Ben 52.1 1 = (% style="color:inherit; font-family:inherit" %)**WECON PLC**(%%) =
Leo Wei 1.1 2
Ben 63.1 3 == **LX3V Serial Protocol** ==
Ben 31.1 4
Ben 20.1 5 Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
Leo Wei 1.1 6
Ben 81.1 7 **1)PLC Settings**
Leo Wei 1.1 8
Ben 20.1 9 |**Item**|**Settings**|**Note**
10 |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
11 |Connection|RS422/RS485|
12 |Baud rate|9600|
13 |Data bit|7|
14 |Parity|EVEN|
15 |Stop bit|1|
16 |PLC station No.|1|
Leo Wei 1.1 17
Ben 82.1 18 **2)PLC Address List**
Ben 20.1 19
20 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
21 |(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
22 |Y|Y|Y o|0~~303237|
23 |M|M|M d|0~~99999|
24 |T|T|T d|0~~99999|
25 |C|C|C d|0~~99999|
26 |S|S|S d|0~~99999|
27 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
28 |Y|Y|Y o|0~~303237|
29 |M|M|M d|0~~99999|
30 |T|T|T d|0~~99999|
31 |C|C|C d|0~~199|
32 |D|D|D d|0~~7999|
33 |S|S|S d|0~~99999|
34 |SD|SD|SD d|8000~~9999|
35
Ben 83.1 36 **3)Configure the communication protocol**
Ben 20.1 37
Ben 80.1 38 [[image:image-20220824152217-1.png]]
39
Ben 83.1 40 **4)hardware connection**
Ben 80.1 41
Ben 20.1 42 * **RS422**
43
Ben 69.1 44 [[image:image-20220824120614-5.png]]
Ben 20.1 45
Ben 68.1 46 * **RS485**
47
Ben 69.1 48 [[image:image-20220824120524-3.png]]
Ben 68.1 49
Ben 63.1 50 == **LX5V Serial Protocol** ==
Ben 28.1 51
Ben 84.1 52 This example introduces the establishment of serial port communication between V-BOX and LX5V. It is introduced through three parts: PLC software configuration, V-BOX software configuration, and hardware wiring.
Ben 20.1 53
54 **Software configuration of PLC**
55
56 **1)PLC programming software**
57
Ben 71.1 58 [[image:image-20220824142722-1.png]]
Ben 20.1 59
60 **2)New PLC project**
61
62 Click New Project and select the PLC model.
63
Ben 33.1 64 [[image:image-20220822172623-2.png]]
Ben 20.1 65
66 **3)Set Serial port parameters**
67
68 Follow the steps below to configure Serial port parameters
69
70 Baud rate:115200
71
72 Data bit:8
73
74 Stop bit:1
75
76 Parity:No verification
77
Ben 33.1 78 [[image:image-20220822172657-3.png]]
Ben 20.1 79
80 **4)Registers list**
81
Ben 33.1 82 [[image:image-20220822172730-4.png]]
Ben 20.1 83
Ben 33.1 84 **V-BOX software configuration**
Ben 28.1 85
Ben 35.1 86 **1)V-BOX programming software**
Ben 20.1 87
Ben 35.1 88 [[image:image-20220824104124-1.png]]
Ben 20.1 89
Ben 35.1 90 **2)V-NET add device**
Ben 20.1 91
Ben 35.1 92 Open V-NET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the access key, password and remark, to add the device.
Ben 20.1 93
Ben 35.1 94 [[image:image-20220824104909-2.png]]
Ben 20.1 95
96 **3)Set communication port parameters**
97
98 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
99
100 Baud rate:115200
101
102 Data bit:8
103
104 Stop bit:1
105
106 Parity:No verification
107
Ben 70.1 108 [[image:image-20220824142130-1.png]]
Ben 20.1 109
110 **hardware connection**
111
112 **1)Hardware wiring diagram**
113
Ben 70.1 114 [[image:image-20220824142546-2.png]]
Ben 28.1 115
Ben 70.1 116 [[image:image-20220824142643-3.png]]
Ben 28.1 117
Ben 74.1 118 The above are all the steps for establishing serial port communication between V-BOX with LX5V PLC.
