... ... @@ -355,27 +355,26 @@
355 355  
356 356  = **Constant pressure water supply** =
357 357  
358 -The following example uses a current sensor to simulate a water pressure test, the sensor specification is 4-20mA current signal, the range is 16 bar. use the sensor to connect to the AI2 terminal port of the VB.
359 -Firstly please check the software version of **F7.11**, **F7.11 **is software version, if the **F7.11 **is greater than 2.064, please use A4 parameter group, A4 parameter group is special parameter for constant pressure water supply project.
360 -F0.20=1 Factory data reset
358 +
359 +The following example uses a current transducer to simulate a water pressure test, the transducer specification is 4-20mA current signal, the range is 16 bar. use the transducer to connect to the AI2 terminal port of the VB.
360 +Please check the software version of F7.11 inverter first, if the software version is greater than 2.064, please use A4 parameter group, A4 parameter group is special parameter for constant pressure water supply project.
361 +F0.20=1 factory data reset
361 361  A4.00=1
362 -A4.01=Set pressure
363 +A4.01=set pressure
363 363  A4.03=Sensor range
364 364  A4.04=0
365 365  
366 366  If the value of F7.11 is less than or equal to 2.064, use PID parameter group F9.
367 -F0.20=1 Factory data reset
368 +F0.20=1 factory data reset
368 368  F0.03=8
369 369  F5.23=2
370 370  F9.01=Upper limit water pressure
371 371  F9.02=1 (AI2)
372 372  F9.28=1
373 -F9.29=Target value
374 +F9.29=Set pressure
374 374  F9.31=Lower limit water pressure
376 +In the parameter setting of group F9, 20mA is the maximum value of the transducer with a range of 16bar, and F9.01/F9.29/F9.31 are the setting parameters for the water pressure in the VB in percentage. For example when the inverter is required to keep the pressure at 8bar, modify F9.29=50%. F9.01 is the upper limit of water pressure setting, it needs to be greater than or equal to F9.29, it is recommended to set F9.29=F9.01
375 375  
376 -
377 -In the parameter setting of group F9, 20mA is the maximum value of the transducer with a range of 16bar, and F9.01/F9.29/F9.31 are the setting parameters for the water pressure in the VB in percentage. For example when the inverter is required to keep the pressure at 8bar, modify F9.29=50%. F9.01 is the upper limit of water pressure setting, it is recommended to set F9.29=F9.01,of course you can set F9.01=80%,it needs to be greater than or equal to F9.29. If when the control effect of the inverter is slow or the descent time is too long, try reducing the integration time: F9.06 = 0.5 or 1.0.
378 -
379 379  = **PID function** =
380 380  
381 381  (% style="text-align:center" %)