Wiki source code of 1 Communication

Version 252.1 by Theodore Xu on 2023/07/10 12:00

Show last authors
1 = Create communication with WECON PLC =
2
3 == **LX3V Serial Protocol** ==
4
5 Supported series: Wecon LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
6
7 **1)V-BOX setting**
8
9 |**Item**|**Settings**|**Note**
10 |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
11 |Connection|RS422/RS485|
12 |Baud rate|9600|
13 |Data bit|7|
14 |Parity|EVEN|
15 |Stop bit|1|
16 |PLC station No.|1|
17
18 **2)Address List**
19
20
21 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
22 |(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
23 |Y|Y|Y o|0~~303237|
24 |M|M|M d|0~~99999|
25 |T|T|T d|0~~99999|
26 |C|C|C d|0~~99999|
27 |S|S|S d|0~~99999|
28 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
29 |Y|Y|Y o|0~~303237|
30 |M|M|M d|0~~99999|
31 |T|T|T d|0~~99999|
32 |C|C|C d|0~~199|
33 |D|D|D d|0~~7999|
34 |S|S|S d|0~~99999|
35 |SD|SD|SD d|8000~~9999|
36
37 **3)Configure the communication protocol**
38
39 [[image:image-20220824152217-1.png||alt="图片-20220824152217-1.png"]]
40
41 **4)Cable Wiring**
42
43 * **RS422**
44
45 [[image:image-20220824120614-5.png]]
46
47 * **RS485**
48
49 [[image:image-20220824120524-3.png]]
50
51 == **LX5V Serial Protocol** ==
52
53 This example introduces the establishment of serial port communication between V-BOX and LX5V. It is introduced through three parts: PLC software configuration, V-BOX software configuration, and hardware wiring.
54
55 **Software configuration of PLC**
56
57 **1)PLC programming software**
58
59 [[image:image-20220824142722-1.png]]
60
61 **2)New PLC project**
62
63 Click New Project and select the PLC model.
64
65 [[image:image-20220822172623-2.png]]
66
67 **3)Set Serial port parameters**
68
69 Follow the steps below to configure Serial port parameters
70
71 Baud rate:115200
72
73 Data bit:8
74
75 Stop bit:1
76
77 Parity:No verification
78
79 [[image:image-20220822172657-3.png]]
80
81 **4)Registers list**
82
83 [[image:image-20220822172730-4.png]]
84
85 **V-BOX software configuration**
86
87 **1)V-BOX programming software**
88
89 [[image:image-20220824104124-1.png]]
90
91 **2)V-NET add device**
92
93 Open V-NET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the access key, password and remark, to add the device.
94
95 [[image:image-20220824104909-2.png]]
96
97 **3)Set communication port parameters**
98
99 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
100
101 Baud rate:115200
102
103 Data bit:8
104
105 Stop bit:1
106
107 Parity:No verification
108
109 [[image:image-20220824142130-1.png]]
110
111 **hardware connection**
112
113 **1)Hardware wiring diagram**
114
115 [[image:image-20220824142546-2.png]]
116
117 [[image:image-20220824142643-3.png]]
118
119 The above are all the steps for establishing serial port communication between V-BOX with LX5V PLC.
120
121 == **LX5V-N Ethernet protocol** ==
122
123 This example introduces the establishment of Ethernet communication between V-BOX and LX5V-N. It is introduced through three parts: PLC software configuration, V-BOX software configuration, and hardware wiring.
124
125 **Software configuration of PLC**
126
127 **1)PLC programming software**
128
129 [[image:image-20220824142722-1.png]]
130
131 **2)New PLC project**
132
133 Click New Project and select the PLC model.
134
135 [[image:image-20220824143613-1.png]]
136
137 **3)Set Ethernet port parameters**
138
139 Follow the steps below to configure Ethernet parameters
140
141 PLC IP address:192.168.39.200
142
143 default gateway:192.168.39.1
144
145 subnet mask:255.255.255.0
146
147 [[image:image-20220824143744-2.png]]
148
149 **4)Registers list**
150
151 [[image:image-20220822172730-4.png]]
152
153 (% id="cke_bm_22473S" style="display:none" %)** **(%%)**V-BOX software configuration**
154
155 **1)V-BOX programming software**
156
157 [[image:image-20220824104124-1.png]]
158
159 **2)V-NET add device**
160
161 Open V-NET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the access key, password and remark, to add the device.
162
163 [[image:image-20220824104909-2.png]]
164
165 **3)Set communication Protocol**
166
167 Click Communication to configure the LX5V plc protocol and IP address.
168
169 [[image:image-20220824144619-1.png]]
170
171 **hardware connection**
172
173 **1)Hardware wiring diagram**
174
175 [[image:image-20220824151127-2.png]]
176
177 The above are all the steps for establishing ethernet communication between V-BOX with LX5V PLC.
178
179 = Create communication with Allen-Bradley(**Rockwell**)** PLC** =
180
181 == **DF1 Advanced Protocol** ==
182
183 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
184
185 **1) V-Box Settings**
186
187 |=Item|=Recommended |=Note
188 |=Protocol|Allen Bradley DF1 Advanced|
189 |=Connection|RS232|
190 |=Baud rate|19200|
191 |=Stop bits|1|
192 |=Data bits|8|
193 |=Parity|None|
194 |=PLC Station No.|1|
195 |=HMI Station No.|0|
196
197 **2) Address List**
198
199 |=**Type**|=**Device registers**|=**Format**|=**Range**|=Note
200 |(% colspan="1" rowspan="7" %)Bit|I1|I1ddd.dd|0.0~~255.15|Only able to communicate with file number I1
201 |O0|O0ddd.dd|0.0~~255.15|Only able to communicate with file number O0
202 |S2|S2ddd.dd|0.0~~255.15|Only able to communicate with file number S2
203 |B3|B3ddd.dd|0.0~~255.15|Only able to communicate with file number B3
204 |BN|BNddddd.dd|0.0~~99255.15|(((
205 Bit data file B0~~B99
206
207 First two digits is for file number
208
209 For example, BN13001.00 represents file number B13, address 001, the 0th bit.
210 )))
211 |N7|N7ddd.dd|0.0~~255.15|Only able to communicate with file number N7
212 |NN|NNddddd.dd|0.0~~99255.15|(((
213 Integer data file bit format N0~~N99
214
215 First two digits is for file number
216
217 For example, NN13001.00 represents file number N13, address 001, the 0th bit.
218 )))
219 |(% rowspan="11" %)Word|S2|S2ddd|0~~255|Only able to communicate with file number S2
220 |T4S|T4Sddd|0~~255|Only able to communicate with file number T4 (Timer Preset Value)
221 |T4P|T4Pddd|0~~255|Only able to communicate with file number T4 (Timer Accumulator Value)
222 |TNS|TNSddddd|0~~99255|(((
223 Timer Preset Value
224
225 First two digits is for file number
226
227 For example, TNS99255 represents file number T99, address 255.
228 )))
229 |TNP|TNPddddd|0~~99255|(((
230 Timer Accumulator Value
231
232 First two digits is for file number
233
234 For example, TNP99255 represents file number T99, address 255.
235 )))
236 |C5S|C5Sddd|0~~255|Only able to communicate with file number C5 (Counter Preset Value)
237 |C5P|C5Pddd|0~~255|Only able to communicate with file number C5 (Counter Accumulator Value)
238 |CNS|CNSddddd|0~~99255|(((
239 Counter Preset Value
240
241 First two digits is for file number
242
243 For example, CNS99255 represents file number C99, address 255.
244 )))
245 |CNP|CNPddddd|0~~99255|(((
246 Counter Accumulator Value
247
248 First two digits is for file number
249
250 For example, CNP99255 represents file number C99, address 255.
251 )))
252 |N7|N7ddd|0~~255|Only able to communicate with file number N7
253 |NN|NNddd|0~~99255|(((
254 Integer data file
255
256 First two digits is for file number
257
258 For example, NN99255 represents file number N99, address 255.
259 )))
260 |(% colspan="1" rowspan="3" %)Double Word|F8|F8ddd|0~~255|(((
261 Only able to communicate with file number N7
262 )))
263 |FN|FNddddd|0~~99255|(((
264 Floating point data file
265
266 First two digits is for file number
267
268 For example, FN99255 represents file number F99, address 255.
269 )))
270 |LN|LNddddd|0~~99255|Long
271
272 **3) Cable Wiring**
273
274 (% style="text-align:center" %)
275 [[image:ABRS232.gif]]
276
277 (% class="wikigeneratedid" id="HMicroLogixA0Protocol" %)
278 (% id="cke_bm_5621S" style="display:none" %)** **
279
280 == **MicroLogix Protocol** ==
281
282 (% class="wikigeneratedid" %)
283 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
284
285 **1)V-BOX setting**
286
287 |**Item**|**Settings**|**Note**
288 |Protocol|Allen-Bradley DF1 Advanced|
289 |Connection|RS232|
290 |Baud rate|19200|
291 |Data bit|8|
292 |Parity|None|
293 |Stop bit|1|
294 |PLC station No.|1|
295
296 **2)Address List**
297
298 |**Type**|**Device registers**|**Format**|**Range**|**Note**
299 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
300 |O|O d.d|0.0~~255.15|
301 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
302 |S|S d.d|0.0~~255.15|
303 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
304 |(% rowspan="9" %)Word|S|S d|0~~255|
305 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
306 |TP|TP nnhh|0~~ffff
307 |CS|CS nnhh|0~~ffff
308 |CP|CP nnhh|0~~ffff
309 |N|N nnhh|0~~ffff
310 |C|C nnhh|0~~ffff
311 |T|T nnhh|0~~ffff
312 |R|R nnhh|0~~ffff
313
314 **3)Configure the communication protocol**[[image:image-20220824152928-1.png]]
315
316 **4)Configure the communication protocol**
317
318 [[image:image-20220824110724-1.png]]
319
320 == **Micro850_FreeTag Protocol** ==
321
322 (((
323 (((
324 This example introduces the establishment of Ethernet communication between Wecon V-box and CompactLogix L1769. It is introduced through three parts: PLC software configuration, V-box software configuration, and hardware wiring.
325 )))
326 )))
327
328 (((
329 (% class="wikigeneratedid" id="HSoftwareconfigurationofPLC" %)
330 (((
331 **Software configuration of PLC**
332 )))
333
334 (% class="wikigeneratedid" id="HPLCprogrammingsoftware" %)
335 (((
336 **1)PLC programming software**
337 )))
338
339 [[image:image-20220714162600-1.png]]
340
341 (% class="wikigeneratedid" id="HNewPLCproject" %)
342 (((
343 **2)New PLC project**
344 )))
345
346 (((
347 (((
348 Click New Project and select the PLC model.
349 )))
350 )))
351
352 (((
353 [[image:image-20220714162617-2.png]]
354 )))
355
356 (((
357
358
359 [[image:image-20220714162652-4.png]]
360 )))
361
362 (((
363 (% class="wikigeneratedid" id="HSetEthernetparameters" %)
364 (((
365 **3)Set Ethernet parameters**
366 )))
367
368 (((
369 (((
370 (((
371 Follow the steps below to configure Ethernet parameters
372 )))
373 )))
374 )))
375
376 (((
377 (((
378 (((
379 PLC IP address:192.168.40.101
380 )))
381 )))
382 )))
383
384 (((
385 (((
386 (((
387 default gateway:192.168.40.1
388 )))
389 )))
390 )))
391
392 (((
393 (((
394 (((
395 subnet mask:255.255.255.0
396 )))
397 )))
398 )))
399
400 (((
401 [[image:image-20220714162713-5.png]]
402 )))
403
404 (((
405
406 )))
407
408 (((
409 (% class="wikigeneratedid" id="HV-boxsoftwareconfiguration" %)
410 (((
411 **V-box software configuration**
412 )))
413
414 (% class="wikigeneratedid" id="HV-boxprogrammingsoftware" %)
415 (((
416 **1)V-box programming software**
417 )))
418
419 (% class="wikigeneratedid" %)
420 (((
421 [[image:image-20220714162725-6.png]]
422 )))
423
424 (% class="wikigeneratedid" id="HConfiguredevicenetwork" %)
425 (((
426 **2)Configure device network**
427 )))
428
429 (((
430 (((
431 (((
432 Click the Configuration Download button[[image:image-20220714115308-8.png||height="22" width="15"]], It is used to configure the device network, update the device time, obtain the device machine code, check the device network, etc.