Ben 20.1 119
Ben 63.1 120 == **LX5V-N Ethernet protocol** ==
Ben 20.1 121
Ben 77.1 122 This example introduces the establishment of Ethernet communication between V-BOX and LX5V-N. It is introduced through three parts: PLC software configuration, V-BOX software configuration, and hardware wiring.
Ben 20.1 123
124 **Software configuration of PLC**
125
126 **1)PLC programming software**
127
Ben 72.1 128 [[image:image-20220824142722-1.png]]
Ben 20.1 129
130 **2)New PLC project**
131
132 Click New Project and select the PLC model.
133
Ben 73.1 134 [[image:image-20220824143613-1.png]]
Ben 20.1 135
136 **3)Set Ethernet port parameters**
137
138 Follow the steps below to configure Ethernet parameters
139
140 PLC IP address:192.168.39.200
141
142 default gateway:192.168.39.1
143
144 subnet mask:255.255.255.0
145
Ben 73.1 146 [[image:image-20220824143744-2.png]]
Ben 20.1 147
148 **4)Registers list**
149
Ben 74.1 150 [[image:image-20220822172730-4.png]]
Ben 20.1 151
Ben 74.1 152 (% id="cke_bm_22473S" style="display:none" %)** **(%%)**V-BOX software configuration**
Ben 20.1 153
Ben 74.1 154 **1)V-BOX programming software**
Ben 20.1 155
Ben 74.1 156 [[image:image-20220824104124-1.png]]
Ben 20.1 157
Ben 74.1 158 **2)V-NET add device**
Ben 20.1 159
Ben 74.1 160 Open V-NET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the access key, password and remark, to add the device.
Ben 20.1 161
Ben 74.1 162 [[image:image-20220824104909-2.png]]
Ben 20.1 163
Ben 79.1 164 **3)Set communication Protocol**
Ben 20.1 165
Ben 74.1 166 Click Communication to configure the LX5V plc protocol and IP address.
Ben 20.1 167
Ben 74.1 168 [[image:image-20220824144619-1.png]]
Ben 20.1 169
170 **hardware connection**
171
172 **1)Hardware wiring diagram**
173
Ben 74.1 174 [[image:image-20220824151127-2.png]]
Ben 20.1 175
Ben 74.1 176 The above are all the steps for establishing ethernet communication between V-BOX with LX5V PLC.
Ben 20.1 177
Ben 23.1 178 = **Rockwell PLC** =
Ben 22.1 179
Ben 63.1 180 == (% id="cke_bm_5621S" style="display:none" %)** **(%%)**MicroLogix Protocol** ==
Ben 37.1 181
182 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
183
Ben 87.1 184 **1)PLC Settings**
Ben 37.1 185
186 |**Item**|**Settings**|**Note**
Ben 85.1 187 |Protocol|Allen-Bradlley DF1 Advanced|
Ben 37.1 188 |Connection|RS232|
189 |Baud rate|19200|
190 |Data bit|8|
191 |Parity|None|
192 |Stop bit|1|
193 |PLC station No.|1|
194
Ben 87.1 195 **2)Address List**
Ben 37.1 196
197 |**Type**|**Device registers**|**Format**|**Range**|**Note**
198 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
199 |O|O d.d|0.0~~255.15|
200 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
201 |S|S d.d|0.0~~255.15|
202 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
203 |(% rowspan="9" %)Word|S|S d|0~~255|
204 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
205 |TP|TP nnhh|0~~ffff
206 |CS|CS nnhh|0~~ffff
207 |CP|CP nnhh|0~~ffff
208 |N|N nnhh|0~~ffff
209 |C|C nnhh|0~~ffff
210 |T|T nnhh|0~~ffff
211 |R|R nnhh|0~~ffff
212
Ben 86.1 213 **3)Configure the communication protocol**[[image:image-20220824152928-1.png]]
Ben 85.1 214
Ben 87.1 215 **4)Configure the communication protocol**
Ben 37.1 216
217 [[image:image-20220824110724-1.png]]
218
Ben 63.1 219 == **CompactLogix Protocol** ==
Ben 37.1 220
Ben 11.1 221 (((
Ben 16.1 222 (((
Ben 38.1 223 This example introduces the establishment of Ethernet communication between Wecon V-box and CompactLogix L1769. It is introduced through three parts: PLC software configuration, V-box software configuration, and hardware wiring.
