Wiki source code of 1 Communication

Version 241.1 by Hunter on 2023/05/19 18:15

Show last authors
1 = Create communication with WECON PLC =
2
3 == **LX3V Serial Protocol** ==
4
5 Supported series: Wecon LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
6
7 **1)V-BOX setting**
8
9 |**Item**|**Settings**|**Note**
10 |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
11 |Connection|RS422/RS485|
12 |Baud rate|9600|
13 |Data bit|7|
14 |Parity|EVEN|
15 |Stop bit|1|
16 |PLC station No.|1|
17
18 **2)Address List**
19
20
21 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
22 |(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
23 |Y|Y|Y o|0~~303237|
24 |M|M|M d|0~~99999|
25 |T|T|T d|0~~99999|
26 |C|C|C d|0~~99999|
27 |S|S|S d|0~~99999|
28 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
29 |Y|Y|Y o|0~~303237|
30 |M|M|M d|0~~99999|
31 |T|T|T d|0~~99999|
32 |C|C|C d|0~~199|
33 |D|D|D d|0~~7999|
34 |S|S|S d|0~~99999|
35 |SD|SD|SD d|8000~~9999|
36
37 **3)Configure the communication protocol**
38
39 [[image:image-20220824152217-1.png||alt="图片-20220824152217-1.png"]]
40
41 **4)Cable Wiring**
42
43 * **RS422**
44
45 [[image:image-20220824120614-5.png]]
46
47 * **RS485**
48
49 [[image:image-20220824120524-3.png]]
50
51 == **LX5V Serial Protocol** ==
52
53 This example introduces the establishment of serial port communication between V-BOX and LX5V. It is introduced through three parts: PLC software configuration, V-BOX software configuration, and hardware wiring.
54
55 **Software configuration of PLC**
56
57 **1)PLC programming software**
58
59 [[image:image-20220824142722-1.png]]
60
61 **2)New PLC project**
62
63 Click New Project and select the PLC model.
64
65 [[image:image-20220822172623-2.png]]
66
67 **3)Set Serial port parameters**
68
69 Follow the steps below to configure Serial port parameters
70
71 Baud rate:115200
72
73 Data bit:8
74
75 Stop bit:1
76
77 Parity:No verification
78
79 [[image:image-20220822172657-3.png]]
80
81 **4)Registers list**
82
83 [[image:image-20220822172730-4.png]]
84
85 **V-BOX software configuration**
86
87 **1)V-BOX programming software**
88
89 [[image:image-20220824104124-1.png]]
90
91 **2)V-NET add device**
92
93 Open V-NET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the access key, password and remark, to add the device.
94
95 [[image:image-20220824104909-2.png]]
96
97 **3)Set communication port parameters**
98
99 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
100
101 Baud rate:115200
102
103 Data bit:8
104
105 Stop bit:1
106
107 Parity:No verification
108
109 [[image:image-20220824142130-1.png]]
110
111 **hardware connection**
112
113 **1)Hardware wiring diagram**
114
115 [[image:image-20220824142546-2.png]]
116
117 [[image:image-20220824142643-3.png]]
118
119 The above are all the steps for establishing serial port communication between V-BOX with LX5V PLC.
120
121 == **LX5V-N Ethernet protocol** ==
122
123 This example introduces the establishment of Ethernet communication between V-BOX and LX5V-N. It is introduced through three parts: PLC software configuration, V-BOX software configuration, and hardware wiring.
124
125 **Software configuration of PLC**
126
127 **1)PLC programming software**
128
129 [[image:image-20220824142722-1.png]]
130
131 **2)New PLC project**
132
133 Click New Project and select the PLC model.
134
135 [[image:image-20220824143613-1.png]]
136
137 **3)Set Ethernet port parameters**
138
139 Follow the steps below to configure Ethernet parameters
140
141 PLC IP address:192.168.39.200
142
143 default gateway:192.168.39.1
144
145 subnet mask:255.255.255.0
146
147 [[image:image-20220824143744-2.png]]
148
149 **4)Registers list**
150
151 [[image:image-20220822172730-4.png]]
152
153 (% id="cke_bm_22473S" style="display:none" %)** **(%%)**V-BOX software configuration**
154
155 **1)V-BOX programming software**
156
157 [[image:image-20220824104124-1.png]]
158
159 **2)V-NET add device**
160
161 Open V-NET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the access key, password and remark, to add the device.
162
163 [[image:image-20220824104909-2.png]]
164
165 **3)Set communication Protocol**
166
167 Click Communication to configure the LX5V plc protocol and IP address.
168
169 [[image:image-20220824144619-1.png]]
170
171 **hardware connection**
172
173 **1)Hardware wiring diagram**
174
175 [[image:image-20220824151127-2.png]]
176
177 The above are all the steps for establishing ethernet communication between V-BOX with LX5V PLC.
178
179 = Create communication with Allen-Bradley(**Rockwell**)** PLC** =
180
181 == **DF1 Advanced Protocol** ==
182
183 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
184
185 **1) V-Box Settings**
186
187 |=Item|=Recommended |=Note
188 |=Protocol|Allen Bradley DF1 Advanced|
189 |=Connection|RS232|
190 |=Baud rate|19200|
191 |=Stop bits|1|
192 |=Data bits|8|
193 |=Parity|None|
194 |=PLC Station No.|1|
195 |=HMI Station No.|0|
196
197 **2) Address List**
198
199 |=**Type**|=**Device registers**|=**Format**|=**Range**|=Note
200 |(% colspan="1" rowspan="7" %)Bit|I1|I1ddd.dd|0.0~~255.15|Only able to communicate with file number I1
201 |O0|O0ddd.dd|0.0~~255.15|Only able to communicate with file number O0
202 |S2|S2ddd.dd|0.0~~255.15|Only able to communicate with file number S2
203 |B3|B3ddd.dd|0.0~~255.15|Only able to communicate with file number B3
204 |BN|BNddddd.dd|0.0~~99255.15|(((
205 Bit data file B0~~B99
206
207 First two digits is for file number
208
209 For example, BN13001.00 represents file number B13, address 001, the 0th bit.
210 )))
211 |N7|N7ddd.dd|0.0~~255.15|Only able to communicate with file number N7
212 |NN|NNddddd.dd|0.0~~99255.15|(((
213 Integer data file bit format N0~~N99
214
215 First two digits is for file number
216
217 For example, NN13001.00 represents file number N13, address 001, the 0th bit.
218 )))
219 |(% rowspan="11" %)Word|S2|S2ddd|0~~255|Only able to communicate with file number S2
220 |T4S|T4Sddd|0~~255|Only able to communicate with file number T4 (Timer Preset Value)
221 |T4P|T4Pddd|0~~255|Only able to communicate with file number T4 (Timer Accumulator Value)
222 |TNS|TNSddddd|0~~99255|(((
223 Timer Preset Value
224
225 First two digits is for file number
226
227 For example, TNS99255 represents file number T99, address 255.
228 )))
229 |TNP|TNPddddd|0~~99255|(((
230 Timer Accumulator Value
231
232 First two digits is for file number
233
234 For example, TNP99255 represents file number T99, address 255.
235 )))
236 |C5S|C5Sddd|0~~255|Only able to communicate with file number C5 (Counter Preset Value)
237 |C5P|C5Pddd|0~~255|Only able to communicate with file number C5 (Counter Accumulator Value)
238 |CNS|CNSddddd|0~~99255|(((
239 Counter Preset Value
240
241 First two digits is for file number
242
243 For example, CNS99255 represents file number C99, address 255.
244 )))
245 |CNP|CNPddddd|0~~99255|(((
246 Counter Accumulator Value
247
248 First two digits is for file number
249
250 For example, CNP99255 represents file number C99, address 255.
251 )))
252 |N7|N7ddd|0~~255|Only able to communicate with file number N7
253 |NN|NNddd|0~~99255|(((
254 Integer data file
255
256 First two digits is for file number
257
258 For example, NN99255 represents file number N99, address 255.
259 )))
260 |(% colspan="1" rowspan="3" %)Double Word|F8|F8ddd|0~~255|(((
261 Only able to communicate with file number N7
262 )))
263 |FN|FNddddd|0~~99255|(((
264 Floating point data file
265
266 First two digits is for file number
267
268 For example, FN99255 represents file number F99, address 255.
269 )))
270 |LN|LNddddd|0~~99255|Long
271
272 **3) Cable Wiring**
273
274 (% style="text-align:center" %)
275 [[image:ABRS232.gif]]
276
277 (% class="wikigeneratedid" id="HMicroLogixA0Protocol" %)
278 (% id="cke_bm_5621S" style="display:none" %)** **
279
280 == **MicroLogix Protocol** ==
281
282 (% class="wikigeneratedid" %)
283 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
284
285 **1)V-BOX setting**
286
287 |**Item**|**Settings**|**Note**
288 |Protocol|Allen-Bradley DF1 Advanced|
289 |Connection|RS232|
290 |Baud rate|19200|
291 |Data bit|8|
292 |Parity|None|
293 |Stop bit|1|
294 |PLC station No.|1|
295
296 **2)Address List**
297
298 |**Type**|**Device registers**|**Format**|**Range**|**Note**
299 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
300 |O|O d.d|0.0~~255.15|
301 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
302 |S|S d.d|0.0~~255.15|
303 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
304 |(% rowspan="9" %)Word|S|S d|0~~255|
305 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
306 |TP|TP nnhh|0~~ffff
307 |CS|CS nnhh|0~~ffff
308 |CP|CP nnhh|0~~ffff
309 |N|N nnhh|0~~ffff
310 |C|C nnhh|0~~ffff
311 |T|T nnhh|0~~ffff
312 |R|R nnhh|0~~ffff
313
314 **3)Configure the communication protocol**[[image:image-20220824152928-1.png]]
315
316 **4)Configure the communication protocol**
317
318 [[image:image-20220824110724-1.png]]
319
320 == **Micro850_FreeTag Protocol** ==
321
322 (((
323 (((
324 This example introduces the establishment of Ethernet communication between Wecon V-box and CompactLogix L1769. It is introduced through three parts: PLC software configuration, V-box software configuration, and hardware wiring.
