)New PLC project**
62
63 Click New Project and select the PLC model.
64
65 [[image:image-20220822172623-2.png]]
66
67 **3)Set Serial port parameters**
68
69 Follow the steps below to configure Serial port parameters
70
71 Baud rate:115200
72
73 Data bit:8
74
75 Stop bit:1
76
77 Parity:No verification
78
79 [[image:image-20220822172657-3.png]]
80
81 **4)Registers list**
82
83 [[image:image-20220822172730-4.png]]
84
85 **V-BOX software configuration**
86
87 **1)V-BOX programming software**
88
89 [[image:image-20220824104124-1.png]]
90
91 **2)V-NET add device**
92
93 Open V-NET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the access key, password and remark, to add the device.
94
95 [[image:image-20220824104909-2.png]]
96
97 **3)Set communication port parameters**
98
99 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
100
101 Baud rate:115200
102
103 Data bit:8
104
105 Stop bit:1
106
107 Parity:No verification
108
109 [[image:image-20220824142130-1.png]]
110
111 **hardware connection**
112
113 **1)Hardware wiring diagram**
114
115 [[image:image-20220824142546-2.png]]
116
117 [[image:image-20220824142643-3.png]]
118
119 The above are all the steps for establishing serial port communication between V-BOX with LX5V PLC.
120
121 == **LX5V-N Ethernet protocol** ==
122
123 This example introduces the establishment of Ethernet communication between V-BOX and LX5V-N. It is introduced through three parts: PLC software configuration, V-BOX software configuration, and hardware wiring.
124
125 **Software configuration of PLC**
126
127 **1)PLC programming software**
128
129 [[image:image-20220824142722-1.png]]
130
131 **2)New PLC project**
132
133 Click New Project and select the PLC model.
134
135 [[image:image-20220824143613-1.png]]
136
137 **3)Set Ethernet port parameters**
138
139 Follow the steps below to configure Ethernet parameters
140
141 PLC IP address:192.168.39.200
142
143 default gateway:192.168.39.1
144
145 subnet mask:255.255.255.0
146
147 [[image:image-20220824143744-2.png]]
148
149 **4)Registers list**
150
151 [[image:image-20220822172730-4.png]]
152
153 (% id="cke_bm_22473S" style="display:none" %)** **(%%)**V-BOX software configuration**
154
155 **1)V-BOX programming software**
156
157 [[image:image-20220824104124-1.png]]
158
159 **2)V-NET add device**
160
161 Open V-NET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the access key, password and remark, to add the device.
162
163 [[image:image-20220824104909-2.png]]
164
165 **3)Set communication Protocol**
166
167 Click Communication to configure the LX5V plc protocol and IP address.
168
169 [[image:image-20220824144619-1.png]]
170
171 **hardware connection**
172
173 **1)Hardware wiring diagram**
174
175 [[image:image-20220824151127-2.png]]
176
177 The above are all the steps for establishing ethernet communication between V-BOX with LX5V PLC.
178
179 = Create communication with Allen-Bradley(**Rockwell**)** PLC** =
180
181 == **DF1 Advanced Protocol** ==
182
183 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
184
185 **1) V-Box Settings**
186
187 |=Item|=Recommended |=Note
188 |=Protocol|Allen Bradley DF1 Advanced|
189 |=Connection|RS232|
190 |=Baud rate|19200|
191 |=Stop bits|1|
192 |=Data bits|8|
193 |=Parity|None|
194 |=PLC Station No.|1|
195 |=HMI Station No.|0|
196
197 **2) Address List**
198
199 |=**Type**|=**Device registers**|=**Format**|=**Range**|=Note
200 |(% colspan="1" rowspan="7" %)Bit|I1|I1ddd.dd|0.0~~255.15|Only able to communicate with file number I1
201 |O0|O0ddd.dd|0.0~~255.15|Only able to communicate with file number O0
202 |S2|S2ddd.dd|0.0~~255.15|Only able to communicate with file number S2
203 |B3|B3ddd.dd|0.0~~255.15|Only able to communicate with file number B3
204 |BN|BNddddd.dd|0.0~~99255.15|(((
205 Bit data file B0~~B99
206
207 First two digits is for file number
208
209 For example, BN13001.00 represents file number B13, address 001, the 0th bit.
210 )))
211 |N7|N7ddd.dd|0.0~~255.15|Only able to communicate with file number N7
212 |NN|NNddddd.dd|0.0~~99255.15|(((
213 Integer data file bit format N0~~N99
214
215 First two digits is for file number
216
217 For example, NN13001.00 represents file number N13, address 001, the 0th bit.
218 )))
219 |(% rowspan="11" %)Word|S2|S2ddd|0~~255|Only able to communicate with file number S2
220 |T4S|T4Sddd|0~~255|Only able to communicate with file number T4 (Timer Preset Value)
221 |T4P|T4Pddd|0~~255|Only able to communicate with file number T4 (Timer Accumulator Value)
222 |TNS|TNSddddd|0~~99255|(((
223 Timer Preset Value
224
225 First two digits is for file number
226
227 For example, TNS99255 represents file number T99, address 255.
228 )))
229 |TNP|TNPddddd|0~~99255|(((
230 Timer Accumulator Value
231
232 First two digits is for file number
233
234 For example, TNP99255 represents file number T99, address 255.
235 )))
236 |C5S|C5Sddd|0~~255|Only able to communicate with file number C5 (Counter Preset Value)
237 |C5P|C5Pddd|0~~255|Only able to communicate with file number C5 (Counter Accumulator Value)
238 |CNS|CNSddddd|0~~99255|(((
239 Counter Preset Value
240
241 First two digits is for file number
242
243 For example, CNS99255 represents file number C99, address 255.
244 )))
245 |CNP|CNPddddd|0~~99255|(((
246 Counter Accumulator Value
247
248 First two digits is for file number
249
250 For example, CNP99255 represents file number C99, address 255.
251 )))
252 |N7|N7ddd|0~~255|Only able to communicate with file number N7
253 |NN|NNddd|0~~99255|(((
254 Integer data file
255
256 First two digits is for file number
257
258 For example, NN99255 represents file number N99, address 255.
259 )))
260 |(% colspan="1" rowspan="3" %)Double Word|F8|F8ddd|0~~255|(((
261 Only able to communicate with file number N7
262 )))
263 |FN|FNddddd|0~~99255|(((
264 Floating point data file
265
266 First two digits is for file number
267
268 For example, FN99255 represents file number F99, address 255.
269 )))
270 |LN|LNddddd|0~~99255|Long
271
272 **3) Cable Wiring**
273
274 (% style="text-align:center" %)
275 [[image:ABRS232.gif]]
276
277 (% class="wikigeneratedid" id="HMicroLogixA0Protocol" %)
278 (% id="cke_bm_5621S" style="display:none" %)** **
279
280 == **MicroLogix Protocol** ==
281
282 (% class="wikigeneratedid" %)
283 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
284
285 **1)V-BOX setting**
286
287 |**Item**|**Settings**|**Note**
288 |Protocol|Allen-Bradley DF1 Advanced|
289 |Connection|RS232|
290 |Baud rate|19200|
291 |Data bit|8|
292 |Parity|None|
293 |Stop bit|1|
294 |PLC station No.|1|
295
296 **2)Address List**
297
298 |**Type**|**Device registers**|**Format**|**Range**|**Note**
299 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
300 |O|O d.d|0.0~~255.15|
301 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
302 |S|S d.d|0.0~~255.15|
303 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
304 |(% rowspan="9" %)Word|S|S d|0~~255|
305 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
306 |TP|TP nnhh|0~~ffff
307 |CS|CS nnhh|0~~ffff
308 |CP|CP nnhh|0~~ffff
309 |N|N nnhh|0~~ffff
310 |C|C nnhh|0~~ffff
311 |T|T nnhh|0~~ffff
312 |R|R nnhh|0~~ffff
313
314 **3)Configure the communication protocol**[[image:image-20220824152928-1.png]]
315
316 **4)Configure the communication protocol**
317
318 [[image:image-20220824110724-1.png]]
319
320 == **Micro850_FreeTag Protocol** ==
321
322 (((
323 (((
324 This example introduces the establishment of Ethernet communication between Wecon V-box and CompactLogix L1769. It is introduced through three parts: PLC software configuration, V-box software configuration, and hardware wiring.
325 )))
326 )))
327
328 (((
329 (% class="wikigeneratedid" id="HSoftwareconfigurationofPLC" %)
330 (((
331 **Software configuration of PLC**
332 )))
333
334 (% class="wikigeneratedid" id="HPLCprogrammingsoftware" %)
335 (((
336 **1)PLC programming software**
337 )))
338
339 [[image:image-20220714162600-1.png]]
340
341 (% class="wikigeneratedid" id="HNewPLCproject" %)
342 (((
343 **2)New PLC project**
344 )))
345
346 (((
347 (((
348 Click New Project and select the PLC model.
349 )))
350 )))
351
352 (((
353 [[image:image-20220714162617-2.png]]
354 )))
355
356 (((
357
358
359 [[image:image-20220714162652-4.png]]
360 )))
361
362 (((
363 (% class="wikigeneratedid" id="HSetEthernetparameters" %)
364 (((
365 **3)Set Ethernet parameters**
366 )))
367
368 (((
369 (((
370 (((
371 Follow the steps below to configure Ethernet parameters
372 )))
373 )))
374 )))
375
376 (((
377 (((
378 (((
379 PLC IP address:192.168.40.101
380 )))
381 )))
382 )))
383
384 (((
385 (((
386 (((
387 default gateway:192.168.40.1
388 )))
389 )))
390 )))
391
392 (((
393 (((
394 (((
395 subnet mask:255.255.255.0
396 )))
397 )))
398 )))
399
400 (((
401 [[image:image-20220714162713-5.png]]
402 )))
403
404 (((
405
406 )))
407
408 (((
409 (% class="wikigeneratedid" id="HV-boxsoftwareconfiguration" %)
410 (((
411 **V-box software configuration**
412 )))
413
414 (% class="wikigeneratedid" id="HV-boxprogrammingsoftware" %)
415 (((
416 **1)V-box programming software**
417 )))
418
419 (% class="wikigeneratedid" %)
420 (((
421 [[image:image-20220714162725-6.png]]
422 )))
423
424 (% class="wikigeneratedid" id="HConfiguredevicenetwork" %)
425 (((
426 **2)Configure device network**
427 )))
428
429 (((
430 (((
431 (((
432 Click the Configuration Download button[[image:image-20220714115308-8.png||height="22" width="15"]], It is used to configure the device network, update the device time, obtain the device machine code, check the device network, etc.