Ben 16.1 224 )))
Ben 11.1 225 )))
226
227 (((
Ben 15.1 228 (% class="wikigeneratedid" id="HSoftwareconfigurationofPLC" %)
229 (((
230 **Software configuration of PLC**
Ben 11.1 231 )))
232
Ben 15.1 233 (% class="wikigeneratedid" id="HPLCprogrammingsoftware" %)
Ben 11.1 234 (((
Ben 15.1 235 **1)PLC programming software**
236 )))
Ben 11.1 237
Ben 17.1 238 [[image:image-20220714162600-1.png]]
Ben 11.1 239
Ben 15.1 240 (% class="wikigeneratedid" id="HNewPLCproject" %)
Ben 11.1 241 (((
Ben 15.1 242 **2)New PLC project**
Ben 11.1 243 )))
244
245 (((
Ben 16.1 246 (((
Ben 15.1 247 Click New Project and select the PLC model.
Ben 11.1 248 )))
Ben 16.1 249 )))
Ben 11.1 250
251 (((
Ben 17.1 252 [[image:image-20220714162617-2.png]]
Ben 11.1 253 )))
254
255 (((
Ben 17.1 256
Ben 16.1 257
Ben 17.1 258 [[image:image-20220714162652-4.png]]
Ben 11.1 259 )))
260
261 (((
Ben 15.1 262 (% class="wikigeneratedid" id="HSetEthernetparameters" %)
263 (((
264 **3)Set Ethernet parameters**
265 )))
Ben 11.1 266
267 (((
Ben 15.1 268 (((
Ben 16.1 269 (((
Ben 11.1 270 Follow the steps below to configure Ethernet parameters
271 )))
Ben 15.1 272 )))
Ben 16.1 273 )))
Ben 11.1 274
275 (((
Ben 15.1 276 (((
Ben 16.1 277 (((
Ben 11.1 278 PLC IP address:192.168.40.101
279 )))
Ben 15.1 280 )))
Ben 16.1 281 )))
Ben 11.1 282
283 (((
Ben 15.1 284 (((
Ben 16.1 285 (((
Ben 11.1 286 default gateway:192.168.40.1
287 )))
Ben 15.1 288 )))
Ben 16.1 289 )))
Ben 11.1 290
291 (((
Ben 15.1 292 (((
Ben 16.1 293 (((
Ben 11.1 294 subnet mask:255.255.255.0
295 )))
Ben 15.1 296 )))
Ben 16.1 297 )))
Ben 11.1 298
299 (((
Ben 17.1 300 [[image:image-20220714162713-5.png]]
Ben 11.1 301 )))
302
303 (((
304
305 )))
306
307 (((
Ben 15.1 308 (% class="wikigeneratedid" id="HV-boxsoftwareconfiguration" %)
309 (((
310 **V-box software configuration**
311 )))
Ben 11.1 312
Ben 15.1 313 (% class="wikigeneratedid" id="HV-boxprogrammingsoftware" %)
314 (((
315 **1)V-box programming software**
316 )))
Ben 11.1 317
Ben 15.1 318 (% class="wikigeneratedid" %)
319 (((
Ben 17.1 320 [[image:image-20220714162725-6.png]]
Ben 15.1 321 )))
Ben 11.1 322
Ben 15.1 323 (% class="wikigeneratedid" id="HConfiguredevicenetwork" %)
324 (((
325 **2)Configure device network**
326 )))
Ben 11.1 327
328 (((
Ben 15.1 329 (((
Ben 16.1 330 (((
Ben 11.1 331 Click the Configuration Download button[[image:image-20220714115308-8.png||height="22" width="15"]], It is used to configure the device network, update the device time, obtain the device machine code, check the device network, etc.
