Summary
-
Page properties (1 modified, 0 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -357,14 +357,14 @@ 357 357 358 358 The following example uses a current sensor to simulate a water pressure test, the sensor specification is 4-20mA current signal, the range is 16 bar. use the sensor to connect to the AI2 terminal port of the VB. 359 359 Firstly please check the software version of **F7.11**, **F7.11 **is software version, if the **F7.11 **is greater than 2.064, please use A4 parameter group, A4 parameter group is special parameter for constant pressure water supply project. 360 -F0.20=1 factory data reset360 +F0.20=1 Factory data reset 361 361 A4.00=1 362 -A4.01= set pressure362 +A4.01=Set pressure 363 363 A4.03=Sensor range 364 364 A4.04=0 365 365 366 366 If the value of F7.11 is less than or equal to 2.064, use PID parameter group F9. 367 -F0.20=1 factory data reset367 +F0.20=1 Factory data reset 368 368 F0.03=8 369 369 F5.23=2 370 370 F9.01=Upper limit water pressure