355 355  
356 += **Constant pressure water supply** =
357 +
358 +The following example uses a current sensor to simulate a water pressure test, the sensor specification is 4-20mA current signal, the range is 16 bar. use the sensor to connect to the AI2 terminal port of the VB.
359 +Firstly please check the software version of **F7.11**, **F7.11 **is software version, if the **F7.11 **is greater than 2.064, please use A4 parameter group, A4 parameter group is special parameter for constant pressure water supply project.
360 +F0.20=1 factory data reset
361 +A4.00=1
362 +A4.01=set pressure
363 +A4.03=Sensor range
364 +A4.04=0
365 +
366 +If the value of F7.11 is less than or equal to 2.064, use PID parameter group F9.
367 +F0.20=1 factory data reset
368 +F0.03=8
369 +F5.23=2
370 +F9.01=Upper limit water pressure
371 +F9.02=1 (AI2)
372 +F9.28=1
373 +F9.29=Set pressure
374 +F9.31=Lower limit water pressure
375 +
376 +
377 +In the parameter setting of group F9, 20mA is the maximum value of the transducer with a range of 16bar, and F9.01/F9.29/F9.31 are the setting parameters for the water pressure in the VB in percentage. For example when the inverter is required to keep the pressure at 8bar, modify F9.29=50%. F9.01 is the upper limit of water pressure setting, it needs to be greater than or equal to F9.29, it is recommended to set F9.29=F9.01