325 )))
326 )))
327
328 (((
329 (% class="wikigeneratedid" id="HSoftwareconfigurationofPLC" %)
330 (((
331 **Software configuration of PLC**
332 )))
333
334 (% class="wikigeneratedid" id="HPLCprogrammingsoftware" %)
335 (((
336 **1)PLC programming software**
337 )))
338
339 [[image:image-20220714162600-1.png]]
340
341 (% class="wikigeneratedid" id="HNewPLCproject" %)
342 (((
343 **2)New PLC project**
344 )))
345
346 (((
347 (((
348 Click New Project and select the PLC model.
349 )))
350 )))
351
352 (((
353 [[image:image-20220714162617-2.png]]
354 )))
355
356 (((
357
358
359 [[image:image-20220714162652-4.png]]
360 )))
361
362 (((
363 (% class="wikigeneratedid" id="HSetEthernetparameters" %)
364 (((
365 **3)Set Ethernet parameters**
366 )))
367
368 (((
369 (((
370 (((
371 Follow the steps below to configure Ethernet parameters
372 )))
373 )))
374 )))
375
376 (((
377 (((
378 (((
379 PLC IP address:192.168.40.101
380 )))
381 )))
382 )))
383
384 (((
385 (((
386 (((
387 default gateway:192.168.40.1
388 )))
389 )))
390 )))
391
392 (((
393 (((
394 (((
395 subnet mask:255.255.255.0
396 )))
397 )))
398 )))
399
400 (((
401 [[image:image-20220714162713-5.png]]
402 )))
403
404 (((
405
406 )))
407
408 (((
409 (% class="wikigeneratedid" id="HV-boxsoftwareconfiguration" %)
410 (((
411 **V-box software configuration**
412 )))
413
414 (% class="wikigeneratedid" id="HV-boxprogrammingsoftware" %)
415 (((
416 **1)V-box programming software**
417 )))
418
419 (% class="wikigeneratedid" %)
420 (((
421 [[image:image-20220714162725-6.png]]
422 )))
423
424 (% class="wikigeneratedid" id="HConfiguredevicenetwork" %)
425 (((
426 **2)Configure device network**
427 )))
428
429 (((
430 (((
431 (((
432 Click the Configuration Download button[[image:image-20220714115308-8.png||height="22" width="15"]], It is used to configure the device network, update the device time, obtain the device machine code, check the device network, etc.
433 )))
434
435 (((
436 In the example below, the IP address of V-Box is configured as 192.168.40.66, and the networking method is 4G connection
437 )))
438 )))
439 )))
440
441 (((
442 (((
443 [[image:image-20220714162737-7.png]]
444
445
446 )))
447 )))
448 )))
449 )))
450
451 (% class="wikigeneratedid" id="HV-netadddevice" %)
452 (((
453 **3)V-net add device**
454 )))
455 )))
456
457 (((
458 (((
459 Open VNET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the device machine code/product code, device password, and device alias to add the device.   [[image:image-20220714162752-8.png]]
460 )))
461
462
463 )))
464
465 (((
466 (% class="wikigeneratedid" id="HSetcommunicationportparameters" %)
467 (((
468 **4)Set communication port parameters**
469 )))
470
471 (((
472 In the device list on the left, find the Vbox that communicates with the L1769, click it and select configuration,communication port configuration in the main interface to add a communication protocol.
473 )))
474
475 [[image:image-20220714162805-9.png]]
476 )))
477
478 (((
479 The communication port is selected as Ethernet, the device type is selected as Allen-Bradley, the protocol is Allen-BradleyMicro850_FreeTag EthemetIP, and the IP is the internal IP address of the L1769 PLC. The port number is 44818.
480 )))
481
482 [[image:image-20220824164346-1.png]]
483
484
485 (((
486 After adding the protocol Allen-BradleyMicro850_FreeTag, click[[image:image-20220714143838-2.png]]icon add label.[[image:image-20220714162827-11.png]]
487 )))
488
489 (% class="wikigeneratedid" id="HEngineeringproduction" %)
490 (((
491 **5)Engineering production**
492 )))
493
494 (% class="wikigeneratedid" %)
495 (((
496 (((
497 According to your own needs, use the V-NET client software to edit the required data monitoring points.
498 )))
499
500 [[image:image-20220714162841-12.png]]
501
502
503 (((
504 **hardware connection**
505 )))
506 )))
507
508 (((
509 **1)Hardware wiring diagram**
510 )))
511
512 (((
513 (((
514 This example introduces Wecon V-box with Allen-Bradley L1769 PLC to establish communication through Ethernet. The connection diagram is as follows:
515 )))
516
517 [[image:image-20220714162856-13.png]]
518
519 (((
520 The above are all the steps for establishing Ethernet communication between Wecon V-box with CompactLogix L1769 PLC.
521
522
523 == **Micro850_FreeTag Protocol(new)** ==
524
525 This example introduces the establishment of Ethernet communication between Wecon V-box and 2080-LC50-48QWB,Micro850. It is introduced through three parts: PLC software configuration, V-box software configuration.
526
527 (% class="wikigeneratedid" id="HSoftwareconfigurationofPLC" %)
528 (((
529 **Software configuration of PLC**
530 )))
531
532 (% class="wikigeneratedid" id="HPLCprogrammingsoftware" %)
533 (((
534 **1)PLC programming software:Connected Components Workbench™**
535
536 (% style="text-align:center" %)
537 [[image:software.png]]
538
539 **2)New PLC project**
540
541 Click New Project and select the PLC model.
542
543 (% style="text-align:center" %)
544 [[image:project create.png]]
545
546 **3)Set Ethernet parameters**
547
548 Follow the steps below to configure Ethernet parameters
549
550 PLC IP address:192.168.39.56
551
552 default gateway:192.168.39.1
553
554 subnet mask:255.255.255.0
555
556 (% style="text-align:center" %)
557 [[image:Ethernet.png]]
558
559 **4)connect PLC**
560
561 **When downloading the setting, need to change the status of the PLC to PRG**
562
563 (% style="text-align:center" %)
564 [[image:conne ab plc.png]]
565
566 **V-box software configuration**
567
568 **1)V-box programming software**
569
570 (% style="text-align:center" %)
571 [[image:v-net client vers.png]]
572
573 **2)Set communication port parameters**
574
575 In the device list on the left, find the Vbox that communicates with the L1769, click it and select configuration,communication port configuration in the main interface to add a communication protocol.
576
577 (% style="text-align:center" %)
578 [[image:V-NET_Client_t2Rg2wpSoY.png]]
579
580 The communication port is selected as Ethernet, the device type is selected as Allen-Bradley, the protocol is Allen-BradleyMicro850_FreeTag EthemetIP, and the IP is the internal IP address of the L1769 PLC. The port number is 44818.
581
582 (% style="text-align:center" %)
583 [[image:V-NET_Client_communication.png]]
584
585 Export variables from PLC, select CSV file, comma delimited.(% id="cke_bm_1950S" style="display:none" %)
586
587 (% style="text-align:center" %)
588 [[image:export1.png]]
589
590 (% style="text-align:center" %)
591 [[image:CCW.Shell_E5Cwj4tUL3.png]]
592
593 After adding the protocol Allen-BradleyMicro850_FreeTag, click[[image:https://docs.we-con.com.cn/bin/download/V-BOX/V-Net/Training/1%20Communication/WebHome/image-20220714143838-2.png?rev=1.1||alt="image-20220714143838-2.png"]]icon add label.
594
595 (% style="text-align:center" %)
596 [[image:V-NET_Client_TNBuqy7T5r.png]]
597
598 **3)Engineering production**
599
600 According to your own needs, use the V-NET client software to edit the required data monitoring points.
601
602 (% style="text-align:center" %)
603 [[image:V-NET_Client_KOR0AHEA4M.png]]
604
605
606 )))
607
608 == **Ethernet DF1 Protocol** ==
609
610 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Allen-Bradley%20Ethernet%20DF1.zip]]
611
612 = Create communication with **Crouzet PLC** =
613
614 == **CROUZET M3 (FBD)** ==
615
616 Support Series: Crouzet Millenium 3 CD12/CB12
617
618 **1)V-BOX setting**
619
620 |=Item|=Recommended |=Note
621 |=Protocol|CROUZET M3 (FBD)|
622 |=Connection|RS232|
623 |=Baud rate|115200|
624 |=Stop bits|1|
625 |=Data bits|7|
626 |=Parity|EVEN|
627
628 **2)Address List**
629
630 |=**Type**|=**Device registers**|=**Format**|=**Range**|=Note
631 |(% rowspan="4" %)Bit|I|I DD|1~~99|Input
632 |SLIBit|SLIBit DD.dd|1.0~~24.15|Serial Link Input
633 |SLOBit|SLOBit DD.dd|25.0~~48.15|Serial Link Output(Read only)
634 |State|State D|1~~1|PLC state(Read only)
635 |(% rowspan="5" %)Word|AI|AI DD|1~~99|Analog Input
636 |SLIn|SLIn DD|1~~24|Serial Link Input
637 |SLOut|SLOut DD|25~~48|Serial Link Output(Read only)
638 |Time|Time D|1~~6|(((
639 Time1: Second
640
641 Time2: Minute
642
643 Time3: Hour
644
645 Time4: Day
646
647 Time5: Month
648
649 Time6: Year
650 )))
651 |Order|Order D|1~~1|(((
652 Running command(Write only)
653
654 ~=2: Run mode; =1: Stop mode;
655 )))
656
657 **3)Cable Wiring**
658
659 (% style="text-align:center" %)
660 [[image:CrouzetRS232 VBox.png]]
661
662 {{info}}
663 **✎Note: **As the wiring diagram indicated, this protocol requires the DB9 serial port pin 4. But pin 4 is undefined for all V-Box, so it need the user to solder a Pull-up resistor to make the pin 4 working. As for how to solder the resistor on the motherboard, please contact with Wecon technical support for the details.
664 {{/info}}
665
666 = Create communication with EMERSON PLC =
667
668 == **RTU Slave Protocol** ==
669
670 Supported series: EC10 series
671
672 **1)V-BOX setting**
673
674 |**Items**|**Settings**|**Note**
675 |Protocol|Emerson 984 RTU Slave MODBUS|
676 |Connection|RS485|
677 |Baud rate|19200|
678 |Data bit|8|
679 |Parity|EVEN|
680 |Stop bit|1|
681 |Device station No.|1|Need to be same as the PLC setting
682
683 (% class="wikigeneratedid" %)
684 **2)PLC Setting**
685
686 (% class="wikigeneratedid" %)
687 Remember to use the Control Star to enable the Modbus RTU communication for port 1 in system block before dowload into PLC.