433 )))
434
435 (((
436 In the example below, the IP address of V-Box is configured as 192.168.40.66, and the networking method is 4G connection
437 )))
438 )))
439 )))
440
441 (((
442 (((
443 [[image:image-20220714162737-7.png]]
444
445
446 )))
447 )))
448 )))
449 )))
450
451 (% class="wikigeneratedid" id="HV-netadddevice" %)
452 (((
453 **3)V-net add device**
454 )))
455 )))
456
457 (((
458 (((
459 Open VNET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the device machine code/product code, device password, and device alias to add the device.   [[image:image-20220714162752-8.png]]
460 )))
461
462
463 )))
464
465 (((
466 (% class="wikigeneratedid" id="HSetcommunicationportparameters" %)
467 (((
468 **4)Set communication port parameters**
469 )))
470
471 (((
472 In the device list on the left, find the Vbox that communicates with the L1769, click it and select configuration,communication port configuration in the main interface to add a communication protocol.
473 )))
474
475 [[image:image-20220714162805-9.png]]
476 )))
477
478 (((
479 The communication port is selected as Ethernet, the device type is selected as Allen-Bradley, the protocol is Allen-BradleyMicro850_FreeTag EthemetIP, and the IP is the internal IP address of the L1769 PLC. The port number is 44818.
480 )))
481
482 [[image:image-20220824164346-1.png]]
483
484
485 (((
486 After adding the protocol Allen-BradleyMicro850_FreeTag, click[[image:image-20220714143838-2.png]]icon add label.[[image:image-20220714162827-11.png]]
487 )))
488
489 (% class="wikigeneratedid" id="HEngineeringproduction" %)
490 (((
491 **5)Engineering production**
492 )))
493
494 (% class="wikigeneratedid" %)
495 (((
496 (((
497 According to your own needs, use the V-NET client software to edit the required data monitoring points.
498 )))
499
500 [[image:image-20220714162841-12.png]]
501
502
503 (((
504 **hardware connection**
505 )))
506 )))
507
508 (((
509 **1)Hardware wiring diagram**
510 )))
511
512 (((
513 (((
514 This example introduces Wecon V-box with Allen-Bradley L1769 PLC to establish communication through Ethernet. The connection diagram is as follows:
515 )))
516
517 [[image:image-20220714162856-13.png]]
518
519 (((
520 The above are all the steps for establishing Ethernet communication between Wecon V-box with CompactLogix L1769 PLC.
521
522
523 == **Micro850_FreeTag Protocol(new)** ==
524
525 This example introduces the establishment of Ethernet communication between Wecon V-box and 2080-LC50-48QWB,Micro850. It is introduced through three parts: PLC software configuration, V-box software configuration.
526
527 (% class="wikigeneratedid" id="HSoftwareconfigurationofPLC" %)
528 (((
529 **Software configuration of PLC**
530 )))
531
532 (% class="wikigeneratedid" id="HPLCprogrammingsoftware" %)
533 (((
534 **1)PLC programming software:Connected Components Workbench™**
535
536 (% style="text-align:center" %)
537 [[image:software.png]]
538
539 **2)New PLC project**
540
541 Click New Project and select the PLC model.
542
543 (% style="text-align:center" %)
544 [[image:project create.png]]
545
546 **3)Set Ethernet parameters**
547
548 Follow the steps below to configure Ethernet parameters
549
550 PLC IP address:192.168.39.56
551
552 default gateway:192.168.39.1
553
554 subnet mask:255.255.255.0
555
556 (% style="text-align:center" %)
557 [[image:Ethernet.png]]
558
559 **4)connect PLC**
560
561 **When downloading the setting, need to change the status of the PLC to PRG**
562
563 (% style="text-align:center" %)
564 [[image:conne ab plc.png]]
565
566 **V-box software configuration**
567
568 **1)V-box programming software**
569
570 (% style="text-align:center" %)
571 [[image:v-net client vers.png]]
572
573 **2)Set communication port parameters**
574
575 In the device list on the left, find the Vbox that communicates with the L1769, click it and select configuration,communication port configuration in the main interface to add a communication protocol.
576
577 (% style="text-align:center" %)
578 [[image:V-NET_Client_t2Rg2wpSoY.png]]
579
580 The communication port is selected as Ethernet, the device type is selected as Allen-Bradley, the protocol is Allen-BradleyMicro850_FreeTag EthemetIP, and the IP is the internal IP address of the L1769 PLC. The port number is 44818.
581
582 (% style="text-align:center" %)
583 [[image:V-NET_Client_communication.png]]
584
585 Export variables from PLC, select CSV file, comma delimited.(% id="cke_bm_1950S" style="display:none" %)
586
587 (% style="text-align:center" %)
588 [[image:export1.png]]
589
590 (% style="text-align:center" %)
591 [[image:CCW.Shell_E5Cwj4tUL3.png]]
592
593 After adding the protocol Allen-BradleyMicro850_FreeTag, click[[image:https://docs.we-con.com.cn/bin/download/V-BOX/V-Net/Training/1%20Communication/WebHome/image-20220714143838-2.png?rev=1.1||alt="image-20220714143838-2.png"]]icon add label.
594
595 (% style="text-align:center" %)
596 [[image:V-NET_Client_TNBuqy7T5r.png]]
597
598 **3)Engineering production**
599
600 According to your own needs, use the V-NET client software to edit the required data monitoring points.
601
602 (% style="text-align:center" %)
603 [[image:V-NET_Client_KOR0AHEA4M.png]]
604
605
606 )))
607
608 == **Ethernet DF1 Protocol** ==
609
610 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Allen-Bradley%20Ethernet%20DF1.zip]]
611
612 = Create communication with **Crouzet PLC** =
613
614 == **CROUZET M3 (FBD)** ==
615
616 Support Series: Crouzet Millenium 3 CD12/CB12
617
618 **1)V-BOX setting**
619
620 |=Item|=Recommended |=Note
621 |=Protocol|CROUZET M3 (FBD)|
622 |=Connection|RS232|
623 |=Baud rate|115200|
624 |=Stop bits|1|
625 |=Data bits|7|
626 |=Parity|EVEN|
627
628 **2)Address List**
629
630 |=**Type**|=**Device registers**|=**Format**|=**Range**|=Note
631 |(% rowspan="4" %)Bit|I|I DD|1~~99|Input
632 |SLIBit|SLIBit DD.dd|1.0~~24.15|Serial Link Input
633 |SLOBit|SLOBit DD.dd|25.0~~48.15|Serial Link Output(Read only)
634 |State|State D|1~~1|PLC state(Read only)
635 |(% rowspan="5" %)Word|AI|AI DD|1~~99|Analog Input
636 |SLIn|SLIn DD|1~~24|Serial Link Input
637 |SLOut|SLOut DD|25~~48|Serial Link Output(Read only)
638 |Time|Time D|1~~6|(((
639 Time1: Second
640
641 Time2: Minute
642
643 Time3: Hour
644
645 Time4: Day
646
647 Time5: Month
648
649 Time6: Year
650 )))
651 |Order|Order D|1~~1|(((
652 Running command(Write only)
653
654 ~=2: Run mode; =1: Stop mode;
655 )))
656
657 **3)Cable Wiring**
658
659 (% style="text-align:center" %)
660 [[image:CrouzetRS232 VBox.png]]
661
662 {{info}}
663 **✎Note: **As the wiring diagram indicated, this protocol requires the DB9 serial port pin 4. But pin 4 is undefined for all V-Box, so it need the user to solder a Pull-up resistor to make the pin 4 working. As for how to solder the resistor on the motherboard, please contact with Wecon technical support for the details.
664 {{/info}}
665
666 = Create communication with EMERSON PLC =
667
668 = **RTU Slave Protocol** =
669
670 Supported series: EC10 series
671
672 **1)V-BOX setting**
673
674 |**Items**|**Settings**|**Note**
675 |Protocol|Emerson 984 RTU Slave MODBUS|
676 |Connection|RS485|
677 |Baud rate|19200|
678 |Data bit|8|
679 |Parity|EVEN|
680 |Stop bit|1|
681 |Device station No.|1|Need to be same as the PLC setting
682
683 (% class="wikigeneratedid" %)
684 **2)PLC Setting**
685
686 (% class="wikigeneratedid" %)
687 Remember to use the Control Star to enable the Modbus RTU communication for port 1 in system block before dowload into PLC.
