25.1 | 1 | = **Modbus RTU** = |
![]() |
1.1 | 2 | |
![]() |
10.1 | 3 | === **V-BOX as master** === |
![]() |
1.1 | 4 | |
5 | Select the protocol “(% class="mark" %)Modbus RTU Slave(All Fuction)”, | ||
6 | |||
7 | (% class="mark" %)then set BaudRate,Port,Stop Bit,Data Bit,Parity | ||
8 | |||
9 | (% style="text-align:center" %) | ||
![]() |
6.1 | 10 | [[image:1624342015914-382.png||height="486" width="800" class="img-thumbnail"]] |
![]() |
1.1 | 11 | |
![]() |
10.1 | 12 | === **V-BOX as slave** === |
![]() |
1.1 | 13 | |
14 | Select the protocol “(% class="mark" %)**Modbus RTU Master”**, | ||
15 | |||
16 | (% class="mark" %)then set BaudRate,Port,Stop Bit,Data Bit,Parity | ||
17 | |||
18 | (% style="text-align:center" %) | ||
![]() |
6.1 | 19 | [[image:1624348709622-711.png||queryString="width=809&height=493" height="488" width="800" class="img-thumbnail"]] |
![]() |
1.1 | 20 | |
21 | **Address List** | ||
22 | |||
23 | (% class="table-bordered" %) | ||
24 | |**Type**|**Register**|**Function code & Description** | ||
25 | |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers) | ||
26 | |06 (write single register: write a binary value to a holding register) | ||
27 | |10 (write values to multiple addresses ) | ||
28 | |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers) | ||
29 | |06 (write single register: write a binary value to a holding register) | ||
30 | |10 (write values to multiple addresses ) | ||
31 | |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers) | ||
32 | |06 (write single register: write a binary value to a holding register) | ||
33 | |10 (write values to multiple addresses ) | ||
34 | |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers) | ||
35 | |10 (write values to multiple addresses ) | ||
36 | |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state) | ||
37 | |05 (Force a single coil to force the on/off state of a logic coil) | ||
38 | |0F (Write multiple bits, ie write continuously) | ||
39 | |(% rowspan="3" %)1|02 (Read the input state) | ||
40 | |05 (Force a single coil to force the on/off state of a logic coil) | ||
41 | |0F (Write multiple bits) | ||
42 | |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils) | ||
43 | |05 (Force a single coil to force the on/off state of a logic coil) | ||
44 | |0F (Write multiple bits) | ||
45 | |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils) | ||
46 | |0F (Write multiple bits) | ||
47 | |||
![]() |
24.1 | 48 | = **WECON PLC** = |
![]() |
1.1 | 49 | |
![]() |
20.1 | 50 | Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM |
![]() |
1.1 | 51 | |
![]() |
20.1 | 52 | **HMI Settings** |
![]() |
1.1 | 53 | |
![]() |
20.1 | 54 | |**Item**|**Settings**|**Note** |
55 | |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM| | ||
56 | |Connection|RS422/RS485| | ||
57 | |Baud rate|9600| | ||
58 | |Data bit|7| | ||
59 | |Parity|EVEN| | ||
60 | |Stop bit|1| | ||
61 | |PLC station No.|1| | ||
![]() |
1.1 | 62 | |
![]() |
20.1 | 63 | **Address List** |
64 | |||
65 | |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note** | ||
66 | |(% rowspan="6" %)Bit|X|X|Xo|0~~303237| | ||
