1 | = (% style="color:inherit; font-family:inherit" %)**WECON PLC**(%%) = | ||
2 | |||
3 | == **LX3V Serial Protocol** == | ||
4 | |||
5 | Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM | ||
6 | |||
7 | **HMI Settings** | ||
8 | |||
9 | |**Item**|**Settings**|**Note** | ||
10 | |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM| | ||
11 | |Connection|RS422/RS485| | ||
12 | |Baud rate|9600| | ||
13 | |Data bit|7| | ||
14 | |Parity|EVEN| | ||
15 | |Stop bit|1| | ||
16 | |PLC station No.|1| | ||
17 | |||
18 | **Address List** | ||
19 | |||
20 | |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note** | ||
21 | |(% rowspan="6" %)Bit|X|X|Xo|0~~303237| | ||
22 | |Y|Y|Y o|0~~303237| | ||
23 | |M|M|M d|0~~99999| | ||
24 | |T|T|T d|0~~99999| | ||
25 | |C|C|C d|0~~99999| | ||
26 | |S|S|S d|0~~99999| | ||
27 | |(% rowspan="8" %)Word|X|X|Xo|0~~303237| | ||
28 | |Y|Y|Y o|0~~303237| | ||
29 | |M|M|M d|0~~99999| | ||
30 | |T|T|T d|0~~99999| | ||
31 | |C|C|C d|0~~199| | ||
32 | |D|D|D d|0~~7999| | ||
33 | |S|S|S d|0~~99999| | ||
34 | |SD|SD|SD d|8000~~9999| | ||
35 | |||
36 | **Cable Wiring** | ||
37 | |||
38 | * **RS422** | ||
39 | |||
40 | [[image:image-20220824120614-5.png]] | ||
41 | |||
42 | * **RS485** | ||
43 | |||
44 | [[image:image-20220824120524-3.png]] | ||
45 | |||
46 | == **LX5V Serial Protocol** == | ||
47 | |||
48 | This example introduces the establishment of serial port communication between Wecon V-BOX and LX5V. It is introduced through three parts: PLC software configuration, HMI software configuration, and hardware wiring. | ||
49 | |||
50 | **Software configuration of PLC** | ||
51 | |||
52 | **1)PLC programming software** | ||
53 | |||
54 | [[image:image-20220822172553-1.png]] | ||
55 | |||
56 | **2)New PLC project** | ||
57 | |||
58 | Click New Project and select the PLC model. | ||
59 | |||
60 | [[image:image-20220822172623-2.png]] | ||
61 | |||
62 | **3)Set Serial port parameters** | ||
63 | |||
64 | Follow the steps below to configure Serial port parameters | ||
65 | |||
66 | Baud rate:115200 | ||
67 | |||
68 | Data bit:8 | ||
69 | |||
70 | Stop bit:1 | ||
71 | |||
72 | Parity:No verification | ||
73 | |||
74 | [[image:image-20220822172657-3.png]] | ||
75 | |||
76 | **4)Registers list** | ||
77 | |||
78 | [[image:image-20220822172730-4.png]] | ||
79 | |||
80 | **V-BOX software configuration** | ||
81 | |||
82 | **1)V-BOX programming software** | ||
83 | |||
84 | [[image:image-20220824104124-1.png]] | ||
85 | |||
86 | **2)V-NET add device** | ||
87 | |||
88 | Open V-NET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the access key, password and remark, to add the device. | ||
89 | |||
90 | [[image:image-20220824104909-2.png]] | ||
91 | |||
92 | |||
93 | **3)Set communication port parameters** | ||
94 | |||
95 | Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port. | ||
96 | |||
97 | Baud rate:115200 | ||
98 | |||
99 | Data bit:8 | ||
100 | |||
101 | Stop bit:1 | ||
102 | |||
103 | Parity:No verification | ||
104 | |||
105 | [[image:image-20220811104012-1.png]] | ||
106 | |||
107 | |||
108 | **hardware connection** | ||
109 | |||
110 | **1)Hardware wiring diagram** | ||
111 | |||
112 | This example introduces WeconHMI with LX5V PLC to establish communication through serial port. The connection diagram is as follows: | ||
113 | |||
114 | |||
115 | |||
116 | [[image:image-20220811103005-4.png]] | ||
117 | |||