688
689 (% style="text-align:center" %)
690 [[image:ControlStarSystemBlock.png]]
691
692 (% style="text-align:center" %)
693 [[image:ControlStarCommunicate.png]]
694
695 (% style="text-align:center" %)
696 [[image:ControlStarModbus.png]]
697
698 (% class="wikigeneratedid" %)
699 **3)Address List**
700
701 |**Type**|**Device registers**|**Format**|**Range**|**Note**
702 |(% colspan="1" rowspan="12" %)Bit|Y|YOOO|0~~377|
703 |X|XOOO|0~~377|
704 |M0|M0DDDD|0~~2047|
705 |M1|M1DDDDD|2048~~10239|
706 |SM0|SM0DDD|0~~255|
707 |SM1|SM1DDD|256~~511|
708 |S0|S0DDDD|0~~1023|
709 |S1|S1DDDD|1024~~4095|
710 |T0|T0DDD|0~~255|
711 |T1|T1DDD|256~~511|
712 |C0|C0DDD|0~~255|
713 |C1|C1DDD|256~~306|
714 |(% colspan="1" rowspan="7" %)Word|D|DDDDD|0~~7999|
715 |Z|ZDD|0~~15|
716 |TW0|TW0DDD|0~~255|
717 |TW1|TW1DDD|256~~511|
718 |SD0|SD0DDD|0~~255|
719 |SD1|SD1DDD|256~~511|
720 |CW|CWDDD|0~~306|
721 |(% colspan="1" rowspan="2" %)Double Word|CW0|CW0DDD|200~~255|
722 |CW1|CW1DDDDD|256~~99999|
723
724 **4) Cable Wiring**
725
726 (% style="text-align:center" %)
727 [[image:Emerson.png]]
728
729 = Create communication with HollySys PLC =
730
731 == **LK Modbus RTU** ==
732
733 Supported Series: HollySys LK series PLC
734
735 **1)V-BOX setting**
736
737 |**Items**|**Settings**|**Note**
738 |Protocol|HollySys LK Modbus RTU|
739 |Connection|RS485|
740 |Baud rate|38400|
741 |Data bit|8|
742 |Parity|None|
743 |Stop bit|1|
744 |Device station No.|1|
745
746 **2)Address List**
747
748 |=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note**
749 |Bit|QX|QXDDDDD.dd|0~~65535.15|
750 |Bit|IX|IXDDDDD.dd|0~~65535.15|
751 |Bit|MX|MXDDDDD.dd|0~~65535.15|
752 |Word|QW|QWDDDDD|0~~99999|
753 |Word|IW|IWDDDDD|0~~99999|
754 |Word|MW|MWDDDDD|0~~99999|
755 |Word|MD|MDDDDDD|0~~99999|
756
757 **3)Cable Wiring**
758
759 (% style="text-align:center" %)
760 [[image:Hollysys485-2.png]]
761
762 = Create communication with **Siemens PLC** =
763
764 == **S7-200 Smart Ethernet Protocol** ==
765
766 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20S7-200%20Smart.zip]]
767
768
769 == **S7-300 Ethernet Protocol** ==
770
771 Supported Series: Siemens S7-300 series PLC
772
773 **1)V-BOX setting**
774
775 |**Items**|**Settings**|**Note**
776 |Protocol|Simens S7-300 Ethernet|
777 |Connection|Ethernet|
778 |Port No.|102|
779 |PLC station No.|2|Need to be same as the PLC setting
780
781 **2)Address List**
782
783 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
784 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
785 |Q|Q|Q ddddd.o|0.0~~99999.7|
786 |M|M|M ddddd.o|0.0~~99999.7|
787 |DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
788 nn: block number;
789
790 dddd: address;
791 )))
792 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
793 |Q|QW|QW ddddd|0~~99999|
794 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
795 |MW|MW ddddd|0~~99999|(((
796 MW0=MB(0~~1)
797
798 MW2=MB(2~~3)
799
800 Address value is a multiple of 2
801 )))
802 |MD|MD ddddd|0~~99999|(((
803 MD0=MB(0~~3)
804
805 MD4=MB(4~~7)
806
807 Address value is a multiple of 4
808 )))
809 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
810 nn: block number;
811
812 dddd: address
813 )))
814 |DBxDBW|DBxDBW nndddd|0~~99999999
815 |DBxDBD|DBxDBD nndddd|0~~99999999
816
817 **3)Configure the communication protocol**
818
819 [[image:image-20220824161345-1.png]]
820
821 **4)Cable Wiring**
822
823 [[image:image-20220824161450-2.png]]
824 )))
825 )))
826
827 == **S7-1200 Ethernet Protocol** ==
828
829 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]]
830
831 == **S7-XXX Ethernet Protocol** ==
832
833 Supported Series: Siemens S7-400, S7-1200 and S7-1500
834
835 **1)V-BOX setting**
836
837 |=**Items**|=**Settings**|=**Note**
838 |Protocol|Siemens S7-XXX|
839 |Connection|Ethernet|
840 |Port No.|102|
841 |Device No.|Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|
842 |HMI No.|Rack (Default as 0)|
843
844 Slot from TIA Portal is equal to Device No. of V-net
845
846 Rack from TIA Portal is equal to HMI No. of V-net
847
848 [[image:image-20220824162459-3.png]]
849
850 [[image:image-20220824163305-2.png]]
851
852 **2)Address List**
853
854 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
855 |(% rowspan="4" %)Bit|I|I|M d.o|(((
856 d:0~-~-9999
857
858 o:0-7
859 )))|
860 |Q|Q|Q d.o|(((
861 d:0~-~-9999
862
863 o:0-7
864 )))|
865 |M|M|M d.o|(((
866 d:0~-~-9999
867
868 o:0-7
869 )))|
870 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
871 nn:0-9999,
872
873 dddd:0-9999,
874
875 o:0-7
876 )))|(((
877 nn:DB No.
878
879 dddd:address value
880
881 o: digit address
882 )))
883 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
884 |M|MW|MW d|d:0-99999|(((
885 MW0=MB(0~~1)
886
887 MW2=MB(2~~3)
888
889 Address value is a multiple of 2
890 )))
891 |M|MD|MD d|d:0-99999|(((
892 MD0=MB(0~~3)
893
894 MD4=MB(4~~7)
895
896 Address value is a multiple of 4
897 )))
898 |I|IW|IW d|d:0-99999|
899 |Q|QW|QW d|d:0-99999|
900 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
901 nn:0-9999
902
903 dddd:0-9999
904 )))|(((
905 nn:DB No.
906
907 dddd:address value
908 )))
909 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
910 nn:0-9999
911
912 dddd:0-9999
913 )))|(((
914 nn:DB No.
915
916 dddd:address value
917
918 Address value is a multiple of 2
919 )))
920 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
921 nn:0-9999
922
923 dddd:0-9999
924 )))|(((
925 nn:DB No.
926
927 dddd:address value
928
929 Address value is a multiple of 4
930 )))
931
932 **3)Configure the communication protocol**
933
934 [[image:image-20220824163448-3.png]]
935
936 **✎Note:**
937
938 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three V-BOX.
939 * V-BOX access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
940
941 **4)Cable Wiring**
942
943 [[image:image-20220824162342-2.png]]
944
945 == **LOGO Ethernet Protocol** ==
946
947 Supported Series: Siemens Logo 0BA0, 0BA1 series
948
949 **V-BOX Settings**
950
951
952 |**Items**|**Settings**|**Note**
953 |Protocol|Siemens LOGO|
954 |Connection|Ethernet|
955 |Port No.|102|
956 |PLC station No.|2|
957
958 **Address List**
959
960
961 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
962 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
963 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
964 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
965 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
966 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
967 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
968 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
969 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
970 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
971 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
972 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
973 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
974 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
975 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
976 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
977
978 **PLC Settings in LOGO Software:**
979
980 Click [Tools]~-~-[Ethernet Connections],shown as below.
981
982 (% style="text-align:center" %)
983 [[image:PIStudio.12\.PLC protocols.WebHome@12.PLC Protocol_html_8b9d2322edf89519.png]]
984
985 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
986
987 (% style="text-align:center" %)
988 [[image:PIStudio.12\.PLC protocols.WebHome@image-20221228142937-4.png]]
989
990 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
991
992 (% style="text-align:center" %)
993 [[image:PIStudio.12\.PLC protocols.WebHome@image-20221228143047-5.png]]
994
995 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
996
997 (% style="text-align:center" %)
998 [[image:PIStudio.12\.PLC protocols.WebHome@image-20221228143246-6.png]]
999
1000 **V-BOX Communication Settings**
1001
1002 Set PLC IP in [IP Address] settings;
1003
1004 (% style="text-align:center" %)
1005 [[image:LldwDGntf4.png]]
1006
1007 Enable V-BOX Ethernet in [Network];
1008
1009 (% style="text-align:center" %)
1010 [[image:WgvjfWbQif.png]]
1011
1012 TSAP setting
1013
1014 * The initialization script needs to set the source TSAP address and the target TSAP address, otherwise the communication will not be successful.
1015
1016 {{code language="LUA"}}
1017 function init.main()
1018 addr_setword("@W_0#HSW1200",8192) -- Set the source TSAP address
1019 addr_setword("@W_0#HSW1201",4096) -- Set the destination TSAP address
1020 end
1021 {{/code}}
1022
1023 Note: The name of the test script is init, 8192 and 4096 are the data used for the test, there is no HSW address in the register option, but you can directly set the value of the corresponding address through the code.
1024
1025 **✎Note:**
1026
1027 * **Communication port configuration: **
1028 ** Continuous length needs to be set to 0.
1029 ** Integration interval needs to be set to 1. (no change may result in data errors)
1030 ** Set Port and Device Station NO.
1031 ** Other set as defaulted.
1032 * **Notes on the use of registers:**
1033 ** Register VD: Use only registers that are multiples of 4, such as 0, 4, 8, etc.