688
689 (% style="text-align:center" %)
690 [[image:ControlStarSystemBlock.png]]
691
692 (% style="text-align:center" %)
693 [[image:ControlStarCommunicate.png]]
694
695 (% style="text-align:center" %)
696 [[image:ControlStarModbus.png]]
697
698 (% class="wikigeneratedid" %)
699 **3)Address List**
700
701 |**Type**|**Device registers**|**Format**|**Range**|**Note**
702 |(% colspan="1" rowspan="12" %)Bit|Y|YOOO|0~~377|
703 |X|XOOO|0~~377|
704 |M0|M0DDDD|0~~2047|
705 |M1|M1DDDDD|2048~~10239|
706 |SM0|SM0DDD|0~~255|
707 |SM1|SM1DDD|256~~511|
708 |S0|S0DDDD|0~~1023|
709 |S1|S1DDDD|1024~~4095|
710 |T0|T0DDD|0~~255|
711 |T1|T1DDD|256~~511|
712 |C0|C0DDD|0~~255|
713 |C1|C1DDD|256~~306|
714 |(% colspan="1" rowspan="7" %)Word|D|DDDDD|0~~7999|
715 |Z|ZDD|0~~15|
716 |TW0|TW0DDD|0~~255|
717 |TW1|TW1DDD|256~~511|
718 |SD0|SD0DDD|0~~255|
719 |SD1|SD1DDD|256~~511|
720 |CW|CWDDD|0~~306|
721 |(% colspan="1" rowspan="2" %)Double Word|CW0|CW0DDD|200~~255|
722 |CW1|CW1DDDDD|256~~99999|
723
724 **4) Cable Wiring**
725
726 (% style="text-align:center" %)
727 [[image:Emerson.png]]
728
729 = Create communication with HollySys PLC =
730
731 == **LK Modbus RTU** ==
732
733 Supported Series: HollySys LK series PLC
734
735 **1)V-BOX setting**
736
737 |**Items**|**Settings**|**Note**
738 |Protocol|HollySys LK Modbus RTU|
739 |Connection|RS485|
740 |Baud rate|38400|
741 |Data bit|8|
742 |Parity|None|
743 |Stop bit|1|
744 |Device station No.|1|
745
746 **2)Address List**
747
748 |=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note**
749 |Bit|QX|QXDDDDD.dd|0~~65535.15|
750 |Bit|IX|IXDDDDD.dd|0~~65535.15|
751 |Bit|MX|MXDDDDD.dd|0~~65535.15|
752 |Word|QW|QWDDDDD|0~~99999|
753 |Word|IW|IWDDDDD|0~~99999|
754 |Word|MW|MWDDDDD|0~~99999|
755 |Word|MD|MDDDDDD|0~~99999|
756
757 **3)Cable Wiring**
758
759 (% style="text-align:center" %)
760 [[image:Hollysys485-2.png]]
761
762 == **LM Modbus RTU** ==
763
764 (% class="wikigeneratedid" %)
765 Supported Series: HollySys LM3109/LM3107 PLC
766
767 (% class="wikigeneratedid" %)
768 **1)V-BOX setting**
769
770 |(% style="width:208px" %)**Items**|(% style="width:310px" %)**Settings**|(% style="width:365px" %)**Optional**|(% style="width:152px" %)**Note**
771 |(% style="width:208px" %)Protocol|(% style="width:310px" %)HollySys LM Modbus RTU|(% style="width:365px" %)HollySys LM Modbus RTU|(% style="width:152px" %)
772 |(% style="width:208px" %)Connection|(% style="width:310px" %)RS232|(% style="width:365px" %)RS485|(% style="width:152px" %)
773 |(% style="width:208px" %)Baud rate|(% style="width:310px" %)38400|(% style="width:365px" %)38400|(% style="width:152px" %)
774 |(% style="width:208px" %)Data bit|(% style="width:310px" %)8|(% style="width:365px" %)8|(% style="width:152px" %)
775 |(% style="width:208px" %)Parity|(% style="width:310px" %)None|(% style="width:365px" %)None|(% style="width:152px" %)
776 |(% style="width:208px" %)Stop bit|(% style="width:310px" %)1|(% style="width:365px" %)1|(% style="width:152px" %)
777 |(% style="width:208px" %)Device station No.|(% style="width:310px" %)1|(% style="width:365px" %)1|(% style="width:152px" %)
778
779 **2)Address List**
780
781 |=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note**
782 |Bit|QX|QXDDDDD.o|0~~99999.7|
783 |Bit|IX|IXDDDDD.o|0~~99999.7|
784 |Bit|MX|MXDDDDD.o|0~~99999.7|
785 |Word|QW|QWDDDDD|0~~99999|
786 |Word|IW|IWDDDDD|0~~99999|
787 |Word|MW|MWDDDDD|0~~99999|
788 |Word|MD|MDDDDDD|0~~99999|
789
790 **Cable Wiring**
791
792 RS232
793
794 (% style="text-align:center" %)
795 [[image:HollySysRS232.png]]
796
797 RS485
798
799 (% style="text-align:center" %)
800 [[image:Hollysys LM Modbus RTU.gif]]
801
802 = Create communication with **Siemens PLC** =
803
804 == **S7-200 Smart Ethernet Protocol** ==
805
806 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20S7-200%20Smart.zip]]
807
808
809 == **S7-300 Ethernet Protocol** ==
810
811 Supported Series: Siemens S7-300 series PLC
812
813 **1)V-BOX setting**
814
815 |**Items**|**Settings**|**Note**
816 |Protocol|Simens S7-300 Ethernet|
817 |Connection|Ethernet|
818 |Port No.|102|
819 |PLC station No.|2|Need to be same as the PLC setting
820
821 **2)Address List**
822
823 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
824 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
825 |Q|Q|Q ddddd.o|0.0~~99999.7|
826 |M|M|M ddddd.o|0.0~~99999.7|
827 |DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
828 nn: block number;
829
830 dddd: address;
831 )))
832 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
833 |Q|QW|QW ddddd|0~~99999|
834 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
835 |MW|MW ddddd|0~~99999|(((
836 MW0=MB(0~~1)
837
838 MW2=MB(2~~3)
839
840 Address value is a multiple of 2
841 )))
842 |MD|MD ddddd|0~~99999|(((
843 MD0=MB(0~~3)
844
845 MD4=MB(4~~7)
846
847 Address value is a multiple of 4
848 )))
849 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
850 nn: block number;
851
852 dddd: address
853 )))
854 |DBxDBW|DBxDBW nndddd|0~~99999999
855 |DBxDBD|DBxDBD nndddd|0~~99999999
856
857 **3)Configure the communication protocol**
858
859 [[image:image-20220824161345-1.png]]
860
861 **4)Cable Wiring**
862
863 [[image:image-20220824161450-2.png]]
864 )))
865 )))
866
867 == **S7-1200 Ethernet Protocol** ==
868
869 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]]
870
871 == **S7-XXX Ethernet Protocol** ==
872
873 Supported Series: Siemens S7-400, S7-1200 and S7-1500
874
875 **1)V-BOX setting**
876
877 |=**Items**|=**Settings**|=**Note**
878 |Protocol|Siemens S7-XXX|
879 |Connection|Ethernet|
880 |Port No.|102|
881 |Device No.|Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|
882 |HMI No.|Rack (Default as 0)|
883
884 Slot from TIA Portal is equal to Device No. of V-net
885
886 Rack from TIA Portal is equal to HMI No. of V-net
887
888 [[image:image-20220824162459-3.png]]
889
890 [[image:image-20220824163305-2.png]]
891
892 **2)Address List**
893
894 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
895 |(% rowspan="4" %)Bit|I|I|M d.o|(((
896 d:0~-~-9999
897
898 o:0-7
899 )))|
900 |Q|Q|Q d.o|(((
901 d:0~-~-9999
902
903 o:0-7
904 )))|
905 |M|M|M d.o|(((
906 d:0~-~-9999
907
908 o:0-7
909 )))|
910 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
911 nn:0-9999,
912
913 dddd:0-9999,
914
915 o:0-7
916 )))|(((
917 nn:DB No.
918
919 dddd:address value
920
921 o: digit address
922 )))
923 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
924 |M|MW|MW d|d:0-99999|(((
925 MW0=MB(0~~1)
926
927 MW2=MB(2~~3)
928
929 Address value is a multiple of 2
930 )))
931 |M|MD|MD d|d:0-99999|(((
932 MD0=MB(0~~3)
933
934 MD4=MB(4~~7)
935
936 Address value is a multiple of 4
937 )))
938 |I|IW|IW d|d:0-99999|
939 |Q|QW|QW d|d:0-99999|
940 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
941 nn:0-9999
942
943 dddd:0-9999
944 )))|(((
945 nn:DB No.
946
947 dddd:address value
948 )))
949 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
950 nn:0-9999
951
952 dddd:0-9999
953 )))|(((
954 nn:DB No.
955
956 dddd:address value
957
958 Address value is a multiple of 2
959 )))
960 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
961 nn:0-9999
962
963 dddd:0-9999
964 )))|(((
965 nn:DB No.
966
967 dddd:address value
968
969 Address value is a multiple of 4
970 )))
971
972 **3)Configure the communication protocol**
973
974 [[image:image-20220824163448-3.png]]
975
976 **✎Note:**
977
978 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three V-BOX.
979 * V-BOX access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
980
981 **4)Cable Wiring**
982
983 [[image:image-20220824162342-2.png]]
984
985 == **LOGO Ethernet Protocol** ==
986
987 Supported Series: Siemens Logo 0BA0, 0BA1 series
988
989 **V-BOX Settings**
990
991
992 |**Items**|**Settings**|**Note**
993 |Protocol|Siemens LOGO|
994 |Connection|Ethernet|
995 |Port No.|102|
996 |PLC station No.|2|
997
998 **Address List**
999
1000
1001 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
1002 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
1003 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
1004 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
1005 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
1006 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
1007 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
1008 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
1009 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
1010 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
1011 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
1012 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
1013 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
1014 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
1015 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
1016 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
1017
1018 **PLC Settings in LOGO Software:**
1019
1020 Click [Tools]~-~-[Ethernet Connections],shown as below.
1021
1022 (% style="text-align:center" %)
1023 [[image:PIStudio.12\.PLC protocols.WebHome@12.PLC Protocol_html_8b9d2322edf89519.png]]
1024
1025 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
1026
1027 (% style="text-align:center" %)
1028 [[image:PIStudio.12\.PLC protocols.WebHome@image-20221228142937-4.png]]
1029
1030 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
1031
1032 (% style="text-align:center" %)
1033 [[image:PIStudio.12\.PLC protocols.WebHome@image-20221228143047-5.png]]
1034
1035 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
1036
1037 (% style="text-align:center" %)
1038 [[image:PIStudio.12\.PLC protocols.WebHome@image-20221228143246-6.png]]
1039
1040 **V-BOX Communication Settings**
1041
1042 Set PLC IP in [IP Address] settings;
1043
1044 (% style="text-align:center" %)
1045 [[image:LldwDGntf4.png]]
1046
1047 Enable V-BOX Ethernet in [Network];
1048
1049 (% style="text-align:center" %)
1050 [[image:WgvjfWbQif.png]]
1051
1052 TSAP setting
1053
1054 * The initialization script needs to set the source TSAP address and the target TSAP address, otherwise the communication will not be successful.
1055
1056 {{code language="LUA"}}
1057 function init.main()
1058 addr_setword("@W_0#HSW1200",8192) -- Set the source TSAP address
1059 addr_setword("@W_0#HSW1201",4096) -- Set the destination TSAP address
1060 end
1061 {{/code}}
1062
1063 Note: The name of the test script is init, 8192 and 4096 are the data used for the test, there is no HSW address in the register option, but you can directly set the value of the corresponding address through the code.
1064
1065 **✎Note:**
1066
1067 * **Communication port configuration: **
1068 ** Continuous length needs to be set to 0.
1069 ** Integration interval needs to be set to 1. (no change may result in data errors)
1070 ** Set Port and Device Station NO.
1071 ** Other set as defaulted.
1072 * **Notes on the use of registers:**
1073 ** Register VD: Use only registers that are multiples of 4, such as 0, 4, 8, etc.