433 )))
434
435 (((
436 In the example below, the IP address of V-Box is configured as 192.168.40.66, and the networking method is 4G connection
437 )))
438 )))
439 )))
440
441 (((
442 (((
443 [[image:image-20220714162737-7.png]]
444
445
446 )))
447 )))
448 )))
449 )))
450
451 (% class="wikigeneratedid" id="HV-netadddevice" %)
452 (((
453 **3)V-net add device**
454 )))
455 )))
456
457 (((
458 (((
459 Open VNET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the device machine code/product code, device password, and device alias to add the device.   [[image:image-20220714162752-8.png]]
460 )))
461
462
463 )))
464
465 (((
466 (% class="wikigeneratedid" id="HSetcommunicationportparameters" %)
467 (((
468 **4)Set communication port parameters**
469 )))
470
471 (((
472 In the device list on the left, find the Vbox that communicates with the L1769, click it and select configuration,communication port configuration in the main interface to add a communication protocol.
473 )))
474
475 [[image:image-20220714162805-9.png]]
476 )))
477
478 (((
479 The communication port is selected as Ethernet, the device type is selected as Allen-Bradley, the protocol is Allen-BradleyMicro850_FreeTag EthemetIP, and the IP is the internal IP address of the L1769 PLC. The port number is 44818.
480 )))
481
482 [[image:image-20220824164346-1.png]]
483
484
485 (((
486 After adding the protocol Allen-BradleyMicro850_FreeTag, click[[image:image-20220714143838-2.png]]icon add label.[[image:image-20220714162827-11.png]]
487 )))
488
489 (% class="wikigeneratedid" id="HEngineeringproduction" %)
490 (((
491 **5)Engineering production**
492 )))
493
494 (% class="wikigeneratedid" %)
495 (((
496 (((
497 According to your own needs, use the V-NET client software to edit the required data monitoring points.
498 )))
499
500 [[image:image-20220714162841-12.png]]
501
502
503 (((
504 **hardware connection**
505 )))
506 )))
507
508 (((
509 **1)Hardware wiring diagram**
510 )))
511
512 (((
513 (((
514 This example introduces Wecon V-box with Allen-Bradley L1769 PLC to establish communication through Ethernet. The connection diagram is as follows:
515 )))
516
517 [[image:image-20220714162856-13.png]]
518
519 (((
520 The above are all the steps for establishing Ethernet communication between Wecon V-box with CompactLogix L1769 PLC.
521
522
523 == **Micro850_FreeTag Protocol(new)** ==
524
525 This example introduces the establishment of Ethernet communication between Wecon V-box and 2080-LC50-48QWB,Micro850. It is introduced through three parts: PLC software configuration, V-box software configuration.
526
527 (% class="wikigeneratedid" id="HSoftwareconfigurationofPLC" %)
528 (((
529 **Software configuration of PLC**
530 )))
531
532 (% class="wikigeneratedid" id="HPLCprogrammingsoftware" %)
533 (((
534 **1)PLC programming software:Connected Components Workbench™**
535
536 (% style="text-align:center" %)
537 [[image:software.png]]
538
539 **2)New PLC project**
540
541 Click New Project and select the PLC model.
542
543 (% style="text-align:center" %)
544 [[image:project create.png]]
545
546 **3)Set Ethernet parameters**
547
548 Follow the steps below to configure Ethernet parameters
549
550 PLC IP address:192.168.39.56
551
552 default gateway:192.168.39.1
553
554 subnet mask:255.255.255.0
555
556 (% style="text-align:center" %)
557 [[image:Ethernet.png]]
558
559 **4)connect PLC**
560
561 **When downloading the setting, need to change the status of the PLC to PRG**
562
563 (% style="text-align:center" %)
564 [[image:conne ab plc.png]]
565
566 **V-box software configuration**
567
568 **1)V-box programming software**
569
570 (% style="text-align:center" %)
571 [[image:v-net client vers.png]]
572
573 **2)Set communication port parameters**
574
575 In the device list on the left, find the Vbox that communicates with the L1769, click it and select configuration,communication port configuration in the main interface to add a communication protocol.
576
577 (% style="text-align:center" %)
578 [[image:V-NET_Client_t2Rg2wpSoY.png]]
579
580 The communication port is selected as Ethernet, the device type is selected as Allen-Bradley, the protocol is Allen-BradleyMicro850_FreeTag EthemetIP, and the IP is the internal IP address of the L1769 PLC. The port number is 44818.
581
582 (% style="text-align:center" %)
583 [[image:V-NET_Client_communication.png]]
584
585 Export variables from PLC, select CSV file, comma delimited.(% id="cke_bm_1950S" style="display:none" %)
586
587 (% style="text-align:center" %)
588 [[image:export1.png]]
589
590 (% style="text-align:center" %)
591 [[image:CCW.Shell_E5Cwj4tUL3.png]]
592
593 After adding the protocol Allen-BradleyMicro850_FreeTag, click[[image:https://docs.we-con.com.cn/bin/download/V-BOX/V-Net/Training/1%20Communication/WebHome/image-20220714143838-2.png?rev=1.1||alt="image-20220714143838-2.png"]]icon add label.
594
595 (% style="text-align:center" %)
596 [[image:V-NET_Client_TNBuqy7T5r.png]]
597
598 **3)Engineering production**
599
600 According to your own needs, use the V-NET client software to edit the required data monitoring points.
601
602 (% style="text-align:center" %)
603 [[image:V-NET_Client_KOR0AHEA4M.png]]
604
605
606 )))
607
608 == **Ethernet DF1 Protocol** ==
609
610 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Allen-Bradley%20Ethernet%20DF1.zip]]
611
612 = Create communication with **Crouzet PLC** =
613
614 == **CROUZET M3 (FBD)** ==
615
616 Support Series: Crouzet Millenium 3 CD12/CB12
617
618 **1)V-BOX setting**
619
620 |=Item|=Recommended |=Note
621 |=Protocol|CROUZET M3 (FBD)|
622 |=Connection|RS232|
623 |=Baud rate|115200|
624 |=Stop bits|1|
625 |=Data bits|7|
626 |=Parity|EVEN|
627
628 **2)Address List**
629
630 |=**Type**|=**Device registers**|=**Format**|=**Range**|=Note
631 |(% rowspan="4" %)Bit|I|I DD|1~~99|Input
632 |SLIBit|SLIBit DD.dd|1.0~~24.15|Serial Link Input
633 |SLOBit|SLOBit DD.dd|25.0~~48.15|Serial Link Output(Read only)
634 |State|State D|1~~1|PLC state(Read only)
635 |(% rowspan="5" %)Word|AI|AI DD|1~~99|Analog Input
636 |SLIn|SLIn DD|1~~24|Serial Link Input
637 |SLOut|SLOut DD|25~~48|Serial Link Output(Read only)
638 |Time|Time D|1~~6|(((
639 Time1: Second
640
641 Time2: Minute
642
643 Time3: Hour
644
645 Time4: Day
646
647 Time5: Month
648
649 Time6: Year
650 )))
651 |Order|Order D|1~~1|(((
652 Running command(Write only)
653
654 ~=2: Run mode; =1: Stop mode;
655 )))
656
657 **3)Cable Wiring**
658
659 (% style="text-align:center" %)
660 [[image:CrouzetRS232 VBox.png]]
661
662 {{info}}
663 **✎Note: **As the wiring diagram indicated, this protocol requires the DB9 serial port pin 4. But pin 4 is undefined for all V-Box, so it need the user to solder a Pull-up resistor to make the pin 4 working. As for how to solder the resistor on the motherboard, please contact with Wecon technical support for the details.
664 {{/info}}
665
666 = Create communication with EMERSON PLC =
667
668 == **RTU Slave Protocol** ==
669
670 Supported series: EC10 series
671
672 **1)V-BOX setting**
673
674 |**Items**|**Settings**|**Note**
675 |Protocol|Emerson 984 RTU Slave MODBUS|
676 |Connection|RS485|
677 |Baud rate|19200|
678 |Data bit|8|
679 |Parity|EVEN|
680 |Stop bit|1|
681 |Device station No.|1|Need to be same as the PLC setting
682
683 (% class="wikigeneratedid" %)
684 **2)PLC Setting**
685
686 (% class="wikigeneratedid" %)
687 Remember to use the Control Star to enable the Modbus RTU communication for port 1 in system block before dowload into PLC.