67 | |Y|Y|Y o|0~~303237| | ||
68 | |M|M|M d|0~~99999| | ||
69 | |T|T|T d|0~~99999| | ||
70 | |C|C|C d|0~~99999| | ||
71 | |S|S|S d|0~~99999| | ||
72 | |(% rowspan="8" %)Word|X|X|Xo|0~~303237| | ||
73 | |Y|Y|Y o|0~~303237| | ||
74 | |M|M|M d|0~~99999| | ||
75 | |T|T|T d|0~~99999| | ||
76 | |C|C|C d|0~~199| | ||
77 | |D|D|D d|0~~7999| | ||
78 | |S|S|S d|0~~99999| | ||
79 | |SD|SD|SD d|8000~~9999| | ||
80 | |||
81 | **Cable Wiring** | ||
82 | |||
83 | * **RS485** | ||
84 | |||
![]() |
1.1 | 85 | (% style="text-align:center" %) |
![]() |
20.1 | 86 | [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]] |
87 | |||
88 | * **RS422** | ||
89 | |||
90 | (% style="text-align:center" %) | ||
91 | [[image:12.PLC Protocol_html_5c7fca9a70da2ee8.png||data-xwiki-image-style-alignment="center" height="247" width="389" class="img-thumbnail"]] | ||
92 | |||
93 | **✎Note:** | ||
94 | |||
95 | * HMI COM3 is available in PI8000 series and COM3 is in COM2(hardware PIN 7 and PIN 8) . | ||
96 | * If PLC <= 20 points,such as LX3V-1208/LX3V-0806 PLC,PLC RS485A and RS485B mean PLC COM2 RS485+ and RS485- .PLC COM2 can support modbus. Please refer to PLC COM2 setting manual. | ||
97 | |||
98 | [[https:~~/~~/drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing>>url:https://drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing]] | ||
99 | |||
100 | |||
![]() |
28.1 | 101 | == **HMI and Wecon LX5V serial communication** == |
102 | |||
![]() |
20.1 | 103 | This example introduces the establishment of serial port communication between Wecon HMI and LX5V. It is introduced through three parts: PLC software configuration, HMI software configuration, and hardware wiring. |
104 | |||
105 | **Software configuration of PLC** | ||
106 | |||
107 | **1)PLC programming software** | ||
108 | |||
109 | [[image:image-20220810164710-1.png]] | ||
110 | |||
![]() |
28.1 | 111 | |
![]() |
20.1 | 112 | **2)New PLC project** |
113 | |||
114 | Click New Project and select the PLC model. | ||
115 | |||
116 | [[image:image-20220810172412-1.png]] | ||
117 | |||
![]() |
28.1 | 118 | |
![]() |
20.1 | 119 | **3)Set Serial port parameters** |
120 | |||
121 | Follow the steps below to configure Serial port parameters | ||
122 | |||
123 | Baud rate:115200 | ||
124 | |||
125 | Data bit:8 | ||
126 | |||
127 | Stop bit:1 | ||
128 | |||
129 | Parity:No verification | ||
130 | |||
131 | [[image:image-20220810165759-3.png]] | ||
132 | |||
![]() |
28.1 | 133 | |
![]() |
20.1 | 134 | **4)Registers list** |
135 | |||
136 | [[image:image-20220811102219-3.png]] | ||
137 | |||
![]() |
28.1 | 138 | |
![]() |
20.1 | 139 | **HMI software configuration** |
140 | |||
141 | **1)HMI programming software** | ||
142 | |||
143 | [[image:image-20220810171237-4.png]] | ||
144 | |||
145 | **2)New HMI project** | ||
146 | |||
147 | Click New Project and select the HMI model. | ||
148 | |||
149 | [[image:image-20220810172010-5.png]] | ||
150 | |||
![]() |
28.1 | 151 | |
![]() |
20.1 | 152 | **3)Set communication port parameters** |
153 | |||
154 | Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port. | ||
155 | |||
156 | Baud rate:115200 | ||
157 | |||
158 | Data bit:8 | ||