118 | [[image:image-20220811103227-7.png]] | ||
119 | |||
120 | The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC. | ||
121 | |||
122 | == **LX5V-N Ethernet protocol** == | ||
123 | |||
124 | This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V. It is introduced through three parts: PLC software configuration, HMI software configuration, and hardware wiring. | ||
125 | |||
126 | **Software configuration of PLC** | ||
127 | |||
128 | **1)PLC programming software** | ||
129 | |||
130 | [[image:image-20220810164710-1.png]] | ||
131 | |||
132 | **2)New PLC project** | ||
133 | |||
134 | Click New Project and select the PLC model. | ||
135 | |||
136 | [[image:image-20220811115454-1.png]] | ||
137 | |||
138 | **3)Set Ethernet port parameters** | ||
139 | |||
140 | Follow the steps below to configure Ethernet parameters | ||
141 | |||
142 | PLC IP address:192.168.39.200 | ||
143 | |||
144 | default gateway:192.168.39.1 | ||
145 | |||
146 | subnet mask:255.255.255.0 | ||
147 | |||
148 | [[image:image-20220811140530-2.png]] | ||
149 | |||
150 | **4)Registers list** | ||
151 | |||
152 | [[image:image-20220811102219-3.png]] | ||
153 | |||
154 | **HMI software configuration** | ||
155 | |||
156 | **1)HMI programming software** | ||
157 | |||
158 | [[image:image-20220810171237-4.png]] | ||
159 | |||
160 | **2)New HMI project** | ||
161 | |||
162 | Click New Project and select the HMI model. | ||
163 | |||
164 | [[image:image-20220810172010-5.png]] | ||
165 | |||
166 | **3)Set communication port parameters** | ||
167 | |||
168 | Click the project setting button on the left to configure the IP address of the HMI machine to ensure that the HMI and PLC IP remain in a local area network. | ||
169 | |||
170 | HMI IP address:192.168.39.201 | ||
171 | |||
172 | default gateway:192.168.39.1 | ||
173 | |||
174 | subnet mask:255.255.255.0 | ||
175 | |||
176 | [[image:image-20220811170753-2.png]] | ||
177 | |||
178 | Next, click Communication Settings to configure the IP of the HMI communication object. | ||
179 | |||
180 | [[image:image-20220811163047-1.png]] | ||
181 | |||
182 | **hardware connection** | ||
183 | |||
184 | **1)Hardware wiring diagram** | ||
185 | |||
186 | This example introduces WeconHMI with LX5V-N PLC to establish communication through ethernet. The connection diagram is as follows: | ||
187 | |||
188 | [[image:image-20220811170248-1.png]] | ||
189 | |||
190 | The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC. | ||
191 | |||
192 | (% style="text-align:center" %) | ||
193 | [[image:1624348978863-771.png||queryString="width=812&height=494" height="487" width="800" class="img-thumbnail"]] | ||
194 | |||
195 | = **Rockwell PLC** = | ||
196 | |||
197 | == (% id="cke_bm_5621S" style="display:none" %)** **(%%)**MicroLogix Protocol** == | ||
198 | |||
199 | MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5 | ||
200 | |||
201 | **HMI Settings** | ||
202 | |||
203 | |**Item**|**Settings**|**Note** | ||
204 | |Protocol|Allen-Bradlley MicroLogix| | ||
205 | |Connection|RS232| | ||
206 | |Baud rate|19200| | ||
207 | |Data bit|8| | ||
208 | |Parity|None| | ||
209 | |Stop bit|1| | ||
210 | |PLC station No.|1| | ||
211 | |||
212 | **Address List** | ||
213 | |||
214 | |**Type**|**Device registers**|**Format**|**Range**|**Note** | ||
215 | |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15| | ||
216 | |O|O d.d|0.0~~255.15| | ||