688
689 (% style="text-align:center" %)
690 [[image:ControlStarSystemBlock.png]]
691
692 (% style="text-align:center" %)
693 [[image:ControlStarCommunicate.png]]
694
695 (% style="text-align:center" %)
696 [[image:ControlStarModbus.png]]
697
698 (% class="wikigeneratedid" %)
699 **3)Address List**
700
701 |**Type**|**Device registers**|**Format**|**Range**|**Note**
702 |(% colspan="1" rowspan="12" %)Bit|Y|YOOO|0~~377|
703 |X|XOOO|0~~377|
704 |M0|M0DDDD|0~~2047|
705 |M1|M1DDDDD|2048~~10239|
706 |SM0|SM0DDD|0~~255|
707 |SM1|SM1DDD|256~~511|
708 |S0|S0DDDD|0~~1023|
709 |S1|S1DDDD|1024~~4095|
710 |T0|T0DDD|0~~255|
711 |T1|T1DDD|256~~511|
712 |C0|C0DDD|0~~255|
713 |C1|C1DDD|256~~306|
714 |(% colspan="1" rowspan="7" %)Word|D|DDDDD|0~~7999|
715 |Z|ZDD|0~~15|
716 |TW0|TW0DDD|0~~255|
717 |TW1|TW1DDD|256~~511|
718 |SD0|SD0DDD|0~~255|
719 |SD1|SD1DDD|256~~511|
720 |CW|CWDDD|0~~306|
721 |(% colspan="1" rowspan="2" %)Double Word|CW0|CW0DDD|200~~255|
722 |CW1|CW1DDDDD|256~~99999|
723
724 **4) Cable Wiring**
725
726 (% style="text-align:center" %)
727 [[image:Emerson.png]]
728
729 = Create communication with HollySys PLC =
730
731 == **LK Modbus RTU** ==
732
733 **1)V-BOX setting**
734
735 |**Items**|**Settings**|**Note**
736 |Protocol|HollySys LK Modbus RTU|
737 |Connection|RS485|
738 |Baud rate|38400|
739 |Data bit|8|
740 |Parity|None|
741 |Stop bit|1|
742 |Device station No.|1|
743
744 **2)Address List**
745
746 |=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note**
747 |Bit|QX|QXDDDDD.dd|0~~65535.15|
748 |Bit|IX|IXDDDDD.dd|0~~65535.15|
749 |Bit|MX|MXDDDDD.dd|0~~65535.15|
750 |Word|QW|QWDDDDD|0~~99999|
751 |Word|IW|IWDDDDD|0~~99999|
752 |Word|MW|MWDDDDD|0~~99999|
753 |Word|MD|MDDDDDD|0~~99999|
754
755 **3)Cable Wiring**
756
757 (% style="text-align:center" %)
758 [[image:Hollysys485-2.png]]
759
760 = Create communication with **Siemens PLC** =
761
762 == **S7-200 Smart Ethernet Protocol** ==
763
764 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20S7-200%20Smart.zip]]
765
766
767 == **S7-300 Ethernet Protocol** ==
768
769 Supported Series: Siemens S7-300 series PLC
770
771 **1)V-BOX setting**
772
773 |**Items**|**Settings**|**Note**
774 |Protocol|Simens S7-300 Ethernet|
775 |Connection|Ethernet|
776 |Port No.|102|
777 |PLC station No.|2|Need to be same as the PLC setting
778
779 **2)Address List**
780
781 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
782 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
783 |Q|Q|Q ddddd.o|0.0~~99999.7|
784 |M|M|M ddddd.o|0.0~~99999.7|
785 |DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
786 nn: block number;
787
788 dddd: address;
789 )))
790 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
791 |Q|QW|QW ddddd|0~~99999|
792 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
793 |MW|MW ddddd|0~~99999|(((
794 MW0=MB(0~~1)
795
796 MW2=MB(2~~3)
797
798 Address value is a multiple of 2
799 )))
800 |MD|MD ddddd|0~~99999|(((
801 MD0=MB(0~~3)
802
803 MD4=MB(4~~7)
804
805 Address value is a multiple of 4
806 )))
807 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
808 nn: block number;
809
810 dddd: address
811 )))
812 |DBxDBW|DBxDBW nndddd|0~~99999999
813 |DBxDBD|DBxDBD nndddd|0~~99999999
814
815 **3)Configure the communication protocol**
816
817 [[image:image-20220824161345-1.png]]
818
819 **4)Cable Wiring**
820
821 [[image:image-20220824161450-2.png]]
822 )))
823 )))
824
825 == **S7-1200 Ethernet Protocol** ==
826
827 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]]
828
829 == **S7-XXX Ethernet Protocol** ==
830
831 Supported Series: Siemens S7-400, S7-1200 and S7-1500
832
833 **1)V-BOX setting**
834
835 |=**Items**|=**Settings**|=**Note**
836 |Protocol|Siemens S7-XXX|
837 |Connection|Ethernet|
838 |Port No.|102|
839 |Device No.|Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|
840 |HMI No.|Rack (Default as 0)|
841
842 Slot from TIA Portal is equal to Device No. of V-net
843
844 Rack from TIA Portal is equal to HMI No. of V-net
845
846 [[image:image-20220824162459-3.png]]
847
848 [[image:image-20220824163305-2.png]]
849
850 **2)Address List**
851
852 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
853 |(% rowspan="4" %)Bit|I|I|M d.o|(((
854 d:0~-~-9999
855
856 o:0-7
857 )))|
858 |Q|Q|Q d.o|(((
859 d:0~-~-9999
860
861 o:0-7
862 )))|
863 |M|M|M d.o|(((
864 d:0~-~-9999
865
866 o:0-7
867 )))|
868 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
869 nn:0-9999,
870
871 dddd:0-9999,
872
873 o:0-7
874 )))|(((
875 nn:DB No.
876
877 dddd:address value
878
879 o: digit address
880 )))
881 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
882 |M|MW|MW d|d:0-99999|(((
883 MW0=MB(0~~1)
884
885 MW2=MB(2~~3)
886
887 Address value is a multiple of 2
888 )))
889 |M|MD|MD d|d:0-99999|(((
890 MD0=MB(0~~3)
891
892 MD4=MB(4~~7)
893
894 Address value is a multiple of 4
895 )))
896 |I|IW|IW d|d:0-99999|
897 |Q|QW|QW d|d:0-99999|
898 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
899 nn:0-9999
900
901 dddd:0-9999
902 )))|(((
903 nn:DB No.
904
905 dddd:address value
906 )))
907 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
908 nn:0-9999
909
910 dddd:0-9999
911 )))|(((
912 nn:DB No.
913
914 dddd:address value
915
916 Address value is a multiple of 2
917 )))
918 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
919 nn:0-9999
920
921 dddd:0-9999
922 )))|(((
923 nn:DB No.
924
925 dddd:address value
926
927 Address value is a multiple of 4
928 )))
929
930 **3)Configure the communication protocol**
931
932 [[image:image-20220824163448-3.png]]
933
934 **✎Note:**
935
936 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three V-BOX.
937 * V-BOX access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
938
939 **4)Cable Wiring**
940
941 [[image:image-20220824162342-2.png]]
942
943 == **LOGO Ethernet Protocol** ==
944
945 Supported Series: Siemens Logo 0BA0, 0BA1 series
946
947 **V-BOX Settings**
948
949
950 |**Items**|**Settings**|**Note**
951 |Protocol|Siemens LOGO|
952 |Connection|Ethernet|
953 |Port No.|102|
954 |PLC station No.|2|
955
956 **Address List**
957
958
959 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
960 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
961 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
962 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
963 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
964 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
965 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
966 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
967 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
968 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
969 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
970 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
971 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
972 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
973 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
974 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
975
976 **PLC Settings in LOGO Software:**
977
978 Click [Tools]~-~-[Ethernet Connections],shown as below.
979
980 (% style="text-align:center" %)
981 [[image:PIStudio.12\.PLC protocols.WebHome@12.PLC Protocol_html_8b9d2322edf89519.png]]
982
983 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
984
985 (% style="text-align:center" %)
986 [[image:PIStudio.12\.PLC protocols.WebHome@image-20221228142937-4.png]]
987
988 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
989
990 (% style="text-align:center" %)
991 [[image:PIStudio.12\.PLC protocols.WebHome@image-20221228143047-5.png]]
992
993 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
994
995 (% style="text-align:center" %)
996 [[image:PIStudio.12\.PLC protocols.WebHome@image-20221228143246-6.png]]
997
998 **V-BOX Communication Settings**
999
1000 Set PLC IP in [IP Address] settings;
1001
1002 (% style="text-align:center" %)
1003 [[image:LldwDGntf4.png]]
1004
1005 Enable V-BOX Ethernet in [Network];
1006
1007 (% style="text-align:center" %)
1008 [[image:WgvjfWbQif.png]]
1009
1010 TSAP setting
1011
1012 * The initialization script needs to set the source TSAP address and the target TSAP address, otherwise the communication will not be successful.
1013
1014 {{code language="LUA"}}
1015 function init.main()
1016 addr_setword("@W_0#HSW1200",8192) -- Set the source TSAP address
1017 addr_setword("@W_0#HSW1201",4096) -- Set the destination TSAP address
1018 end
1019 {{/code}}
1020
1021 Note: The name of the test script is init, 8192 and 4096 are the data used for the test, there is no HSW address in the register option, but you can directly set the value of the corresponding address through the code.
1022
1023 **✎Note:**
1024
1025 * **Communication port configuration: **
1026 ** Continuous length needs to be set to 0.
1027 ** Integration interval needs to be set to 1. (no change may result in data errors)
1028 ** Set Port and Device Station NO.
1029 ** Other set as defaulted.
1030 * **Notes on the use of registers:**
1031 ** Register VD: Use only registers that are multiples of 4, such as 0, 4, 8, etc.
1032 ** Register VW: Use only registers thay are multiples of 2, such as 0, 2, 4 etc. (Using an odd-length register may result in data errors, such as 2 3 4 )
1033
1034 = Create communication with **Mitsubishi PLC** =
1035
1036 == **FX1S,1N,2N Serial Protocol** ==
1037
1038 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
1039
1040 **1)V-BOX Settings**
1041
1042 |**Item**|**Settings**|**Note**
1043 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
1044 |Connection|RS422/RS485/RS232|
1045 |Baud rate|9600~~115200|
1046 |Data bit|7/8|
1047 |Parity|EVEN/Odd/None|
1048 |Stop bit|1/2|
1049 |PLC station No.|1~~255|
1050
1051 **2)Address List**
1052
1053 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1054 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1055 |Y|Y|Y o|0~~303237|
1056 |M|M|M d|0~~99999|
1057 |T|T|T d|0~~99999|
1058 |C|C|C d|0~~99999|
1059 |S|S|S d|0~~99999|
1060 |SM|SM|SM d|8000~~9999|
1061 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1062 |Y|Y|Y o|0~~303237|
1063 |M|M|M d|0~~99999|
1064 |T|T|T d|0~~99999|
1065 |C|C|C d|0~~199|
1066 |D|D|D d|0~~7999|
1067 |S|S|S d|0~~99999|
1068 |SD|SD|SD d|8000~~9999|
1069
1070 **3)Configure the communication protocol**
1071
1072 [[image:image-20220825102844-3.png]]
1073
1074 **4)Cable Wiring**
1075
1076 * **RS422**
1077
1078 [[image:image-20220825103350-4.png]]
1079
1080 [[image:image-20220825100845-4.png]]
1081
1082
1083 == **FX3U,3G,3GA Serial Protocol** ==
1084
1085 Supported Series: Mitsubishi FX3U, FX3G, FX3GA series
1086
1087 **1)V-BOX Settings**
1088
1089 |**Item**|**Settings**|**Note**
1090 |Protocol|Mitsubishi FX3U/3G/3GA|
1091 |Connection|RS422/RS485/RS232|
1092 |Baud rate|9600~~115200|
1093 |Data bit|7/8|
1094 |Parity|EVEN/Odd/None|
1095 |Stop bit|1/2|
1096 |PLC station No.|1~~255|
1097
1098 **2)Address List**
1099
1100 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1101 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1102 |Y|Y|Y o|0~~303237|
1103 |M|M|M d|0~~99999|
1104 |T|T|T d|0~~99999|
1105 |C|C|C d|0~~99999|
1106 |S|S|S d|0~~99999|
1107 |SM|SM|SM d|8000~~9999|
1108 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1109 |Y|Y|Y o|0~~303237|
1110 |M|M|M d|0~~99999|
1111 |T|T|T d|0~~99999|
1112 |C|C|C d|0~~199|
1113 |D|D|D d|0~~7999|
1114 |S|S|S d|0~~99999|
1115 |SD|SD|SD d|8000~~9999|
1116
1117 **3)Configure the communication protocol**
1118
1119 [[image:image-20220825102649-2.png]]
1120
1121 **4)Cable Wiring**
1122
1123 * **RS422**
1124
1125 [[image:image-20220825103421-5.png]]
1126
1127 [[image:image-20220825100845-4.png]]
1128
1129
1130 == **FX3U Ethernet Protocol** ==
1131
1132 Supported Modules: FX3U-ENET-ADP, FX3U-ENET-L
1133
1134 **1)V-BOX Settings**
1135
1136 |Items|Settings|Note
1137 |Protocol|Mitsubishi FX3U|
1138 |Connection|Ethernet|
1139 |Port No.|5009|Must be the same as the PLC setting
1140 |PLC station No.|0|
1141
1142 **2)Address List**
1143
1144 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1145 |(% colspan="1" rowspan="7" %)Bit|X|X|X OOO|0~~377|