1034 ** Register VW: Use only registers thay are multiples of 2, such as 0, 2, 4 etc. (Using an odd-length register may result in data errors, such as 2 3 4 )
1035
1036 = Create communication with **Mitsubishi PLC** =
1037
1038 == **FX1S,1N,2N Serial Protocol** ==
1039
1040 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
1041
1042 **1)V-BOX Settings**
1043
1044 |**Item**|**Settings**|**Note**
1045 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
1046 |Connection|RS422/RS485/RS232|
1047 |Baud rate|9600~~115200|
1048 |Data bit|7/8|
1049 |Parity|EVEN/Odd/None|
1050 |Stop bit|1/2|
1051 |PLC station No.|1~~255|
1052
1053 **2)Address List**
1054
1055 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1056 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1057 |Y|Y|Y o|0~~303237|
1058 |M|M|M d|0~~99999|
1059 |T|T|T d|0~~99999|
1060 |C|C|C d|0~~99999|
1061 |S|S|S d|0~~99999|
1062 |SM|SM|SM d|8000~~9999|
1063 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1064 |Y|Y|Y o|0~~303237|
1065 |M|M|M d|0~~99999|
1066 |T|T|T d|0~~99999|
1067 |C|C|C d|0~~199|
1068 |D|D|D d|0~~7999|
1069 |S|S|S d|0~~99999|
1070 |SD|SD|SD d|8000~~9999|
1071
1072 **3)Configure the communication protocol**
1073
1074 [[image:image-20220825102844-3.png]]
1075
1076 **4)Cable Wiring**
1077
1078 * **RS422**
1079
1080 [[image:image-20220825103350-4.png]]
1081
1082 [[image:image-20220825100845-4.png]]
1083
1084
1085 == **FX3U,3G,3GA Serial Protocol** ==
1086
1087 Supported Series: Mitsubishi FX3U, FX3G, FX3GA series
1088
1089 **1)V-BOX Settings**
1090
1091 |**Item**|**Settings**|**Note**
1092 |Protocol|Mitsubishi FX3U/3G/3GA|
1093 |Connection|RS422/RS485/RS232|
1094 |Baud rate|9600~~115200|
1095 |Data bit|7/8|
1096 |Parity|EVEN/Odd/None|
1097 |Stop bit|1/2|
1098 |PLC station No.|1~~255|
1099
1100 **2)Address List**
1101
1102 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1103 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1104 |Y|Y|Y o|0~~303237|
1105 |M|M|M d|0~~99999|
1106 |T|T|T d|0~~99999|
1107 |C|C|C d|0~~99999|
1108 |S|S|S d|0~~99999|
1109 |SM|SM|SM d|8000~~9999|
1110 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1111 |Y|Y|Y o|0~~303237|
1112 |M|M|M d|0~~99999|
1113 |T|T|T d|0~~99999|
1114 |C|C|C d|0~~199|
1115 |D|D|D d|0~~7999|
1116 |S|S|S d|0~~99999|
1117 |SD|SD|SD d|8000~~9999|
1118
1119 **3)Configure the communication protocol**
1120
1121 [[image:image-20220825102649-2.png]]
1122
1123 **4)Cable Wiring**
1124
1125 * **RS422**
1126
1127 [[image:image-20220825103421-5.png]]
1128
1129 [[image:image-20220825100845-4.png]]
1130
1131
1132 == **FX3U Ethernet Protocol** ==
1133
1134 Supported Modules: FX3U-ENET-ADP, FX3U-ENET-L
1135
1136 **1)V-BOX Settings**
1137
1138 |Items|Settings|Note
1139 |Protocol|Mitsubishi FX3U|
1140 |Connection|Ethernet|
1141 |Port No.|5009|Must be the same as the PLC setting
1142 |PLC station No.|0|
1143
1144 **2)Address List**
1145
1146 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1147 |(% colspan="1" rowspan="7" %)Bit|X|X|X OOO|0~~377|
1148 |Y|Y|Y OOO|0~~377|
1149 |M|M|M DDDD|0~~7679|
1150 |SM|SM|SM DDDD|8000~~8511|
1151 |S|S|S DDDD|0~~4095|
1152 |TS|TS|TS DDD|0~~511|
1153 |CS|CS|CS DDD|0~~255|
1154 |(% colspan="1" rowspan="9" %)Word|CN|CN|CN DDD|0~~199|
1155 |TN|TN|TN DDD|0~~511|
1156 |D|D|D DDDD|0~~7999|
1157 |SD|SD|SD DDDD|8000~~8511|
1158 |R|R|R DDDDD|0~~32767|
1159
1160 **3)Ethernet Module Settings**
1161
1162 FX3U-ENET-L module configuration
1163 Set up the FX3U-ENET-L Ethernet module settings as follows.
1164 Select the module location, which in this document is Module 0.
1165
1166 [[image:image-20221116105850-1.png]]
1167
1168 Select "Operational setting" to enter the following screen.
1169
1170 The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default.
1171
1172 [[image:image-20221116105947-1.png]]
1173
1174 Select "Open setting" to enter the setting interface, the settings are as follows.
1175
1176 The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the
1177
1178 Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module.
1179
1180 [[image:image-20221116110802-1.png]]
1181
1182 Click on "transter setup" - "PC side I/F setting", see the following figure.
1183
1184 After setting, the first download must use the programming cable, as shown in the figure; after that, can
1185
1186 use the IP set in the "Ethernet board" to communicate directly with the network cable.
1187
1188 [[image:image-20221116110832-2.png||height="423" width="708"]]
1189
1190 Read and write data from the Ethernet module
1191
1192 [[image:image-20221116110907-3.png]]
1193
1194 Set "Transter setup" to COM communication, and read or write operation as shown below
1195
1196 [[image:image-20221116110917-4.png]]
1197
1198 **4)PLC Settings (GX Works 2)**
1199
1200 Create a blank FX5U project
1201
1202 Find Current Connection in the navigation
1203
1204 [[image:image-20221116111427-1.png||height="421" width="705"]]
1205
1206 Select Connection Channel List
1207
1208 Select Ethernet board communication
1209
1210 [[image:image-20221116111451-2.png||height="421" width="705"]]
1211
1212 Select Ethernet Module
1213 Set the IP address of the PLC
1214
1215 [[image:image-20221116111509-3.png||height="666" width="699"]]
1216
1217 Read or write PLC data, in this document is read
1218
1219 [[image:image-20221116111651-4.png||height="416" width="697"]]
1220
1221 [[image:image-20221116111727-5.png||height="416" width="697"]]
1222
1223 **4)Configure the communication protocol**
1224
1225 [[image:image-20221119101946-2.png||height="395" width="695"]]
1226
1227 == **FX5U Serial Protocol** ==
1228
1229 Mitsubishi FX5U series PLC
1230
1231 **1)V-BOX Settings**
1232
1233 |**Item**|**Settings**|**Note**
1234 |Protocol|Mitsubishi FX5U|
1235 |Connection|RS422/RS485|
1236 |Baud rate|9600|
1237 |Data bit|7|
1238 |Parity|Odd|
1239 |Stop bit|1|
1240 |PLC station No.|1~~255|Need to be the same as PLC settings
1241
1242 **2)Address List**
1243
1244 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1245 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1246 |Y|Y|Y o|0~~303237|
1247 |M|M|M d|0~~99999|
1248 |B|B|B h|0~~7FFF|
1249 |F|F|F d|0~~32767|
1250 |SB|SB|SB h|0~~7FFF|
1251 |TS|TS|TS d|0~~1023|
1252 |TC|TC|TC d|0~~1023|
1253 |STS|STS|STS d|0~~1023|
1254 |STC|STC|STS d|0~~1023|
1255 |CS|CS|CS d|0~~1023|
1256 |CC|CC|CC d|0~~1023|
1257 |SM|SM|SM d|0~~9999|
1258 |L|L|L d|0~~32767|
1259 |S|S|S d|0~~4095|
1260 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1261 |TN|TN|TN d|0~~1023|
1262 |STN|STN|STN d|0~~1023|
1263 |CN|CN|CN d|0~~1023|
1264 |R|R|R d|0~~32767|
1265 |SW|SW|SW h|0~~7FFF|
1266 |Z|Z|Z d|0~~23|
1267 |D|D|D d|0~~7999|
1268 |SD|SD|SD d|0~~11999|
1269
1270 **3)PLC Settings (GX Works 3)**
1271
1272 Create a blank FX5U project
1273
1274 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
1275
1276 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5c9cb13fac1e6c93.png?width=200&height=462&rev=1.1||alt="12.PLC Protocol_html_5c9cb13fac1e6c93.png" height="462" width="200"]]
1277
1278 Select protocol in the setting item, and set parameters.
1279
1280 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_de942589ca070228.png?width=600&height=324&rev=1.1||alt="12.PLC Protocol_html_de942589ca070228.png" height="324" width="600"]]
1281
1282 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
1283
1284 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_387ec7d00b5feb59.png?width=600&height=323&rev=1.1||alt="12.PLC Protocol_html_387ec7d00b5feb59.png" height="323" width="600"]]
1285
1286 Click the [Apply] button to finish the setting.
1287
1288 Click download and select the items as below, then click [execute] to download the configuration to PLC.
1289
1290 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_cdef1c5ec8cc2105.png?width=600&height=434&rev=1.1||alt="12.PLC Protocol_html_cdef1c5ec8cc2105.png" height="434" width="600"]]
1291
1292 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
1293
1294 Done.
1295
1296 **4)Configure the communication protocol**
1297
1298 [[image:image-20220825104904-1.png]]
1299
1300 **5)Cable Wiring**
1301
1302
1303 * **RS422**
1304
1305 [[image:image-20220825105105-2.png]]
1306
1307 [[image:image-20220825105533-3.png]]
1308
1309 == **FX5U Ethernet Protocol** ==
1310
1311 Mitsubishi FX5U series PLC
1312
1313 **1)V-BOX Settings**
1314
1315 |**Items**|**Settings**|**Note**
1316 |Protocol|Mitsubishi FX5U|
1317 |Connection|Ethernet|
1318 |Port No.|5002|Must be the same as the PLC setting
1319 |PLC station No.|0|
1320
1321 **2)Address List**
1322
1323 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1324 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1325 |Y|Y|Y o|0~~303237|
1326 |M|M|M d|0~~99999|
1327 |B|B|B h|0~~7FFF|
1328 |F|F|F d|0~~32767|
1329 |SB|SB|SB h|0~~7FFF|
1330 |TS|TS|TS d|0~~1023|
1331 |TC|TC|TC d|0~~1023|
1332 |STS|STS|STS d|0~~1023|
1333 |STC|STC|STS d|0~~1023|
1334 |CS|CS|CS d|0~~1023|
1335 |CC|CC|CC d|0~~1023|
1336 |SM|SM|SM d|0~~9999|
1337 |L|L|L d|0~~32767|
1338 |S|S|S d|0~~4095|
1339 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1340 |TN|TN|TN d|0~~1023|
1341 |STN|STN|STN d|0~~1023|
1342 |CN|CN|CN d|0~~1023|
1343 |R|R|R d|0~~32767|
1344 |SW|SW|SW h|0~~7FFF|
1345 |Z|Z|Z d|0~~23|
1346 |D|D|D d|0~~7999|
1347 |SD|SD|SD d|0~~11999|
1348
1349 **3)PLC Settings (GX Works 3)**
1350
1351 Find the [Ethernet port] in the navigation area.
1352
1353 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_8e8f85ace087346c.png?width=300&height=593&rev=1.1||alt="12.PLC Protocol_html_8e8f85ace087346c.png" height="593" width="300"]]
1354
1355 Select [Own Node Settings] in the [Setting Item List];
1356
1357 Set [IP Address], [Subnet Mask], [Default Gateway];
1358
1359 Click [Detailed Settings] into [Ethernet Configuration (Built-in Ethernet Port)] windows;
1360
1361 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5d98495052c8c10e.png?width=600&height=339&rev=1.1||alt="12.PLC Protocol_html_5d98495052c8c10e.png" height="339" width="600"]]
1362
1363 Select [SLMP Connection Module] and add into host station as below picture shows;
1364
1365 Set Port number as 5002 (this is necessary settings);
1366
1367 Click [Close with Reflecting the Setting] to save and close window;
1368
1369 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_14b489fdc6c6589d.png?width=600&height=350&rev=1.1||alt="12.PLC Protocol_html_14b489fdc6c6589d.png" height="350" width="600"]]
1370
1371 Click [Apply] to completed Etherenet settings;
1372
1373 Switch to the [On line data operation] interface as below, check the item and click [Execute] to download.
1374
1375 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_c93025a968a8a9e7.png?width=600&height=434&rev=1.1||alt="12.PLC Protocol_html_c93025a968a8a9e7.png" height="434" width="600"]]
1376
1377 **4)Configure the communication protocol**
1378
1379 [[image:image-20220825112403-1.png||alt="图片-20220825112403-1.png"]]
