Wiki source code of 1 Communication
Version 53.1 by Ben on 2022/08/24 11:35
Hide last authors
author | version | line-number | content |
---|---|---|---|
![]() |
52.1 | 1 | = (% style="color:inherit; font-family:inherit" %)**WECON PLC**(%%) = |
![]() |
1.1 | 2 | |
![]() |
44.1 | 3 | == **LX3V 串行通信** == |
![]() |
31.1 | 4 | |
![]() |
20.1 | 5 | Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM |
![]() |
1.1 | 6 | |
![]() |
20.1 | 7 | **HMI Settings** |
![]() |
1.1 | 8 | |
![]() |
20.1 | 9 | |**Item**|**Settings**|**Note** |
10 | |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM| | ||
11 | |Connection|RS422/RS485| | ||
12 | |Baud rate|9600| | ||
13 | |Data bit|7| | ||
14 | |Parity|EVEN| | ||
15 | |Stop bit|1| | ||
16 | |PLC station No.|1| | ||
![]() |
1.1 | 17 | |
![]() |
20.1 | 18 | **Address List** |
19 | |||
20 | |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note** | ||
21 | |(% rowspan="6" %)Bit|X|X|Xo|0~~303237| | ||
22 | |Y|Y|Y o|0~~303237| | ||
23 | |M|M|M d|0~~99999| | ||
24 | |T|T|T d|0~~99999| | ||
25 | |C|C|C d|0~~99999| | ||
26 | |S|S|S d|0~~99999| | ||
27 | |(% rowspan="8" %)Word|X|X|Xo|0~~303237| | ||
28 | |Y|Y|Y o|0~~303237| | ||
29 | |M|M|M d|0~~99999| | ||
30 | |T|T|T d|0~~99999| | ||
31 | |C|C|C d|0~~199| | ||
32 | |D|D|D d|0~~7999| | ||
33 | |S|S|S d|0~~99999| | ||
34 | |SD|SD|SD d|8000~~9999| | ||
35 | |||
36 | **Cable Wiring** | ||
37 | |||
38 | * **RS485** | ||
39 | |||
![]() |
31.1 | 40 | [[image:image-20220822172124-1.png]] |
![]() |
20.1 | 41 | |
42 | * **RS422** | ||
43 | |||
![]() |
31.1 | 44 | [[image:image-20220822172228-2.png]] |
![]() |
20.1 | 45 | |
![]() |
30.1 | 46 | |
![]() |
20.1 | 47 | **✎Note:** |
48 | |||
49 | * HMI COM3 is available in PI8000 series and COM3 is in COM2(hardware PIN 7 and PIN 8) . | ||
50 | * If PLC <= 20 points,such as LX3V-1208/LX3V-0806 PLC,PLC RS485A and RS485B mean PLC COM2 RS485+ and RS485- .PLC COM2 can support modbus. Please refer to PLC COM2 setting manual. | ||
51 | |||
52 | [[https:~~/~~/drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing>>url:https://drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing]] | ||
53 | |||
![]() |
43.1 | 54 | == **LX5V serial communication** == |
![]() |
28.1 | 55 | |
![]() |
34.1 | 56 | This example introduces the establishment of serial port communication between Wecon V-BOX and LX5V. It is introduced through three parts: PLC software configuration, HMI software configuration, and hardware wiring. |
![]() |
20.1 | 57 | |
58 | **Software configuration of PLC** | ||
59 | |||
60 | **1)PLC programming software** | ||
61 | |||
![]() |
33.1 | 62 | [[image:image-20220822172553-1.png]] |
![]() |
20.1 | 63 | |
64 | **2)New PLC project** | ||
65 | |||
66 | Click New Project and select the PLC model. | ||
67 | |||
![]() |
33.1 | 68 | [[image:image-20220822172623-2.png]] |
![]() |
20.1 | 69 | |
70 | **3)Set Serial port parameters** | ||
71 | |||
72 | Follow the steps below to configure Serial port parameters | ||
73 | |||
74 | Baud rate:115200 | ||
75 | |||
76 | Data bit:8 | ||
77 | |||
78 | Stop bit:1 | ||
79 | |||
80 | Parity:No verification | ||
81 | |||
![]() |
33.1 | 82 | [[image:image-20220822172657-3.png]] |
![]() |
20.1 | 83 | |
84 | **4)Registers list** | ||
85 | |||
![]() |
33.1 | 86 | [[image:image-20220822172730-4.png]] |
![]() |
20.1 | 87 | |
![]() |
33.1 | 88 | **V-BOX software configuration** |