217 | |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex) | ||
218 | |S|S d.d|0.0~~255.15| | ||
219 | |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex) | ||
220 | |(% rowspan="9" %)Word|S|S d|0~~255| | ||
221 | |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex) | ||
222 | |TP|TP nnhh|0~~ffff | ||
223 | |CS|CS nnhh|0~~ffff | ||
224 | |CP|CP nnhh|0~~ffff | ||
225 | |N|N nnhh|0~~ffff | ||
226 | |C|C nnhh|0~~ffff | ||
227 | |T|T nnhh|0~~ffff | ||
228 | |R|R nnhh|0~~ffff | ||
229 | |||
230 | **Cable Wiring** | ||
231 | |||
232 | [[image:image-20220824110724-1.png]] | ||
233 | |||
234 | |||
235 | |||
236 | == **CompactLogix Protocol** == | ||
237 | |||
238 | ((( | ||
239 | ((( | ||
240 | This example introduces the establishment of Ethernet communication between Wecon V-box and CompactLogix L1769. It is introduced through three parts: PLC software configuration, V-box software configuration, and hardware wiring. | ||
241 | ))) | ||
242 | ))) | ||
243 | |||
244 | ((( | ||
245 | (% class="wikigeneratedid" id="HSoftwareconfigurationofPLC" %) | ||
246 | ((( | ||
247 | **Software configuration of PLC** | ||
248 | ))) | ||
249 | |||
250 | (% class="wikigeneratedid" id="HPLCprogrammingsoftware" %) | ||
251 | ((( | ||
252 | **1)PLC programming software** | ||
253 | ))) | ||
254 | |||
255 | [[image:image-20220714162600-1.png]] | ||
256 | |||
257 | (% class="wikigeneratedid" id="HNewPLCproject" %) | ||
258 | ((( | ||
259 | **2)New PLC project** | ||
260 | ))) | ||
261 | |||
262 | ((( | ||
263 | ((( | ||
264 | Click New Project and select the PLC model. | ||
265 | ))) | ||
266 | ))) | ||
267 | |||
268 | ((( | ||
269 | [[image:image-20220714162617-2.png]] | ||
270 | ))) | ||
271 | |||
272 | ((( | ||
273 | |||
274 | |||
275 | [[image:image-20220714162652-4.png]] | ||
276 | ))) | ||
277 | |||
278 | ((( | ||
279 | (% class="wikigeneratedid" id="HSetEthernetparameters" %) | ||
280 | ((( | ||
281 | **3)Set Ethernet parameters** | ||
282 | ))) | ||
283 | |||
284 | ((( | ||
285 | ((( | ||
286 | ((( | ||
287 | Follow the steps below to configure Ethernet parameters | ||
288 | ))) | ||
289 | ))) | ||
290 | ))) | ||
291 | |||
292 | ((( | ||
293 | ((( | ||
294 | ((( | ||
295 | PLC IP address:192.168.40.101 | ||
296 | ))) | ||
297 | ))) | ||
298 | ))) | ||
299 | |||
300 | ((( | ||
301 | ((( | ||
302 | ((( | ||
303 | default gateway:192.168.40.1 | ||
304 | ))) | ||
305 | ))) | ||
306 | ))) | ||
307 | |||
308 | ((( | ||
309 | ((( | ||
310 | ((( | ||
311 | subnet mask:255.255.255.0 | ||
312 | ))) | ||
313 | ))) | ||
314 | ))) | ||
315 | |||
316 | ((( | ||
317 | [[image:image-20220714162713-5.png]] | ||
318 | ))) | ||
319 | |||
320 | ((( | ||
321 | |||
322 | ))) | ||
323 | |||
324 | ((( | ||
325 | (% class="wikigeneratedid" id="HV-boxsoftwareconfiguration" %) | ||
326 | ((( | ||
327 | **V-box software configuration** | ||
328 | ))) | ||
329 | |||
330 | (% class="wikigeneratedid" id="HV-boxprogrammingsoftware" %) | ||
331 | ((( | ||
332 | **1)V-box programming software** | ||
333 | ))) | ||
334 | |||
335 | (% class="wikigeneratedid" %) | ||
336 | ((( | ||
337 | [[image:image-20220714162725-6.png]] | ||
338 | ))) | ||
339 | |||
340 | (% class="wikigeneratedid" id="HConfiguredevicenetwork" %) | ||
341 | ((( | ||
342 | **2)Configure device network** | ||
343 | ))) | ||
344 | |||
345 | ((( | ||
346 | ((( | ||
347 | ((( | ||