159 | |||
160 | Stop bit:1 | ||
161 | |||
162 | Parity:No verification | ||
163 | |||
164 | [[image:image-20220811104012-1.png]] | ||
165 | |||
![]() |
28.1 | 166 | |
![]() |
20.1 | 167 | **hardware connection** |
168 | |||
169 | **1)Hardware wiring diagram** | ||
170 | |||
171 | This example introduces WeconHMI with LX5V PLC to establish communication through serial port. The connection diagram is as follows: | ||
172 | |||
![]() |
28.1 | 173 | |
174 | |||
![]() |
20.1 | 175 | [[image:image-20220811103005-4.png]] |
176 | |||
177 | [[image:image-20220811103227-7.png]] | ||
178 | |||
179 | The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC. | ||
180 | |||
![]() |
28.1 | 181 | == **HMI and Wecon LX5V-N Ethernet communication** == |
![]() |
20.1 | 182 | |
183 | This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V. It is introduced through three parts: PLC software configuration, HMI software configuration, and hardware wiring. | ||
184 | |||
185 | **Software configuration of PLC** | ||
186 | |||
187 | **1)PLC programming software** | ||
188 | |||
189 | [[image:image-20220810164710-1.png]] | ||
190 | |||
191 | **2)New PLC project** | ||
192 | |||
193 | Click New Project and select the PLC model. | ||
194 | |||
195 | [[image:image-20220811115454-1.png]] | ||
196 | |||
197 | **3)Set Ethernet port parameters** | ||
198 | |||
199 | Follow the steps below to configure Ethernet parameters | ||
200 | |||
201 | PLC IP address:192.168.39.200 | ||
202 | |||
203 | default gateway:192.168.39.1 | ||
204 | |||
205 | subnet mask:255.255.255.0 | ||
206 | |||
207 | [[image:image-20220811140530-2.png]] | ||
208 | |||
209 | **4)Registers list** | ||
210 | |||
211 | [[image:image-20220811102219-3.png]] | ||
212 | |||
213 | **HMI software configuration** | ||
214 | |||
215 | **1)HMI programming software** | ||
216 | |||
217 | [[image:image-20220810171237-4.png]] | ||
218 | |||
219 | **2)New HMI project** | ||
220 | |||
221 | Click New Project and select the HMI model. | ||
222 | |||
223 | [[image:image-20220810172010-5.png]] | ||
224 | |||
225 | **3)Set communication port parameters** | ||
226 | |||
227 | Click the project setting button on the left to configure the IP address of the HMI machine to ensure that the HMI and PLC IP remain in a local area network. | ||
228 | |||
229 | HMI IP address:192.168.39.201 | ||
230 | |||
231 | default gateway:192.168.39.1 | ||
232 | |||
233 | subnet mask:255.255.255.0 | ||
234 | |||
235 | [[image:image-20220811170753-2.png]] | ||
236 | |||
237 | Next, click Communication Settings to configure the IP of the HMI communication object. | ||
238 | |||
239 | [[image:image-20220811163047-1.png]] | ||
240 | |||
241 | **hardware connection** | ||
242 | |||
243 | **1)Hardware wiring diagram** | ||
244 | |||
245 | This example introduces WeconHMI with LX5V-N PLC to establish communication through ethernet. The connection diagram is as follows: | ||
246 | |||
247 | [[image:image-20220811170248-1.png]] | ||
248 | |||
249 | The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC. | ||
250 | |||
251 | (% style="text-align:center" %) | ||
![]() |