1380
1381 **5)Cable Wiring**
1382
1383 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1384
1385 == **L02 Serial Protocol** ==
1386
1387 Mitsubishi L02 series CPU built-in serial port.
1388
1389 **1)V-BOX Settings**
1390
1391 |**Item**|**Settings**|**Note**
1392 |Protocol|Mitsubishi L02|
1393 |Connection|RS422|
1394 |Baud rate|115200|
1395 |Data bit|8|
1396 |Parity|Odd|
1397 |Stop bit|1|
1398 |PLC station No.|1~~255|Need to be the same as PLC settings
1399
1400 **2)Address List**
1401
1402 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1403 |Bit|X|X|X h|0~~FFFF|
1404 |Bit|Y|Y|Y h|0~~FFFF|
1405 |Bit|M|M|M d|0~~9999|
1406 |Bit|L|L|L d|0~~9999|
1407 |Bit|F|F|F d|0~~9999|
1408 |Bit|B|B|B h|0~~FFFF|
1409 |Bit|V|V|V d|0~~2047|
1410 |Bit|TC|TC|TC d|0~~9999|
1411 |Bit|SS|SS|SS d|0~~9999|
1412 |Bit|SC|SC|SC d|0~~9999|
1413 |Bit|CS|CS|CS d|0~~9999|
1414 |Bit|CC|CC|CC d|0~~9999|
1415 |Bit|SB|SB|SB h|0~~FFFF|
1416 |Bit|SM|SM|SM d|0~~2047|
1417 |Bit|STS|STS|STS d|0~~1023|
1418 |Bit|S|S|S d|0~~9999|
1419 |Bit|DX|DX|DX h|0~~FFFF|
1420 |Bit|DY|DY|DY h|0~~FFFF|
1421 |Bit|TS|TS|TS d|0~~9999|
1422 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1423 |Word|W|W|W h|0~~FFFF|
1424 |Word|TN|TN|TN d|0~~99999|
1425 |Word|SN|SN|SN d|0~~99999|
1426 |Word|CN|CN|CN d|0~~99999|
1427 |Word|R|R|R d|0~~99999|
1428 |Word|SW|SW|SW h|0~~FFFF|
1429 |Word|Z|Z|Z d|0~~99999|
1430 |Word|ZR|ZR|ZR h|0~~FFFF|
1431 |Word|D|D|D d|0~~99999|
1432
1433 **3)Communication Settings**
1434
1435 [[image:image-20220825160648-3.png]]
1436
1437 **4)Cable Wiring**
1438
1439 * **RS422**
1440
1441 [[image:image-20220825161612-8.png]]
1442
1443 [[image:image-20220825160820-4.png]]
1444
1445 == **L02 Ethernet Protocol** ==
1446
1447 Mitsubishi L series CPU built-in Ethernet port.
1448
1449 **1)V-BOX Settings**
1450
1451 |**Items**|**Settings**|**Note**
1452 |Protocol|MIT L02 CPU MELSEC|
1453 |Connection|Ethernet|
1454 |Port No.|1025|Must be the same as the PLC setting
1455 |PLC station No.|0|Must be the same as the PLC setting
1456
1457 **2)Address List**
1458
1459 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1460 |Bit|X|X|X h|0~~FFFF|
1461 |Bit|Y|Y|Y h|0~~FFFF|
1462 |Bit|M|M|M d|0~~9999|
1463 |Bit|L|L|L d|0~~9999|
1464 |Bit|F|F|F d|0~~9999|
1465 |Bit|B|B|B h|0~~FFFF|
1466 |Bit|V|V|V d|0~~2047|
1467 |Bit|TC|TC|TC d|0~~9999|
1468 |Bit|SS|SS|SS d|0~~9999|
1469 |Bit|SC|SC|SC d|0~~9999|
1470 |Bit|CS|CS|CS d|0~~9999|
1471 |Bit|CC|CC|CC d|0~~9999|
1472 |Bit|SB|SB|SB h|0~~FFFF|
1473 |Bit|SM|SM|SM d|0~~2047|
1474 |Bit|STS|STS|STS d|0~~1023|
1475 |Bit|S|S|S d|0~~9999|
1476 |Bit|DX|DX|DX h|0~~FFFF|
1477 |Bit|DY|DY|DY h|0~~FFFF|
1478 |Bit|TS|TS|TS d|0~~9999|
1479 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1480 |Word|W|W|W h|0~~FFFF|
1481 |Word|TN|TN|TN d|0~~99999|
1482 |Word|SN|SN|SN d|0~~99999|
1483 |Word|CN|CN|CN d|0~~99999|
1484 |Word|R|R|R d|0~~99999|
1485 |Word|SW|SW|SW h|0~~FFFF|
1486 |Word|Z|Z|Z d|0~~99999|
1487 |Word|ZR|ZR|ZR h|0~~FFFF|
1488 |Word|D|D|D d|0~~99999|
1489
1490 **3)PLC Settings (GX Works2 )**
1491
1492 Create a project
1493
1494 Set PLC IP, subnet mask and gateway;
1495
1496 Select [Binary Code] as communication data code;
1497
1498 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_776e17505f3fc6c0.png?width=600&height=524&rev=1.1||alt="12.PLC Protocol_html_776e17505f3fc6c0.png" height="524" width="600"]]
1499
1500 Set PLC port number, for example 1025
1501
1502 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_8d0d1a22d388f70b.png?width=600&height=524&rev=1.1||alt="12.PLC Protocol_html_8d0d1a22d388f70b.png" height="524" width="600"]]
1503
1504 Save settings;
1505
1506 Download project into PLC device;
1507
1508 Restart PLC device;
1509
1510 **4)Configure the communication protocol**
1511
1512 [[image:image-20220825142659-1.png]]
1513
1514 **5)Cable Wiring**
1515
1516 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1517
1518 == **Q12H Serial Protocol** ==
1519
1520 This Demo shows V-BOX communicate with Q12H PLC by Q02H serial Protocol
1521
1522 [[**Download link**>>https://ftp.we-con.com.cn/Download/WIKI/PI%20HMI/Demo/Communication/V-Box%20connect%20PLC%20Q12H.rar]]
1523
1524 == **QJ71E71 Ethernet Protocol** ==
1525
1526 Mitsubishi QJ71E71 Ethernet communication module;
1527
1528 **1)V-BOX Settings**
1529
1530 |**Items**|**Settings**|**Note**
1531 |Protocol|MIT QJ71E71 MELSEC|
1532 |Connection|Ethernet|
1533 |Port No.|1025|Must be the same as the PLC setting
1534 |PLC station No.|0|Must be the same as the PLC setting
1535
1536 **2)Address List**
1537
1538 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1539 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1540 |Y|Y|Y h|0~~1FFF|
1541 |M|M|M d|0~~99999|
1542 |L|L|L d|0~~8191|
1543 |F|F|F d|0~~2047|
1544 |B|B|B h|0~~1FFF|
1545 |V|V|V d|0~~2047|
1546 |TS|TS|TS d|0~~2047|
1547 |TC|TC|TC d|0~~2047|
1548 |SS|SS|SS d|0~~2047|
1549 |SC|SC|SC d|0~~2047|
1550 |CS|CS|CS d|0~~1023|
1551 |CC|CC|CC d|0~~1023|
1552 |SB|SB|SB h|0~~7FF|
1553 |S|S|S d|0~~8191|
1554 |DX|DX|DX h|0~~1FFF|
1555 |DY|DY|DY h|0~~1FFF|
1556 |SM|SM|SM d|8000~~9999|
1557 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1558 |D|D|D d|0~~12287|
1559 |W|W|W h|0~~1FFF|
1560 |TN|TN|TN d|0~~2047|
1561 |SN|SN|SN d|0~~2047|
1562 |CN|CN|CN d|0~~1023|
1563 |R|R|R d|0~~32767|
1564 |SW|SW|SW h|0~~7FF|
1565 |Z|Z|Z d|0~~15|
1566 |ZR|ZR|ZR h|0~~FE7FF|
1567
1568 **3)PLC Settings(GX Works2)**
1569
1570 * Click [Ethernet/CC IE/MELSECNET];
1571 * Please select [Ethernet] as network type;
1572 * Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order);
1573 * Select [Online] as Mode;
1574 * [[image:image-20221119171343-2.png||height="341" width="587"]]
1575 * Click [Operation setting] to set IP;
1576 * Select [Binary Code] as [Communication Data Code];
1577 * [[image:image-20221119171436-3.png||height="354" width="588"]]
1578 * Click [Open setting]
1579 * Set protocol: TCP;
1580 * Set [unpassive] in [Open system];
1581 * Set [receive] in [Fixed buffer];
1582 * Set [procedure Exist] in [Fixed buffer communication];
1583 * Disable [Pairing open];
1584 * Set [No confirm] in [Existence confirmation];
1585 * Host station port number: 5009;
1586 * Save settings;
1587 * [[image:image-20221119171611-4.png||height="354" width="588"]]
1588 * Download project into PLC and restart it
1589
1590 **4)Configure the communication protocol**
1591
1592 [[image:image-20221119171832-5.png||height="354" width="625"]]
1593
1594
1595 **5)Cable Wiring**
1596
1597 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png"]]
1598
1599 = Create communication with **Delta PLC** =
1600
1601 == **DVP Ethernet Protocol** ==
1602
1603 Supoort Series: DELTA DVP20/32/40/60ES200RE/200TE or any DVP models with built-in Ethernet port, DELTA DVPEN01-SL module
1604
1605 **1)V-BOX Settings**
1606
1607 |=**Items**|=**Settings**|=**Note**
1608 |Protocol|DELTA DVP MODBUS TCP|
1609 |Connection|Ethernet|
1610 |Port No.|502|
1611 |Device No.|1|
1612 |VBox Device No.|0|
1613
1614 **2)Address List **
1615
1616 |=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 217px;" %)**VBox registers**|=(% style="width: 168px;" %)**Format**|=(% style="width: 225px;" %)**Range**|=**Note**
1617 |Bit|(% style="width:191px" %)X|(% style="width:217px" %)X|(% style="width:168px" %)X OOO|(% style="width:225px" %)0~~377|
1618 |Bit|(% style="width:191px" %)Y|(% style="width:217px" %)Y|(% style="width:168px" %)Y OOO|(% style="width:225px" %)0~~377|
1619 |Bit|(% style="width:191px" %)M0|(% style="width:217px" %)M0|(% style="width:168px" %)M0DDDD|(% style="width:225px" %)0~~1535|
