Content
... ... @@ -297,8 +297,7 @@
297 297  
298 298  F6.02=1
299 299  
300 -=
301 -**Motor parameter setting and self-learning** =
300 += **Motor parameter setting and self-learning** =
302 302  
303 303  ~1. Familiar with the motor self-learning function.
304 304  Need to input the motor parameters F2.01, F2.02, F2.03, F2.04, F2.05 to adjust the value of F2.11 to 1 (premise F0.01=0) or 2, press ENT first, Press RUN again, the self-learning is completed when the panel returns to the monitoring interface. (Necessary operation when changing to vector control)
... ... @@ -330,10 +330,8 @@
330 330  
331 331  F5.23=2
332 332  
333 -=
334 -**Parameter protection** =
332 += **Parameter protection** =
335 335  
336 -
337 337  ~1. The protection parameters cannot be modified and the parameters are locked.
338 338  
339 339  F0.21=1
... ... @@ -342,10 +342,8 @@
342 342  
343 343  FE.00 = non-zero number
344 344  
345 -=
346 -**Set running time action** =
342 += **Set running time action** =
347 347  
348 -
349 349  ~1. The customer sells the machine to the user, worrying that the customer did not pay on time, set some parameters inside the inverter. After the inverter has been running for 10 hours, the inverter will automatically stop and cannot start. Wait for the user to pay before the machine can run. How to set parameters for such a function?
350 350  FE.00=Set password
351 351  
... ... @@ -406,10 +406,8 @@
406 406  
407 407  Control operation command address: 2000H (premise F0.01=2)
408 408  
409 -=
410 -**Safety and precautions** =
404 += **Safety and precautions** =
411 411  
412 -
413 413  ~1. Familiar with product standard technical specifications. Please refer to the manual
414 414  
415 415  = **Grounding** =
... ... @@ -418,10 +418,8 @@
418 418  ~1. Understand the meaning and function of the ground wire and connect it correctly.
419 419   The grounding terminal E of the inverter must be well grounded, the grounding resistance should be less than 102, and the grounding wire should be thick and short. Multi-strand copper core wire of 3.5mm2 or more should be used.
420 420  