348 | Click the Configuration Download button[[image:image-20220714115308-8.png||height="22" width="15"]], It is used to configure the device network, update the device time, obtain the device machine code, check the device network, etc. | ||
349 | ))) | ||
350 | |||
351 | ((( | ||
352 | In the example below, the IP address of V-Box is configured as 192.168.40.66, and the networking method is 4G connection | ||
353 | ))) | ||
354 | ))) | ||
355 | ))) | ||
356 | |||
357 | ((( | ||
358 | ((( | ||
359 | [[image:image-20220714162737-7.png]] | ||
360 | |||
361 | |||
362 | ))) | ||
363 | ))) | ||
364 | ))) | ||
365 | ))) | ||
366 | |||
367 | (% class="wikigeneratedid" id="HV-netadddevice" %) | ||
368 | ((( | ||
369 | **3)V-net add device** | ||
370 | ))) | ||
371 | ))) | ||
372 | |||
373 | ((( | ||
374 | ((( | ||
375 | Open VNET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the device machine code/product code, device password, and device alias to add the device. [[image:image-20220714162752-8.png]] | ||
376 | ))) | ||
377 | |||
378 | |||
379 | ))) | ||
380 | |||
381 | ((( | ||
382 | (% class="wikigeneratedid" id="HSetcommunicationportparameters" %) | ||
383 | ((( | ||
384 | **4)Set communication port parameters** | ||
385 | ))) | ||
386 | |||
387 | ((( | ||
388 | In the device list on the left, find the Vbox that communicates with the L1769, click it and select configuration,communication port configuration in the main interface to add a communication protocol. | ||
389 | ))) | ||
390 | |||
391 | [[image:image-20220714162805-9.png]] | ||
392 | ))) | ||
393 | |||
394 | ((( | ||
395 | The communication port is selected as Ethernet, the device type is selected as Allen-Bradley, the protocol is Allen-BradleyMicro850_FreeTag EthemetIP, and the IP is the internal IP address of the L1769 PLC. The port number is 44818. | ||
396 | ))) | ||
397 | |||
398 | [[image:image-20220714162814-10.png]] | ||
399 | |||
400 | |||
401 | ((( | ||
402 | After adding the protocol Allen-BradleyMicro850_FreeTag, click[[image:image-20220714143838-2.png]]icon add label.[[image:image-20220714162827-11.png]] | ||
403 | ))) | ||
404 | |||
405 | (% class="wikigeneratedid" id="HEngineeringproduction" %) | ||
406 | ((( | ||
407 | **5)Engineering production** | ||
408 | ))) | ||
409 | |||
410 | (% class="wikigeneratedid" %) | ||
411 | ((( | ||
412 | ((( | ||
413 | According to your own needs, use the V-NET client software to edit the required data monitoring points. | ||
414 | ))) | ||
415 | |||
416 | [[image:image-20220714162841-12.png]] | ||
417 | |||
418 | |||
419 | ((( | ||
420 | **hardware connection** | ||
421 | ))) | ||
422 | ))) | ||
423 | |||
424 | ((( | ||
425 | **1)Hardware wiring diagram** | ||
426 | ))) | ||
427 | |||
428 | ((( | ||
429 | ((( | ||
430 | This example introduces Wecon V-box with Allen-Bradley L1769 PLC to establish communication through Ethernet. The connection diagram is as follows: | ||
431 | ))) | ||
432 | |||
433 | [[image:image-20220714162856-13.png]] | ||
434 | |||
435 | ((( | ||
436 | The above are all the steps for establishing Ethernet communication between Wecon V-box with CompactLogix L1769 PLC. | ||
437 | |||
438 | |||
439 | == **Allen-Bradley Ethernet DF1** == | ||
440 | |||
441 | [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Allen-Bradley%20Ethernet%20DF1.zip]] | ||
442 | |||
443 | |||
444 | = **Siemens PLC** = | ||
445 | |||
446 | == **S7-200 Smart Ethernet Protocol** == | ||
447 | |||