6.1 | 252 | [[image:1624348978863-771.png||queryString="width=812&height=494" height="487" width="800" class="img-thumbnail"]] |
![]() |
1.1 | 253 | |
![]() |
23.1 | 254 | = **Rockwell PLC** = |
![]() |
22.1 | 255 | |
![]() |
27.1 | 256 | == **Communication with AB CompactLogix L1769** == |
![]() |
11.1 | 257 | |
258 | ((( | ||
![]() |
16.1 | 259 | ((( |
![]() |
11.1 | 260 | This example introduces the establishment of Ethernet communication between Wecon V-box and Allen-Bradley L1769. It is introduced through three parts: PLC software configuration, V-box software configuration, and hardware wiring. |
![]() |
16.1 | 261 | ))) |
![]() |
15.1 | 262 | |
263 | |||
![]() |
11.1 | 264 | ))) |
265 | |||
266 | ((( | ||
![]() |
15.1 | 267 | (% class="wikigeneratedid" id="HSoftwareconfigurationofPLC" %) |
268 | ((( | ||
269 | **Software configuration of PLC** | ||
![]() |
11.1 | 270 | ))) |
271 | |||
![]() |
15.1 | 272 | (% class="wikigeneratedid" id="HPLCprogrammingsoftware" %) |
![]() |
11.1 | 273 | ((( |
![]() |
15.1 | 274 | **1)PLC programming software** |
275 | ))) | ||
![]() |
11.1 | 276 | |
![]() |
17.1 | 277 | [[image:image-20220714162600-1.png]] |
![]() |
11.1 | 278 | |
![]() |
15.1 | 279 | (% class="wikigeneratedid" id="HNewPLCproject" %) |
![]() |
11.1 | 280 | ((( |
![]() |
15.1 | 281 | **2)New PLC project** |
![]() |
11.1 | 282 | ))) |
283 | |||
284 | ((( | ||
![]() |
16.1 | 285 | ((( |
![]() |
15.1 | 286 | Click New Project and select the PLC model. |
![]() |
11.1 | 287 | ))) |
![]() |
16.1 | 288 | ))) |
![]() |
11.1 | 289 | |
290 | ((( | ||
![]() |
17.1 | 291 | [[image:image-20220714162617-2.png]] |
![]() |
11.1 | 292 | ))) |
293 | |||
294 | ((( | ||
![]() |
17.1 | 295 | |
![]() |
16.1 | 296 | |
![]() |
17.1 | 297 | [[image:image-20220714162652-4.png]] |
![]() |
11.1 | 298 | ))) |
299 | |||
300 | ((( | ||
![]() |
15.1 | 301 | (% class="wikigeneratedid" id="HSetEthernetparameters" %) |
302 | ((( | ||
303 | **3)Set Ethernet parameters** | ||
304 | ))) | ||
![]() |
11.1 | 305 | |
306 | ((( | ||
![]() |
15.1 | 307 | ((( |
![]() |
16.1 | 308 | ((( |
![]() |
11.1 | 309 | Follow the steps below to configure Ethernet parameters |
310 | ))) | ||
![]() |
15.1 | 311 | ))) |
![]() |
16.1 | 312 | ))) |
![]() |
11.1 | 313 | |
314 | ((( | ||
![]() |
15.1 | 315 | ((( |
![]() |
16.1 | 316 | ((( |
![]() |
11.1 | 317 | PLC IP address:192.168.40.101 |
318 | ))) | ||
![]() |
15.1 | 319 | ))) |
![]() |
16.1 | 320 | ))) |
![]() |
11.1 | 321 | |
322 | ((( | ||
![]() |
15.1 | 323 | ((( |
![]() |
16.1 | 324 | ((( |
![]() |
11.1 | 325 | default gateway:192.168.40.1 |
326 | ))) | ||
![]() |
15.1 | 327 | ))) |
![]() |
16.1 | 328 | ))) |
![]() |
11.1 | 329 | |
330 | ((( | ||
![]() |
15.1 | 331 | ((( |
![]() |
16.1 | 332 | ((( |
![]() |
11.1 | 333 | subnet mask:255.255.255.0 |
334 | ))) | ||
![]() |
15.1 | 335 | ))) |
![]() |
16.1 | 336 | ))) |
![]() |
11.1 | 337 | |
338 | ((( | ||
![]() |
17.1 | 339 | [[image:image-20220714162713-5.png]] |
![]() |
11.1 | 340 | ))) |
341 | |||
342 | ((( | ||
343 | |||
344 | ))) | ||
345 | |||
346 | ((( | ||
![]() |
15.1 | 347 | (% class="wikigeneratedid" id="HV-boxsoftwareconfiguration" %) |