1146 |Y|Y|Y OOO|0~~377|
1147 |M|M|M DDDD|0~~7679|
1148 |SM|SM|SM DDDD|8000~~8511|
1149 |S|S|S DDDD|0~~4095|
1150 |TS|TS|TS DDD|0~~511|
1151 |CS|CS|CS DDD|0~~255|
1152 |(% colspan="1" rowspan="9" %)Word|CN|CN|CN DDD|0~~199|
1153 |TN|TN|TN DDD|0~~511|
1154 |D|D|D DDDD|0~~7999|
1155 |SD|SD|SD DDDD|8000~~8511|
1156 |R|R|R DDDDD|0~~32767|
1157
1158 **3)Ethernet Module Settings**
1159
1160 FX3U-ENET-L module configuration
1161 Set up the FX3U-ENET-L Ethernet module settings as follows.
1162 Select the module location, which in this document is Module 0.
1163
1164 [[image:image-20221116105850-1.png]]
1165
1166 Select "Operational setting" to enter the following screen.
1167
1168 The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default.
1169
1170 [[image:image-20221116105947-1.png]]
1171
1172 Select "Open setting" to enter the setting interface, the settings are as follows.
1173
1174 The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the
1175
1176 Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module.
1177
1178 [[image:image-20221116110802-1.png]]
1179
1180 Click on "transter setup" - "PC side I/F setting", see the following figure.
1181
1182 After setting, the first download must use the programming cable, as shown in the figure; after that, can
1183
1184 use the IP set in the "Ethernet board" to communicate directly with the network cable.
1185
1186 [[image:image-20221116110832-2.png||height="423" width="708"]]
1187
1188 Read and write data from the Ethernet module
1189
1190 [[image:image-20221116110907-3.png]]
1191
1192 Set "Transter setup" to COM communication, and read or write operation as shown below
1193
1194 [[image:image-20221116110917-4.png]]
1195
1196 **4)PLC Settings (GX Works 2)**
1197
1198 Create a blank FX5U project
1199
1200 Find Current Connection in the navigation
1201
1202 [[image:image-20221116111427-1.png||height="421" width="705"]]
1203
1204 Select Connection Channel List
1205
1206 Select Ethernet board communication
1207
1208 [[image:image-20221116111451-2.png||height="421" width="705"]]
1209
1210 Select Ethernet Module
1211 Set the IP address of the PLC
1212
1213 [[image:image-20221116111509-3.png||height="666" width="699"]]
1214
1215 Read or write PLC data, in this document is read
1216
1217 [[image:image-20221116111651-4.png||height="416" width="697"]]
1218
1219 [[image:image-20221116111727-5.png||height="416" width="697"]]
1220
1221 **4)Configure the communication protocol**
1222
1223 [[image:image-20221119101946-2.png||height="395" width="695"]]
1224
1225 == **FX5U Serial Protocol** ==
1226
1227 Mitsubishi FX5U series PLC
1228
1229 **1)V-BOX Settings**
1230
1231 |**Item**|**Settings**|**Note**
1232 |Protocol|Mitsubishi FX5U|
1233 |Connection|RS422/RS485|
1234 |Baud rate|9600|
1235 |Data bit|7|
1236 |Parity|Odd|
1237 |Stop bit|1|
1238 |PLC station No.|1~~255|Need to be the same as PLC settings
1239
1240 **2)Address List**
1241
1242 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1243 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1244 |Y|Y|Y o|0~~303237|
1245 |M|M|M d|0~~99999|
1246 |B|B|B h|0~~7FFF|
1247 |F|F|F d|0~~32767|
1248 |SB|SB|SB h|0~~7FFF|
1249 |TS|TS|TS d|0~~1023|
1250 |TC|TC|TC d|0~~1023|
1251 |STS|STS|STS d|0~~1023|
1252 |STC|STC|STS d|0~~1023|
1253 |CS|CS|CS d|0~~1023|
1254 |CC|CC|CC d|0~~1023|
1255 |SM|SM|SM d|0~~9999|
1256 |L|L|L d|0~~32767|
1257 |S|S|S d|0~~4095|
1258 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1259 |TN|TN|TN d|0~~1023|
1260 |STN|STN|STN d|0~~1023|
1261 |CN|CN|CN d|0~~1023|
1262 |R|R|R d|0~~32767|
1263 |SW|SW|SW h|0~~7FFF|
1264 |Z|Z|Z d|0~~23|
1265 |D|D|D d|0~~7999|
1266 |SD|SD|SD d|0~~11999|
1267
1268 **3)PLC Settings (GX Works 3)**
1269
1270 Create a blank FX5U project
1271
1272 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
1273
1274 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5c9cb13fac1e6c93.png?width=200&height=462&rev=1.1||alt="12.PLC Protocol_html_5c9cb13fac1e6c93.png" height="462" width="200"]]
1275
1276 Select protocol in the setting item, and set parameters.
1277
1278 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_de942589ca070228.png?width=600&height=324&rev=1.1||alt="12.PLC Protocol_html_de942589ca070228.png" height="324" width="600"]]
1279
1280 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
1281
1282 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_387ec7d00b5feb59.png?width=600&height=323&rev=1.1||alt="12.PLC Protocol_html_387ec7d00b5feb59.png" height="323" width="600"]]
1283
1284 Click the [Apply] button to finish the setting.
1285
1286 Click download and select the items as below, then click [execute] to download the configuration to PLC.
1287
1288 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_cdef1c5ec8cc2105.png?width=600&height=434&rev=1.1||alt="12.PLC Protocol_html_cdef1c5ec8cc2105.png" height="434" width="600"]]
1289
1290 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
1291
1292 Done.
1293
1294 **4)Configure the communication protocol**
1295
1296 [[image:image-20220825104904-1.png]]
1297
1298 **5)Cable Wiring**
1299
1300
1301 * **RS422**
1302
1303 [[image:image-20220825105105-2.png]]
1304
1305 [[image:image-20220825105533-3.png]]
1306
1307 == **FX5U Ethernet Protocol** ==
1308
1309 Mitsubishi FX5U series PLC
1310
1311 **1)V-BOX Settings**
1312
1313 |**Items**|**Settings**|**Note**
1314 |Protocol|Mitsubishi FX5U|
1315 |Connection|Ethernet|
1316 |Port No.|5002|Must be the same as the PLC setting
1317 |PLC station No.|0|
1318
1319 **2)Address List**
1320
1321 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1322 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1323 |Y|Y|Y o|0~~303237|
1324 |M|M|M d|0~~99999|
1325 |B|B|B h|0~~7FFF|
1326 |F|F|F d|0~~32767|
1327 |SB|SB|SB h|0~~7FFF|
1328 |TS|TS|TS d|0~~1023|
1329 |TC|TC|TC d|0~~1023|
1330 |STS|STS|STS d|0~~1023|
1331 |STC|STC|STS d|0~~1023|
1332 |CS|CS|CS d|0~~1023|
1333 |CC|CC|CC d|0~~1023|
1334 |SM|SM|SM d|0~~9999|
1335 |L|L|L d|0~~32767|
1336 |S|S|S d|0~~4095|
1337 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1338 |TN|TN|TN d|0~~1023|
1339 |STN|STN|STN d|0~~1023|
1340 |CN|CN|CN d|0~~1023|
1341 |R|R|R d|0~~32767|
1342 |SW|SW|SW h|0~~7FFF|
1343 |Z|Z|Z d|0~~23|
1344 |D|D|D d|0~~7999|
1345 |SD|SD|SD d|0~~11999|
1346
1347 **3)PLC Settings (GX Works 3)**
1348
1349 Find the [Ethernet port] in the navigation area.
1350
1351 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_8e8f85ace087346c.png?width=300&height=593&rev=1.1||alt="12.PLC Protocol_html_8e8f85ace087346c.png" height="593" width="300"]]
1352
1353 Select [Own Node Settings] in the [Setting Item List];
1354
1355 Set [IP Address], [Subnet Mask], [Default Gateway];
1356
1357 Click [Detailed Settings] into [Ethernet Configuration (Built-in Ethernet Port)] windows;
1358
1359 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5d98495052c8c10e.png?width=600&height=339&rev=1.1||alt="12.PLC Protocol_html_5d98495052c8c10e.png" height="339" width="600"]]
1360
1361 Select [SLMP Connection Module] and add into host station as below picture shows;
1362
1363 Set Port number as 5002 (this is necessary settings);
1364
1365 Click [Close with Reflecting the Setting] to save and close window;
1366
1367 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_14b489fdc6c6589d.png?width=600&height=350&rev=1.1||alt="12.PLC Protocol_html_14b489fdc6c6589d.png" height="350" width="600"]]
1368
1369 Click [Apply] to completed Etherenet settings;
1370
1371 Switch to the [On line data operation] interface as below, check the item and click [Execute] to download.
1372
1373 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_c93025a968a8a9e7.png?width=600&height=434&rev=1.1||alt="12.PLC Protocol_html_c93025a968a8a9e7.png" height="434" width="600"]]
1374
1375 **4)Configure the communication protocol**
1376
1377 [[image:image-20220825112403-1.png||alt="图片-20220825112403-1.png"]]