332 )))
Ben 16.1 333
334 (((
335 In the example below, the IP address of V-Box is configured as 192.168.40.66, and the networking method is 4G connection
Ben 15.1 336 )))
Ben 16.1 337 )))
338 )))
Ben 11.1 339
340 (((
Ben 15.1 341 (((
Ben 17.1 342 [[image:image-20220714162737-7.png]]
Ben 16.1 343
344
Ben 11.1 345 )))
346 )))
347 )))
348 )))
349
Ben 15.1 350 (% class="wikigeneratedid" id="HV-netadddevice" %)
Ben 11.1 351 (((
Ben 15.1 352 **3)V-net add device**
Ben 11.1 353 )))
Ben 15.1 354 )))
Ben 11.1 355
356 (((
Ben 16.1 357 (((
Ben 21.1 358 Open VNET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the device machine code/product code, device password, and device alias to add the device.   [[image:image-20220714162752-8.png]]
Ben 11.1 359 )))
360
361
362 )))
363
364 (((
Ben 15.1 365 (% class="wikigeneratedid" id="HSetcommunicationportparameters" %)
366 (((
367 **4)Set communication port parameters**
368 )))
Ben 11.1 369
Ben 16.1 370 (((
371 In the device list on the left, find the Vbox that communicates with the L1769, click it and select configuration,communication port configuration in the main interface to add a communication protocol.
Ben 11.1 372 )))
373
Ben 17.1 374 [[image:image-20220714162805-9.png]]
Ben 16.1 375 )))
376
377 (((
Ben 11.1 378 The communication port is selected as Ethernet, the device type is selected as Allen-Bradley, the protocol is Allen-BradleyMicro850_FreeTag EthemetIP, and the IP is the internal IP address of the L1769 PLC. The port number is 44818.
Ben 16.1 379 )))
Ben 11.1 380
Ben 17.1 381 [[image:image-20220714162814-10.png]]
Ben 11.1 382
383
Ben 16.1 384 (((
Ben 22.1 385 After adding the protocol Allen-BradleyMicro850_FreeTag, click[[image:image-20220714143838-2.png]]icon add label.[[image:image-20220714162827-11.png]]
Ben 16.1 386 )))
Ben 14.1 387
Ben 16.1 388 (% class="wikigeneratedid" id="HEngineeringproduction" %)
389 (((
390 **5)Engineering production**
391 )))
Ben 14.1 392
Ben 16.1 393 (% class="wikigeneratedid" %)
394 (((
395 (((
396 According to your own needs, use the V-NET client software to edit the required data monitoring points.
397 )))
Ben 14.1 398
Ben 17.1 399 [[image:image-20220714162841-12.png]]
Ben 14.1 400
Ben 16.1 401
402 (((
403 **hardware connection**
404 )))
405 )))
406
407 (((
408 **1)Hardware wiring diagram**
409 )))
410
411 (((
412 (((
413 This example introduces Wecon V-box with Allen-Bradley L1769 PLC to establish communication through Ethernet. The connection diagram is as follows:
414 )))
415
Ben 17.1 416 [[image:image-20220714162856-13.png]]
Ben 16.1 417
418 (((
Ben 41.1 419 The above are all the steps for establishing Ethernet communication between Wecon V-box with CompactLogix L1769 PLC.