348 | ((( | ||
349 | **V-box software configuration** | ||
350 | ))) | ||
![]() |
11.1 | 351 | |
![]() |
15.1 | 352 | (% class="wikigeneratedid" id="HV-boxprogrammingsoftware" %) |
353 | ((( | ||
354 | **1)V-box programming software** | ||
355 | ))) | ||
![]() |
11.1 | 356 | |
![]() |
15.1 | 357 | (% class="wikigeneratedid" %) |
358 | ((( | ||
![]() |
17.1 | 359 | [[image:image-20220714162725-6.png]] |
![]() |
15.1 | 360 | ))) |
![]() |
11.1 | 361 | |
![]() |
15.1 | 362 | (% class="wikigeneratedid" id="HConfiguredevicenetwork" %) |
363 | ((( | ||
364 | **2)Configure device network** | ||
365 | ))) | ||
![]() |
11.1 | 366 | |
367 | ((( | ||
![]() |
15.1 | 368 | ((( |
![]() |
16.1 | 369 | ((( |
![]() |
11.1 | 370 | Click the Configuration Download button[[image:image-20220714115308-8.png||height="22" width="15"]], It is used to configure the device network, update the device time, obtain the device machine code, check the device network, etc. |
371 | ))) | ||
![]() |
16.1 | 372 | |
373 | ((( | ||
374 | In the example below, the IP address of V-Box is configured as 192.168.40.66, and the networking method is 4G connection | ||
![]() |
15.1 | 375 | ))) |
![]() |
16.1 | 376 | ))) |
377 | ))) | ||
![]() |
11.1 | 378 | |
379 | ((( | ||
![]() |
15.1 | 380 | ((( |
![]() |
17.1 | 381 | [[image:image-20220714162737-7.png]] |
![]() |
16.1 | 382 | |
383 | |||
![]() |
11.1 | 384 | ))) |
385 | ))) | ||
386 | ))) | ||
387 | ))) | ||
388 | |||
![]() |
15.1 | 389 | (% class="wikigeneratedid" id="HV-netadddevice" %) |
![]() |
11.1 | 390 | ((( |
![]() |
15.1 | 391 | **3)V-net add device** |
![]() |
11.1 | 392 | ))) |
![]() |
15.1 | 393 | ))) |
![]() |
11.1 | 394 | |
395 | ((( | ||
![]() |
16.1 | 396 | ((( |
![]() |
21.1 | 397 | Open VNET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the device machine code/product code, device password, and device alias to add the device. [[image:image-20220714162752-8.png]] |
![]() |
11.1 | 398 | ))) |
399 | |||
400 | |||
401 | ))) | ||
402 | |||
403 | ((( | ||
![]() |
15.1 | 404 | (% class="wikigeneratedid" id="HSetcommunicationportparameters" %) |
405 | ((( | ||
406 | **4)Set communication port parameters** | ||
407 | ))) | ||
![]() |
11.1 | 408 | |
![]() |
16.1 | 409 | ((( |
410 | In the device list on the left, find the Vbox that communicates with the L1769, click it and select configuration,communication port configuration in the main interface to add a communication protocol. | ||
![]() |
11.1 | 411 | ))) |
412 | |||
![]() |
17.1 | 413 | [[image:image-20220714162805-9.png]] |
![]() |
16.1 | 414 | ))) |
415 | |||
416 | ((( | ||
![]() |
11.1 | 417 | The communication port is selected as Ethernet, the device type is selected as Allen-Bradley, the protocol is Allen-BradleyMicro850_FreeTag EthemetIP, and the IP is the internal IP address of the L1769 PLC. The port number is 44818. |
![]() |
16.1 | 418 | ))) |
![]() |
11.1 | 419 | |
![]() |
17.1 | 420 | [[image:image-20220714162814-10.png]] |
![]() |
11.1 | 421 | |
422 | |||
![]() |
16.1 | 423 | ((( |
![]() |
22.1 | 424 | After adding the protocol Allen-BradleyMicro850_FreeTag, click[[image:image-20220714143838-2.png]]icon add label.[[image:image-20220714162827-11.png]] |