![]() |
28.1 | 89 | |
![]() |
35.1 | 90 | **1)V-BOX programming software** |
![]() |
20.1 | 91 | |
![]() |
35.1 | 92 | [[image:image-20220824104124-1.png]] |
![]() |
20.1 | 93 | |
![]() |
35.1 | 94 | **2)V-NET add device** |
![]() |
20.1 | 95 | |
![]() |
35.1 | 96 | Open V-NET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the access key, password and remark, to add the device. |
![]() |
20.1 | 97 | |
![]() |
35.1 | 98 | [[image:image-20220824104909-2.png]] |
![]() |
20.1 | 99 | |
![]() |
28.1 | 100 | |
![]() |
20.1 | 101 | **3)Set communication port parameters** |
102 | |||
103 | Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port. | ||
104 | |||
105 | Baud rate:115200 | ||
106 | |||
107 | Data bit:8 | ||
108 | |||
109 | Stop bit:1 | ||
110 | |||
111 | Parity:No verification | ||
112 | |||
113 | [[image:image-20220811104012-1.png]] | ||
114 | |||
![]() |
28.1 | 115 | |
![]() |
20.1 | 116 | **hardware connection** |
117 | |||
118 | **1)Hardware wiring diagram** | ||
119 | |||
120 | This example introduces WeconHMI with LX5V PLC to establish communication through serial port. The connection diagram is as follows: | ||
121 | |||
![]() |
28.1 | 122 | |
123 | |||
![]() |
20.1 | 124 | [[image:image-20220811103005-4.png]] |
125 | |||
126 | [[image:image-20220811103227-7.png]] | ||
127 | |||
128 | The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC. | ||
129 | |||
![]() |
45.1 | 130 | == **LX5V-N Ethernet communication** == |
![]() |
20.1 | 131 | |
132 | This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V. It is introduced through three parts: PLC software configuration, HMI software configuration, and hardware wiring. | ||
133 | |||
134 | **Software configuration of PLC** | ||
135 | |||
136 | **1)PLC programming software** | ||
137 | |||
138 | [[image:image-20220810164710-1.png]] | ||
139 | |||
140 | **2)New PLC project** | ||
141 | |||
142 | Click New Project and select the PLC model. | ||
143 | |||
144 | [[image:image-20220811115454-1.png]] | ||
145 | |||
146 | **3)Set Ethernet port parameters** | ||
147 | |||
148 | Follow the steps below to configure Ethernet parameters | ||
149 | |||
150 | PLC IP address:192.168.39.200 | ||
151 | |||
152 | default gateway:192.168.39.1 | ||
153 | |||
154 | subnet mask:255.255.255.0 | ||
155 | |||
156 | [[image:image-20220811140530-2.png]] | ||
157 | |||
158 | **4)Registers list** | ||
159 | |||
160 | [[image:image-20220811102219-3.png]] | ||
161 | |||
162 | **HMI software configuration** | ||
163 | |||
164 | **1)HMI programming software** | ||
165 | |||
166 | [[image:image-20220810171237-4.png]] | ||
167 | |||
168 | **2)New HMI project** | ||
169 | |||
170 | Click New Project and select the HMI model. | ||
171 | |||
172 | [[image:image-20220810172010-5.png]] | ||
173 | |||
174 | **3)Set communication port parameters** | ||
175 | |||
176 | Click the project setting button on the left to configure the IP address of the HMI machine to ensure that the HMI and PLC IP remain in a local area network. | ||
177 | |||
178 | HMI IP address:192.168.39.201 | ||
179 | |||
180 | default gateway:192.168.39.1 | ||
181 | |||
182 | subnet mask:255.255.255.0 | ||
183 | |||
184 | [[image:image-20220811170753-2.png]] | ||
185 | |||
186 | Next, click Communication Settings to configure the IP of the HMI communication object. | ||
187 | |||
188 | [[image:image-20220811163047-1.png]] | ||
