... ... @@ -1,1 +1,1 @@
1 -XWiki.Mora
1 +XWiki.AiXia
Content
... ... @@ -353,6 +353,29 @@
353 353  
354 354  F7.05
355 355  
356 += **Constant pressure water supply** =
357 +
358 +The following example uses a current sensor to simulate a water pressure test, the sensor specification is 4-20mA current signal, the range is 16 bar. use the sensor to connect to the AI2 terminal port of the VB.
359 +Firstly please check the software version of **F7.11**, **F7.11 **is software version, if the **F7.11 **is greater than 2.064, please use A4 parameter group, A4 parameter group is special parameter for constant pressure water supply project.
360 +F0.20=1 Factory data reset
361 +A4.00=1
362 +A4.01=Set pressure
363 +A4.03=Sensor range
364 +A4.04=0
365 +
366 +If the value of F7.11 is less than or equal to 2.064, use PID parameter group F9.
367 +F0.20=1 Factory data reset
368 +F0.03=8
369 +F5.23=2
370 +F9.01=Upper limit water pressure
371 +F9.02=1 (AI2)
372 +F9.28=1
373 +F9.29=Target value
374 +F9.31=Lower limit water pressure
375 +
376 +
377 +In the parameter setting of group F9, 20mA is the maximum value of the transducer with a range of 16bar, and F9.01/F9.29/F9.31 are the setting parameters for the water pressure in the VB in percentage. For example when the inverter is required to keep the pressure at 8bar, modify F9.29=50%. F9.01 is the upper limit of water pressure setting, it is recommended to set F9.29=F9.01,of course you can set F9.01=80%,it needs to be greater than or equal to F9.29. If when the control effect of the inverter is slow or the descent time is too long, try reducing the integration time: F9.06 = 0.5 or 1.0.
378 +
356 356  = **PID function** =
357 357  
358 358  (% style="text-align:center" %)
... ... @@ -394,10 +394,6 @@
394 394  
395 395  Control operation command address: 2000H (premise F0.01=2)
396 396  
397 -= **Safety and precautions** =
398 -
399 -~1. Familiar with product standard technical specifications. Please refer to the manual
400 -
401 401  = **Grounding** =
402 402  
403 403  ~1. Understand the meaning and function of the ground wire and connect it correctly.
... ... @@ -423,20 +423,8 @@
423 423  
424 424  Braking resistor
425 425  
426 -= **Power and current value** =
427 -
428 - ~1. Familiar with the rated current of the inverter in different power ranges, please refer to the manual
429 -
430 -= **Braking resistor** =
431 -
432 - ~1. Familiar with the selection of braking resistor. Under what conditions do you need to install a braking resistor? How to install the braking resistor?
433 -
434 -Braking resistors are installed on the and PB ends of the inverter (built-in braking unit)
435 -
436 -= **Fault code and troubleshooting** =
437 -
438 - ~1. Familiar with various fault codes and countermeasures to deal with faults.
439 -
440 440  = **Installation guidance required by EMC** =
441 441  
442 442   The input terminal of the inverter has EMC screw access option.
448 +
449 +