![]() |
16.1 | 425 | ))) |
![]() |
14.1 | 426 | |
![]() |
16.1 | 427 | (% class="wikigeneratedid" id="HEngineeringproduction" %) |
428 | ((( | ||
429 | **5)Engineering production** | ||
430 | ))) | ||
![]() |
14.1 | 431 | |
![]() |
16.1 | 432 | (% class="wikigeneratedid" %) |
433 | ((( | ||
434 | ((( | ||
435 | According to your own needs, use the V-NET client software to edit the required data monitoring points. | ||
436 | ))) | ||
![]() |
14.1 | 437 | |
![]() |
17.1 | 438 | [[image:image-20220714162841-12.png]] |
![]() |
14.1 | 439 | |
![]() |
16.1 | 440 | |
441 | ((( | ||
442 | **hardware connection** | ||
443 | ))) | ||
444 | ))) | ||
445 | |||
446 | ((( | ||
447 | **1)Hardware wiring diagram** | ||
448 | ))) | ||
449 | |||
450 | ((( | ||
451 | ((( | ||
452 | This example introduces Wecon V-box with Allen-Bradley L1769 PLC to establish communication through Ethernet. The connection diagram is as follows: | ||
453 | ))) | ||
454 | |||
![]() |
17.1 | 455 | [[image:image-20220714162856-13.png]] |
![]() |
16.1 | 456 | |
457 | ((( | ||
458 | The above are all the steps for establishing Ethernet communication between Wecon V-box with Allen-Bradley L1769 PLC. | ||
![]() |
26.1 | 459 | |
460 | |||
461 | == **Allen-Bradley Ethernet DF1** == | ||
462 | |||
463 | [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Allen-Bradley%20Ethernet%20DF1.zip]] | ||
464 | |||
465 | |||
466 | = **Siemens PLC** = | ||
![]() |
16.1 | 467 | ))) |
468 | ))) | ||
469 | |||
![]() |
10.1 | 470 | == **Siemens S7-1200** == |
![]() |
1.1 | 471 | |
472 | [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]] | ||
473 | |||
![]() |
10.1 | 474 | == **Communication with S7-200 Smart** == |
![]() |
1.1 | 475 | |
476 | [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20S7-200%20Smart.zip]] | ||
477 | |||
![]() |
26.1 | 478 | = **Delta PLC** = |
479 | |||
![]() |
10.1 | 480 | == **Delta DVP Ethernet** == |
![]() |
1.1 | 481 | |
482 | [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Delta%20DVP%20Ethernet.zip]] | ||
483 | |||
![]() |
10.1 | 484 | == **Delta DVP Serial Protocol** == |
![]() |
1.1 | 485 | |
486 | [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Delta%20DVP%20Ethernet.zip]] | ||
487 | |||
![]() |
10.1 | 488 | == **Communicate with Mitsubishi FX Series** == |
![]() |
6.1 | 489 | |
490 | [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20Mitsubishi%20FX%20Series.zip]] | ||
491 | |||
![]() |
10.1 | 492 | == **Communicate with VB inverter** == |
![]() |
6.1 | 493 | |
494 | [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20VB%20inverter.zip]] | ||
495 | |||
![]() |
10.1 | 496 | == **Omron CP1 Series** == |
![]() |
7.1 | 497 | |
![]() |
8.1 | 498 | [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CP1%20Series.zip]] |
![]() |
7.1 | 499 | |
![]() |
10.1 | 500 | == **Omron CJ2M** == |
![]() |
7.1 | 501 | |
![]() |
8.1 | 502 | [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CJ2M.zip]] |
![]() |
7.1 | 503 | |
![]() |
1.1 | 504 | = **2 User define protocol** = |
505 | |||
![]() |