189 | |||
190 | **hardware connection** | ||
191 | |||
192 | **1)Hardware wiring diagram** | ||
193 | |||
194 | This example introduces WeconHMI with LX5V-N PLC to establish communication through ethernet. The connection diagram is as follows: | ||
195 | |||
196 | [[image:image-20220811170248-1.png]] | ||
197 | |||
198 | The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC. | ||
199 | |||
200 | (% style="text-align:center" %) | ||
![]() |
6.1 | 201 | [[image:1624348978863-771.png||queryString="width=812&height=494" height="487" width="800" class="img-thumbnail"]] |
![]() |
1.1 | 202 | |
![]() |
23.1 | 203 | = **Rockwell PLC** = |
![]() |
22.1 | 204 | |
![]() |
37.1 | 205 | == (% id="cke_bm_5621S" style="display:none" %)** **(%%)**MicroLogix** == |
206 | |||
207 | MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5 | ||
208 | |||
209 | **HMI Settings** | ||
210 | |||
211 | |**Item**|**Settings**|**Note** | ||
212 | |Protocol|Allen-Bradlley MicroLogix| | ||
213 | |Connection|RS232| | ||
214 | |Baud rate|19200| | ||
215 | |Data bit|8| | ||
216 | |Parity|None| | ||
217 | |Stop bit|1| | ||
218 | |PLC station No.|1| | ||
219 | |||
220 | **Address List** | ||
221 | |||
222 | |**Type**|**Device registers**|**Format**|**Range**|**Note** | ||
223 | |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15| | ||
224 | |O|O d.d|0.0~~255.15| | ||
225 | |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex) | ||
226 | |S|S d.d|0.0~~255.15| | ||
227 | |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex) | ||
228 | |(% rowspan="9" %)Word|S|S d|0~~255| | ||
229 | |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex) | ||
230 | |TP|TP nnhh|0~~ffff | ||
231 | |CS|CS nnhh|0~~ffff | ||
232 | |CP|CP nnhh|0~~ffff | ||
233 | |N|N nnhh|0~~ffff | ||
234 | |C|C nnhh|0~~ffff | ||
235 | |T|T nnhh|0~~ffff | ||
236 | |R|R nnhh|0~~ffff | ||
237 | |||
238 | **Cable Wiring** | ||
239 | |||
240 | [[image:image-20220824110724-1.png]] | ||
241 | |||
242 | |||
243 | |||
244 | == **CompactLogix** == | ||
245 | |||
![]() |
11.1 | 246 | ((( |
![]() |
16.1 | 247 | ((( |
![]() |
38.1 | 248 | This example introduces the establishment of Ethernet communication between Wecon V-box and CompactLogix L1769. It is introduced through three parts: PLC software configuration, V-box software configuration, and hardware wiring. |
![]() |
16.1 | 249 | ))) |
![]() |
11.1 | 250 | ))) |
251 | |||
252 | ((( | ||
![]() |
15.1 | 253 | (% class="wikigeneratedid" id="HSoftwareconfigurationofPLC" %) |
254 | ((( | ||
255 | **Software configuration of PLC** | ||
![]() |
11.1 | 256 | ))) |
257 | |||
![]() |
15.1 | 258 | (% class="wikigeneratedid" id="HPLCprogrammingsoftware" %) |
![]() |
11.1 | 259 | ((( |
![]() |
15.1 | 260 | **1)PLC programming software** |
261 | ))) | ||
![]() |
11.1 | 262 | |
![]() |
17.1 | 263 | [[image:image-20220714162600-1.png]] |
![]() |
11.1 | 264 | |
![]() |
15.1 | 265 | (% class="wikigeneratedid" id="HNewPLCproject" %) |
![]() |
11.1 | 266 | ((( |
![]() |
15.1 | 267 | **2)New PLC project** |
![]() |
11.1 | 268 | ))) |
269 | |||
270 | ((( | ||
![]() |
16.1 | 271 | ((( |
![]() |
15.1 | 272 | Click New Project and select the PLC model. |
![]() |
11.1 | 273 | ))) |
![]() |
16.1 | 274 | ))) |
![]() |
11.1 | 275 | |
276 | ((( | ||
![]() |
17.1 | 277 | [[image:image-20220714162617-2.png]] |
![]() |
11.1 | 278 | ))) |