448 | [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20S7-200%20Smart.zip]] | ||
449 | ))) | ||
450 | ))) | ||
451 | |||
452 | == **S7-1200 Ethernet Protocol** == | ||
453 | |||
454 | [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]] | ||
455 | |||
456 | = **Mitsubishi PLC** = | ||
457 | |||
458 | == **Mitsubishi FX Series Protocol** == | ||
459 | |||
460 | [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20Mitsubishi%20FX%20Series.zip]] | ||
461 | |||
462 | = **Delta PLC** = | ||
463 | |||
464 | == **DVP Ethernet Protocol** == | ||
465 | |||
466 | [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Delta%20DVP%20Ethernet.zip]] | ||
467 | |||
468 | == **DVP Serial Protocol** == | ||
469 | |||
470 | [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Delta%20DVP%20Ethernet.zip]] | ||
471 | |||
472 | = **Omron PLC** = | ||
473 | |||
474 | == **CP1 Series Protocol** == | ||
475 | |||
476 | [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CP1%20Series.zip]] | ||
477 | |||
478 | == **CJ2M Series Protocol** == | ||
479 | |||
480 | [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CJ2M.zip]] | ||
481 | |||
482 | = **Modbus RTU** = | ||
483 | |||
484 | == **V-BOX as master** == | ||
485 | |||
486 | Select the protocol “(% class="mark" %)Modbus RTU Slave(All Fuction)”, | ||
487 | |||
488 | (% class="mark" %)then set BaudRate,Port,Stop Bit,Data Bit,Parity | ||
489 | |||
490 | (% style="text-align:center" %) | ||
491 | [[image:1624342015914-382.png||height="486" width="800" class="img-thumbnail"]] | ||
492 | |||
493 | == **V-BOX as slave** == | ||
494 | |||
495 | Select the protocol “(% class="mark" %)**Modbus RTU Master”**, | ||
496 | |||
497 | (% class="mark" %)then set BaudRate,Port,Stop Bit,Data Bit,Parity | ||
498 | |||
499 | (% style="text-align:center" %) | ||
500 | [[image:1624348709622-711.png||queryString="width=809&height=493" height="488" width="800" class="img-thumbnail"]] | ||
501 | |||
502 | **Address List** | ||
503 | |||
504 | (% class="table-bordered" %) | ||
505 | |**Type**|**Register**|**Function code & Description** | ||
506 | |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers) | ||
507 | |06 (write single register: write a binary value to a holding register) | ||
508 | |10 (write values to multiple addresses ) | ||
509 | |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers) | ||
510 | |06 (write single register: write a binary value to a holding register) | ||
511 | |10 (write values to multiple addresses ) | ||
512 | |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers) | ||
513 | |06 (write single register: write a binary value to a holding register) | ||
514 | |10 (write values to multiple addresses ) | ||
515 | |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers) | ||
516 | |10 (write values to multiple addresses ) | ||
517 | |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state) | ||
518 | |05 (Force a single coil to force the on/off state of a logic coil) | ||
519 | |0F (Write multiple bits, ie write continuously) | ||
520 | |(% rowspan="3" %)1|02 (Read the input state) | ||
521 | |05 (Force a single coil to force the on/off state of a logic coil) | ||
522 | |0F (Write multiple bits) | ||
523 | |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils) | ||
524 | |05 (Force a single coil to force the on/off state of a logic coil) | ||
525 | |0F (Write multiple bits) | ||
526 | |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils) | ||