19.1 | 506 | More serial port script instruction,please refer manual:[[Lua script function>>doc:V-BOX.V-Net.Manual.04 Lua Script.01 Lua Functions.WebHome]]~-~-->[[3.Serial port operation>>url:http://docs.we-con.com.cn/wiki/vbox/view/HMI/04.Lua%20script%20%20function%20and%20operation/01.Lua%20script%20function/#H3.Serialportoperation]] |
![]() |
1.1 | 507 | |
![]() |
10.1 | 508 | == **Read the temperature sensor.** == |
![]() |
1.1 | 509 | |
510 | the commond format is as beliow: | ||
511 | |||
512 | Send commond:01 03 02 00 00 03 04 73 | ||
513 | |||
514 | Feedback commond:01 03 06 07 F7 0E 7E B7 35 | ||
515 | |||
516 | Temperature data:07 F7,desimal = 2039,it means temperature is 20.39℃. | ||
517 | |||
518 | Humidity data:0E 7E,desimal = 3710, it mean humidity is 37.10%RH. | ||
519 | |||
520 | Script Demo: | ||
521 | |||
522 | ~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-- | ||
523 | |||
524 | function com.main() | ||
525 | ~-~-dosomething | ||
526 | openPlc() | ||
527 | end | ||
528 | function openPlc() | ||
529 | if obj then | ||
530 | ~-~- If the serial port opened,then read/write data by timing | ||
531 | |||
532 | local wri = string.pack(">HHHH",0X0103,0X0200,0X0003,0X0473) | ||
533 | local arr = reading(wri) | ||
534 | ~-~- if arr ~~=nil then | ||
535 | ~-~- if arr[1] ==33 and arr[2] ==v[2][2] and arr[3] ==v[2][3] then | ||
536 | ~-~- local A = arr[4]*256 | ||
537 | ~-~- local B = A+arr[5] | ||
538 | ~-~- addr_setword(v[1],B) | ||
539 | ~-~- end | ||
540 | ~-~- end | ||
541 | |||
542 | else | ||
543 | ~-~-judge if there is a serial object, then initialize and open the serial port | ||
544 | local configs = { | ||
545 | name = 'COM1', ~-~-Select serial port COM1 | ||
546 | mode = 485, ~-~-Communication mode RS485 | ||
547 | baud_rate = 9600, ~-~-Baud rate 9600 | ||
548 | stop_bit = 1, ~-~-stop bit 1 | ||
549 | data_len = 8, ~-~-data length 8 | ||
550 | check_bit = 'NONE', ~-~-no parity | ||
551 | |||
552 | } | ||
553 | obj,err = serial.open(configs) ~-~-Open serial port | ||
554 | if not obj then | ||
555 | print("serial open :failed", err) ~-~- Open serial port failed | ||
556 | end | ||
557 | end | ||
558 | end | ||
559 | |||
560 | function reading(wri) | ||
561 | obj:flush() ~-~- Clear serial port | ||
562 | obj:write(wri) ~-~- Write serial port | ||
563 | print(string.byte(wri,1,#wri)) | ||
564 | obj:flush() ~-~- Clear serial port | ||
565 | local readed =obj:read(9,1000) ~-~- Read 9 bytes, timeout 1 second | ||
566 | if readed and readed ~~= "" then | ||
567 | ~-~- judge that a non-empty string is read | ||
568 | print(string.byte(readed,1,#readed)) | ||
569 | a={string.byte(readed, 1, #readed)} | ||
570 | if nil ~~= a[4] and nil ~~= a[5] and nil ~~= a[6] and nil ~~= a[7] then | ||
571 | a1=a[4]*256+a[5] | ||
572 | a2=a[6]*256+a[7] | ||
573 | addr_setword("@HDW0",a1) | ||
574 | addr_setword("@HDW1",a2) | ||
575 | end | ||
576 | return {string.byte(readed, 1, #readed)} | ||
577 | elseif readed == nil then | ||
578 | print("serial read err:", err or "") | ||
579 | return nil | ||
580 | end | ||
581 | return nil | ||
582 | end | ||
583 | |||
584 | ~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~- |