279 | |||
280 | ((( | ||
![]() |
17.1 | 281 | |
![]() |
16.1 | 282 | |
![]() |
17.1 | 283 | [[image:image-20220714162652-4.png]] |
![]() |
11.1 | 284 | ))) |
285 | |||
286 | ((( | ||
![]() |
15.1 | 287 | (% class="wikigeneratedid" id="HSetEthernetparameters" %) |
288 | ((( | ||
289 | **3)Set Ethernet parameters** | ||
290 | ))) | ||
![]() |
11.1 | 291 | |
292 | ((( | ||
![]() |
15.1 | 293 | ((( |
![]() |
16.1 | 294 | ((( |
![]() |
11.1 | 295 | Follow the steps below to configure Ethernet parameters |
296 | ))) | ||
![]() |
15.1 | 297 | ))) |
![]() |
16.1 | 298 | ))) |
![]() |
11.1 | 299 | |
300 | ((( | ||
![]() |
15.1 | 301 | ((( |
![]() |
16.1 | 302 | ((( |
![]() |
11.1 | 303 | PLC IP address:192.168.40.101 |
304 | ))) | ||
![]() |
15.1 | 305 | ))) |
![]() |
16.1 | 306 | ))) |
![]() |
11.1 | 307 | |
308 | ((( | ||
![]() |
15.1 | 309 | ((( |
![]() |
16.1 | 310 | ((( |
![]() |
11.1 | 311 | default gateway:192.168.40.1 |
312 | ))) | ||
![]() |
15.1 | 313 | ))) |
![]() |
16.1 | 314 | ))) |
![]() |
11.1 | 315 | |
316 | ((( | ||
![]() |
15.1 | 317 | ((( |
![]() |
16.1 | 318 | ((( |
![]() |
11.1 | 319 | subnet mask:255.255.255.0 |
320 | ))) | ||
![]() |
15.1 | 321 | ))) |
![]() |
16.1 | 322 | ))) |
![]() |
11.1 | 323 | |
324 | ((( | ||
![]() |
17.1 | 325 | [[image:image-20220714162713-5.png]] |
![]() |
11.1 | 326 | ))) |
327 | |||
328 | ((( | ||
329 | |||
330 | ))) | ||
331 | |||
332 | ((( | ||
![]() |
15.1 | 333 | (% class="wikigeneratedid" id="HV-boxsoftwareconfiguration" %) |
334 | ((( | ||
335 | **V-box software configuration** | ||
336 | ))) | ||
![]() |
11.1 | 337 | |
![]() |
15.1 | 338 | (% class="wikigeneratedid" id="HV-boxprogrammingsoftware" %) |
339 | ((( | ||
340 | **1)V-box programming software** | ||
341 | ))) | ||
![]() |
11.1 | 342 | |
![]() |
15.1 | 343 | (% class="wikigeneratedid" %) |
344 | ((( | ||
![]() |
17.1 | 345 | [[image:image-20220714162725-6.png]] |
![]() |
15.1 | 346 | ))) |
![]() |
11.1 | 347 | |
![]() |
15.1 | 348 | (% class="wikigeneratedid" id="HConfiguredevicenetwork" %) |
349 | ((( | ||
350 | **2)Configure device network** | ||
351 | ))) | ||
![]() |
11.1 | 352 | |
353 | ((( | ||
![]() |
15.1 | 354 | ((( |
![]() |
16.1 | 355 | ((( |
![]() |
11.1 | 356 | Click the Configuration Download button[[image:image-20220714115308-8.png||height="22" width="15"]], It is used to configure the device network, update the device time, obtain the device machine code, check the device network, etc. |
357 | ))) | ||
![]() |
16.1 | 358 | |
359 | ((( | ||
360 | In the example below, the IP address of V-Box is configured as 192.168.40.66, and the networking method is 4G connection | ||
![]() |
15.1 | 361 | ))) |
![]() |
16.1 | 362 | ))) |
363 | ))) | ||
![]() |
11.1 | 364 | |
365 | ((( | ||
![]() |
15.1 | 366 | ((( |
![]() |
17.1 | 367 | [[image:image-20220714162737-7.png]] |
![]() |
16.1 | 368 | |
369 | |||
![]() |
11.1 | 370 | ))) |
371 | ))) | ||
372 | ))) | ||
373 | ))) | ||
374 | |||
![]() |
15.1 | 375 | (% class="wikigeneratedid" id="HV-netadddevice" %) |
![]() |
11.1 | 376 | ((( |
![]() |
15.1 | 377 | **3)V-net add device** |
![]() |
11.1 | 378 | ))) |
![]() |
15.1 | 379 | ))) |
![]() |
11.1 | 380 | |
381 | ((( | ||
![]() |
16.1 | 382 | ((( |
![]() |
21.1 | 383 | Open VNET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the device machine code/product code, device password, and device alias to add the device. [[image:image-20220714162752-8.png]] |