1378
1379 **5)Cable Wiring**
1380
1381 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1382
1383 == **L02 Serial Protocol** ==
1384
1385 Mitsubishi L02 series CPU built-in serial port.
1386
1387 **1)V-BOX Settings**
1388
1389 |**Item**|**Settings**|**Note**
1390 |Protocol|Mitsubishi L02|
1391 |Connection|RS422|
1392 |Baud rate|115200|
1393 |Data bit|8|
1394 |Parity|Odd|
1395 |Stop bit|1|
1396 |PLC station No.|1~~255|Need to be the same as PLC settings
1397
1398 **2)Address List**
1399
1400 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1401 |Bit|X|X|X h|0~~FFFF|
1402 |Bit|Y|Y|Y h|0~~FFFF|
1403 |Bit|M|M|M d|0~~9999|
1404 |Bit|L|L|L d|0~~9999|
1405 |Bit|F|F|F d|0~~9999|
1406 |Bit|B|B|B h|0~~FFFF|
1407 |Bit|V|V|V d|0~~2047|
1408 |Bit|TC|TC|TC d|0~~9999|
1409 |Bit|SS|SS|SS d|0~~9999|
1410 |Bit|SC|SC|SC d|0~~9999|
1411 |Bit|CS|CS|CS d|0~~9999|
1412 |Bit|CC|CC|CC d|0~~9999|
1413 |Bit|SB|SB|SB h|0~~FFFF|
1414 |Bit|SM|SM|SM d|0~~2047|
1415 |Bit|STS|STS|STS d|0~~1023|
1416 |Bit|S|S|S d|0~~9999|
1417 |Bit|DX|DX|DX h|0~~FFFF|
1418 |Bit|DY|DY|DY h|0~~FFFF|
1419 |Bit|TS|TS|TS d|0~~9999|
1420 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1421 |Word|W|W|W h|0~~FFFF|
1422 |Word|TN|TN|TN d|0~~99999|
1423 |Word|SN|SN|SN d|0~~99999|
1424 |Word|CN|CN|CN d|0~~99999|
1425 |Word|R|R|R d|0~~99999|
1426 |Word|SW|SW|SW h|0~~FFFF|
1427 |Word|Z|Z|Z d|0~~99999|
1428 |Word|ZR|ZR|ZR h|0~~FFFF|
1429 |Word|D|D|D d|0~~99999|
1430
1431 **3)Communication Settings**
1432
1433 [[image:image-20220825160648-3.png]]
1434
1435 **4)Cable Wiring**
1436
1437 * **RS422**
1438
1439 [[image:image-20220825161612-8.png]]
1440
1441 [[image:image-20220825160820-4.png]]
1442
1443 == **L02 Ethernet Protocol** ==
1444
1445 Mitsubishi L series CPU built-in Ethernet port.
1446
1447 **1)V-BOX Settings**
1448
1449 |**Items**|**Settings**|**Note**
1450 |Protocol|MIT L02 CPU MELSEC|
1451 |Connection|Ethernet|
1452 |Port No.|1025|Must be the same as the PLC setting
1453 |PLC station No.|0|Must be the same as the PLC setting
1454
1455 **2)Address List**
1456
1457 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1458 |Bit|X|X|X h|0~~FFFF|
1459 |Bit|Y|Y|Y h|0~~FFFF|
1460 |Bit|M|M|M d|0~~9999|
1461 |Bit|L|L|L d|0~~9999|
1462 |Bit|F|F|F d|0~~9999|
1463 |Bit|B|B|B h|0~~FFFF|
1464 |Bit|V|V|V d|0~~2047|
1465 |Bit|TC|TC|TC d|0~~9999|
1466 |Bit|SS|SS|SS d|0~~9999|
1467 |Bit|SC|SC|SC d|0~~9999|
1468 |Bit|CS|CS|CS d|0~~9999|
1469 |Bit|CC|CC|CC d|0~~9999|
1470 |Bit|SB|SB|SB h|0~~FFFF|
1471 |Bit|SM|SM|SM d|0~~2047|
1472 |Bit|STS|STS|STS d|0~~1023|
1473 |Bit|S|S|S d|0~~9999|
1474 |Bit|DX|DX|DX h|0~~FFFF|
1475 |Bit|DY|DY|DY h|0~~FFFF|
1476 |Bit|TS|TS|TS d|0~~9999|
1477 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1478 |Word|W|W|W h|0~~FFFF|
1479 |Word|TN|TN|TN d|0~~99999|
1480 |Word|SN|SN|SN d|0~~99999|
1481 |Word|CN|CN|CN d|0~~99999|
1482 |Word|R|R|R d|0~~99999|
1483 |Word|SW|SW|SW h|0~~FFFF|
1484 |Word|Z|Z|Z d|0~~99999|
1485 |Word|ZR|ZR|ZR h|0~~FFFF|
1486 |Word|D|D|D d|0~~99999|
1487
1488 **3)PLC Settings (GX Works2 )**
1489
1490 Create a project
1491
1492 Set PLC IP, subnet mask and gateway;
1493
1494 Select [Binary Code] as communication data code;
1495
1496 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_776e17505f3fc6c0.png?width=600&height=524&rev=1.1||alt="12.PLC Protocol_html_776e17505f3fc6c0.png" height="524" width="600"]]
1497
1498 Set PLC port number, for example 1025
1499
1500 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_8d0d1a22d388f70b.png?width=600&height=524&rev=1.1||alt="12.PLC Protocol_html_8d0d1a22d388f70b.png" height="524" width="600"]]
1501
1502 Save settings;
1503
1504 Download project into PLC device;
1505
1506 Restart PLC device;
1507
1508 **4)Configure the communication protocol**
1509
1510 [[image:image-20220825142659-1.png]]
1511
1512 **5)Cable Wiring**
1513
1514 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1515
1516 == **Q12H Serial Protocol** ==
1517
1518 This Demo shows V-BOX communicate with Q12H PLC by Q02H serial Protocol
1519
1520 [[**Download link**>>https://ftp.we-con.com.cn/Download/WIKI/PI%20HMI/Demo/Communication/V-Box%20connect%20PLC%20Q12H.rar]]
1521
1522 == **QJ71E71 Ethernet Protocol** ==
1523
1524 Mitsubishi QJ71E71 Ethernet communication module;
1525
1526 **1)V-BOX Settings**
1527
1528 |**Items**|**Settings**|**Note**
1529 |Protocol|MIT QJ71E71 MELSEC|
1530 |Connection|Ethernet|
1531 |Port No.|1025|Must be the same as the PLC setting
1532 |PLC station No.|0|Must be the same as the PLC setting
1533
1534 **2)Address List**
1535
1536 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1537 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1538 |Y|Y|Y h|0~~1FFF|
1539 |M|M|M d|0~~99999|
1540 |L|L|L d|0~~8191|
1541 |F|F|F d|0~~2047|
1542 |B|B|B h|0~~1FFF|
1543 |V|V|V d|0~~2047|
1544 |TS|TS|TS d|0~~2047|
1545 |TC|TC|TC d|0~~2047|
1546 |SS|SS|SS d|0~~2047|
1547 |SC|SC|SC d|0~~2047|
1548 |CS|CS|CS d|0~~1023|
1549 |CC|CC|CC d|0~~1023|
1550 |SB|SB|SB h|0~~7FF|
1551 |S|S|S d|0~~8191|
1552 |DX|DX|DX h|0~~1FFF|
1553 |DY|DY|DY h|0~~1FFF|
1554 |SM|SM|SM d|8000~~9999|
1555 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1556 |D|D|D d|0~~12287|
1557 |W|W|W h|0~~1FFF|
1558 |TN|TN|TN d|0~~2047|
1559 |SN|SN|SN d|0~~2047|
1560 |CN|CN|CN d|0~~1023|
1561 |R|R|R d|0~~32767|
1562 |SW|SW|SW h|0~~7FF|
1563 |Z|Z|Z d|0~~15|
1564 |ZR|ZR|ZR h|0~~FE7FF|
1565
1566 **3)PLC Settings(GX Works2)**
1567
1568 * Click [Ethernet/CC IE/MELSECNET];
1569 * Please select [Ethernet] as network type;
1570 * Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order);
1571 * Select [Online] as Mode;
1572 * [[image:image-20221119171343-2.png||height="341" width="587"]]
1573 * Click [Operation setting] to set IP;
1574 * Select [Binary Code] as [Communication Data Code];
1575 * [[image:image-20221119171436-3.png||height="354" width="588"]]
1576 * Click [Open setting]
1577 * Set protocol: TCP;
1578 * Set [unpassive] in [Open system];
1579 * Set [receive] in [Fixed buffer];
1580 * Set [procedure Exist] in [Fixed buffer communication];
1581 * Disable [Pairing open];
1582 * Set [No confirm] in [Existence confirmation];
1583 * Host station port number: 5009;
1584 * Save settings;
1585 * [[image:image-20221119171611-4.png||height="354" width="588"]]
1586 * Download project into PLC and restart it
1587
1588 **4)Configure the communication protocol**
1589
1590 [[image:image-20221119171832-5.png||height="354" width="625"]]
1591
1592
1593 **5)Cable Wiring**
1594
1595 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png"]]
1596
1597 = Create communication with **Delta PLC** =
1598
1599 == **DVP Ethernet Protocol** ==
1600
1601 Supoort Series: DELTA DVP20/32/40/60ES200RE/200TE or any DVP models with built-in Ethernet port, DELTA DVPEN01-SL module
1602
1603 **1)V-BOX Settings**
1604
1605 |=**Items**|=**Settings**|=**Note**
1606 |Protocol|DELTA DVP MODBUS TCP|
1607 |Connection|Ethernet|
1608 |Port No.|502|
1609 |Device No.|1|
1610 |VBox Device No.|0|
1611
1612 **2)Address List **
1613
1614 |=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 217px;" %)**VBox registers**|=(% style="width: 168px;" %)**Format**|=(% style="width: 225px;" %)**Range**|=**Note**
1615 |Bit|(% style="width:191px" %)X|(% style="width:217px" %)X|(% style="width:168px" %)X OOO|(% style="width:225px" %)0~~377|
1616 |Bit|(% style="width:191px" %)Y|(% style="width:217px" %)Y|(% style="width:168px" %)Y OOO|(% style="width:225px" %)0~~377|
1617 |Bit|(% style="width:191px" %)M0|(% style="width:217px" %)M0|(% style="width:168px" %)M0DDDD|(% style="width:225px" %)0~~1535|
1618 |Bit|(% style="width:191px" %)M1|(% style="width:217px" %)M1|(% style="width:168px" %)M1DDDD|(% style="width:225px" %)1536~~4096|
1619 |Bit|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDD|(% style="width:225px" %)0~~255|
1620 |Bit|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~255|
1621 |Bit|(% style="width:191px" %)S|(% style="width:217px" %)S|(% style="width:168px" %)SDDDD|(% style="width:225px" %)0~~1023|
1622 |Word|(% style="width:191px" %)D0|(% style="width:217px" %)D0|(% style="width:168px" %)D0DDDD|(% style="width:225px" %)0~~4095|
1623 |Word|(% style="width:191px" %)D1|(% style="width:217px" %)D1|(% style="width:168px" %)D1DDDD|(% style="width:225px" %)4096~~11999|
1624 |Word|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDD|(% style="width:225px" %)0~~255|
1625 |Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~199|
1626 |Double Word|(% style="width:191px" %)HC|(% style="width:217px" %)HC|(% style="width:168px" %)HCDDD|(% style="width:225px" %)200~~255|
1627
1628 **3) PLC Setting:**
1629
1630 ~1. Create new project in Delta WPL Soft, and click Setting to open the communication settings:
1631
1632 (% style="text-align:center" %)
1633 [[image:DVPEthernetWPLSoft2.png]]
1634
1635 2. Set up the communication type and PLC IP:
1636
1637 (% style="text-align:center" %)
1638 [[image:DVPEthernetSetup.png]]
1639
1640 (% class="wikigeneratedid" %)
1641 3. Click OK and save the settings. Then click Communication on toolbar, then click Transfer Setup to open new window:
1642
1643 (% style="text-align:center" %)
1644 [[image:DVPEthernetTransfer.png]]
1645
1646 (% class="wikigeneratedid" %)
1647 4. Select Communication Mode as PC => PLC to download or select PC <=PLC to upload:
1648
1649 (% style="text-align:center" %)
1650 [[image:DVPEthernetPLCtoPC.png]]
1651
1652 5. Click Auto-Search Ethernet Module to find the PLC on the same LAN network:
1653
1654 (% style="text-align:center" %)
1655 [[image:DVPEthernetAutoSearch.png]]
1656
1657 **4) V-BOX Setting:**
1658
1659 Set the same IP address according to the setting from WPL Soft:
1660
1661 (% style="text-align:center" %)
1662 [[image:DVPEthernetVNETPortocol.png]]
1663
1664 == **DVP serial protocol** ==
1665
1666 Supoort Series: DELTA DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX
1667
1668 **1)V-BOX Settings**
1669
1670 |=**Items**|=**Settings**|=**Note**
1671 |Protocol|DELTA DVP PROTOCOL|
1672 |Connection|RS232|
1673 |Baud Rate|9600|
1674 |Stop Bit|1|
1675 |Data Bit|7|
1676 |Parity|EVEN|
1677 |Device No.|1|
1678
1679 (% class="wikigeneratedid" %)
1680 **2)Address List**
1681
1682 |=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 217px;" %)**VBox registers**|=(% style="width: 168px;" %)**Format**|=(% style="width: 225px;" %)**Range**|=**Note**
1683 |Bit|(% style="width:191px" %)X|(% style="width:217px" %)X|(% style="width:168px" %)X OOOOOO|(% style="width:225px" %)0~~303237|
1684 |Bit|(% style="width:191px" %)Y|(% style="width:217px" %)Y|(% style="width:168px" %)Y OOOOOO|(% style="width:225px" %)0~~303237|
1685 |Bit|(% style="width:191px" %)M|(% style="width:217px" %)M|(% style="width:168px" %)MDDDDD|(% style="width:225px" %)0~~99999|
1686 |Bit|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDDDD|(% style="width:225px" %)0~~99999|
1687 |Bit|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDDDD|(% style="width:225px" %)0~~99999|
1688 |Bit|(% style="width:191px" %)S|(% style="width:217px" %)S|(% style="width:168px" %)SDDDDD|(% style="width:225px" %)0~~99999|
1689 |Word|(% style="width:191px" %)D|(% style="width:217px" %)D|(% style="width:168px" %)D DDDDD|(% style="width:225px" %)0~~99999|
1690 |Word|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDDDD|(% style="width:225px" %)0~~99999|
1691 |Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~199|
1692 |Double Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDDDD|(% style="width:225px" %)200~~99999|
1693
1694 (% class="wikigeneratedid" %)
1695 **3)Wiring Diagram**
1696
1697 (% style="text-align:center" %)
1698 [[image:Delta DVP PROTOCOLSerial232.png]]
1699
1700 == **AS Ethernet Protocol** ==
1701
1702 **1)V-BOX Settings**
1703
1704 |=**Items**|=**Settings**|=**Note**
1705 |Protocol|DELTA AS300 MODBUS TCP|
1706 |Connection|Ethernet|
1707 |Port No.|502|
1708 |Device No.|1|
1709 |HMI No.|0|
1710
1711 **2)Address List**
1712
1713 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1714 |Bit|X|X|X d|0~~63|
1715 |Bit|Y|Y|Y d|0~~63|
1716 |Bit|D|D|D d|0~~29999|
1717 |Bit|M|M|M d|0~~8191|
1718 |Bit|SM|SM|SM d|0~~4095|
1719 |Bit|S|S|S h|0~~2047|
1720 |Bit|T|T|T d|0~~511|
1721 |Bit|C|C|C d|0~~511|
1722 |Bit|HC|HC|HC d|0~~255|
1723 |Word|X|X|X h|0~~63|
1724 |Word|Y|Y|Y d|0~~63|
1725 |Word|SR|SR|SR d|0~~2047|
1726 |Word|D|D|D d|0~~29999|
1727 |Word|T|T|T d|0~~511|
1728 |Word|C|C|C h|0~~511|
1729 |Word|E|E|E d|0~~9|
1730
1731 **3)Configure the communication protocol**
1732
1733 [[image:image-20220831160010-4.png]]
1734
1735 **4)Cable Wiring**
1736
1737 Figure
1738
1739 [[image:image-20220831155101-1.png]][[image:image-20220831160055-5.png]]
1740
1741 Pin Definition Diagram
1742
1743 [[image:image-20220831155157-3.png]]
1744
1745 = Create communication with **Omron PLC** =
1746
1747 == **CP1 Series Protocol ** ==
1748
1749 [[下载链接>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CP1%20Series.zip]]
1750
1751 == **CP2M Series Protocol** ==
1752
1753 [[下载链接>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CJ2M.zip]]
1754
1755
1756 == **EC55 Series Protocol** ==
1757
1758 Supported device: EC55 temperature instrument
1759
1760 **1)V-BOX Settings**
1761
1762 |**Items**|**Settings**|**Note**
1763 |Protocol|Omron EC55|
1764 |Connection|RS485 (9600, 2, 7, EVEN)|
1765 |Port No.|None|
1766 |PLC station No.|0|
1767
1768 **2)Address List**
1769
1770 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
1771 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
1772 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
1773 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
1774 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
1775 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
1776 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
1777 |CP|-|0-6|Read controller intrinsic property
1778 |CS|-|0-2|Read controller states
1779 |CA|-|0-17|Action command
1780
1781 **3)Device Settings**
1782
1783 Omron E5CC PLC configuration
1784
1785 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
1786
1787 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_3d95e093792ba98a.png?width=550&height=229&rev=1.1||alt="12.PLC Protocol_html_3d95e093792ba98a.png" height="229" width="550"]]
1788
1789 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
1790
1791 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_be583aa69dd6cf4c.png?width=550&height=242&rev=1.1||alt="12.PLC Protocol_html_be583aa69dd6cf4c.png" height="242" width="550"]]
1792
1793 **✎Note:** The communication settings for HMI should be consistent with this setting.
1794
1795 **4)Configure the communication protocol**
1796
1797 [[image:image-20220831161041-1.png]]
1798
1799 **5)Cable Wiring**
1800
1801 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5e9a81a14106da9e.png?width=392&height=223&rev=1.1||alt="12.PLC Protocol_html_5e9a81a14106da9e.png" height="223" width="392"]]
1802
1803 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_1897d92be6948d58.png?width=393&height=223&rev=1.1||alt="12.PLC Protocol_html_1897d92be6948d58.png" height="223" width="393"]]
1804
1805 **✎Note:**
1806
1807 * COM3 only available in PI8000/PI9000 series.
1808 * CA address could not support continuous writing function;
1809 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
1810 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
1811 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
1812 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
1813 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
1814 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
1815 * [[image:image-20220831161356-1.png]]Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
1816
1817 = Create communication with Xinje** PLC** =
1818
1819 == **XC serial protocol** ==
1820
1821 **1)V-BOX Settings**
1822
1823 |**Item**|**Settings**|**Note**
1824 |Protocol|XINJE XC MODBUS|
1825 |Connection|RS232|
1826 |Baud rate|19200|
1827 |Data bit|8|
1828 |Parity|EVEN|
1829 |Stop bit|1|
1830 |PLC station No.|1|
1831
1832 **2)Address List**
1833
1834 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1835 |Bit|M|M|M d|0~~8511|
1836 |Bit|X|X|X o|0~~1747|
1837 |Bit|Y|Y|Y o|0~~1747|
1838 |Bit|S|S|S d|0~~1023|
1839 |Bit|T|T|T d|0~~4095|
1840 |Bit|C|C|C d|0~~634|
1841 |Word|D|D|D d|0~~8511|
1842 |Word|TD|TD|TD d|0~~618|
1843 |Word|CD|CD|CD d|0~~634|
1844 |Word|FD|FD|FD d|0~~8511|
1845
1846 **3)Configure the communication protocol**
1847
1848
1849 [[image:image-20220831163041-1.png]]
1850
1851 **4)Cable Wiring**
1852
1853 Figure
1854
1855 [[image:image-20220831163406-2.png]][[image:image-20220831163422-3.png]]
1856
1857 Pin Definition Diagram
1858
1859 [[image:image-20220831163441-4.png]]
1860
1861 == **XD serial protocol** ==
1862
1863 **1)V-BOX Settings**
1864
1865 Supported Series: Xinjie XD/XE Series PLC
1866
1867 |**Item**|**Settings**|**Note**
1868 |Protocol|XINJE XD/XC MODBUS|
1869 |Connection|RS232|
1870 |Baud rate|19200|
1871 |Data bit|8|
1872 |Parity|EVEN|
1873 |Stop bit|1|
1874 |PLC station No.|1|
1875
1876 **2)Address List**
1877
1878 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1879 |Bit|M|M|M d|0~~74999|
1880 |Bit|X1xx|X1xx|X1xx o|0~~1177|
1881 |Bit|X2xx|X2xx|X2xx o|0~~277|
1882 |Bit|X|X|X o|0~~77|
1883 |Bit|Y1xx|Y1xx|Y1xx o|0~~1177|
1884 |Bit|Y2xx|Y2xx|Y2xx o|0~~277|
1885 |Bit|Y|Y|Y o|0~~4095|
1886 |Bit|SM|SM|SM d|0~~4999|(((