Ben 26.1 420
421
422 == **Allen-Bradley Ethernet DF1** ==
423
424 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Allen-Bradley%20Ethernet%20DF1.zip]]
425
426
427 = **Siemens PLC** =
Ben 61.1 428
Ben 63.1 429 == **S7-200 Smart Ethernet Protocol** ==
Ben 61.1 430
431 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20S7-200%20Smart.zip]]
Ben 88.1 432
433
Ben 89.1 434 == ** S7-300 Ethernet Protocol** ==
Ben 88.1 435
436 Supported Series: Siemens S7-300 series PLC
437
438 **HMI Setting**
439
440 |**Items**|**Settings**|**Note**
441 |Protocol|Simens S7-300 Ethernet|
442 |Connection|Ethernet|
443 |Port No.|102|
444 |PLC station No.|2|Need to be same as the PLC setting
445
446 **Address List**
447
448 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
449 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
450 |Q|Q|Q ddddd.o|0.0~~99999.7|
451 |M|M|M ddddd.o|0.0~~99999.7|
452 |DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
453 nn: block number;
454
455 dddd: address;
Ben 16.1 456 )))
Ben 88.1 457 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
458 |Q|QW|QW ddddd|0~~99999|
459 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
460 |MW|MW ddddd|0~~99999|(((
461 MW0=MB(0~~1)
462
463 MW2=MB(2~~3)
464
465 Address value is a multiple of 2
Ben 16.1 466 )))
Ben 88.1 467 |MD|MD ddddd|0~~99999|(((
468 MD0=MB(0~~3)
Ben 16.1 469
Ben 88.1 470 MD4=MB(4~~7)
471
472 Address value is a multiple of 4
473 )))
474 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
475 nn: block number;
476
477 dddd: address
478 )))
479 |DBxDBW|DBxDBW nndddd|0~~99999999
480 |DBxDBD|DBxDBD nndddd|0~~99999999
481
482 **Communication Settings**
483
484 Enable HMI Ethernet in [Project Settings];
485
486 (% style="text-align:center" %)
487 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
488
489 Set PLC IP in [Device IP] settings;
490
491 (% style="text-align:center" %)
492 [[image:12.PLC Protocol_html_910b1a0aa9e2201c.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
493
494 * PLC IP Address: PLC IP
495 * PLC pot No.: 102(fixed)
496 * Network:TCP_Client_2N(fixed)
497
498 (% style="text-align:center" %)
499 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
500
501 * Wait timeout: depend on actual network situation (more than 1500 ms)
502
503 **Cable Wiring**
504
505 (% style="text-align:center" %)
506 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
507 )))
508 )))
509
Ben 63.1 510 == **S7-1200 Ethernet Protocol** ==
Leo Wei 1.1 511
512 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]]
513
Ben 56.1 514 = **Mitsubishi PLC** =
515
Ben 63.1 516 == **Mitsubishi FX Series Protocol** ==
Ben 56.1 517
518 [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20Mitsubishi%20FX%20Series.zip]]
519
Ben 26.1 520 = **Delta PLC** =
521
Ben 64.1 522 == **DVP Ethernet Protocol** ==
Leo Wei 1.1 523
524 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Delta%20DVP%20Ethernet.zip]]
525
Ben 63.1 526 == **DVP Serial Protocol** ==
Leo Wei 1.1 527
528 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Delta%20DVP%20Ethernet.zip]]
529
Ben 48.1 530 = **Omron PLC** =
531
Ben 65.1 532 == **CP1 Series Protocol** ==
Jim 7.1 533
Jim 8.1 534 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CP1%20Series.zip]]
Jim 7.1 535
Ben 65.1 536 == **CJ2M Series Protocol** ==
Jim 7.1 537
Jim 8.1 538 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CJ2M.zip]]
Jim 7.1 539
Ben 50.1 540 = **Modbus RTU** =
541
Ben 53.1 542 == **V-BOX as master** ==
Ben 50.1 543
544 Select the protocol “(% class="mark" %)Modbus RTU Slave(All Fuction)”,
545
546 (% class="mark" %)then set BaudRate,Port,Stop Bit,Data Bit,Parity
547
548 (% style="text-align:center" %)
549 [[image:1624342015914-382.png||height="486" width="800" class="img-thumbnail"]]
550
Ben 53.1 551 == **V-BOX as slave** ==
Ben 50.1 552
553 Select the protocol “(% class="mark" %)**Modbus RTU Master”**,
554
555 (% class="mark" %)then set BaudRate,Port,Stop Bit,Data Bit,Parity
556
557 (% style="text-align:center" %)
558 [[image:1624348709622-711.png||queryString="width=809&height=493" height="488" width="800" class="img-thumbnail"]]
559
560 **Address List**
561
562 (% class="table-bordered" %)