![]() |
11.1 | 384 | ))) |
385 | |||
386 | |||
387 | ))) | ||
388 | |||
389 | ((( | ||
![]() |
15.1 | 390 | (% class="wikigeneratedid" id="HSetcommunicationportparameters" %) |
391 | ((( | ||
392 | **4)Set communication port parameters** | ||
393 | ))) | ||
![]() |
11.1 | 394 | |
![]() |
16.1 | 395 | ((( |
396 | In the device list on the left, find the Vbox that communicates with the L1769, click it and select configuration,communication port configuration in the main interface to add a communication protocol. | ||
![]() |
11.1 | 397 | ))) |
398 | |||
![]() |
17.1 | 399 | [[image:image-20220714162805-9.png]] |
![]() |
16.1 | 400 | ))) |
401 | |||
402 | ((( | ||
![]() |
11.1 | 403 | The communication port is selected as Ethernet, the device type is selected as Allen-Bradley, the protocol is Allen-BradleyMicro850_FreeTag EthemetIP, and the IP is the internal IP address of the L1769 PLC. The port number is 44818. |
![]() |
16.1 | 404 | ))) |
![]() |
11.1 | 405 | |
![]() |
17.1 | 406 | [[image:image-20220714162814-10.png]] |
![]() |
11.1 | 407 | |
408 | |||
![]() |
16.1 | 409 | ((( |
![]() |
22.1 | 410 | After adding the protocol Allen-BradleyMicro850_FreeTag, click[[image:image-20220714143838-2.png]]icon add label.[[image:image-20220714162827-11.png]] |
![]() |
16.1 | 411 | ))) |
![]() |
14.1 | 412 | |
![]() |
16.1 | 413 | (% class="wikigeneratedid" id="HEngineeringproduction" %) |
414 | ((( | ||
415 | **5)Engineering production** | ||
416 | ))) | ||
![]() |
14.1 | 417 | |
![]() |
16.1 | 418 | (% class="wikigeneratedid" %) |
419 | ((( | ||
420 | ((( | ||
421 | According to your own needs, use the V-NET client software to edit the required data monitoring points. | ||
422 | ))) | ||
![]() |
14.1 | 423 | |
![]() |
17.1 | 424 | [[image:image-20220714162841-12.png]] |
![]() |
14.1 | 425 | |
![]() |
16.1 | 426 | |
427 | ((( | ||
428 | **hardware connection** | ||
429 | ))) | ||
430 | ))) | ||
431 | |||
432 | ((( | ||
433 | **1)Hardware wiring diagram** | ||
434 | ))) | ||
435 | |||
436 | ((( | ||
437 | ((( | ||
438 | This example introduces Wecon V-box with Allen-Bradley L1769 PLC to establish communication through Ethernet. The connection diagram is as follows: | ||
439 | ))) | ||
440 | |||
![]() |
17.1 | 441 | [[image:image-20220714162856-13.png]] |
![]() |
16.1 | 442 | |
443 | ((( | ||
![]() |
41.1 | 444 | The above are all the steps for establishing Ethernet communication between Wecon V-box with CompactLogix L1769 PLC. |
![]() |
26.1 | 445 | |
446 | |||
447 | == **Allen-Bradley Ethernet DF1** == | ||
448 | |||
449 | [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Allen-Bradley%20Ethernet%20DF1.zip]] | ||
450 | |||
451 | |||
452 | = **Siemens PLC** = | ||
![]() |
16.1 | 453 | ))) |
454 | ))) | ||
455 | |||
![]() |
10.1 | 456 | == **Siemens S7-1200** == |
![]() |
1.1 | 457 | |
458 | [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]] | ||
459 | |||
![]() |
10.1 | 460 | == **Communication with S7-200 Smart** == |
![]() |
1.1 | 461 | |
462 | [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20S7-200%20Smart.zip]] | ||
463 | |||
![]() |
26.1 | 464 | = **Delta PLC** = |
465 | |||
![]() |
10.1 | 466 | == **Delta DVP Ethernet** == |
![]() |
1.1 | 467 | |
468 | [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Delta%20DVP%20Ethernet.zip]] | ||
