... ... @@ -357,14 +357,14 @@
357 357  
358 358  The following example uses a current sensor to simulate a water pressure test, the sensor specification is 4-20mA current signal, the range is 16 bar. use the sensor to connect to the AI2 terminal port of the VB.
359 359  Firstly please check the software version of **F7.11**, **F7.11 **is software version, if the **F7.11 **is greater than 2.064, please use A4 parameter group, A4 parameter group is special parameter for constant pressure water supply project.
360 -F0.20=1 factory data reset
360 +F0.20=1 Factory data reset
361 361  A4.00=1
362 -A4.01=set pressure
362 +A4.01=Set pressure
363 363  A4.03=Sensor range
364 364  A4.04=0
365 365  
366 366  If the value of F7.11 is less than or equal to 2.064, use PID parameter group F9.
367 -F0.20=1 factory data reset
367 +F0.20=1 Factory data reset
368 368  F0.03=8
369 369  F5.23=2
370 370  F9.01=Upper limit water pressure
... ... @@ -374,7 +374,7 @@
374 374  F9.31=Lower limit water pressure
375 375  
376 376  
377 -In the parameter setting of group F9, 20mA is the maximum value of the transducer with a range of 16bar, and F9.01/F9.29/F9.31 are the setting parameters for the water pressure in the VB in percentage. For example when the inverter is required to keep the pressure at 8bar, modify F9.29=50%. F9.01 is the upper limit of water pressure setting, it is recommended to set F9.29=F9.01,of course you can set F9.01=80%,it needs to be greater than or equal to F9.29.
377 +In the parameter setting of group F9, 20mA is the maximum value of the transducer with a range of 16bar, and F9.01/F9.29/F9.31 are the setting parameters for the water pressure in the VB in percentage. For example when the inverter is required to keep the pressure at 8bar, modify F9.29=50%. F9.01 is the upper limit of water pressure setting, it is recommended to set F9.29=F9.01,of course you can set F9.01=80%,it needs to be greater than or equal to F9.29. If when the control effect of the inverter is slow or the descent time is too long, try reducing the integration time: F9.06 = 0.5 or 1.0.
378 378  
379 379  = **PID function** =