... ... @@ -370,7 +370,7 @@
370 370  F9.01=Upper limit water pressure
371 371  F9.02=1 (AI2)
372 372  F9.28=1
373 -F9.29=Set pressure
373 +F9.29=Target value
374 374  F9.31=Lower limit water pressure
375 375  
376 376  
... ... @@ -417,10 +417,6 @@
417 417  
418 418  Control operation command address: 2000H (premise F0.01=2)
419 419  
420 -= **Safety and precautions** =
421 -
422 -~1. Familiar with product standard technical specifications. Please refer to the manual
423 -
424 424  = **Grounding** =
425 425  
426 426  ~1. Understand the meaning and function of the ground wire and connect it correctly.
... ... @@ -446,20 +446,83 @@
446 446  
447 447  Braking resistor
448 448  
449 -= **Power and current value** =
445 += **Installation guidance required by EMC** =
450 450  
451 - ~1. Familiar with the rated current of the inverter in different power ranges, please refer to the manual
447 + The input terminal of the inverter has EMC screw access option.
452 452  
453 -= **Braking resistor** =
449 +(% style="text-align:center" %)
450 +[[image:企业微信截图_16890580824807.png||height="394" width="284"]]
454 454  
455 - ~1. Familiar with the selection of braking resistor. Under what conditions do you need to install a braking resistor? How to install the braking resistor?
452 +
456 456  
457 -Braking resistors are installed on the and PB ends of the inverter (built-in braking unit)
454 += Torque mode control on winding project =
458 458  
459 -= **Fault code and troubleshooting** =
456 +Torque mode can only be vector control, torque control refers to the strength, that in the torque mode F0.03 is the default value, modify F0.03 for other values is invalid.
460 460  
461 - ~1. Familiar with various fault codes and countermeasures to deal with faults.
458 +Debugging ideas:
462 462  
463 -= **Installation guidance required by EMC** =
460 +~1. According to the application requirements of the torque command and the upper limit of the frequency.
464 464  
465 - The input terminal of the inverter has EMC screw access option.
462 +2. Set the frequency acceleration/deceleration time F0.18/F0.19 and the torque acceleration/deceleration time F3.14/F3.15, the torque acceleration/deceleration time is less than or equal to the frequency acceleration/deceleration time.
463 +
464 +3. Start the motor and observe whether the motor can run or not, if it can't run normally, rotate the motor with external force, if it can be started, it is judged to be necessary to increase the static friction coefficient compensation.
465 +
466 +4. After the motor is running, observe the motor running state, if the motor is blocked, check whether it is shaking when it is blocked, if it is shaking, increase F3.07, generally 0.01 amplitude increment.
467 +
468 +5. When the torque command F3.10 is lower than the percentage of "no-load current / rated current", the running frequency is about: rated frequency * torque command percentage * rated current / no-load current.
469 +
470 +6. Static Friction Compensation Logic: During startup, the torque command 1 = F3.11* F3.24 /100 is passed to the performance; after a maintenance time of F3.25 seconds, it reverts to torque command 2 = F3.11; the switching of torque commands 1 /2 occurs through the torque acceleration and deceleration times F3.14 / F3.15;
471 +
472 +7. Auxiliary debugging parameters: filter coefficient F3.07 and static friction compensation F3.24/ F3.25.
473 +
474 +F0.00=0 Vector control
475 +
476 +F0.18=2.0 Acceleration time
477 +
478 +F0.19=2.0 Deceleration time
479 +
480 +F2.01=Motor rated power
481 +
482 +F2.02=Motor rated voltage
483 +
484 +F2.03=Rated motor current
485 +
486 +F2.04=Rated motor frequency
487 +
488 +F2.05=Rated motor speed
489 +
490 +F2.11=1 Static tuning
491 +
492 +F3.01=0.2 Speed loop integration time
493 +
494 +F3.07=0.005 Speed loop filter coefficient
495 +
496 +F3.09=1 Torque control
497 +
498 +F3.10=1 Torque control upper limit source
499 +
500 +F3.11=200 Torque upper limit setting
501 +
502 +F3.12=50 Torque control maximum frequency
503 +
504 +F3.14=1.2 Torque control acceleration time
505 +
506 +F3.15=1.2 Torque control deceleration time
507 +
508 +F3.16=120 Torque stiffness factor
509 +
510 +Torque control commissioning instructions:
511 +
512 +F0.18: Frequency acceleration time
513 +
514 +F0.19: Frequency deceleration time
515 +
516 +F3.14: Torque acceleration time
517 +
518 +F3.15: Torque deceleration time
519 +
520 +F3.07: Frequency low-pass filtering factor
521 +
522 +F3.24: Static friction compensation
523 +
524 +F3.25: Static friction compensation time