469 | |||
![]() |
10.1 | 470 | == **Delta DVP Serial Protocol** == |
![]() |
1.1 | 471 | |
472 | [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Delta%20DVP%20Ethernet.zip]] | ||
473 | |||
![]() |
47.1 | 474 | = **Mitsubishi PLC** = |
475 | |||
![]() |
10.1 | 476 | == **Communicate with Mitsubishi FX Series** == |
![]() |
6.1 | 477 | |
478 | [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20Mitsubishi%20FX%20Series.zip]] | ||
479 | |||
![]() |
48.1 | 480 | = **Omron PLC** = |
481 | |||
![]() |
10.1 | 482 | == **Omron CP1 Series** == |
![]() |
7.1 | 483 | |
![]() |
8.1 | 484 | [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CP1%20Series.zip]] |
![]() |
7.1 | 485 | |
![]() |
10.1 | 486 | == **Omron CJ2M** == |
![]() |
7.1 | 487 | |
![]() |
8.1 | 488 | [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CJ2M.zip]] |
![]() |
7.1 | 489 | |
![]() |
50.1 | 490 | = **Modbus RTU** = |
491 | |||
![]() |
53.1 | 492 | == **V-BOX as master** == |
![]() |
50.1 | 493 | |
494 | Select the protocol “(% class="mark" %)Modbus RTU Slave(All Fuction)”, | ||
495 | |||
496 | (% class="mark" %)then set BaudRate,Port,Stop Bit,Data Bit,Parity | ||
497 | |||
498 | (% style="text-align:center" %) | ||
499 | [[image:1624342015914-382.png||height="486" width="800" class="img-thumbnail"]] | ||
500 | |||
![]() |
53.1 | 501 | == **V-BOX as slave** == |
![]() |
50.1 | 502 | |
503 | Select the protocol “(% class="mark" %)**Modbus RTU Master”**, | ||
504 | |||
505 | (% class="mark" %)then set BaudRate,Port,Stop Bit,Data Bit,Parity | ||
506 | |||
507 | (% style="text-align:center" %) | ||
508 | [[image:1624348709622-711.png||queryString="width=809&height=493" height="488" width="800" class="img-thumbnail"]] | ||
509 | |||
510 | **Address List** | ||
511 | |||
512 | (% class="table-bordered" %) | ||
513 | |**Type**|**Register**|**Function code & Description** | ||
514 | |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers) | ||
515 | |06 (write single register: write a binary value to a holding register) | ||
516 | |10 (write values to multiple addresses ) | ||
517 | |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers) | ||
518 | |06 (write single register: write a binary value to a holding register) | ||
519 | |10 (write values to multiple addresses ) | ||
520 | |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers) | ||
521 | |06 (write single register: write a binary value to a holding register) | ||
522 | |10 (write values to multiple addresses ) | ||
523 | |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers) | ||
524 | |10 (write values to multiple addresses ) | ||
525 | |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state) | ||
526 | |05 (Force a single coil to force the on/off state of a logic coil) | ||
527 | |0F (Write multiple bits, ie write continuously) | ||
528 | |(% rowspan="3" %)1|02 (Read the input state) | ||
529 | |05 (Force a single coil to force the on/off state of a logic coil) | ||
530 | |0F (Write multiple bits) | ||
531 | |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils) | ||
532 | |05 (Force a single coil to force the on/off state of a logic coil) | ||
533 | |0F (Write multiple bits) | ||
534 | |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils) | ||
535 | |0F (Write multiple bits) | ||
536 | |||
![]() |
52.1 | 537 | == **Communicate with VB inverter** == |