1074 ** Register VW: Use only registers thay are multiples of 2, such as 0, 2, 4 etc. (Using an odd-length register may result in data errors, such as 2 3 4 )
1075
1076 = Create communication with **Mitsubishi PLC** =
1077
1078 == **FX1S,1N,2N Serial Protocol** ==
1079
1080 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
1081
1082 **1)V-BOX Settings**
1083
1084 |**Item**|**Settings**|**Note**
1085 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
1086 |Connection|RS422/RS485/RS232|
1087 |Baud rate|9600~~115200|
1088 |Data bit|7/8|
1089 |Parity|EVEN/Odd/None|
1090 |Stop bit|1/2|
1091 |PLC station No.|1~~255|
1092
1093 **2)Address List**
1094
1095 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1096 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1097 |Y|Y|Y o|0~~303237|
1098 |M|M|M d|0~~99999|
1099 |T|T|T d|0~~99999|
1100 |C|C|C d|0~~99999|
1101 |S|S|S d|0~~99999|
1102 |SM|SM|SM d|8000~~9999|
1103 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1104 |Y|Y|Y o|0~~303237|
1105 |M|M|M d|0~~99999|
1106 |T|T|T d|0~~99999|
1107 |C|C|C d|0~~199|
1108 |D|D|D d|0~~7999|
1109 |S|S|S d|0~~99999|
1110 |SD|SD|SD d|8000~~9999|
1111
1112 **3)Configure the communication protocol**
1113
1114 [[image:image-20220825102844-3.png]]
1115
1116 **4)Cable Wiring**
1117
1118 * **RS422**
1119
1120 [[image:image-20220825103350-4.png]]
1121
1122 [[image:image-20220825100845-4.png]]
1123
1124
1125 == **FX3U,3G,3GA Serial Protocol** ==
1126
1127 Supported Series: Mitsubishi FX3U, FX3G, FX3GA series
1128
1129 **1)V-BOX Settings**
1130
1131 |**Item**|**Settings**|**Note**
1132 |Protocol|Mitsubishi FX3U/3G/3GA|
1133 |Connection|RS422/RS485/RS232|
1134 |Baud rate|9600~~115200|
1135 |Data bit|7/8|
1136 |Parity|EVEN/Odd/None|
1137 |Stop bit|1/2|
1138 |PLC station No.|1~~255|
1139
1140 **2)Address List**
1141
1142 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1143 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1144 |Y|Y|Y o|0~~303237|
1145 |M|M|M d|0~~99999|
1146 |T|T|T d|0~~99999|
1147 |C|C|C d|0~~99999|
1148 |S|S|S d|0~~99999|
1149 |SM|SM|SM d|8000~~9999|
1150 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1151 |Y|Y|Y o|0~~303237|
1152 |M|M|M d|0~~99999|
1153 |T|T|T d|0~~99999|
1154 |C|C|C d|0~~199|
1155 |D|D|D d|0~~7999|
1156 |S|S|S d|0~~99999|
1157 |SD|SD|SD d|8000~~9999|
1158
1159 **3)Configure the communication protocol**
1160
1161 [[image:image-20220825102649-2.png]]
1162
1163 **4)Cable Wiring**
1164
1165 * **RS422**
1166
1167 [[image:image-20220825103421-5.png]]
1168
1169 [[image:image-20220825100845-4.png]]
1170
1171
1172 == **FX3U Ethernet Protocol** ==
1173
1174 Supported Modules: FX3U-ENET-ADP, FX3U-ENET-L
1175
1176 **1)V-BOX Settings**
1177
1178 |Items|Settings|Note
1179 |Protocol|Mitsubishi FX3U|
1180 |Connection|Ethernet|
1181 |Port No.|5009|Must be the same as the PLC setting
1182 |PLC station No.|0|
1183
1184 **2)Address List**
1185
1186 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1187 |(% colspan="1" rowspan="7" %)Bit|X|X|X OOO|0~~377|
1188 |Y|Y|Y OOO|0~~377|
1189 |M|M|M DDDD|0~~7679|
1190 |SM|SM|SM DDDD|8000~~8511|
1191 |S|S|S DDDD|0~~4095|
1192 |TS|TS|TS DDD|0~~511|
1193 |CS|CS|CS DDD|0~~255|
1194 |(% colspan="1" rowspan="9" %)Word|CN|CN|CN DDD|0~~199|
1195 |TN|TN|TN DDD|0~~511|
1196 |D|D|D DDDD|0~~7999|
1197 |SD|SD|SD DDDD|8000~~8511|
1198 |R|R|R DDDDD|0~~32767|
1199
1200 **3)Ethernet Module Settings**
1201
1202 FX3U-ENET-L module configuration
1203 Set up the FX3U-ENET-L Ethernet module settings as follows.
1204 Select the module location, which in this document is Module 0.
1205
1206 [[image:image-20221116105850-1.png]]
1207
1208 Select "Operational setting" to enter the following screen.
1209
1210 The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default.
1211
1212 [[image:image-20221116105947-1.png]]
1213
1214 Select "Open setting" to enter the setting interface, the settings are as follows.
1215
1216 The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the
1217
1218 Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module.
1219
1220 [[image:image-20221116110802-1.png]]
1221
1222 Click on "transter setup" - "PC side I/F setting", see the following figure.
1223
1224 After setting, the first download must use the programming cable, as shown in the figure; after that, can
1225
1226 use the IP set in the "Ethernet board" to communicate directly with the network cable.
1227
1228 [[image:image-20221116110832-2.png||height="423" width="708"]]
1229
1230 Read and write data from the Ethernet module
1231
1232 [[image:image-20221116110907-3.png]]
1233
1234 Set "Transter setup" to COM communication, and read or write operation as shown below
1235
1236 [[image:image-20221116110917-4.png]]
1237
1238 **4)PLC Settings (GX Works 2)**
1239
1240 Create a blank FX5U project
1241
1242 Find Current Connection in the navigation
1243
1244 [[image:image-20221116111427-1.png||height="421" width="705"]]
1245
1246 Select Connection Channel List
1247
1248 Select Ethernet board communication
1249
1250 [[image:image-20221116111451-2.png||height="421" width="705"]]
1251
1252 Select Ethernet Module
1253 Set the IP address of the PLC
1254
1255 [[image:image-20221116111509-3.png||height="666" width="699"]]
1256
1257 Read or write PLC data, in this document is read
1258
1259 [[image:image-20221116111651-4.png||height="416" width="697"]]
1260
1261 [[image:image-20221116111727-5.png||height="416" width="697"]]
1262
1263 **4)Configure the communication protocol**
1264
1265 [[image:image-20221119101946-2.png||height="395" width="695"]]
1266
1267 == **FX5U Serial Protocol** ==
1268
1269 Mitsubishi FX5U series PLC
1270
1271 **1)V-BOX Settings**
1272
1273 |**Item**|**Settings**|**Note**
1274 |Protocol|Mitsubishi FX5U|
1275 |Connection|RS422/RS485|
1276 |Baud rate|9600|
1277 |Data bit|7|
1278 |Parity|Odd|
1279 |Stop bit|1|
1280 |PLC station No.|1~~255|Need to be the same as PLC settings
1281
1282 **2)Address List**
1283
1284 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1285 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1286 |Y|Y|Y o|0~~303237|
1287 |M|M|M d|0~~99999|
1288 |B|B|B h|0~~7FFF|
1289 |F|F|F d|0~~32767|
1290 |SB|SB|SB h|0~~7FFF|
1291 |TS|TS|TS d|0~~1023|
1292 |TC|TC|TC d|0~~1023|
1293 |STS|STS|STS d|0~~1023|
1294 |STC|STC|STS d|0~~1023|
1295 |CS|CS|CS d|0~~1023|
1296 |CC|CC|CC d|0~~1023|
1297 |SM|SM|SM d|0~~9999|
1298 |L|L|L d|0~~32767|
1299 |S|S|S d|0~~4095|
1300 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1301 |TN|TN|TN d|0~~1023|
1302 |STN|STN|STN d|0~~1023|
1303 |CN|CN|CN d|0~~1023|
1304 |R|R|R d|0~~32767|
1305 |SW|SW|SW h|0~~7FFF|
1306 |Z|Z|Z d|0~~23|
1307 |D|D|D d|0~~7999|
1308 |SD|SD|SD d|0~~11999|
1309
1310 **3)PLC Settings (GX Works 3)**
1311
1312 Create a blank FX5U project
1313
1314 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
1315
1316 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5c9cb13fac1e6c93.png?width=200&height=462&rev=1.1||alt="12.PLC Protocol_html_5c9cb13fac1e6c93.png" height="462" width="200"]]
1317
1318 Select protocol in the setting item, and set parameters.
1319
1320 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_de942589ca070228.png?width=600&height=324&rev=1.1||alt="12.PLC Protocol_html_de942589ca070228.png" height="324" width="600"]]
1321
1322 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
1323
1324 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_387ec7d00b5feb59.png?width=600&height=323&rev=1.1||alt="12.PLC Protocol_html_387ec7d00b5feb59.png" height="323" width="600"]]
1325
1326 Click the [Apply] button to finish the setting.
1327
1328 Click download and select the items as below, then click [execute] to download the configuration to PLC.
1329
1330 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_cdef1c5ec8cc2105.png?width=600&height=434&rev=1.1||alt="12.PLC Protocol_html_cdef1c5ec8cc2105.png" height="434" width="600"]]
1331
1332 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
1333
1334 Done.
1335
1336 **4)Configure the communication protocol**
1337
1338 [[image:image-20220825104904-1.png]]
1339
1340 **5)Cable Wiring**
1341
1342
1343 * **RS422**
1344
1345 [[image:image-20220825105105-2.png]]
1346
1347 [[image:image-20220825105533-3.png]]
1348
1349 == **FX5U Ethernet Protocol** ==
1350
1351 Mitsubishi FX5U series PLC
1352
1353 **1)V-BOX Settings**
1354
1355 |**Items**|**Settings**|**Note**
1356 |Protocol|Mitsubishi FX5U|
1357 |Connection|Ethernet|
1358 |Port No.|5002|Must be the same as the PLC setting
1359 |PLC station No.|0|
1360
1361 **2)Address List**
1362
1363 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1364 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1365 |Y|Y|Y o|0~~303237|
1366 |M|M|M d|0~~99999|
1367 |B|B|B h|0~~7FFF|
1368 |F|F|F d|0~~32767|
1369 |SB|SB|SB h|0~~7FFF|
1370 |TS|TS|TS d|0~~1023|
1371 |TC|TC|TC d|0~~1023|
1372 |STS|STS|STS d|0~~1023|
1373 |STC|STC|STS d|0~~1023|
1374 |CS|CS|CS d|0~~1023|
1375 |CC|CC|CC d|0~~1023|
1376 |SM|SM|SM d|0~~9999|
1377 |L|L|L d|0~~32767|
1378 |S|S|S d|0~~4095|
1379 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1380 |TN|TN|TN d|0~~1023|
1381 |STN|STN|STN d|0~~1023|
1382 |CN|CN|CN d|0~~1023|
1383 |R|R|R d|0~~32767|
1384 |SW|SW|SW h|0~~7FFF|
1385 |Z|Z|Z d|0~~23|
1386 |D|D|D d|0~~7999|
1387 |SD|SD|SD d|0~~11999|
1388
1389 **3)PLC Settings (GX Works 3)**
1390
1391 Find the [Ethernet port] in the navigation area.
1392
1393 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_8e8f85ace087346c.png?width=300&height=593&rev=1.1||alt="12.PLC Protocol_html_8e8f85ace087346c.png" height="593" width="300"]]
1394
1395 Select [Own Node Settings] in the [Setting Item List];
1396
1397 Set [IP Address], [Subnet Mask], [Default Gateway];
1398
1399 Click [Detailed Settings] into [Ethernet Configuration (Built-in Ethernet Port)] windows;
1400
1401 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5d98495052c8c10e.png?width=600&height=339&rev=1.1||alt="12.PLC Protocol_html_5d98495052c8c10e.png" height="339" width="600"]]
1402
1403 Select [SLMP Connection Module] and add into host station as below picture shows;
1404
1405 Set Port number as 5002 (this is necessary settings);
1406
1407 Click [Close with Reflecting the Setting] to save and close window;
1408
1409 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_14b489fdc6c6589d.png?width=600&height=350&rev=1.1||alt="12.PLC Protocol_html_14b489fdc6c6589d.png" height="350" width="600"]]
1410
1411 Click [Apply] to completed Etherenet settings;
1412
1413 Switch to the [On line data operation] interface as below, check the item and click [Execute] to download.
1414
1415 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_c93025a968a8a9e7.png?width=600&height=434&rev=1.1||alt="12.PLC Protocol_html_c93025a968a8a9e7.png" height="434" width="600"]]
1416
1417 **4)Configure the communication protocol**
1418
1419 [[image:image-20220825112403-1.png||alt="图片-20220825112403-1.png"]]