1887
1888 )))
1889 |Bit|T|T|T d|0~~4999|
1890 |Bit|C|C|C d|0~~4999|
1891 |Bit|ET|ET|ET d|0~~31|
1892 |Bit|SE|SE|SE d|0~~31|
1893 |Bit|HM|HM|HM d|0~~11999|
1894 |Bit|HSC|HSC|HSC d|0~~39|
1895 |Bit|HS|HS|HS d|0~~999|
1896 |Bit|HT|HT|HT d|0~~1999|
1897 |Bit|HC|HC|HC d|0~~1999|
1898 |Bit|S|S|S d|0~~7999|
1899 |Word|D|D|D d|0~~69999|
1900 |Word|ID|ID|ID d|0~~99|
1901 |Word|ID1xx|ID1xx|ID1xx d|0~~999|
1902 |Word|ID2xx|ID2xx|ID2xx d|0~~299|
1903 |Word|QD|QD|QD d|0~~99|
1904 |Word|QD1xx|QD1xx|QD1xx d|0~~999|
1905 |Word|QD2xx|QD2xx|QD2xx d|0~~299|
1906 |Word|SD|SD|SD d|0~~4999|
1907 |Word|TD|TD|TD d|0~~575|
1908 |Word|CD|CD|CD d|0~~575|
1909 |Word|ETD|ETD|ETD d|0~~31|
1910 |Word|HD|HD|HD d|0~~24999|
1911 |Word|HSD|HSD|HSD d|0~~1023|
1912 |Word|HTD|HTD|HTD d|0~~95|
1913 |Word|HCD|HCD|HCD d|0~~95|
1914 |Word|HSCD|HSCD|HSCD d|0~~31|
1915 |Word|FD|FD|FD d|0~~8191|
1916 |Word|SFD|SFD|SFD d|0~~5999|
1917 |Word|FS|FS|FS d|0~~47|
1918
1919 **3)Configure the communication protocol**
1920
1921 [[image:image-20220831163923-7.png]]
1922
1923
1924
1925 **4)Cable Wiring**
1926
1927 Figure
1928
1929 [[image:image-20220831163406-2.png]][[image:image-20220831163553-6.png]]
1930
1931 Pin Definition Diagram
1932
1933 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830160232-3.png?rev=1.1||alt="image-20220830160232-3.png"]]
1934
1935 = Create communication with **Schneider PLC** =
1936
1937 == **Schneider MODBUS RTU** ==
1938
1939 **1)V-BOX Setting**
1940
1941 |=**Parameters**|=**Recommended**|=**Notes**
1942 |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
1943 |**Connection**|RS485|
1944 |**Baud rate**|19200|
1945 |**Data bit**|8|
1946 |**Parity**|Even|
1947 |**Stop bit**|1|
1948 |**PLC station No.**|1|
1949
1950 **2)Address List**
1951
1952 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
1953 |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
1954 |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
1955 |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
1956 |W|MW|DDDDDD|0 ~~ 999999|Output register
1957 |DW|MD|DDDDDD|0 ~~ 999999|Output register
1958
1959 **3)Configure the communication protocol**
1960
1961 [[image:image-20220902104329-1.png]]
1962
1963 **4)Cable Wiring**
1964
1965 **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
1966
1967 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220817154212-1.jpeg?width=554&height=315&rev=1.1||alt="image-20220817154212-1.jpeg" height="315" width="554"]]
1968
1969 = Create communication with Inovance** PLC** =
1970
1971 == **H3U serial protocol** ==
1972
1973 **1)V-BOX Settings**
1974
1975 |**Item**|**Settings**|**Note**
1976 |Protocol|INOVANCE H3U PLC|
1977 |Connection|RS422|
1978 |Baud rate|9600|
1979 |Data bit|7|
1980 |Parity|EVEN|
1981 |Stop bit|1|
1982 |PLC station No.|0|
1983
1984 **2)Address List**
1985
1986 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1987 |Bit|X|X|X o|0~~303237|
1988 |Bit|Y|Y|Y o|0~~303237|
1989 |Bit|M|M|M d|0~~99999|
1990 |Bit|T|T|T d|0~~99999|
1991 |Bit|C|C|C d|0~~99999|
1992 |Bit|SM|SM|SM d|8000~~999|
1993 |Bit|S|T|S d|0~~99999|
1994 |Bit|Lamp|Lamp|Lamp d|0~~0|
1995 |Word|X|X|X o|0~~303237|
1996 |Word|Y|Y|Y o|0~~303237|
1997 |Word|M|M|M d|0~~99999|
1998 |Word|T|T|T d|0~~99999|
1999 |Word|C|C|C d|0~~199|
2000 |Word|D|D|D d|0~~7999|
2001 |Word|S|S|S d|0~~99999|
2002 |Word|SD|SD|SD d|8000~~9999|
2003 |Word|R|R|R d|0~~32767|
2004
2005 **3)Configure the communication protocol**
2006
2007 [[image:image-20220831164626-1.png]]
2008
2009
2010
2011 **4)Cable Wiring**
2012
2013 Figure
2014
2015 [[image:image-20220831164646-2.png]][[image:image-20220831164700-3.png]]
2016
2017 Pin Definition Diagram
2018
2019 [[image:image-20220831164731-4.png]]
2020
2021 = Create communication with Panasonic** PLC** =
2022
2023 == **FP serial protocol** ==
2024
2025 **1)V-BOX Settings**
2026
2027 |**Item**|**Settings**|**Note**
2028 |Protocol|Panasonic FP MFWTOCOL|
2029 |Connection|RS232|
2030 |Baud rate|9600|
2031 |Data bit|8|
2032 |Parity|ODD|
2033 |Stop bit|1|
2034 |PLC station No.|1|
2035
2036 **2)Address List**
2037
2038 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
2039 |Bit|X|X|X d|0~~9999|
2040 |Bit|Y|Y|Y d|0~~9999|
2041 |Bit|R|R|R d|0~~9999|
2042 |Bit|T|T|T d|0~~9999|
2043 |Bit|C|C|C d|0~~9999|
2044 |Bit|L|L|L d|0~~9999|
2045 |Word|WX|WX|WX d|0~~9999|
2046 |Word|WY|WY|WY d|0~~9999|
2047 |Word|WR|WR|WR d|0~~9999|
2048 |Word|WL|WL|WL d|0~~9999|
2049 |Word|LD|LD|LD d|0~~9999|
2050 |Word|DT|DT|DT d|0~~65535|
2051 |Word|FL|FL|FL d|0~~9999|
2052 |Word|EV|EV|EV d|0~~9999|
2053 |Word|SV|SV|SV d|0~~9999|
2054
2055 **3)Configure the communication protocol**
2056
2057 [[image:image-20220831165238-4.png]]
2058
2059
2060
2061 **4)Cable Wiring**
2062
2063 Figure
2064
2065 [[image:image-20220831165031-3.png]][[image:image-20220831165017-2.png]]
2066
2067 Pin Definition Diagram
2068
2069 [[image:image-20220831165008-1.png]]
2070
2071 = Create communication with LS** PLC** =
2072
2073 == **XBC serial protocol** ==
2074
2075 **1)V-BOX Settings**
2076
2077 |**Item**|**Settings**|**Note**
2078 |Protocol|LS XBC CNet|
2079 |Connection|RS232|
2080 |Baud rate|115200|
2081 |Data bit|8|
2082 |Parity|NONE|
2083 |Stop bit|1|
2084 |PLC station No.|1|
2085
2086 **2)Address List**
2087
2088 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
2089 |Bit|P|P|P d|0~~2047|
2090 |Bit|M|M|M d|0~~2047|
2091 |Bit|L|L|L d|0~~11263|
2092 |Bit|K|K|K d|0~~16183|
2093 |Bit|F|F|F d|0~~2047|
2094 |Bit|D|D|D d|0~~32767|
2095 |Bit|R|R|R d|0~~32767|
2096 |Bit|U|U|U d|0~~4095|
2097 |Word|P|P|P d|0~~2047|
2098 |Word|M|M|M d|0~~2047|
2099 |Word|L|L|L d|0~~11263|
2100 |Word|K|K|K d|0~~16183|
2101 |Word|F|F|F d|0~~2047|
2102 |Word|C|C|C d|0~~2047|
2103 |Word|T|T|T d|0~~2047|
2104 |Word|D|D|D d|0~~32767|
2105 |Word|N|N|N d|0~~21503|
2106 |Word|R|R|R d|0~~32767|
2107 |Word|U|U|U d|0~~4095|
2108 |Word|Z|Z|Z d|0~~127|
2109 |Word|S|S|S d|0~~127|
2110
2111 **3)Configure the communication protocol**
2112
2113 [[image:image-20220831170147-1.png]]
2114
2115 **4)Cable Wiring**
2116
2117 Figure
2118
2119 [[image:image-20220831170306-4.png]][[image:image-20220831170254-3.png]]
2120
2121 Pin Definition Diagram
2122
2123 [[image:image-20220831170215-2.png]]
2124
2125 == **XGK FEnet Ethernet protocol** ==
2126
2127 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
2128
2129 **1)V-BOX Settings**
2130
2131 |**Items**|**Settings**|**Note**
2132 |Protocol|LG XGK FEnet(Ethernet)|
2133 |Connection|Ethernet|
2134 |Port No.|2004|
2135
2136 **2)Address List**
2137
2138 |**Type**|**Register**|**Range**|**Format**|**Note**
2139 |(% rowspan="14" %)Word|P|0~~2047|P d|
2140 |M|0~~2047|M d|
2141 |K|0~~2047|K d|
2142 |F|0~~2047|F d|
2143 |T|0~~2047|T d|
2144 |C|0~~2047|C d|
2145 |Z|0~~127|Z d|
2146 |S|0~~127|S d|
2147 |L|0~~11263|L d|
2148 |N|0~~21503|N d|
2149 |D|0~~32767|D d|
2150 |R|0~~32767|R d|
2151 |ZR|0~~65535|ZR d|
2152 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
2153
2154 **✎Note:**
2155
2156 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
2157 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
2158 * All bit registers are in the form of bits in word, and the range is the same as the word register;
2159
2160 **3)Communication Settings**
2161
2162 [[image:image-20220831171127-1.png]]
2163
2164 **4)Cable Wiring**
2165
2166 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2167
2168 = Create communication with **Modbus ** =
2169
2170 == **MODBUS RTU Slave (All function)** ==
2171
2172 Select the protocol "Modbus RTU Slave (All Fuction)",
2173
2174 Then set baud rate, port, stop bits, data bits, parity.
2175
2176 (% style="text-align:center" %)
2177 [[image:1624342015914-382.png||height="486" width="800" class="img-thumbnail"]]
2178
2179 == **Communicate with Modbus Meter** ==
2180
2181 The following example is using the Linfee meter LNF96EY to demonstrate how to set up the Modbus communication.
2182
2183 ~1. Wiring the RS485 cable first. Because the pin 58 is A, the pin 59 is B for meter. Here we use the COM1 to connect. So the diagram like follows:
2184
2185 (% style="text-align:center" %)
2186 [[image:LinfeeTerminalDiagram.png]]
2187
2188 2. Check the specific Modbus parameter in the communication menu from LED display.
2189
2190 So from the following pictures, we can know the Meter Address is 85, Baud rate is 9600, CRC None.
2191
2192 {{info}}
2193 **✎Note: **Meter address usually corresponding to the Modbus Slave Station No. on the Modbus communication.
2194 {{/info}}
2195
2196 (% style="text-align:center" %)
2197 [[image:MeterModbusAllView.png]]
2198
2199 (% class="wikigeneratedid" %)
2200 3. Set up the communication in the Configuration tab.
