Changes for page 4 Common function of VB
Last modified by Theodore Xu on 2025/02/27 09:58
From version 19.1
edited by Theodore Xu
on 2024/04/09 17:12
on 2024/04/09 17:12
Change comment:
There is no comment for this version
Summary
-
Page properties (4 modified, 0 added, 0 removed)
-
Attachments (0 modified, 0 added, 2 removed)
Details
- Page properties
-
- Title
-
... ... @@ -1,1 +1,1 @@ 1 - 4Common function of VB1 +Common function of VB - Parent
-
... ... @@ -1,1 +1,1 @@ 1 - VFD.WebHome1 +3\. Demo.WebHome - Author
-
... ... @@ -1,1 +1,1 @@ 1 -XWiki. AiXia1 +XWiki.admin - Content
-
... ... @@ -40,7 +40,7 @@ 40 40 41 41 F0.07=01 42 42 43 -6. 43 +6.On some equipment, two potentiometers are required to adjust the speed, one potentiometer 0-10V controls 20HZ, and the other potentiometer controls 0-10V control 25HZ so that the spindle frequency is superimposed, and the frequency is 45HZ. 44 44 45 45 F0.03=2 46 46 ... ... @@ -66,7 +66,7 @@ 66 66 67 67 = **Acceleration time** = 68 68 69 - ~1.When the device is started, the customer feels that the startup time is too long or the startup time is too short, which parameters need to be modified? (This parameter should be fine-tuned appropriately according to the equipment load. Improper setting can easily cause fault alarms such as overcurrent).69 +1 When the device is started, the customer feels that the startup time is too long or the startup time is too short, which parameters need to be modified? (This parameter should be fine-tuned appropriately according to the equipment load. Improper setting can easily cause fault alarms such as overcurrent). 70 70 71 71 F0.18 (appropriate setting) etc. 72 72 ... ... @@ -238,6 +238,7 @@ 238 238 239 239 = **Digital input function** = 240 240 241 + 241 241 ~1. Since an external switch is needed on the device to control the emergency stop of the motor, which function parameter should be set? 242 242 243 243 F5.02=10 ... ... @@ -263,11 +263,13 @@ 263 263 264 264 = **Digital output function** = 265 265 267 + 266 266 ~1. The customer needs to use the FM open-collector output function. When the inverter fails, output a switch value to make the fault alarm lamp/fault buzzer act, so that the on-site operator knows that the inverter has a fault alarm and what to do Setup and wiring? 267 267 268 268 F6.00=1 269 269 270 270 F6.01=2 273 + 271 271 272 272 2. When the inverter runs more than 20HZ, the relay T1A and T1C terminals output a switch value to control an indicator light, so that the indicator line is connected and the indicator light is on. How to set up and wire? 273 273 ... ... @@ -294,7 +294,8 @@ 294 294 295 295 F6.02=1 296 296 297 -= **Motor parameter setting and self-learning** = 300 += 301 +**Motor parameter setting and self-learning** = 298 298 299 299 ~1. Familiar with the motor self-learning function. 300 300 Need to input the motor parameters F2.01, F2.02, F2.03, F2.04, F2.05 to adjust the value of F2.11 to 1 (premise F0.01=0) or 2, press ENT first, Press RUN again, the self-learning is completed when the panel returns to the monitoring interface. (Necessary operation when changing to vector control) ... ... @@ -301,10 +301,12 @@ 301 301 302 302 = **Display monitoring** = 303 303 308 + 304 304 ~1. Master the functions of F7.03, F7.04, and F7.05, all of which are used for display and monitoring. Please refer to page 35 of the manual for details 305 305 306 306 = **Operating mode selection** = 307 307 313 + 308 308 ~1. Master the definition of each control mode of the F0.00 parameter group. 309 309 310 310 Vector control, V/F control ... ... @@ -311,6 +311,7 @@ 311 311 312 312 = **Analog signal gain** = 313 313 320 + 314 314 ~1. The user uses the AI1 terminal function, and the device is given a voltage of 0-5V for speed regulation. Which parameter should be modified accordingly? 315 315 316 316 F0.03=2 ... ... @@ -323,8 +323,10 @@ 323 323 324 324 F5.23=2 325 325 326 -= **Parameter protection** = 333 += 334 +**Parameter protection** = 327 327 336 + 328 328 ~1. The protection parameters cannot be modified and the parameters are locked. 329 329 330 330 F0.21=1 ... ... @@ -333,8 +333,10 @@ 333 333 334 334 FE.00 = non-zero number 335 335 336 -= **Set running time action** = 345 += 346 +**Set running time action** = 337 337 348 + 338 338 ~1. The customer sells the machine to the user, worrying that the customer did not pay on time, set some parameters inside the inverter. After the inverter has been running for 10 hours, the inverter will automatically stop and cannot start. Wait for the user to pay before the machine can run. How to set parameters for such a function? 