1620 |Bit|(% style="width:191px" %)M1|(% style="width:217px" %)M1|(% style="width:168px" %)M1DDDD|(% style="width:225px" %)1536~~4096|
1621 |Bit|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDD|(% style="width:225px" %)0~~255|
1622 |Bit|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~255|
1623 |Bit|(% style="width:191px" %)S|(% style="width:217px" %)S|(% style="width:168px" %)SDDDD|(% style="width:225px" %)0~~1023|
1624 |Word|(% style="width:191px" %)D0|(% style="width:217px" %)D0|(% style="width:168px" %)D0DDDD|(% style="width:225px" %)0~~4095|
1625 |Word|(% style="width:191px" %)D1|(% style="width:217px" %)D1|(% style="width:168px" %)D1DDDD|(% style="width:225px" %)4096~~11999|
1626 |Word|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDD|(% style="width:225px" %)0~~255|
1627 |Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~199|
1628 |Double Word|(% style="width:191px" %)HC|(% style="width:217px" %)HC|(% style="width:168px" %)HCDDD|(% style="width:225px" %)200~~255|
1629
1630 **3) PLC Setting:**
1631
1632 ~1. Create new project in Delta WPL Soft, and click Setting to open the communication settings:
1633
1634 (% style="text-align:center" %)
1635 [[image:DVPEthernetWPLSoft2.png]]
1636
1637 2. Set up the communication type and PLC IP:
1638
1639 (% style="text-align:center" %)
1640 [[image:DVPEthernetSetup.png]]
1641
1642 (% class="wikigeneratedid" %)
1643 3. Click OK and save the settings. Then click Communication on toolbar, then click Transfer Setup to open new window:
1644
1645 (% style="text-align:center" %)
1646 [[image:DVPEthernetTransfer.png]]
1647
1648 (% class="wikigeneratedid" %)
1649 4. Select Communication Mode as PC => PLC to download or select PC <=PLC to upload:
1650
1651 (% style="text-align:center" %)
1652 [[image:DVPEthernetPLCtoPC.png]]
1653
1654 5. Click Auto-Search Ethernet Module to find the PLC on the same LAN network:
1655
1656 (% style="text-align:center" %)
1657 [[image:DVPEthernetAutoSearch.png]]
1658
1659 **4) V-BOX Setting:**
1660
1661 Set the same IP address according to the setting from WPL Soft:
1662
1663 (% style="text-align:center" %)
1664 [[image:DVPEthernetVNETPortocol.png]]
1665
1666 == **DVP serial protocol** ==
1667
1668 Supoort Series: DELTA DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX
1669
1670 **1)V-BOX Settings**
1671
1672 |=**Items**|=**Settings**|=**Note**
1673 |Protocol|DELTA DVP PROTOCOL|
1674 |Connection|RS232|
1675 |Baud Rate|9600|
1676 |Stop Bit|1|
1677 |Data Bit|7|
1678 |Parity|EVEN|
1679 |Device No.|1|
1680
1681 (% class="wikigeneratedid" %)
1682 **2)Address List**
1683
1684 |=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 217px;" %)**VBox registers**|=(% style="width: 168px;" %)**Format**|=(% style="width: 225px;" %)**Range**|=**Note**
1685 |Bit|(% style="width:191px" %)X|(% style="width:217px" %)X|(% style="width:168px" %)X OOOOOO|(% style="width:225px" %)0~~303237|
1686 |Bit|(% style="width:191px" %)Y|(% style="width:217px" %)Y|(% style="width:168px" %)Y OOOOOO|(% style="width:225px" %)0~~303237|
1687 |Bit|(% style="width:191px" %)M|(% style="width:217px" %)M|(% style="width:168px" %)MDDDDD|(% style="width:225px" %)0~~99999|
1688 |Bit|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDDDD|(% style="width:225px" %)0~~99999|
1689 |Bit|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDDDD|(% style="width:225px" %)0~~99999|
1690 |Bit|(% style="width:191px" %)S|(% style="width:217px" %)S|(% style="width:168px" %)SDDDDD|(% style="width:225px" %)0~~99999|
1691 |Word|(% style="width:191px" %)D|(% style="width:217px" %)D|(% style="width:168px" %)D DDDDD|(% style="width:225px" %)0~~99999|
1692 |Word|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDDDD|(% style="width:225px" %)0~~99999|
1693 |Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~199|
1694 |Double Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDDDD|(% style="width:225px" %)200~~99999|
1695
1696 (% class="wikigeneratedid" %)
1697 **3)Wiring Diagram**
1698
1699 (% style="text-align:center" %)
1700 [[image:Delta DVP PROTOCOLSerial232.png]]
1701
1702 == **AS Ethernet Protocol** ==
1703
1704 **1)V-BOX Settings**
1705
1706 |=**Items**|=**Settings**|=**Note**
1707 |Protocol|DELTA AS300 MODBUS TCP|
1708 |Connection|Ethernet|
1709 |Port No.|502|
1710 |Device No.|1|
1711 |HMI No.|0|
1712
1713 **2)Address List**
1714
1715 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1716 |Bit|X|X|X d|0~~63|
1717 |Bit|Y|Y|Y d|0~~63|
1718 |Bit|D|D|D d|0~~29999|
1719 |Bit|M|M|M d|0~~8191|
1720 |Bit|SM|SM|SM d|0~~4095|
1721 |Bit|S|S|S h|0~~2047|
1722 |Bit|T|T|T d|0~~511|
1723 |Bit|C|C|C d|0~~511|
1724 |Bit|HC|HC|HC d|0~~255|
1725 |Word|X|X|X h|0~~63|
1726 |Word|Y|Y|Y d|0~~63|
1727 |Word|SR|SR|SR d|0~~2047|
1728 |Word|D|D|D d|0~~29999|
1729 |Word|T|T|T d|0~~511|
1730 |Word|C|C|C h|0~~511|
1731 |Word|E|E|E d|0~~9|
1732
1733 **3)Configure the communication protocol**
1734
1735 [[image:image-20220831160010-4.png]]
1736
1737 **4)Cable Wiring**
1738
1739 Figure
1740
1741 [[image:image-20220831155101-1.png]][[image:image-20220831160055-5.png]]
1742
1743 Pin Definition Diagram
1744
1745 [[image:image-20220831155157-3.png]]
1746
1747 = Create communication with **Omron PLC** =
1748
1749 == **CP1 Series Protocol ** ==
1750
1751 [[下载链接>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CP1%20Series.zip]]
1752
1753 == **CP2M Series Protocol** ==
1754
1755 [[下载链接>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CJ2M.zip]]
1756
1757
1758 == **EC55 Series Protocol** ==
1759
1760 Supported device: EC55 temperature instrument
1761
1762 **1)V-BOX Settings**
1763
1764 |**Items**|**Settings**|**Note**
1765 |Protocol|Omron EC55|
1766 |Connection|RS485 (9600, 2, 7, EVEN)|
1767 |Port No.|None|
1768 |PLC station No.|0|
1769
1770 **2)Address List**
1771
1772 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
1773 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
1774 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
1775 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
1776 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
1777 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
1778 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
1779 |CP|-|0-6|Read controller intrinsic property
1780 |CS|-|0-2|Read controller states
1781 |CA|-|0-17|Action command
1782
1783 **3)Device Settings**
1784
1785 Omron E5CC PLC configuration
1786
1787 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
1788
1789 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_3d95e093792ba98a.png?width=550&height=229&rev=1.1||alt="12.PLC Protocol_html_3d95e093792ba98a.png" height="229" width="550"]]
1790
1791 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
1792
1793 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_be583aa69dd6cf4c.png?width=550&height=242&rev=1.1||alt="12.PLC Protocol_html_be583aa69dd6cf4c.png" height="242" width="550"]]
1794
1795 **✎Note:** The communication settings for HMI should be consistent with this setting.
1796
1797 **4)Configure the communication protocol**
1798
1799 [[image:image-20220831161041-1.png]]
1800
1801 **5)Cable Wiring**
1802
1803 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5e9a81a14106da9e.png?width=392&height=223&rev=1.1||alt="12.PLC Protocol_html_5e9a81a14106da9e.png" height="223" width="392"]]
1804
1805 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_1897d92be6948d58.png?width=393&height=223&rev=1.1||alt="12.PLC Protocol_html_1897d92be6948d58.png" height="223" width="393"]]
1806
1807 **✎Note:**
1808
1809 * COM3 only available in PI8000/PI9000 series.