1420
1421 **5)Cable Wiring**
1422
1423 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1424
1425 == **L02 Serial Protocol** ==
1426
1427 Mitsubishi L02 series CPU built-in serial port.
1428
1429 **1)V-BOX Settings**
1430
1431 |**Item**|**Settings**|**Note**
1432 |Protocol|Mitsubishi L02|
1433 |Connection|RS422|
1434 |Baud rate|115200|
1435 |Data bit|8|
1436 |Parity|Odd|
1437 |Stop bit|1|
1438 |PLC station No.|1~~255|Need to be the same as PLC settings
1439
1440 **2)Address List**
1441
1442 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1443 |Bit|X|X|X h|0~~FFFF|
1444 |Bit|Y|Y|Y h|0~~FFFF|
1445 |Bit|M|M|M d|0~~9999|
1446 |Bit|L|L|L d|0~~9999|
1447 |Bit|F|F|F d|0~~9999|
1448 |Bit|B|B|B h|0~~FFFF|
1449 |Bit|V|V|V d|0~~2047|
1450 |Bit|TC|TC|TC d|0~~9999|
1451 |Bit|SS|SS|SS d|0~~9999|
1452 |Bit|SC|SC|SC d|0~~9999|
1453 |Bit|CS|CS|CS d|0~~9999|
1454 |Bit|CC|CC|CC d|0~~9999|
1455 |Bit|SB|SB|SB h|0~~FFFF|
1456 |Bit|SM|SM|SM d|0~~2047|
1457 |Bit|STS|STS|STS d|0~~1023|
1458 |Bit|S|S|S d|0~~9999|
1459 |Bit|DX|DX|DX h|0~~FFFF|
1460 |Bit|DY|DY|DY h|0~~FFFF|
1461 |Bit|TS|TS|TS d|0~~9999|
1462 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1463 |Word|W|W|W h|0~~FFFF|
1464 |Word|TN|TN|TN d|0~~99999|
1465 |Word|SN|SN|SN d|0~~99999|
1466 |Word|CN|CN|CN d|0~~99999|
1467 |Word|R|R|R d|0~~99999|
1468 |Word|SW|SW|SW h|0~~FFFF|
1469 |Word|Z|Z|Z d|0~~99999|
1470 |Word|ZR|ZR|ZR h|0~~FFFF|
1471 |Word|D|D|D d|0~~99999|
1472
1473 **3)Communication Settings**
1474
1475 [[image:image-20220825160648-3.png]]
1476
1477 **4)Cable Wiring**
1478
1479 * **RS422**
1480
1481 [[image:image-20220825161612-8.png]]
1482
1483 [[image:image-20220825160820-4.png]]
1484
1485 == **L02 Ethernet Protocol** ==
1486
1487 Mitsubishi L series CPU built-in Ethernet port.
1488
1489 **1)V-BOX Settings**
1490
1491 |**Items**|**Settings**|**Note**
1492 |Protocol|MIT L02 CPU MELSEC|
1493 |Connection|Ethernet|
1494 |Port No.|1025|Must be the same as the PLC setting
1495 |PLC station No.|0|Must be the same as the PLC setting
1496
1497 **2)Address List**
1498
1499 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1500 |Bit|X|X|X h|0~~FFFF|
1501 |Bit|Y|Y|Y h|0~~FFFF|
1502 |Bit|M|M|M d|0~~9999|
1503 |Bit|L|L|L d|0~~9999|
1504 |Bit|F|F|F d|0~~9999|
1505 |Bit|B|B|B h|0~~FFFF|
1506 |Bit|V|V|V d|0~~2047|
1507 |Bit|TC|TC|TC d|0~~9999|
1508 |Bit|SS|SS|SS d|0~~9999|
1509 |Bit|SC|SC|SC d|0~~9999|
1510 |Bit|CS|CS|CS d|0~~9999|
1511 |Bit|CC|CC|CC d|0~~9999|
1512 |Bit|SB|SB|SB h|0~~FFFF|
1513 |Bit|SM|SM|SM d|0~~2047|
1514 |Bit|STS|STS|STS d|0~~1023|
1515 |Bit|S|S|S d|0~~9999|
1516 |Bit|DX|DX|DX h|0~~FFFF|
1517 |Bit|DY|DY|DY h|0~~FFFF|
1518 |Bit|TS|TS|TS d|0~~9999|
1519 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1520 |Word|W|W|W h|0~~FFFF|
1521 |Word|TN|TN|TN d|0~~99999|
1522 |Word|SN|SN|SN d|0~~99999|
1523 |Word|CN|CN|CN d|0~~99999|
1524 |Word|R|R|R d|0~~99999|
1525 |Word|SW|SW|SW h|0~~FFFF|
1526 |Word|Z|Z|Z d|0~~99999|
1527 |Word|ZR|ZR|ZR h|0~~FFFF|
1528 |Word|D|D|D d|0~~99999|
1529
1530 **3)PLC Settings (GX Works2 )**
1531
1532 Create a project
1533
1534 Set PLC IP, subnet mask and gateway;
1535
1536 Select [Binary Code] as communication data code;
1537
1538 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_776e17505f3fc6c0.png?width=600&height=524&rev=1.1||alt="12.PLC Protocol_html_776e17505f3fc6c0.png" height="524" width="600"]]
1539
1540 Set PLC port number, for example 1025
1541
1542 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_8d0d1a22d388f70b.png?width=600&height=524&rev=1.1||alt="12.PLC Protocol_html_8d0d1a22d388f70b.png" height="524" width="600"]]
1543
1544 Save settings;
1545
1546 Download project into PLC device;
1547
1548 Restart PLC device;
1549
1550 **4)Configure the communication protocol**
1551
1552 [[image:image-20220825142659-1.png]]
1553
1554 **5)Cable Wiring**
1555
1556 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1557
1558 == **Q12H Serial Protocol** ==
1559
1560 This Demo shows V-BOX communicate with Q12H PLC by Q02H serial Protocol
1561
1562 [[**Download link**>>https://ftp.we-con.com.cn/Download/WIKI/PI%20HMI/Demo/Communication/V-Box%20connect%20PLC%20Q12H.rar]]
1563
1564 == **QJ71E71 Ethernet Protocol** ==
1565
1566 Mitsubishi QJ71E71 Ethernet communication module;
1567
1568 **1)V-BOX Settings**
1569
1570 |**Items**|**Settings**|**Note**
1571 |Protocol|MIT QJ71E71 MELSEC|
1572 |Connection|Ethernet|
1573 |Port No.|1025|Must be the same as the PLC setting
1574 |PLC station No.|0|Must be the same as the PLC setting
1575
1576 **2)Address List**
1577
1578 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1579 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1580 |Y|Y|Y h|0~~1FFF|
1581 |M|M|M d|0~~99999|
1582 |L|L|L d|0~~8191|
1583 |F|F|F d|0~~2047|
1584 |B|B|B h|0~~1FFF|
1585 |V|V|V d|0~~2047|
1586 |TS|TS|TS d|0~~2047|
1587 |TC|TC|TC d|0~~2047|
1588 |SS|SS|SS d|0~~2047|
1589 |SC|SC|SC d|0~~2047|
1590 |CS|CS|CS d|0~~1023|
1591 |CC|CC|CC d|0~~1023|
1592 |SB|SB|SB h|0~~7FF|
1593 |S|S|S d|0~~8191|
1594 |DX|DX|DX h|0~~1FFF|
1595 |DY|DY|DY h|0~~1FFF|
1596 |SM|SM|SM d|8000~~9999|
1597 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1598 |D|D|D d|0~~12287|
1599 |W|W|W h|0~~1FFF|
1600 |TN|TN|TN d|0~~2047|
1601 |SN|SN|SN d|0~~2047|
1602 |CN|CN|CN d|0~~1023|
1603 |R|R|R d|0~~32767|
1604 |SW|SW|SW h|0~~7FF|
1605 |Z|Z|Z d|0~~15|
1606 |ZR|ZR|ZR h|0~~FE7FF|
1607
1608 **3)PLC Settings(GX Works2)**
1609
1610 * Click [Ethernet/CC IE/MELSECNET];
1611 * Please select [Ethernet] as network type;
1612 * Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order);
1613 * Select [Online] as Mode;
1614 * [[image:image-20221119171343-2.png||height="341" width="587"]]
1615 * Click [Operation setting] to set IP;
1616 * Select [Binary Code] as [Communication Data Code];
1617 * [[image:image-20221119171436-3.png||height="354" width="588"]]
1618 * Click [Open setting]
1619 * Set protocol: TCP;
1620 * Set [unpassive] in [Open system];
1621 * Set [receive] in [Fixed buffer];
1622 * Set [procedure Exist] in [Fixed buffer communication];
1623 * Disable [Pairing open];
1624 * Set [No confirm] in [Existence confirmation];
1625 * Host station port number: 5009;
1626 * Save settings;
1627 * [[image:image-20221119171611-4.png||height="354" width="588"]]
1628 * Download project into PLC and restart it
1629
1630 **4)Configure the communication protocol**
1631
1632 [[image:image-20221119171832-5.png||height="354" width="625"]]
1633
1634
1635 **5)Cable Wiring**
1636
1637 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png"]]
1638
1639 = Create communication with **Delta PLC** =
1640
1641 == **DVP Ethernet Protocol** ==
1642
1643 Supoort Series: DELTA DVP20/32/40/60ES200RE/200TE or any DVP models with built-in Ethernet port, DELTA DVPEN01-SL module
1644
1645 **1)V-BOX Settings**
1646
1647 |=**Items**|=**Settings**|=**Note**
1648 |Protocol|DELTA DVP MODBUS TCP|
1649 |Connection|Ethernet|
1650 |Port No.|502|
1651 |Device No.|1|
1652 |VBox Device No.|0|
1653
1654 **2)Address List **
1655
1656 |=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 217px;" %)**VBox registers**|=(% style="width: 168px;" %)**Format**|=(% style="width: 225px;" %)**Range**|=**Note**
1657 |Bit|(% style="width:191px" %)X|(% style="width:217px" %)X|(% style="width:168px" %)X OOO|(% style="width:225px" %)0~~377|
1658 |Bit|(% style="width:191px" %)Y|(% style="width:217px" %)Y|(% style="width:168px" %)Y OOO|(% style="width:225px" %)0~~377|
1659 |Bit|(% style="width:191px" %)M0|(% style="width:217px" %)M0|(% style="width:168px" %)M0DDDD|(% style="width:225px" %)0~~1535|
1660 |Bit|(% style="width:191px" %)M1|(% style="width:217px" %)M1|(% style="width:168px" %)M1DDDD|(% style="width:225px" %)1536~~4096|
1661 |Bit|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDD|(% style="width:225px" %)0~~255|
1662 |Bit|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~255|
1663 |Bit|(% style="width:191px" %)S|(% style="width:217px" %)S|(% style="width:168px" %)SDDDD|(% style="width:225px" %)0~~1023|
1664 |Word|(% style="width:191px" %)D0|(% style="width:217px" %)D0|(% style="width:168px" %)D0DDDD|(% style="width:225px" %)0~~4095|
1665 |Word|(% style="width:191px" %)D1|(% style="width:217px" %)D1|(% style="width:168px" %)D1DDDD|(% style="width:225px" %)4096~~11999|
1666 |Word|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDD|(% style="width:225px" %)0~~255|
1667 |Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~199|
1668 |Double Word|(% style="width:191px" %)HC|(% style="width:217px" %)HC|(% style="width:168px" %)HCDDD|(% style="width:225px" %)200~~255|
1669
1670 **3) PLC Setting:**
1671
1672 ~1. Create new project in Delta WPL Soft, and click Setting to open the communication settings:
1673
1674 (% style="text-align:center" %)
1675 [[image:DVPEthernetWPLSoft2.png]]
1676
1677 2. Set up the communication type and PLC IP:
1678
1679 (% style="text-align:center" %)
1680 [[image:DVPEthernetSetup.png]]
1681
1682 (% class="wikigeneratedid" %)
1683 3. Click OK and save the settings. Then click Communication on toolbar, then click Transfer Setup to open new window:
1684
1685 (% style="text-align:center" %)
1686 [[image:DVPEthernetTransfer.png]]
1687
1688 (% class="wikigeneratedid" %)
1689 4. Select Communication Mode as PC => PLC to download or select PC <=PLC to upload:
1690
1691 (% style="text-align:center" %)
1692 [[image:DVPEthernetPLCtoPC.png]]
1693
1694 5. Click Auto-Search Ethernet Module to find the PLC on the same LAN network:
1695
1696 (% style="text-align:center" %)
1697 [[image:DVPEthernetAutoSearch.png]]
1698
1699 **4) V-BOX Setting:**
1700
1701 Set the same IP address according to the setting from WPL Soft:
1702
1703 (% style="text-align:center" %)
1704 [[image:DVPEthernetVNETPortocol.png]]
1705
1706 == **DVP serial protocol** ==
1707
1708 Supoort Series: DELTA DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX
1709
1710 **1)V-BOX Settings**
1711
1712 |=**Items**|=**Settings**|=**Note**
1713 |Protocol|DELTA DVP PROTOCOL|
1714 |Connection|RS232|
1715 |Baud Rate|9600|
1716 |Stop Bit|1|
1717 |Data Bit|7|
1718 |Parity|EVEN|
1719 |Device No.|1|
1720
1721 (% class="wikigeneratedid" %)
1722 **2)Address List**
1723
1724 |=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 217px;" %)**VBox registers**|=(% style="width: 168px;" %)**Format**|=(% style="width: 225px;" %)**Range**|=**Note**
1725 |Bit|(% style="width:191px" %)X|(% style="width:217px" %)X|(% style="width:168px" %)X OOOOOO|(% style="width:225px" %)0~~303237|
1726 |Bit|(% style="width:191px" %)Y|(% style="width:217px" %)Y|(% style="width:168px" %)Y OOOOOO|(% style="width:225px" %)0~~303237|
1727 |Bit|(% style="width:191px" %)M|(% style="width:217px" %)M|(% style="width:168px" %)MDDDDD|(% style="width:225px" %)0~~99999|
1728 |Bit|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDDDD|(% style="width:225px" %)0~~99999|
1729 |Bit|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDDDD|(% style="width:225px" %)0~~99999|
1730 |Bit|(% style="width:191px" %)S|(% style="width:217px" %)S|(% style="width:168px" %)SDDDDD|(% style="width:225px" %)0~~99999|
1731 |Word|(% style="width:191px" %)D|(% style="width:217px" %)D|(% style="width:168px" %)D DDDDD|(% style="width:225px" %)0~~99999|
1732 |Word|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDDDD|(% style="width:225px" %)0~~99999|
1733 |Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~199|
1734 |Double Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDDDD|(% style="width:225px" %)200~~99999|
1735
1736 (% class="wikigeneratedid" %)
1737 **3)Wiring Diagram**
1738
1739 (% style="text-align:center" %)
1740 [[image:Delta DVP PROTOCOLSerial232.png]]
1741
1742 == **AS Ethernet Protocol** ==
1743
1744 **1)V-BOX Settings**
1745
1746 |=**Items**|=**Settings**|=**Note**
1747 |Protocol|DELTA AS300 MODBUS TCP|
1748 |Connection|Ethernet|
1749 |Port No.|502|
1750 |Device No.|1|
1751 |HMI No.|0|
1752
1753 **2)Address List**
1754
1755 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1756 |Bit|X|X|X d|0~~63|
1757 |Bit|Y|Y|Y d|0~~63|
1758 |Bit|D|D|D d|0~~29999|
1759 |Bit|M|M|M d|0~~8191|
1760 |Bit|SM|SM|SM d|0~~4095|
1761 |Bit|S|S|S h|0~~2047|
1762 |Bit|T|T|T d|0~~511|
1763 |Bit|C|C|C d|0~~511|
1764 |Bit|HC|HC|HC d|0~~255|
1765 |Word|X|X|X h|0~~63|
1766 |Word|Y|Y|Y d|0~~63|
1767 |Word|SR|SR|SR d|0~~2047|
1768 |Word|D|D|D d|0~~29999|
1769 |Word|T|T|T d|0~~511|
1770 |Word|C|C|C h|0~~511|
1771 |Word|E|E|E d|0~~9|
1772
1773 **3)Configure the communication protocol**
1774
1775 [[image:image-20220831160010-4.png]]
1776
1777 **4)Cable Wiring**
1778
1779 Figure
1780
1781 [[image:image-20220831155101-1.png]][[image:image-20220831160055-5.png]]
1782
1783 Pin Definition Diagram
1784
1785 [[image:image-20220831155157-3.png]]
1786
1787 = Create communication with **Omron PLC** =
1788
1789 == **CP1 Series Protocol ** ==
1790
1791 [[下载链接>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CP1%20Series.zip]]
1792
1793 == **CP2M Series Protocol** ==
1794
1795 [[下载链接>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CJ2M.zip]]
1796
1797
1798 == **EC55 Series Protocol** ==
1799
1800 Supported device: EC55 temperature instrument
1801
1802 **1)V-BOX Settings**
1803
1804 |**Items**|**Settings**|**Note**
1805 |Protocol|Omron EC55|
1806 |Connection|RS485 (9600, 2, 7, EVEN)|
1807 |Port No.|None|
1808 |PLC station No.|0|
1809
1810 **2)Address List**
1811
1812 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
1813 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
1814 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
1815 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
1816 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
1817 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
1818 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
1819 |CP|-|0-6|Read controller intrinsic property
1820 |CS|-|0-2|Read controller states
1821 |CA|-|0-17|Action command
1822
1823 **3)Device Settings**
1824
1825 Omron E5CC PLC configuration
1826
1827 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
1828
1829 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_3d95e093792ba98a.png?width=550&height=229&rev=1.1||alt="12.PLC Protocol_html_3d95e093792ba98a.png" height="229" width="550"]]
1830
1831 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
1832
1833 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_be583aa69dd6cf4c.png?width=550&height=242&rev=1.1||alt="12.PLC Protocol_html_be583aa69dd6cf4c.png" height="242" width="550"]]
1834
1835 **✎Note:** The communication settings for HMI should be consistent with this setting.
1836
1837 **4)Configure the communication protocol**
1838
1839 [[image:image-20220831161041-1.png]]
1840
1841 **5)Cable Wiring**
1842
1843 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5e9a81a14106da9e.png?width=392&height=223&rev=1.1||alt="12.PLC Protocol_html_5e9a81a14106da9e.png" height="223" width="392"]]
1844
1845 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_1897d92be6948d58.png?width=393&height=223&rev=1.1||alt="12.PLC Protocol_html_1897d92be6948d58.png" height="223" width="393"]]
1846
1847 **✎Note:**
1848
1849 * COM3 only available in PI8000/PI9000 series.
1850 * CA address could not support continuous writing function;
1851 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
1852 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
1853 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
1854 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
1855 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
1856 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
1857 * [[image:image-20220831161356-1.png]]Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
1858
1859 = Create communication with Xinje** PLC** =
1860
1861 == **XC serial protocol** ==
1862
1863 **1)V-BOX Settings**
1864
1865 |**Item**|**Settings**|**Note**
1866 |Protocol|XINJE XC MODBUS|
1867 |Connection|RS232|
1868 |Baud rate|19200|
1869 |Data bit|8|
1870 |Parity|EVEN|
1871 |Stop bit|1|
1872 |PLC station No.|1|
1873
1874 **2)Address List**
1875
1876 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1877 |Bit|M|M|M d|0~~8511|
1878 |Bit|X|X|X o|0~~1747|
1879 |Bit|Y|Y|Y o|0~~1747|
1880 |Bit|S|S|S d|0~~1023|
1881 |Bit|T|T|T d|0~~4095|
1882 |Bit|C|C|C d|0~~634|
1883 |Word|D|D|D d|0~~8511|
1884 |Word|TD|TD|TD d|0~~618|
1885 |Word|CD|CD|CD d|0~~634|
1886 |Word|FD|FD|FD d|0~~8511|
1887
1888 **3)Configure the communication protocol**
1889
1890
1891 [[image:image-20220831163041-1.png]]
1892
1893 **4)Cable Wiring**
1894
1895 Figure
1896
1897 [[image:image-20220831163406-2.png]][[image:image-20220831163422-3.png]]
1898
1899 Pin Definition Diagram
1900
1901 [[image:image-20220831163441-4.png]]
1902
1903 == **XD serial protocol** ==
1904
1905 **1)V-BOX Settings**
1906
1907 Supported Series: Xinjie XD/XE Series PLC
1908
1909 |**Item**|**Settings**|**Note**
1910 |Protocol|XINJE XD/XC MODBUS|
1911 |Connection|RS232|
1912 |Baud rate|19200|
1913 |Data bit|8|
1914 |Parity|EVEN|
1915 |Stop bit|1|
1916 |PLC station No.|1|
1917
1918 **2)Address List**
1919
1920 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1921 |Bit|M|M|M d|0~~74999|
1922 |Bit|X1xx|X1xx|X1xx o|0~~1177|
1923 |Bit|X2xx|X2xx|X2xx o|0~~277|
1924 |Bit|X|X|X o|0~~77|
1925 |Bit|Y1xx|Y1xx|Y1xx o|0~~1177|
1926 |Bit|Y2xx|Y2xx|Y2xx o|0~~277|
1927 |Bit|Y|Y|Y o|0~~4095|
1928 |Bit|SM|SM|SM d|0~~4999|(((
1929
1930 )))
1931 |Bit|T|T|T d|0~~4999|
1932 |Bit|C|C|C d|0~~4999|
1933 |Bit|ET|ET|ET d|0~~31|
1934 |Bit|SE|SE|SE d|0~~31|
1935 |Bit|HM|HM|HM d|0~~11999|
1936 |Bit|HSC|HSC|HSC d|0~~39|
1937 |Bit|HS|HS|HS d|0~~999|
1938 |Bit|HT|HT|HT d|0~~1999|
1939 |Bit|HC|HC|HC d|0~~1999|
1940 |Bit|S|S|S d|0~~7999|
1941 |Word|D|D|D d|0~~69999|
1942 |Word|ID|ID|ID d|0~~99|
1943 |Word|ID1xx|ID1xx|ID1xx d|0~~999|
1944 |Word|ID2xx|ID2xx|ID2xx d|0~~299|
1945 |Word|QD|QD|QD d|0~~99|
1946 |Word|QD1xx|QD1xx|QD1xx d|0~~999|
1947 |Word|QD2xx|QD2xx|QD2xx d|0~~299|
1948 |Word|SD|SD|SD d|0~~4999|
1949 |Word|TD|TD|TD d|0~~575|
1950 |Word|CD|CD|CD d|0~~575|
1951 |Word|ETD|ETD|ETD d|0~~31|
1952 |Word|HD|HD|HD d|0~~24999|