563 |**Type**|**Register**|**Function code & Description**
564 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
565 |06 (write single register: write a binary value to a holding register)
566 |10 (write values to multiple addresses )
567 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
568 |06 (write single register: write a binary value to a holding register)
569 |10 (write values to multiple addresses )
570 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
571 |06 (write single register: write a binary value to a holding register)
572 |10 (write values to multiple addresses )
573 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
574 |10 (write values to multiple addresses )
575 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
576 |05 (Force a single coil to force the on/off state of a logic coil)
577 |0F (Write multiple bits, ie write continuously)
578 |(% rowspan="3" %)1|02 (Read the input state)
579 |05 (Force a single coil to force the on/off state of a logic coil)
580 |0F (Write multiple bits)
581 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
582 |05 (Force a single coil to force the on/off state of a logic coil)
583 |0F (Write multiple bits)
584 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
585 |0F (Write multiple bits)
586
Ben 55.1 587 == **communicate with VB inverter** ==
Ben 52.1 588
589 [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20VB%20inverter.zip]]
590
Ben 51.1 591 = **User define protocol** =
Leo Wei 1.1 592
Stone Wu 19.1 593 More serial port script instruction,please refer manual:[[Lua script function>>doc:V-BOX.V-Net.Manual.04 Lua Script.01 Lua Functions.WebHome]]~-~-->[[3.Serial port operation>>url:http://docs.we-con.com.cn/wiki/vbox/view/HMI/04.Lua%20script%20%20function%20and%20operation/01.Lua%20script%20function/#H3.Serialportoperation]]
Leo Wei 1.1 594
Stone Wu 10.1 595 == **Read the temperature sensor.** ==
Leo Wei 1.1 596
597 the commond format is as beliow:
598
599 Send commond:01 03 02 00 00 03 04 73
600
601 Feedback commond:01 03 06 07 F7 0E 7E B7 35
602
603 Temperature data:07 F7,desimal = 2039,it means temperature is 20.39℃.
604
605 Humidity data:0E 7E,desimal = 3710, it mean humidity is 37.10%RH.
606
607 Script Demo:
608
609 ~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~--
610
611 function com.main()
612 ~-~-dosomething
613 openPlc()
614 end
615 function openPlc()
616 if obj then
617 ~-~- If the serial port opened,then read/write data by timing
618
619 local wri = string.pack(">HHHH",0X0103,0X0200,0X0003,0X0473)
620 local arr = reading(wri)
621 ~-~- if arr ~~=nil then
622 ~-~- if arr[1] ==33 and arr[2] ==v[2][2] and arr[3] ==v[2][3] then
623 ~-~- local A = arr[4]*256
624 ~-~- local B = A+arr[5]
625 ~-~- addr_setword(v[1],B)
626 ~-~- end
627 ~-~- end
628
629 else
630 ~-~-judge if there is a serial object, then initialize and open the serial port
631 local configs = {
632 name = 'COM1', ~-~-Select serial port COM1
633 mode = 485, ~-~-Communication mode RS485
634 baud_rate = 9600, ~-~-Baud rate 9600
635 stop_bit = 1, ~-~-stop bit 1
636 data_len = 8, ~-~-data length 8
637 check_bit = 'NONE', ~-~-no parity
638
639 }
640 obj,err = serial.open(configs) ~-~-Open serial port
641 if not obj then
642 print("serial open :failed", err) ~-~- Open serial port failed
643 end
644 end
645 end
646
647 function reading(wri)
648 obj:flush() ~-~- Clear serial port
649 obj:write(wri) ~-~- Write serial port
650 print(string.byte(wri,1,#wri))
651 obj:flush() ~-~- Clear serial port 
652 local readed =obj:read(9,1000) ~-~- Read 9 bytes, timeout 1 second
653 if readed and readed ~~= "" then 
654 ~-~- judge that a non-empty string is read
655 print(string.byte(readed,1,#readed))
656 a={string.byte(readed, 1, #readed)}
657 if nil ~~= a[4] and nil ~~= a[5] and nil ~~= a[6] and nil ~~= a[7] then
658 a1=a[4]*256+a[5]
659 a2=a[6]*256+a[7]
660 addr_setword("@HDW0",a1)
661 addr_setword("@HDW1",a2)
662 end
663 return {string.byte(readed, 1, #readed)}
664 elseif readed == nil then
665 print("serial read err:", err or "")
666 return nil
667 end
668 return nil
669 end
670
671 ~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-