527 | |0F (Write multiple bits) | ||
528 | |||
529 | == **communicate with VB inverter** == | ||
530 | |||
531 | [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20VB%20inverter.zip]] | ||
532 | |||
533 | = **User define protocol** = | ||
534 | |||
535 | More serial port script instruction,please refer manual:[[Lua script function>>doc:V-BOX.V-Net.Manual.04 Lua Script.01 Lua Functions.WebHome]]~-~-->[[3.Serial port operation>>url:http://docs.we-con.com.cn/wiki/vbox/view/HMI/04.Lua%20script%20%20function%20and%20operation/01.Lua%20script%20function/#H3.Serialportoperation]] | ||
536 | |||
537 | == **Read the temperature sensor.** == | ||
538 | |||
539 | the commond format is as beliow: | ||
540 | |||
541 | Send commond:01 03 02 00 00 03 04 73 | ||
542 | |||
543 | Feedback commond:01 03 06 07 F7 0E 7E B7 35 | ||
544 | |||
545 | Temperature data:07 F7,desimal = 2039,it means temperature is 20.39℃. | ||
546 | |||
547 | Humidity data:0E 7E,desimal = 3710, it mean humidity is 37.10%RH. | ||
548 | |||
549 | Script Demo: | ||
550 | |||
551 | ~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-- | ||
552 | |||
553 | function com.main() | ||
554 | ~-~-dosomething | ||
555 | openPlc() | ||
556 | end | ||
557 | function openPlc() | ||
558 | if obj then | ||
559 | ~-~- If the serial port opened,then read/write data by timing | ||
560 | |||
561 | local wri = string.pack(">HHHH",0X0103,0X0200,0X0003,0X0473) | ||
562 | local arr = reading(wri) | ||
563 | ~-~- if arr ~~=nil then | ||
564 | ~-~- if arr[1] ==33 and arr[2] ==v[2][2] and arr[3] ==v[2][3] then | ||
565 | ~-~- local A = arr[4]*256 | ||
566 | ~-~- local B = A+arr[5] | ||
567 | ~-~- addr_setword(v[1],B) | ||
568 | ~-~- end | ||
569 | ~-~- end | ||
570 | |||
571 | else | ||
572 | ~-~-judge if there is a serial object, then initialize and open the serial port | ||
573 | local configs = { | ||
574 | name = 'COM1', ~-~-Select serial port COM1 | ||
575 | mode = 485, ~-~-Communication mode RS485 | ||
576 | baud_rate = 9600, ~-~-Baud rate 9600 | ||
577 | stop_bit = 1, ~-~-stop bit 1 | ||
578 | data_len = 8, ~-~-data length 8 | ||
579 | check_bit = 'NONE', ~-~-no parity | ||
580 | |||
581 | } | ||
582 | obj,err = serial.open(configs) ~-~-Open serial port | ||
583 | if not obj then | ||
584 | print("serial open :failed", err) ~-~- Open serial port failed | ||
585 | end | ||
586 | end | ||
587 | end | ||
588 | |||
589 | function reading(wri) | ||
590 | obj:flush() ~-~- Clear serial port | ||
591 | obj:write(wri) ~-~- Write serial port | ||
592 | print(string.byte(wri,1,#wri)) | ||
593 | obj:flush() ~-~- Clear serial port | ||
594 | local readed =obj:read(9,1000) ~-~- Read 9 bytes, timeout 1 second | ||
595 | if readed and readed ~~= "" then | ||
596 | ~-~- judge that a non-empty string is read | ||
597 | print(string.byte(readed,1,#readed)) | ||
598 | a={string.byte(readed, 1, #readed)} | ||
599 | if nil ~~= a[4] and nil ~~= a[5] and nil ~~= a[6] and nil ~~= a[7] then | ||
600 | a1=a[4]*256+a[5] | ||
601 | a2=a[6]*256+a[7] | ||
602 | addr_setword("@HDW0",a1) | ||
603 | addr_setword("@HDW1",a2) | ||
604 | end | ||
605 | return {string.byte(readed, 1, #readed)} | ||
606 | elseif readed == nil then | ||
607 | print("serial read err:", err or "") | ||
608 | return nil | ||
609 | end | ||
610 | return nil | ||
611 | end | ||
612 | |||
613 | ~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~- |