1953 |Word|HSD|HSD|HSD d|0~~1023|
1954 |Word|HTD|HTD|HTD d|0~~95|
1955 |Word|HCD|HCD|HCD d|0~~95|
1956 |Word|HSCD|HSCD|HSCD d|0~~31|
1957 |Word|FD|FD|FD d|0~~8191|
1958 |Word|SFD|SFD|SFD d|0~~5999|
1959 |Word|FS|FS|FS d|0~~47|
1960
1961 **3)Configure the communication protocol**
1962
1963 [[image:image-20220831163923-7.png]]
1964
1965
1966
1967 **4)Cable Wiring**
1968
1969 Figure
1970
1971 [[image:image-20220831163406-2.png]][[image:image-20220831163553-6.png]]
1972
1973 Pin Definition Diagram
1974
1975 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830160232-3.png?rev=1.1||alt="image-20220830160232-3.png"]]
1976
1977 = Create communication with **Schneider PLC** =
1978
1979 == **Schneider MODBUS RTU** ==
1980
1981 **1)V-BOX Setting**
1982
1983 |=**Parameters**|=**Recommended**|=**Notes**
1984 |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
1985 |**Connection**|RS485|
1986 |**Baud rate**|19200|
1987 |**Data bit**|8|
1988 |**Parity**|Even|
1989 |**Stop bit**|1|
1990 |**PLC station No.**|1|
1991
1992 **2)Address List**
1993
1994 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
1995 |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
1996 |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
1997 |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
1998 |W|MW|DDDDDD|0 ~~ 999999|Output register
1999 |DW|MD|DDDDDD|0 ~~ 999999|Output register
2000
2001 **3)Configure the communication protocol**
2002
2003 [[image:image-20220902104329-1.png]]
2004
2005 **4)Cable Wiring**
2006
2007 **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
2008
2009 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220817154212-1.jpeg?width=554&height=315&rev=1.1||alt="image-20220817154212-1.jpeg" height="315" width="554"]]
2010
2011 = Create communication with Inovance** PLC** =
2012
2013 == **H3U serial protocol** ==
2014
2015 **1)V-BOX Settings**
2016
2017 |**Item**|**Settings**|**Note**
2018 |Protocol|INOVANCE H3U PLC|
2019 |Connection|RS422|
2020 |Baud rate|9600|
2021 |Data bit|7|
2022 |Parity|EVEN|
2023 |Stop bit|1|
2024 |PLC station No.|0|
2025
2026 **2)Address List**
2027
2028 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
2029 |Bit|X|X|X o|0~~303237|
2030 |Bit|Y|Y|Y o|0~~303237|
2031 |Bit|M|M|M d|0~~99999|
2032 |Bit|T|T|T d|0~~99999|
2033 |Bit|C|C|C d|0~~99999|
2034 |Bit|SM|SM|SM d|8000~~999|
2035 |Bit|S|T|S d|0~~99999|
2036 |Bit|Lamp|Lamp|Lamp d|0~~0|
2037 |Word|X|X|X o|0~~303237|
2038 |Word|Y|Y|Y o|0~~303237|
2039 |Word|M|M|M d|0~~99999|
2040 |Word|T|T|T d|0~~99999|
2041 |Word|C|C|C d|0~~199|
2042 |Word|D|D|D d|0~~7999|
2043 |Word|S|S|S d|0~~99999|
2044 |Word|SD|SD|SD d|8000~~9999|
2045 |Word|R|R|R d|0~~32767|
2046
2047 **3)Configure the communication protocol**
2048
2049 [[image:image-20220831164626-1.png]]
2050
2051
2052
2053 **4)Cable Wiring**
2054
2055 Figure
2056
2057 [[image:image-20220831164646-2.png]][[image:image-20220831164700-3.png]]
2058
2059 Pin Definition Diagram
2060
2061 [[image:image-20220831164731-4.png]]
2062
2063 = Create communication with Panasonic** PLC** =
2064
2065 == **FP serial protocol** ==
2066
2067 **1)V-BOX Settings**
2068
2069 |**Item**|**Settings**|**Note**
2070 |Protocol|Panasonic FP MFWTOCOL|
2071 |Connection|RS232|
2072 |Baud rate|9600|
2073 |Data bit|8|
2074 |Parity|ODD|
2075 |Stop bit|1|
2076 |PLC station No.|1|
2077
2078 **2)Address List**
2079
2080 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
2081 |Bit|X|X|X d|0~~9999|
2082 |Bit|Y|Y|Y d|0~~9999|
2083 |Bit|R|R|R d|0~~9999|
2084 |Bit|T|T|T d|0~~9999|
2085 |Bit|C|C|C d|0~~9999|
2086 |Bit|L|L|L d|0~~9999|
2087 |Word|WX|WX|WX d|0~~9999|
2088 |Word|WY|WY|WY d|0~~9999|
2089 |Word|WR|WR|WR d|0~~9999|
2090 |Word|WL|WL|WL d|0~~9999|
2091 |Word|LD|LD|LD d|0~~9999|
2092 |Word|DT|DT|DT d|0~~65535|
2093 |Word|FL|FL|FL d|0~~9999|
2094 |Word|EV|EV|EV d|0~~9999|
2095 |Word|SV|SV|SV d|0~~9999|
2096
2097 **3)Configure the communication protocol**
2098
2099 [[image:image-20220831165238-4.png]]
2100
2101
2102
2103 **4)Cable Wiring**
2104
2105 Figure
2106
2107 [[image:image-20220831165031-3.png]][[image:image-20220831165017-2.png]]
2108
2109 Pin Definition Diagram
2110
2111 [[image:image-20220831165008-1.png]]
2112
2113 = Create communication with LS** PLC** =
2114
2115 == **XBC serial protocol** ==
2116
2117 **1)V-BOX Settings**
2118
2119 |**Item**|**Settings**|**Note**
2120 |Protocol|LS XBC CNet|
2121 |Connection|RS232|
2122 |Baud rate|115200|
2123 |Data bit|8|
2124 |Parity|NONE|
2125 |Stop bit|1|
2126 |PLC station No.|1|
2127
2128 **2)Address List**
2129
2130 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
2131 |Bit|P|P|P d|0~~2047|
2132 |Bit|M|M|M d|0~~2047|
2133 |Bit|L|L|L d|0~~11263|
2134 |Bit|K|K|K d|0~~16183|
2135 |Bit|F|F|F d|0~~2047|
2136 |Bit|D|D|D d|0~~32767|
2137 |Bit|R|R|R d|0~~32767|
2138 |Bit|U|U|U d|0~~4095|
2139 |Word|P|P|P d|0~~2047|
2140 |Word|M|M|M d|0~~2047|
2141 |Word|L|L|L d|0~~11263|
2142 |Word|K|K|K d|0~~16183|
2143 |Word|F|F|F d|0~~2047|
2144 |Word|C|C|C d|0~~2047|
2145 |Word|T|T|T d|0~~2047|
2146 |Word|D|D|D d|0~~32767|
2147 |Word|N|N|N d|0~~21503|
2148 |Word|R|R|R d|0~~32767|
2149 |Word|U|U|U d|0~~4095|
2150 |Word|Z|Z|Z d|0~~127|
2151 |Word|S|S|S d|0~~127|
2152
2153 **3)Configure the communication protocol**
2154
2155 [[image:image-20220831170147-1.png]]
2156
2157 **4)Cable Wiring**
2158
2159 Figure
2160
2161 [[image:image-20220831170306-4.png]][[image:image-20220831170254-3.png]]
2162
2163 Pin Definition Diagram
2164
2165 [[image:image-20220831170215-2.png]]
2166
2167 == **XGK FEnet Ethernet protocol** ==
2168
2169 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
2170
2171 **1)V-BOX Settings**
2172
2173 |**Items**|**Settings**|**Note**
2174 |Protocol|LG XGK FEnet(Ethernet)|
2175 |Connection|Ethernet|
2176 |Port No.|2004|
2177
2178 **2)Address List**
2179
2180 |**Type**|**Register**|**Range**|**Format**|**Note**
2181 |(% rowspan="14" %)Word|P|0~~2047|P d|
2182 |M|0~~2047|M d|
2183 |K|0~~2047|K d|
2184 |F|0~~2047|F d|
2185 |T|0~~2047|T d|
2186 |C|0~~2047|C d|
2187 |Z|0~~127|Z d|
2188 |S|0~~127|S d|
2189 |L|0~~11263|L d|
2190 |N|0~~21503|N d|
2191 |D|0~~32767|D d|
2192 |R|0~~32767|R d|
2193 |ZR|0~~65535|ZR d|
2194 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
2195
2196 **✎Note:**
2197
2198 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
2199 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
2200 * All bit registers are in the form of bits in word, and the range is the same as the word register;
2201
2202 **3)Communication Settings**
2203
2204 [[image:image-20220831171127-1.png]]
2205
2206 **4)Cable Wiring**
2207
2208 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2209
2210 = Create communication with INVT PLC =
2211
2212 **1)V-BOX setting**
2213
2214 |**Item**|**Settings**|**Note**
2215 |Protocol|INVT_IVC2L|
2216 |Connection|RS232|
2217 |Baud rate|19200|
2218 |Data bit|8|
2219 |Parity|EVEN|
2220 |Stop bit|1|
2221 |PLC station No.|1
2222
2223 **2)Address List**
2224
2225
2226 |**Type**|**Device registers**|**Format**|**Range**|**Note**
2227 |(% colspan="1" rowspan="7" %)Bit|X|XOOO|0~~377|
2228 |Y|YOOO|0~~377|
2229 |M|MDDDD|0~~1999|
2230 |SM|SMDDD|0~~255|
2231 |S|SDDD|0~~991|
2232 |T|TDDD|0~~255|
2233 |C|CDDD|0~~255|
2234 |(% rowspan="5" %)Word|D|DDDDD|0~~7999|
2235 |SD|SDDDD|0~~255|
2236 |Z|ZDD|0~~15|
2237 |T|TDDD|0~~255|
2238 |C|CDDD|0~~199|
2239 |Double word|C|CDDD|200~~255|
2240
2241 **3)Communication Settings**
2242
2243 (% style="text-align:center" %)
2244 [[image:盒子创建英威腾.png]]
2245
2246 **4)PLC software**
2247
2248 (% style="text-align:center" %)
2249 [[image:英威腾软件.png]]
2250
2251 **5)PLC setting **
2252
2253 Open the INVI plc software, create a new project or open a project that has already been created
2254
2255 (% style="text-align:center" %)
2256 [[image:英威腾创建1.png]]
2257
2258 Configure serial port parameters.
2259
2260 (% style="text-align:center" %)
2261 [[image:英威腾创建2.png]]
2262
2263 PC connect PLC
2264
2265 (% style="text-align:center" %)
2266 [[image:英威腾创建3.png]]
2267
2268 Download
2269
2270 (% style="text-align:center" %)
2271 [[image:英威腾下载.png]]
2272
2273 **6)Cable Wiring**
2274
2275 (% style="text-align:center" %)
2276 [[image:wire.png]]
2277
2278 = Create communication with **Modbus ** =
2279
2280 == **MODBUS RTU Slave (All function)** ==
2281
2282 Select the protocol "Modbus RTU Slave (All Fuction)",
2283
2284 Then set baud rate, port, stop bits, data bits, parity.
2285
2286 (% style="text-align:center" %)
2287 [[image:1624342015914-382.png||height="486" width="800" class="img-thumbnail"]]
2288
2289 == **Communicate with Modbus Meter** ==
2290
2291 The following example is using the Linfee meter LNF96EY to demonstrate how to set up the Modbus communication.
2292
2293 ~1. Wiring the RS485 cable first. Because the pin 58 is A, the pin 59 is B for meter. Here we use the COM1 to connect. So the diagram like follows:
2294
2295 (% style="text-align:center" %)
2296 [[image:LinfeeTerminalDiagram.png]]
2297
2298 2. Check the specific Modbus parameter in the communication menu from LED display.