1810 * CA address could not support continuous writing function;
1811 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
1812 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
1813 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
1814 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
1815 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
1816 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
1817 * [[image:image-20220831161356-1.png]]Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
1818
1819 = Create communication with Xinje** PLC** =
1820
1821 == **XC serial protocol** ==
1822
1823 **1)V-BOX Settings**
1824
1825 |**Item**|**Settings**|**Note**
1826 |Protocol|XINJE XC MODBUS|
1827 |Connection|RS232|
1828 |Baud rate|19200|
1829 |Data bit|8|
1830 |Parity|EVEN|
1831 |Stop bit|1|
1832 |PLC station No.|1|
1833
1834 **2)Address List**
1835
1836 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1837 |Bit|M|M|M d|0~~8511|
1838 |Bit|X|X|X o|0~~1747|
1839 |Bit|Y|Y|Y o|0~~1747|
1840 |Bit|S|S|S d|0~~1023|
1841 |Bit|T|T|T d|0~~4095|
1842 |Bit|C|C|C d|0~~634|
1843 |Word|D|D|D d|0~~8511|
1844 |Word|TD|TD|TD d|0~~618|
1845 |Word|CD|CD|CD d|0~~634|
1846 |Word|FD|FD|FD d|0~~8511|
1847
1848 **3)Configure the communication protocol**
1849
1850
1851 [[image:image-20220831163041-1.png]]
1852
1853 **4)Cable Wiring**
1854
1855 Figure
1856
1857 [[image:image-20220831163406-2.png]][[image:image-20220831163422-3.png]]
1858
1859 Pin Definition Diagram
1860
1861 [[image:image-20220831163441-4.png]]
1862
1863 == **XD serial protocol** ==
1864
1865 **1)V-BOX Settings**
1866
1867 Supported Series: Xinjie XD/XE Series PLC
1868
1869 |**Item**|**Settings**|**Note**
1870 |Protocol|XINJE XD/XC MODBUS|
1871 |Connection|RS232|
1872 |Baud rate|19200|
1873 |Data bit|8|
1874 |Parity|EVEN|
1875 |Stop bit|1|
1876 |PLC station No.|1|
1877
1878 **2)Address List**
1879
1880 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1881 |Bit|M|M|M d|0~~74999|
1882 |Bit|X1xx|X1xx|X1xx o|0~~1177|
1883 |Bit|X2xx|X2xx|X2xx o|0~~277|
1884 |Bit|X|X|X o|0~~77|
1885 |Bit|Y1xx|Y1xx|Y1xx o|0~~1177|
1886 |Bit|Y2xx|Y2xx|Y2xx o|0~~277|
1887 |Bit|Y|Y|Y o|0~~4095|
1888 |Bit|SM|SM|SM d|0~~4999|(((
1889
1890 )))
1891 |Bit|T|T|T d|0~~4999|
1892 |Bit|C|C|C d|0~~4999|
1893 |Bit|ET|ET|ET d|0~~31|
1894 |Bit|SE|SE|SE d|0~~31|
1895 |Bit|HM|HM|HM d|0~~11999|
1896 |Bit|HSC|HSC|HSC d|0~~39|
1897 |Bit|HS|HS|HS d|0~~999|
1898 |Bit|HT|HT|HT d|0~~1999|
1899 |Bit|HC|HC|HC d|0~~1999|
1900 |Bit|S|S|S d|0~~7999|
1901 |Word|D|D|D d|0~~69999|
1902 |Word|ID|ID|ID d|0~~99|
1903 |Word|ID1xx|ID1xx|ID1xx d|0~~999|
1904 |Word|ID2xx|ID2xx|ID2xx d|0~~299|
1905 |Word|QD|QD|QD d|0~~99|
1906 |Word|QD1xx|QD1xx|QD1xx d|0~~999|
1907 |Word|QD2xx|QD2xx|QD2xx d|0~~299|
1908 |Word|SD|SD|SD d|0~~4999|
1909 |Word|TD|TD|TD d|0~~575|
1910 |Word|CD|CD|CD d|0~~575|
1911 |Word|ETD|ETD|ETD d|0~~31|
1912 |Word|HD|HD|HD d|0~~24999|
1913 |Word|HSD|HSD|HSD d|0~~1023|
1914 |Word|HTD|HTD|HTD d|0~~95|
1915 |Word|HCD|HCD|HCD d|0~~95|
1916 |Word|HSCD|HSCD|HSCD d|0~~31|
1917 |Word|FD|FD|FD d|0~~8191|
1918 |Word|SFD|SFD|SFD d|0~~5999|
1919 |Word|FS|FS|FS d|0~~47|
1920
1921 **3)Configure the communication protocol**
1922
1923 [[image:image-20220831163923-7.png]]
1924
1925
1926
1927 **4)Cable Wiring**
1928
1929 Figure
1930
1931 [[image:image-20220831163406-2.png]][[image:image-20220831163553-6.png]]
1932
1933 Pin Definition Diagram
1934
1935 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830160232-3.png?rev=1.1||alt="image-20220830160232-3.png"]]
1936
1937 = Create communication with **Schneider PLC** =
1938
1939 == **Schneider MODBUS RTU** ==
1940
1941 **1)V-BOX Setting**
1942
1943 |=**Parameters**|=**Recommended**|=**Notes**
1944 |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
1945 |**Connection**|RS485|
1946 |**Baud rate**|19200|
1947 |**Data bit**|8|
1948 |**Parity**|Even|
1949 |**Stop bit**|1|
1950 |**PLC station No.**|1|
1951
1952 **2)Address List**
1953
1954 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
1955 |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
1956 |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
1957 |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
1958 |W|MW|DDDDDD|0 ~~ 999999|Output register
1959 |DW|MD|DDDDDD|0 ~~ 999999|Output register
1960
1961 **3)Configure the communication protocol**
1962
1963 [[image:image-20220902104329-1.png]]
1964
1965 **4)Cable Wiring**
1966
1967 **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
1968
1969 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220817154212-1.jpeg?width=554&height=315&rev=1.1||alt="image-20220817154212-1.jpeg" height="315" width="554"]]
1970
1971 = Create communication with Inovance** PLC** =
1972
1973 == **H3U serial protocol** ==
1974
1975 **1)V-BOX Settings**
1976
1977 |**Item**|**Settings**|**Note**
1978 |Protocol|INOVANCE H3U PLC|
1979 |Connection|RS422|
1980 |Baud rate|9600|
1981 |Data bit|7|
1982 |Parity|EVEN|
1983 |Stop bit|1|
1984 |PLC station No.|0|
1985
1986 **2)Address List**
1987
1988 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1989 |Bit|X|X|X o|0~~303237|
1990 |Bit|Y|Y|Y o|0~~303237|
1991 |Bit|M|M|M d|0~~99999|
1992 |Bit|T|T|T d|0~~99999|
1993 |Bit|C|C|C d|0~~99999|
1994 |Bit|SM|SM|SM d|8000~~999|
1995 |Bit|S|T|S d|0~~99999|
1996 |Bit|Lamp|Lamp|Lamp d|0~~0|
1997 |Word|X|X|X o|0~~303237|
1998 |Word|Y|Y|Y o|0~~303237|
1999 |Word|M|M|M d|0~~99999|
2000 |Word|T|T|T d|0~~99999|
2001 |Word|C|C|C d|0~~199|
2002 |Word|D|D|D d|0~~7999|
2003 |Word|S|S|S d|0~~99999|
2004 |Word|SD|SD|SD d|8000~~9999|
2005 |Word|R|R|R d|0~~32767|
2006
2007 **3)Configure the communication protocol**
2008
2009 [[image:image-20220831164626-1.png]]
2010
2011
2012
2013 **4)Cable Wiring**
2014
2015 Figure
2016
2017 [[image:image-20220831164646-2.png]][[image:image-20220831164700-3.png]]
2018
2019 Pin Definition Diagram
2020
2021 [[image:image-20220831164731-4.png]]
2022
2023 = Create communication with Panasonic** PLC** =
2024
2025 == **FP serial protocol** ==
2026
2027 **1)V-BOX Settings**
2028
2029 |**Item**|**Settings**|**Note**
2030 |Protocol|Panasonic FP MFWTOCOL|
2031 |Connection|RS232|
2032 |Baud rate|9600|
2033 |Data bit|8|
2034 |Parity|ODD|
2035 |Stop bit|1|
2036 |PLC station No.|1|
2037
2038 **2)Address List**
2039
2040 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
2041 |Bit|X|X|X d|0~~9999|
2042 |Bit|Y|Y|Y d|0~~9999|
2043 |Bit|R|R|R d|0~~9999|
2044 |Bit|T|T|T d|0~~9999|
2045 |Bit|C|C|C d|0~~9999|
2046 |Bit|L|L|L d|0~~9999|
2047 |Word|WX|WX|WX d|0~~9999|
2048 |Word|WY|WY|WY d|0~~9999|
2049 |Word|WR|WR|WR d|0~~9999|
2050 |Word|WL|WL|WL d|0~~9999|
2051 |Word|LD|LD|LD d|0~~9999|
2052 |Word|DT|DT|DT d|0~~65535|
2053 |Word|FL|FL|FL d|0~~9999|
2054 |Word|EV|EV|EV d|0~~9999|
2055 |Word|SV|SV|SV d|0~~9999|
2056
2057 **3)Configure the communication protocol**
2058
2059 [[image:image-20220831165238-4.png]]
2060
2061
2062
2063 **4)Cable Wiring**
2064
2065 Figure
2066
2067 [[image:image-20220831165031-3.png]][[image:image-20220831165017-2.png]]
2068
2069 Pin Definition Diagram
2070
2071 [[image:image-20220831165008-1.png]]
2072
2073 = Create communication with LS** PLC** =
2074
2075 == **XBC serial protocol** ==
2076
2077 **1)V-BOX Settings**
2078
2079 |**Item**|**Settings**|**Note**
2080 |Protocol|LS XBC CNet|
2081 |Connection|RS232|
2082 |Baud rate|115200|
2083 |Data bit|8|
2084 |Parity|NONE|
2085 |Stop bit|1|
2086 |PLC station No.|1|
2087
2088 **2)Address List**
2089
2090 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
2091 |Bit|P|P|P d|0~~2047|
2092 |Bit|M|M|M d|0~~2047|
2093 |Bit|L|L|L d|0~~11263|
2094 |Bit|K|K|K d|0~~16183|
2095 |Bit|F|F|F d|0~~2047|
2096 |Bit|D|D|D d|0~~32767|
2097 |Bit|R|R|R d|0~~32767|
2098 |Bit|U|U|U d|0~~4095|
2099 |Word|P|P|P d|0~~2047|
2100 |Word|M|M|M d|0~~2047|
2101 |Word|L|L|L d|0~~11263|
2102 |Word|K|K|K d|0~~16183|
2103 |Word|F|F|F d|0~~2047|
2104 |Word|C|C|C d|0~~2047|
2105 |Word|T|T|T d|0~~2047|
2106 |Word|D|D|D d|0~~32767|
2107 |Word|N|N|N d|0~~21503|
2108 |Word|R|R|R d|0~~32767|
2109 |Word|U|U|U d|0~~4095|
2110 |Word|Z|Z|Z d|0~~127|
2111 |Word|S|S|S d|0~~127|
2112
2113 **3)Configure the communication protocol**
2114
2115 [[image:image-20220831170147-1.png]]
2116
2117 **4)Cable Wiring**
2118
2119 Figure
2120
2121 [[image:image-20220831170306-4.png]][[image:image-20220831170254-3.png]]
2122
2123 Pin Definition Diagram
2124
2125 [[image:image-20220831170215-2.png]]
2126
2127 == **XGK FEnet Ethernet protocol** ==
2128
2129 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
2130
2131 **1)V-BOX Settings**
2132
2133 |**Items**|**Settings**|**Note**
2134 |Protocol|LG XGK FEnet(Ethernet)|
2135 |Connection|Ethernet|
2136 |Port No.|2004|
2137
2138 **2)Address List**
2139
2140 |**Type**|**Register**|**Range**|**Format**|**Note**
2141 |(% rowspan="14" %)Word|P|0~~2047|P d|
2142 |M|0~~2047|M d|
2143 |K|0~~2047|K d|
2144 |F|0~~2047|F d|
2145 |T|0~~2047|T d|
2146 |C|0~~2047|C d|
2147 |Z|0~~127|Z d|
2148 |S|0~~127|S d|
2149 |L|0~~11263|L d|
2150 |N|0~~21503|N d|
2151 |D|0~~32767|D d|
2152 |R|0~~32767|R d|
2153 |ZR|0~~65535|ZR d|
2154 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
2155
2156 **✎Note:**
2157
2158 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
2159 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
2160 * All bit registers are in the form of bits in word, and the range is the same as the word register;
2161
2162 **3)Communication Settings**
2163
2164 [[image:image-20220831171127-1.png]]
2165
2166 **4)Cable Wiring**
2167
2168 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2169
2170 = Create communication with **Modbus ** =
2171
2172 == **MODBUS RTU Slave (All function)** ==
2173
2174 Select the protocol "Modbus RTU Slave (All Fuction)",
2175
2176 Then set baud rate, port, stop bits, data bits, parity.
2177
2178 (% style="text-align:center" %)
2179 [[image:1624342015914-382.png||height="486" width="800" class="img-thumbnail"]]
2180
2181 == **Communicate with Modbus Meter** ==
2182
2183 The following example is using the Linfee meter LNF96EY to demonstrate how to set up the Modbus communication.
2184
2185 ~1. Wiring the RS485 cable first. Because the pin 58 is A, the pin 59 is B for meter. Here we use the COM1 to connect. So the diagram like follows:
2186
2187 (% style="text-align:center" %)
2188 [[image:LinfeeTerminalDiagram.png]]
2189
2190 2. Check the specific Modbus parameter in the communication menu from LED display.
2191
2192 So from the following pictures, we can know the Meter Address is 85, Baud rate is 9600, CRC None.
2193
2194 {{info}}
2195 **✎Note: **Meter address usually corresponding to the Modbus Slave Station No. on the Modbus communication.