538 | |||
539 | [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20VB%20inverter.zip]] | ||
540 | |||
![]() |
51.1 | 541 | = **User define protocol** = |
![]() |
1.1 | 542 | |
![]() |
19.1 | 543 | More serial port script instruction,please refer manual:[[Lua script function>>doc:V-BOX.V-Net.Manual.04 Lua Script.01 Lua Functions.WebHome]]~-~-->[[3.Serial port operation>>url:http://docs.we-con.com.cn/wiki/vbox/view/HMI/04.Lua%20script%20%20function%20and%20operation/01.Lua%20script%20function/#H3.Serialportoperation]] |
![]() |
1.1 | 544 | |
![]() |
10.1 | 545 | == **Read the temperature sensor.** == |
![]() |
1.1 | 546 | |
547 | the commond format is as beliow: | ||
548 | |||
549 | Send commond:01 03 02 00 00 03 04 73 | ||
550 | |||
551 | Feedback commond:01 03 06 07 F7 0E 7E B7 35 | ||
552 | |||
553 | Temperature data:07 F7,desimal = 2039,it means temperature is 20.39℃. | ||
554 | |||
555 | Humidity data:0E 7E,desimal = 3710, it mean humidity is 37.10%RH. | ||
556 | |||
557 | Script Demo: | ||
558 | |||
559 | ~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-- | ||
560 | |||
561 | function com.main() | ||
562 | ~-~-dosomething | ||
563 | openPlc() | ||
564 | end | ||
565 | function openPlc() | ||
566 | if obj then | ||
567 | ~-~- If the serial port opened,then read/write data by timing | ||
568 | |||
569 | local wri = string.pack(">HHHH",0X0103,0X0200,0X0003,0X0473) | ||
570 | local arr = reading(wri) | ||
571 | ~-~- if arr ~~=nil then | ||
572 | ~-~- if arr[1] ==33 and arr[2] ==v[2][2] and arr[3] ==v[2][3] then | ||
573 | ~-~- local A = arr[4]*256 | ||
574 | ~-~- local B = A+arr[5] | ||
575 | ~-~- addr_setword(v[1],B) | ||
576 | ~-~- end | ||
577 | ~-~- end | ||
578 | |||
579 | else | ||
580 | ~-~-judge if there is a serial object, then initialize and open the serial port | ||
581 | local configs = { | ||
582 | name = 'COM1', ~-~-Select serial port COM1 | ||
583 | mode = 485, ~-~-Communication mode RS485 | ||
584 | baud_rate = 9600, ~-~-Baud rate 9600 | ||
585 | stop_bit = 1, ~-~-stop bit 1 | ||
586 | data_len = 8, ~-~-data length 8 | ||
587 | check_bit = 'NONE', ~-~-no parity | ||
588 | |||
589 | } | ||
590 | obj,err = serial.open(configs) ~-~-Open serial port | ||
591 | if not obj then | ||
592 | print("serial open :failed", err) ~-~- Open serial port failed | ||
593 | end | ||
594 | end | ||
595 | end | ||
596 | |||
597 | function reading(wri) | ||
598 | obj:flush() ~-~- Clear serial port | ||
599 | obj:write(wri) ~-~- Write serial port | ||
600 | print(string.byte(wri,1,#wri)) | ||
601 | obj:flush() ~-~- Clear serial port | ||
602 | local readed =obj:read(9,1000) ~-~- Read 9 bytes, timeout 1 second | ||
603 | if readed and readed ~~= "" then | ||
604 | ~-~- judge that a non-empty string is read | ||
605 | print(string.byte(readed,1,#readed)) | ||
606 | a={string.byte(readed, 1, #readed)} | ||
607 | if nil ~~= a[4] and nil ~~= a[5] and nil ~~= a[6] and nil ~~= a[7] then | ||
608 | a1=a[4]*256+a[5] | ||
609 | a2=a[6]*256+a[7] | ||
610 | addr_setword("@HDW0",a1) | ||
611 | addr_setword("@HDW1",a2) | ||
612 | end | ||
613 | return {string.byte(readed, 1, #readed)} | ||
614 | elseif readed == nil then | ||
615 | print("serial read err:", err or "") | ||
616 | return nil | ||
617 | end | ||
618 | return nil | ||
619 | end | ||
620 | |||
621 | ~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~- |