2299
2300 So from the following pictures, we can know the Meter Address is 85, Baud rate is 9600, CRC None.
2301
2302 {{info}}
2303 **✎Note: **Meter address usually corresponding to the Modbus Slave Station No. on the Modbus communication.
2304 {{/info}}
2305
2306 (% style="text-align:center" %)
2307 [[image:MeterModbusAllView.png]]
2308
2309 (% class="wikigeneratedid" %)
2310 3. Set up the communication in the Configuration tab.
2311
2312 (% class="wikigeneratedid" %)
2313 Select the protocol as **ModBus RTU Slave (All Function)**. And set the communication parameters like below.
2314
2315 (% style="text-align:center" %)
2316 [[image:VNETCommunicationtabmeter.png]]
2317
2318 (% class="wikigeneratedid" %)
2319 4. Create new real-time monitoring tag accroding to Modbus manual
2320
2321 (% class="wikigeneratedid" %)
2322 Enter the address we want to read from the meter. The following table is intercept part of the manual for Linfee Modbus manual.
2323
2324 (% class="wikigeneratedid" %)
2325 **0x03/0x04 command data register address**:
2326
2327 (% style="width:1142.22px" %)
2328 |(% style="display:none" %) |=(% colspan="2" rowspan="1" style="width: 165px;" %)Address(% style="display:none" %) |=Description|=Data Format|=(% style="width: 254px;" %)Data Length(Word)|=(% style="width: 282px;" %)Remark
2329 |(%%)(% style="display:none" %) (%%) HEX|(% style="width:107px" %)DEC|(%%)(% style="display:none" %) (%%) |(% style="width:100px" %) |(%%)(% style="display:none" %) (%%) |(% style="width:318px" %)
2330 |(% style="width:107px" %)0x00|(% style="width:100px" %)0|Reserved| | |(% style="width:318px" %)
2331 |(% style="width:107px" %)0x02|(% style="width:100px" %)2|Reserved| | |(% style="width:318px" %)
2332 |(% style="width:107px" %)0x04|(% style="width:100px" %)4|Reserved| | |(% style="width:318px" %)
2333 |(% style="width:107px" %)0x06|(% style="width:100px" %)6|Ua|float|2|(% style="width:318px" %)Phase Voltage data, Unit V
2334 |(% style="width:107px" %)0x08|(% style="width:100px" %)8|Ub|float|2|(% style="width:318px" %)Phase Voltage data, Unit V
2335 |(% style="width:107px" %)0x0A|(% style="width:100px" %)10|Uc|float|2|(% style="width:318px" %)Phase Voltage data, Unit V
2336 |(% style="width:107px" %)0x0C|(% style="width:100px" %)12|Uab|float|2|(% style="width:318px" %)Line Voltage data, Unit V
2337 |(% style="width:107px" %)0x0E|(% style="width:100px" %)14|Ubc|float|2|(% style="width:318px" %)Line Voltage data, Unit V
2338 |(% style="width:107px" %)0x10|(% style="width:100px" %)16|Uca|float|2|(% style="width:318px" %)Line Voltage data, Unit V
2339 |(% style="width:107px" %)0x12|(% style="width:100px" %)18|Ia|float|2|(% style="width:318px" %)Phase Current data, Unit A
2340 |(% style="width:107px" %)0x14|(% style="width:100px" %)20|Ib|float|2|(% style="width:318px" %)Phase Current data, Unit A
2341 |(% style="width:107px" %)0x16|(% style="width:100px" %)22|Ic|float|2|(% style="width:318px" %)Phase Current data, Unit A
2342
2343 {{info}}
2344 **✎Note: **We usually use the Data Type 4 for read the Modbus registers(Function Code 03)
2345 {{/info}}
2346
2347 For example, here we want to read the Phase Voltage Ua (Modbus offset 0006), the Modbus register main No. requires input decimal number, and check whether the actual address has one address offset, so the tag configured like the following screenshot:
2348
2349 (% style="text-align:center" %)
2350 [[image:VNETModbusTagSettings.png]]
2351
2352 (% style="text-align:center" %)
2353 [[image:VNETModbusTagByteSettings.png]]
2354
2355 {{info}}
2356 **✎Note: **If the read value is incorrect, please check whether need to change the Byte order.
2357 {{/info}}
2358
2359 Set the Modbus Slave Station No.
2360
2361 (% style="text-align:center" %)
2362 [[image:ModbusStationSettings.png]]
2363
2364 If the communication is setup successfully, the tag will show green light.
2365
2366 (% style="text-align:center" %)
2367 [[image:Monitoringtaggreenlight.png]]
2368
2369 == **MODBUS RTU Master** ==
2370
2371 Select the protocol "Modbus RTU Master",
2372
2373 Then set baud rate, port, stop bits, data bits, parity
2374
2375 (% style="text-align:center" %)
2376 [[image:1624348709622-711.png||queryString="width=809&height=493" height="488" width="800" class="img-thumbnail"]]
2377
2378 **address list**
2379
2380 (% class="table-bordered" %)
2381 |=(% scope="row" %)**Type**|=**Data Type**|=**Function code and description**
2382 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (Read Input Registers: Read the current binary value in one or more input registers)
2383 |06 (write single register: write a binary value to a holding register)
2384 |10 (write values to multiple addresses )
2385 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
2386 |06 (write single register: write a binary value to a holding register)
2387 |10 (write values to multiple addresses )
2388 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
2389 |06 (write single register: write a binary value to a holding register)
2390 |10 (write values to multiple addresses )
2391 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
2392 |10 (write values to multiple addresses )
2393 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
2394 |05 (Force a single coil to force the on/off state of a logic coil)
2395 |0F (Write multiple bits, ie write continuously)
2396 |(% rowspan="3" %)1|02 (Read the input state)
2397 |05 (Force a single coil to force the on/off state of a logic coil)
2398 |0F (Write multiple bits)
2399 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
2400 |05 (Force a single coil to force the on/off state of a logic coil)
2401 |0F (Write multiple bits)
2402 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
2403 |0F (Write multiple bits)
2404
2405 == **MODBUS TCP Slave (All function)** ==
2406
2407 Supported series: MODBUS TCP controller
2408
2409 V-B0X works as MODBUS TCP MASTER connecting with TCP SLAVE
2410
2411 **1)V-BOX Setting**
2412
2413 |**Items**|**Settings**|**Note**
2414 |Protocol|MODBUS TCP Slave (All function)|
2415 |Connection|Ethernet|
2416 |Port No.|502|
2417 |PLC station No.|1
2418
2419 **2)Address List**
2420
2421 |=**Type**|=**Data Type**|=**Function code & Description**
2422 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
2423 |06 (write single register: write a binary value to a holding register)
2424 |10 (write values to multiple addresses )
2425 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
2426 |06 (write single register: write a binary value to a holding register)
2427 |10 (write values to multiple addresses )
2428 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
2429 |06 (write single register: write a binary value to a holding register)
2430 |10 (write values to multiple addresses )
2431 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
2432 |10 (write values to multiple addresses )
2433 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
2434 |05 (Force a single coil to force the on/off state of a logic coil)
2435 |0F (Write multiple bits, ie write continuously)
2436 |(% rowspan="3" %)1|02 (Read the input state)
2437 |05 (Force a single coil to force the on/off state of a logic coil)
2438 |0F (Write multiple bits)
2439 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
2440 |05 (Force a single coil to force the on/off state of a logic coil)
2441 |0F (Write multiple bits)
2442 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
2443 |0F (Write multiple bits)
2444
2445 **3)Communication Settings**
2446
2447 Configure V-BOX Ethernet IP in Networking Settings
2448
2449 [[image:image-20220902111833-3.png]]
2450
2451
2452 Configure PLC Ethernet IP in Communication;
2453
2454 [[image:image-20220902111121-1.png]]
2455
2456 **4)Cable Wiring**
2457
2458 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2459
2460 == **communicate with VB inverter** ==
2461
2462 [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20VB%20inverter.zip]]
2463
2464 = **User define protocol** =
2465
2466 More serial port script instruction,please refer manual:[[Lua script function>>doc:V-BOX.V-Net.Manual.04 Lua Script.01 Lua Functions.WebHome]]~-~-->[[3.Serial port operation>>url:http://docs.we-con.com.cn/wiki/vbox/view/HMI/04.Lua%20script%20%20function%20and%20operation/01.Lua%20script%20function/#H3.Serialportoperation]]
2467
2468 == **Read the temperature sensor.** ==
2469
2470 the commond format is as beliow:
2471
2472 Send commond:01 03 02 00 00 03 04 73
2473
2474 Feedback commond:01 03 06 07 F7 0E 7E B7 35
2475
2476 Temperature data:07 F7,desimal = 2039,it means temperature is 20.39℃.
2477
2478 Humidity data:0E 7E,desimal = 3710, it mean humidity is 37.10%RH.
2479
2480 Script Demo:
2481
2482 ~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~--
2483
2484 function com.main()
2485 ~-~-dosomething
2486 openPlc()
2487 end
2488 function openPlc()
2489 if obj then
2490 ~-~- If the serial port opened,then read/write data by timing
2491
2492 local wri = string.pack(">HHHH",0X0103,0X0200,0X0003,0X0473)
2493 local arr = reading(wri)
2494 ~-~- if arr ~~=nil then
2495 ~-~- if arr[1] ==33 and arr[2] ==v[2][2] and arr[3] ==v[2][3] then
2496 ~-~- local A = arr[4]*256
2497 ~-~- local B = A+arr[5]
2498 ~-~- addr_setword(v[1],B)
2499 ~-~- end
2500 ~-~- end
2501
2502 else
2503 ~-~-judge if there is a serial object, then initialize and open the serial port
2504 local configs = {
2505 name = 'COM1', ~-~-Select serial port COM1
2506 mode = 485, ~-~-Communication mode RS485
2507 baud_rate = 9600, ~-~-Baud rate 9600
2508 stop_bit = 1, ~-~-stop bit 1
2509 data_len = 8, ~-~-data length 8
2510 check_bit = 'NONE', ~-~-no parity
2511
2512 }
2513 obj,err = serial.open(configs) ~-~-Open serial port
2514 if not obj then
2515 print("serial open :failed", err) ~-~- Open serial port failed
2516 end
2517 end
2518 end
2519
2520 function reading(wri)
2521 obj:flush() ~-~- Clear serial port
2522 obj:write(wri) ~-~- Write serial port
2523 print(string.byte(wri,1,#wri))
2524 obj:flush() ~-~- Clear serial port 
2525 local readed =obj:read(9,1000) ~-~- Read 9 bytes, timeout 1 second
2526 if readed and readed ~~= "" then 
2527 ~-~- judge that a non-empty string is read
2528 print(string.byte(readed,1,#readed))
2529 a={string.byte(readed, 1, #readed)}
2530 if nil ~~= a[4] and nil ~~= a[5] and nil ~~= a[6] and nil ~~= a[7] then
2531 a1=a[4]*256+a[5]
2532 a2=a[6]*256+a[7]
2533 addr_setword("@HDW0",a1)
2534 addr_setword("@HDW1",a2)
2535 end
2536 return {string.byte(readed, 1, #readed)}
2537 elseif readed == nil then
2538 print("serial read err:", err or "")
2539 return nil
2540 end
2541 return nil
2542 end
2543
2544 ~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-