2196 {{/info}}
2197
2198 (% style="text-align:center" %)
2199 [[image:MeterModbusAllView.png]]
2200
2201 (% class="wikigeneratedid" %)
2202 3. Set up the communication in the Configuration tab.
2203
2204 (% class="wikigeneratedid" %)
2205 Select the protocol as **ModBus RTU Slave (All Function)**. And set the communication parameters like below.
2206
2207 (% style="text-align:center" %)
2208 [[image:VNETCommunicationtabmeter.png]]
2209
2210 (% class="wikigeneratedid" %)
2211 4. Create new real-time monitoring tag accroding to Modbus manual
2212
2213 (% class="wikigeneratedid" %)
2214 Enter the address we want to read from the meter. The following table is intercept part of the manual for Linfee Modbus manual.
2215
2216 (% class="wikigeneratedid" %)
2217 **0x03/0x04 command data register address**:
2218
2219 (% style="width:1142.22px" %)
2220 |(% style="display:none" %) |=(% colspan="2" rowspan="1" style="width: 165px;" %)Address(% style="display:none" %) |=Description|=Data Format|=(% style="width: 254px;" %)Data Length(Word)|=(% style="width: 282px;" %)Remark
2221 |(%%)(% style="display:none" %) (%%) HEX|(% style="width:107px" %)DEC|(%%)(% style="display:none" %) (%%) |(% style="width:100px" %) |(%%)(% style="display:none" %) (%%) |(% style="width:318px" %)
2222 |(% style="width:107px" %)0x00|(% style="width:100px" %)0|Reserved| | |(% style="width:318px" %)
2223 |(% style="width:107px" %)0x02|(% style="width:100px" %)2|Reserved| | |(% style="width:318px" %)
2224 |(% style="width:107px" %)0x04|(% style="width:100px" %)4|Reserved| | |(% style="width:318px" %)
2225 |(% style="width:107px" %)0x06|(% style="width:100px" %)6|Ua|float|2|(% style="width:318px" %)Phase Voltage data, Unit V
2226 |(% style="width:107px" %)0x08|(% style="width:100px" %)8|Ub|float|2|(% style="width:318px" %)Phase Voltage data, Unit V
2227 |(% style="width:107px" %)0x0A|(% style="width:100px" %)10|Uc|float|2|(% style="width:318px" %)Phase Voltage data, Unit V
2228 |(% style="width:107px" %)0x0C|(% style="width:100px" %)12|Uab|float|2|(% style="width:318px" %)Line Voltage data, Unit V
2229 |(% style="width:107px" %)0x0E|(% style="width:100px" %)14|Ubc|float|2|(% style="width:318px" %)Line Voltage data, Unit V
2230 |(% style="width:107px" %)0x10|(% style="width:100px" %)16|Uca|float|2|(% style="width:318px" %)Line Voltage data, Unit V
2231 |(% style="width:107px" %)0x12|(% style="width:100px" %)18|Ia|float|2|(% style="width:318px" %)Phase Current data, Unit A
2232 |(% style="width:107px" %)0x14|(% style="width:100px" %)20|Ib|float|2|(% style="width:318px" %)Phase Current data, Unit A
2233 |(% style="width:107px" %)0x16|(% style="width:100px" %)22|Ic|float|2|(% style="width:318px" %)Phase Current data, Unit A
2234
2235 {{info}}
2236 **✎Note: **We usually use the Data Type 4 for read the Modbus registers(Function Code 03)
2237 {{/info}}
2238
2239 For example, here we want to read the Phase Voltage Ua (Modbus offset 0006), the Modbus register main No. requires input decimal number, and check whether the actual address has one address offset, so the tag configured like the following screenshot:
2240
2241 (% style="text-align:center" %)
2242 [[image:VNETModbusTagSettings.png]]
2243
2244 (% style="text-align:center" %)
2245 [[image:VNETModbusTagByteSettings.png]]
2246
2247 {{info}}
2248 **✎Note: **If the read value is incorrect, please check whether need to change the Byte order.
2249 {{/info}}
2250
2251 Set the Modbus Slave Station No.
2252
2253 (% style="text-align:center" %)
2254 [[image:ModbusStationSettings.png]]
2255
2256 If the communication is setup successfully, the tag will show green light.
2257
2258 (% style="text-align:center" %)
2259 [[image:Monitoringtaggreenlight.png]]
2260
2261 == **MODBUS RTU Master** ==
2262
2263 Select the protocol "Modbus RTU Master",
2264
2265 Then set baud rate, port, stop bits, data bits, parity
2266
2267 (% style="text-align:center" %)
2268 [[image:1624348709622-711.png||queryString="width=809&height=493" height="488" width="800" class="img-thumbnail"]]
2269
2270 **address list**
2271
2272 (% class="table-bordered" %)
2273 |=(% scope="row" %)**Type**|=**Data Type**|=**Function code and description**
2274 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (Read Input Registers: Read the current binary value in one or more input registers)
2275 |06 (write single register: write a binary value to a holding register)
2276 |10 (write values to multiple addresses )
2277 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
2278 |06 (write single register: write a binary value to a holding register)
2279 |10 (write values to multiple addresses )
2280 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
2281 |06 (write single register: write a binary value to a holding register)
2282 |10 (write values to multiple addresses )
2283 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
2284 |10 (write values to multiple addresses )
2285 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
2286 |05 (Force a single coil to force the on/off state of a logic coil)
2287 |0F (Write multiple bits, ie write continuously)
2288 |(% rowspan="3" %)1|02 (Read the input state)
2289 |05 (Force a single coil to force the on/off state of a logic coil)
2290 |0F (Write multiple bits)
2291 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
2292 |05 (Force a single coil to force the on/off state of a logic coil)
2293 |0F (Write multiple bits)
2294 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
2295 |0F (Write multiple bits)
2296
2297 == **MODBUS TCP Slave (All function)** ==
2298
2299 Supported series: MODBUS TCP controller
2300
2301 V-B0X works as MODBUS TCP MASTER connecting with TCP SLAVE
2302
2303 **1)V-BOX Setting**
2304
2305 |**Items**|**Settings**|**Note**
2306 |Protocol|MODBUS TCP Slave (All function)|
2307 |Connection|Ethernet|
2308 |Port No.|502|
2309 |PLC station No.|1
2310
2311 **2)Address List**
2312
2313 |=**Type**|=**Data Type**|=**Function code & Description**
2314 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
2315 |06 (write single register: write a binary value to a holding register)
2316 |10 (write values to multiple addresses )
2317 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
2318 |06 (write single register: write a binary value to a holding register)
2319 |10 (write values to multiple addresses )
2320 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
2321 |06 (write single register: write a binary value to a holding register)
2322 |10 (write values to multiple addresses )
2323 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
2324 |10 (write values to multiple addresses )
2325 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
2326 |05 (Force a single coil to force the on/off state of a logic coil)
2327 |0F (Write multiple bits, ie write continuously)
2328 |(% rowspan="3" %)1|02 (Read the input state)
2329 |05 (Force a single coil to force the on/off state of a logic coil)
2330 |0F (Write multiple bits)
2331 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
2332 |05 (Force a single coil to force the on/off state of a logic coil)
2333 |0F (Write multiple bits)
2334 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
2335 |0F (Write multiple bits)
2336
2337 **3)Communication Settings**
2338
2339 Configure V-BOX Ethernet IP in Networking Settings
2340
2341 [[image:image-20220902111833-3.png]]
2342
2343
2344 Configure PLC Ethernet IP in Communication;
2345
2346 [[image:image-20220902111121-1.png]]
2347
2348 **4)Cable Wiring**
2349
2350 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2351
2352 == **communicate with VB inverter** ==
2353
2354 [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20VB%20inverter.zip]]
2355
2356 = **User define protocol** =
2357
2358 More serial port script instruction,please refer manual:[[Lua script function>>doc:V-BOX.V-Net.Manual.04 Lua Script.01 Lua Functions.WebHome]]~-~-->[[3.Serial port operation>>url:http://docs.we-con.com.cn/wiki/vbox/view/HMI/04.Lua%20script%20%20function%20and%20operation/01.Lua%20script%20function/#H3.Serialportoperation]]
2359
2360 == **Read the temperature sensor.** ==
2361
2362 the commond format is as beliow:
2363
2364 Send commond:01 03 02 00 00 03 04 73
2365
2366 Feedback commond:01 03 06 07 F7 0E 7E B7 35
2367
2368 Temperature data:07 F7,desimal = 2039,it means temperature is 20.39℃.
2369
2370 Humidity data:0E 7E,desimal = 3710, it mean humidity is 37.10%RH.
2371
2372 Script Demo:
2373
2374 ~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~--
2375
2376 function com.main()
2377 ~-~-dosomething
2378 openPlc()
2379 end
2380 function openPlc()
2381 if obj then
2382 ~-~- If the serial port opened,then read/write data by timing
2383
2384 local wri = string.pack(">HHHH",0X0103,0X0200,0X0003,0X0473)
2385 local arr = reading(wri)
2386 ~-~- if arr ~~=nil then
2387 ~-~- if arr[1] ==33 and arr[2] ==v[2][2] and arr[3] ==v[2][3] then
2388 ~-~- local A = arr[4]*256
2389 ~-~- local B = A+arr[5]
2390 ~-~- addr_setword(v[1],B)
2391 ~-~- end
2392 ~-~- end
2393
2394 else
2395 ~-~-judge if there is a serial object, then initialize and open the serial port
2396 local configs = {
2397 name = 'COM1', ~-~-Select serial port COM1
2398 mode = 485, ~-~-Communication mode RS485
2399 baud_rate = 9600, ~-~-Baud rate 9600
2400 stop_bit = 1, ~-~-stop bit 1
2401 data_len = 8, ~-~-data length 8
2402 check_bit = 'NONE', ~-~-no parity
2403
2404 }
2405 obj,err = serial.open(configs) ~-~-Open serial port
2406 if not obj then
2407 print("serial open :failed", err) ~-~- Open serial port failed
2408 end
2409 end
2410 end
2411
2412 function reading(wri)
2413 obj:flush() ~-~- Clear serial port
2414 obj:write(wri) ~-~- Write serial port
2415 print(string.byte(wri,1,#wri))
2416 obj:flush() ~-~- Clear serial port 
2417 local readed =obj:read(9,1000) ~-~- Read 9 bytes, timeout 1 second
2418 if readed and readed ~~= "" then 
2419 ~-~- judge that a non-empty string is read
2420 print(string.byte(readed,1,#readed))
2421 a={string.byte(readed, 1, #readed)}
2422 if nil ~~= a[4] and nil ~~= a[5] and nil ~~= a[6] and nil ~~= a[7] then
2423 a1=a[4]*256+a[5]
2424 a2=a[6]*256+a[7]
2425 addr_setword("@HDW0",a1)
2426 addr_setword("@HDW1",a2)
2427 end
2428 return {string.byte(readed, 1, #readed)}
2429 elseif readed == nil then
2430 print("serial read err:", err or "")
2431 return nil
2432 end
2433 return nil
2434 end
2435
2436 ~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-