339 339 FE.00=Set password 340 340 ... ... @@ -344,6 +344,7 @@ 344 344 345 345 = **Display monitoring options** = 346 346 358 + 347 347 ~1. The user requires the inverter to display only the speed during operation, which parameter should be modified? 348 348 349 349 F7.03=4000 ... ... @@ -352,34 +352,10 @@ 352 352 2. The user requires the inverter to display various states during shutdown. Which parameter can be set? 353 353 354 354 F7.05 367 + 355 355 356 -= **Constant pressure water supply** = 357 - 358 -The following example uses a current sensor to simulate a water pressure test, the sensor specification is 4-20mA current signal, the range is 16 bar. use the sensor to connect to the AI2 terminal port of the VB. 359 -Firstly please check the software version of **F7.11**, **F7.11 **is software version, if the **F7.11 **is greater than 2.064, please use A4 parameter group, A4 parameter group is special parameter for constant pressure water supply project. 360 -F0.20=1 factory data reset 361 -A4.00=1 362 -A4.01=set pressure 363 -A4.03=Sensor range 364 -A4.04=0 365 - 366 -If the value of F7.11 is less than or equal to 2.064, use PID parameter group F9. 367 -F0.20=1 factory data reset 368 -F0.03=8 369 -F5.23=2 370 -F9.01=Upper limit water pressure 371 -F9.02=1 (AI2) 372 -F9.28=1 373 -F9.29=Set pressure 374 -F9.31=Lower limit water pressure 375 - 376 - 377 -In the parameter setting of group F9, 20mA is the maximum value of the transducer with a range of 16bar, and F9.01/F9.29/F9.31 are the setting parameters for the water pressure in the VB in percentage. For example when the inverter is required to keep the pressure at 8bar, modify F9.29=50%. F9.01 is the upper limit of water pressure setting, it needs to be greater than or equal to F9.29, it is recommended to set F9.29=F9.01 378 - 379 379 = **PID function** = 380 380 381 -(% style="text-align:center" %) 382 -[[image:生产流程图.png]] 383 383 384 384 ~1. To be familiar with the PID function of constant pressure water supply, the feedback signal sources are remote pressure gauges and pressure transmitters. How to wire and which parameters should be set? For example, the maximum range of the remote pressure gauge is 1Mpa, and the current user needs to set the panel 0.45 MPa kg pressure, how to set the pressure? 385 385 F0.01=0 (panel start and stop)/1 (terminal start and stop) ... ... @@ -410,6 +410,7 @@ 410 410 411 411 = **Communication function** = 412 412 401 + 413 413 ~1. Familiar with RS485 communication function, communication address, communication speed, communication format, how to set it? Familiar with the address of communication function? 414 414 Please refer to page 129 of the manual 415 415 ... ... @@ -417,17 +417,22 @@ 417 417 418 418 Control operation command address: 2000H (premise F0.01=2) 419 419 420 -= **Safety and precautions** = 409 += 410 +**Safety and precautions** = 421 421 412 + 422 422 ~1. Familiar with product standard technical specifications. Please refer to the manual 423 423 424 424 = **Grounding** = 425 425 417 + 426 426 ~1. Understand the meaning and function of the ground wire and connect it correctly. 427 427 The grounding terminal E of the inverter must be well grounded, the grounding resistance should be less than 102, and the grounding wire should be thick and short. Multi-strand copper core wire of 3.5mm2 or more should be used. 428 428 429 -= **Peripheral lines** = 421 += 422 +**Peripheral lines** = 430 430 424 + 431 431 ~1. Understand the role of peripheral line equipment: 432 432 433 433 Open ... ... @@ -446,20 +446,30 @@ 446 446 447 447 Braking resistor 448 448 449 -= **Power and current value** = 443 += 444 +**Power and current value** = 450 450 446 + 451 451 ~1. Familiar with the rated current of the inverter in different power ranges, please refer to the manual 452 452 453 -= **Braking resistor** = 449 += 450 +**Braking resistor** = 454 454 452 + 455 455 ~1. Familiar with the selection of braking resistor. Under what conditions do you need to install a braking resistor? How to install the braking resistor? 456 456 457 457 Braking resistors are installed on the and PB ends of the inverter (built-in braking unit) 458 458 459 -= **Fault code and troubleshooting** = 457 += 458 +**Fault code and troubleshooting** = 460 460 460 + 461 461 ~1. Familiar with various fault codes and countermeasures to deal with faults. 462 462 463 -= **Installation guidance required by EMC** = 463 += 464 +**Installation guidance required by EMC** = 464 464 466 + 465 465 The input terminal of the inverter has EMC screw access option. 468 + 469 +
- PID原理图.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.AiXia - Size
-
... ... @@ -1,1 +1,0 @@ 1 -53.5 KB - Content
- 生产流程图.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.AiXia - Size
-
... ... @@ -1,1 +1,0 @@ 1 -1.0 MB - Content