Changes for page 6 Modbus and PNP/NPN conversion
Last modified by Theodore Xu on 2024/04/10 09:11
From version 30.1
edited by Leo Wei
on 2023/12/29 09:51
on 2023/12/29 09:51
Change comment:
Deleted image "1703814552069-173.png"
To version 36.1
edited by Theodore Xu
on 2024/04/10 09:11
on 2024/04/10 09:11
Change comment:
There is no comment for this version
Summary
-
Page properties (2 modified, 0 added, 0 removed)
Details
- Page properties
-
- Author
-
... ... @@ -1,1 +1,1 @@ 1 -XWiki. admin1 +XWiki.AiXia - Content
-
... ... @@ -1,5 +3,3 @@ 1 -== [[image:1703814552069-173.png||height="402" width="739"]] == 2 - 3 3 == **Modbus** == 4 4 5 5 **Communication specifications** ... ... @@ -27,7 +27,7 @@ 27 27 28 28 **RS485 Connection Topology** 29 29 30 -RS485 bus connection topology is shown in the following figure. 485 bus is recommended to use shielded twisted pair (STP), 485+, 485-: Adopt twisted pair to connect; Only 120 Ω terminal matching resistors are connected at both ends of the bus to prevent signal reflection; All node 485 signal grounds are connected together; Connect 128 nodes at most, and the distance between branches of each node should be less than 3m. 28 +RS485 bus connection topology is shown in the following figure. 485 bus is recommended to use shielded twisted pair (STP), 485+, 485-: **Adopt twisted pair to connect**; Only 120 Ω terminal matching resistors are connected at both ends of the bus to prevent signal reflection; All node 485 signal grounds are connected together; Connect 128 nodes at most, and the distance between branches of each node should be less than 3m. 31 31 32 32 **Multi-node connection mode** 33 33 ... ... @@ -53,6 +53,11 @@ 53 53 54 54 The maximum number of nodes and transmission distance supported by our standard RS485 circuit at different rates are shown in the following table. 55 55 54 +The communication distance between the inverter and other devices should not exceed **200 meters**, if it exceeds two hundred meters it may cause unstable communication. If the communication distance **exceeds 200 meters**, the following measures need to be included: 55 + 56 +* Communication cable:Adopt twisted pair to connect 57 +* anti-interference magnetic ring 58 + 56 56 |Transmission distance (m)|Rate (kbps)|Number of nodes|Wire diameter 57 57 |100|115.2|128|AWG26 58 58 |1000|19.2|128|AWG26 ... ... @@ -63,7 +63,7 @@ 63 63 64 64 (% class="box infomessage" %) 65 65 ((( 66 -**✎Note:VM series manufactured after April 2023 can support this feature! !**69 +**✎Note:VM series manufactured after April 2023 can support this feature!** 67 67 ))) 68 68 69 69 NPN/PNP switching has been added to the VM series machines, enabling fast switching between the two modes. ... ... @@ -108,10 +108,7 @@ 108 108 109 109 The control signals of VB series products are compatible with both NPN and PNP signal types. 110 110 111 -(% class="wikigeneratedid" id="HScheme" %) 112 -**Scheme** 113 - 114 -|=**Function**|=**Address definition**|=**Data meaning** 114 +|= |=**Low-power model**|=**High-power model** 115 115 |Adapted power|((( 116 116 220V:0.75-2.2kW 117 117 ... ... @@ -255,7 +255,7 @@ 255 255 (% style="text-align:center" %) 256 256 [[image:Three-wire control mode 2.png||height="332" width="436"]] 257 257 258 -**Among them: **SB1 Stop button;SB2 Reverseand reverse control;buttons SB3 Run button;258 +**Among them: **SB1 Stop button;SB2 Forward and reverse control buttons; SB3 Run button; 259 259 260 260 Refer to the following table for running commands corresponding to switching signals: 261 261