2201
2202 (% class="wikigeneratedid" %)
2203 Select the protocol as **ModBus RTU Slave (All Function)**. And set the communication parameters like below.
2204
2205 (% style="text-align:center" %)
2206 [[image:VNETCommunicationtabmeter.png]]
2207
2208 (% class="wikigeneratedid" %)
2209 4. Create new real-time monitoring tag accroding to Modbus manual
2210
2211 (% class="wikigeneratedid" %)
2212 Enter the address we want to read from the meter. The following table is intercept part of the manual for Linfee Modbus manual.
2213
2214 (% class="wikigeneratedid" %)
2215 **0x03/0x04 command data register address**:
2216
2217 (% style="width:1142.22px" %)
2218 |(% style="display:none" %) |=(% colspan="2" rowspan="1" style="width: 165px;" %)Address(% style="display:none" %) |=Description|=Data Format|=(% style="width: 254px;" %)Data Length(Word)|=(% style="width: 282px;" %)Remark
2219 |(%%)(% style="display:none" %) (%%) HEX|(% style="width:107px" %)DEC|(%%)(% style="display:none" %) (%%) |(% style="width:100px" %) |(%%)(% style="display:none" %) (%%) |(% style="width:318px" %)
2220 |(% style="width:107px" %)0x00|(% style="width:100px" %)0|Reserved| | |(% style="width:318px" %)
2221 |(% style="width:107px" %)0x02|(% style="width:100px" %)2|Reserved| | |(% style="width:318px" %)
2222 |(% style="width:107px" %)0x04|(% style="width:100px" %)4|Reserved| | |(% style="width:318px" %)
2223 |(% style="width:107px" %)0x06|(% style="width:100px" %)6|Ua|float|2|(% style="width:318px" %)Phase Voltage data, Unit V
2224 |(% style="width:107px" %)0x08|(% style="width:100px" %)8|Ub|float|2|(% style="width:318px" %)Phase Voltage data, Unit V
2225 |(% style="width:107px" %)0x0A|(% style="width:100px" %)10|Uc|float|2|(% style="width:318px" %)Phase Voltage data, Unit V
2226 |(% style="width:107px" %)0x0C|(% style="width:100px" %)12|Uab|float|2|(% style="width:318px" %)Line Voltage data, Unit V
2227 |(% style="width:107px" %)0x0E|(% style="width:100px" %)14|Ubc|float|2|(% style="width:318px" %)Line Voltage data, Unit V
2228 |(% style="width:107px" %)0x10|(% style="width:100px" %)16|Uca|float|2|(% style="width:318px" %)Line Voltage data, Unit V
2229 |(% style="width:107px" %)0x12|(% style="width:100px" %)18|Ia|float|2|(% style="width:318px" %)Phase Current data, Unit A
2230 |(% style="width:107px" %)0x14|(% style="width:100px" %)20|Ib|float|2|(% style="width:318px" %)Phase Current data, Unit A
2231 |(% style="width:107px" %)0x16|(% style="width:100px" %)22|Ic|float|2|(% style="width:318px" %)Phase Current data, Unit A
2232
2233 {{info}}
2234 **✎Note: **We usually use the Data Type 4 for read the Modbus registers(Function Code 03)
2235 {{/info}}
2236
2237 For example, here we want to read the Phase Voltage Ua (Modbus offset 0006), the Modbus register main No. requires input decimal number, and check whether the actual address has one address offset, so the tag configured like the following screenshot:
2238
2239 (% style="text-align:center" %)
2240 [[image:VNETModbusTagSettings.png]]
2241
2242 (% style="text-align:center" %)
2243 [[image:VNETModbusTagByteSettings.png]]
2244
2245 {{info}}
2246 **✎Note: **If the read value is incorrect, please check whether need to change the Byte order.
2247 {{/info}}
2248
2249 Set the Modbus Slave Station No.
2250
2251 (% style="text-align:center" %)
2252 [[image:ModbusStationSettings.png]]
2253
2254 If the communication is setup successfully, the tag will show green light.
2255
2256 (% style="text-align:center" %)
2257 [[image:Monitoringtaggreenlight.png]]
2258
2259 == **MODBUS RTU Master** ==
2260
2261 Select the protocol "Modbus RTU Master",
2262
2263 Then set baud rate, port, stop bits, data bits, parity
2264
2265 (% style="text-align:center" %)
2266 [[image:1624348709622-711.png||queryString="width=809&height=493" height="488" width="800" class="img-thumbnail"]]
2267
2268 **address list**
2269
2270 (% class="table-bordered" %)
2271 |=(% scope="row" %)**Type**|=**Data Type**|=**Function code and description**
2272 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (Read Input Registers: Read the current binary value in one or more input registers)
2273 |06 (write single register: write a binary value to a holding register)
2274 |10 (write values to multiple addresses )
2275 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
2276 |06 (write single register: write a binary value to a holding register)
2277 |10 (write values to multiple addresses )
2278 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
2279 |06 (write single register: write a binary value to a holding register)
2280 |10 (write values to multiple addresses )
2281 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
2282 |10 (write values to multiple addresses )
2283 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
2284 |05 (Force a single coil to force the on/off state of a logic coil)
2285 |0F (Write multiple bits, ie write continuously)
2286 |(% rowspan="3" %)1|02 (Read the input state)
2287 |05 (Force a single coil to force the on/off state of a logic coil)
2288 |0F (Write multiple bits)
2289 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
2290 |05 (Force a single coil to force the on/off state of a logic coil)
2291 |0F (Write multiple bits)
2292 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
2293 |0F (Write multiple bits)
2294
2295 == **MODBUS TCP Slave (All function)** ==
2296
2297 Supported series: MODBUS TCP controller
2298
2299 V-B0X works as MODBUS TCP MASTER connecting with TCP SLAVE
2300
2301 **1)V-BOX Setting**
2302
2303 |**Items**|**Settings**|**Note**
2304 |Protocol|MODBUS TCP Slave (All function)|
2305 |Connection|Ethernet|
2306 |Port No.|502|
2307 |PLC station No.|1
2308
2309 **2)Address List**
2310
2311 |=**Type**|=**Data Type**|=**Function code & Description**
2312 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
2313 |06 (write single register: write a binary value to a holding register)
2314 |10 (write values to multiple addresses )
2315 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
2316 |06 (write single register: write a binary value to a holding register)
2317 |10 (write values to multiple addresses )
2318 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
2319 |06 (write single register: write a binary value to a holding register)
2320 |10 (write values to multiple addresses )
2321 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
2322 |10 (write values to multiple addresses )
2323 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
2324 |05 (Force a single coil to force the on/off state of a logic coil)
2325 |0F (Write multiple bits, ie write continuously)
2326 |(% rowspan="3" %)1|02 (Read the input state)
2327 |05 (Force a single coil to force the on/off state of a logic coil)
2328 |0F (Write multiple bits)
2329 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
2330 |05 (Force a single coil to force the on/off state of a logic coil)
2331 |0F (Write multiple bits)
2332 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
2333 |0F (Write multiple bits)
2334
2335 **3)Communication Settings**
2336
2337 Configure V-BOX Ethernet IP in Networking Settings
2338
2339 [[image:image-20220902111833-3.png]]
2340
2341
2342 Configure PLC Ethernet IP in Communication;
2343
2344 [[image:image-20220902111121-1.png]]
2345
2346 **4)Cable Wiring**
2347
2348 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2349
2350 == **communicate with VB inverter** ==
2351
2352 [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20VB%20inverter.zip]]
2353
2354 = **User define protocol** =
2355
2356 More serial port script instruction,please refer manual:[[Lua script function>>doc:V-BOX.V-Net.Manual.04 Lua Script.01 Lua Functions.WebHome]]~-~-->[[3.Serial port operation>>url:http://docs.we-con.com.cn/wiki/vbox/view/HMI/04.Lua%20script%20%20function%20and%20operation/01.Lua%20script%20function/#H3.Serialportoperation]]
2357
2358 == **Read the temperature sensor.** ==
2359
2360 the commond format is as beliow:
2361
2362 Send commond:01 03 02 00 00 03 04 73
2363
2364 Feedback commond:01 03 06 07 F7 0E 7E B7 35
2365
2366 Temperature data:07 F7,desimal = 2039,it means temperature is 20.39℃.
2367
2368 Humidity data:0E 7E,desimal = 3710, it mean humidity is 37.10%RH.
2369
2370 Script Demo:
2371
2372 ~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~--
2373
2374 function com.main()
2375 ~-~-dosomething
2376 openPlc()
2377 end
2378 function openPlc()
2379 if obj then
2380 ~-~- If the serial port opened,then read/write data by timing
2381
2382 local wri = string.pack(">HHHH",0X0103,0X0200,0X0003,0X0473)
2383 local arr = reading(wri)
2384 ~-~- if arr ~~=nil then
2385 ~-~- if arr[1] ==33 and arr[2] ==v[2][2] and arr[3] ==v[2][3] then
2386 ~-~- local A = arr[4]*256
2387 ~-~- local B = A+arr[5]
2388 ~-~- addr_setword(v[1],B)
2389 ~-~- end
2390 ~-~- end
2391
2392 else
2393 ~-~-judge if there is a serial object, then initialize and open the serial port
2394 local configs = {
2395 name = 'COM1', ~-~-Select serial port COM1
2396 mode = 485, ~-~-Communication mode RS485
2397 baud_rate = 9600, ~-~-Baud rate 9600
2398 stop_bit = 1, ~-~-stop bit 1
2399 data_len = 8, ~-~-data length 8
2400 check_bit = 'NONE', ~-~-no parity
2401
2402 }
2403 obj,err = serial.open(configs) ~-~-Open serial port
2404 if not obj then
2405 print("serial open :failed", err) ~-~- Open serial port failed
2406 end
2407 end
2408 end
2409
2410 function reading(wri)
2411 obj:flush() ~-~- Clear serial port
2412 obj:write(wri) ~-~- Write serial port
2413 print(string.byte(wri,1,#wri))
2414 obj:flush() ~-~- Clear serial port 
2415 local readed =obj:read(9,1000) ~-~- Read 9 bytes, timeout 1 second
2416 if readed and readed ~~= "" then 
2417 ~-~- judge that a non-empty string is read
2418 print(string.byte(readed,1,#readed))
2419 a={string.byte(readed, 1, #readed)}
2420 if nil ~~= a[4] and nil ~~= a[5] and nil ~~= a[6] and nil ~~= a[7] then
2421 a1=a[4]*256+a[5]
2422 a2=a[6]*256+a[7]
2423 addr_setword("@HDW0",a1)
2424 addr_setword("@HDW1",a2)
2425 end
2426 return {string.byte(readed, 1, #readed)}
2427 elseif readed == nil then
2428 print("serial read err:", err or "")
2429 return nil
2430 end
2431 return nil
2432 end
2433
2434 ~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-