Changes for page 4 Common function of VB

Last modified by Theodore Xu on 2025/02/27 09:58

From version 28.1
edited by Theodore Xu
on 2024/04/22 14:31
Change comment: There is no comment for this version
To version 18.1
edited by Theodore Xu
on 2024/04/09 15:18
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -355,27 +355,26 @@
355 355  
356 356  = **Constant pressure water supply** =
357 357  
358 -The following example uses a current sensor to simulate a water pressure test, the sensor specification is 4-20mA current signal, the range is 16 bar. use the sensor to connect to the AI2 terminal port of the VB.
359 -Firstly please check the software version of **F7.11**, **F7.11 **is software version, if the **F7.11 **is greater than 2.064, please use A4 parameter group, A4 parameter group is special parameter for constant pressure water supply project.
360 -F0.20=1 Factory data reset
358 +
359 +The following example uses a current transducer to simulate a water pressure test, the transducer specification is 4-20mA current signal, the range is 16 bar. use the transducer to connect to the AI2 terminal port of the VB.
360 +Please check the software version of F7.11 inverter first, if the software version is greater than 2.064, please use A4 parameter group, A4 parameter group is special parameter for constant pressure water supply project.
361 +F0.20=1 factory data reset
361 361  A4.00=1
362 -A4.01=Set pressure
363 +A4.01=set pressure
363 363  A4.03=Sensor range
364 364  A4.04=0
365 365  
366 366  If the value of F7.11 is less than or equal to 2.064, use PID parameter group F9.
367 -F0.20=1 Factory data reset
368 +F0.20=1 factory data reset
368 368  F0.03=8
369 369  F5.23=2
370 370  F9.01=Upper limit water pressure
371 371  F9.02=1 (AI2)
372 372  F9.28=1
373 -F9.29=Target value
374 +F9.29=Set pressure
374 374  F9.31=Lower limit water pressure
376 +In the parameter setting of group F9, 20mA is the maximum value of the transducer with a range of 16bar, and F9.01/F9.29/F9.31 are the setting parameters for the water pressure in the VB in percentage. For example when the inverter is required to keep the pressure at 8bar, modify F9.29=50%. F9.01 is the upper limit of water pressure setting, it needs to be greater than or equal to F9.29, it is recommended to set F9.29=F9.01
375 375  
376 -
377 -In the parameter setting of group F9, 20mA is the maximum value of the transducer with a range of 16bar, and F9.01/F9.29/F9.31 are the setting parameters for the water pressure in the VB in percentage. For example when the inverter is required to keep the pressure at 8bar, modify F9.29=50%. F9.01 is the upper limit of water pressure setting, it is recommended to set F9.29=F9.01,of course you can set F9.01=80%,it needs to be greater than or equal to F9.29. If when the control effect of the inverter is slow or the descent time is too long, try reducing the integration time: F9.06 = 0.5 or 1.0.
378 -
379 379  = **PID function** =
380 380  
381 381  (% style="text-align:center" %)
... ... @@ -417,6 +417,10 @@
417 417  
418 418  Control operation command address: 2000H (premise F0.01=2)
419 419  
419 += **Safety and precautions** =
420 +
421 +~1. Familiar with product standard technical specifications. Please refer to the manual
422 +
420 420  = **Grounding** =
421 421  
422 422  ~1. Understand the meaning and function of the ground wire and connect it correctly.
... ... @@ -442,78 +442,20 @@
442 442  
443 443  Braking resistor
444 444  
445 -= **Installation guidance required by EMC** =
448 += **Power and current value** =
446 446  
447 - The input terminal of the inverter has EMC screw access option.
450 + ~1. Familiar with the rated current of the inverter in different power ranges, please refer to the manual
448 448  
449 -= Torque mode control winding project =
452 += **Braking resistor** =
450 450  
451 -Torque mode can only be vector control, torque control refers to the strength, that in the torque mode F0.03 is the default value, modify F0.03 for other values is invalid.
454 + ~1. Familiar with the selection of braking resistor. Under what conditions do you need to install a braking resistor? How to install the braking resistor?
452 452  
453 -Debugging ideas:
456 +Braking resistors are installed on the and PB ends of the inverter (built-in braking unit)
454 454  
455 -~1. According to the application requirements of the torque command and the upper limit of the frequency.
458 += **Fault code and troubleshooting** =
456 456  
457 -2. Set the frequency acceleration/deceleration time F0.18/F0.19 and the torque acceleration/deceleration time F3.14/F3.15, the torque acceleration/deceleration time is less than or equal to the frequency acceleration/deceleration time.
460 + ~1. Familiar with various fault codes and countermeasures to deal with faults.
458 458  
459 -3. Start the motor and observe whether the motor can run or not, if it can't run normally, rotate the motor with external force, if it can be started, it is judged to be necessary to increase the static friction coefficient compensation.
462 += **Installation guidance required by EMC** =
460 460  
461 -4. After the motor is running, observe the motor running state, if the motor is blocked, check whether it is shaking when it is blocked, if it is shaking, increase F3.07, generally 0.01 amplitude increment.
462 -
463 -5. When the torque command F3.10 is lower than the percentage of "no-load current / rated current", the running frequency is about: rated frequency * torque command percentage * rated current / no-load current.
464 -
465 -6. Static Friction Compensation Logic: During startup, the torque command 1 = F3.11* F3.24 /100 is passed to the performance; after a maintenance time of F3.25 seconds, it reverts to torque command 2 = F3.11; the switching of torque commands 1 /2 occurs through the torque acceleration and deceleration times F3.14 / F3.15;
466 -
467 -7. Auxiliary debugging parameters: filter coefficient F3.07 and static friction compensation F3.24/ F3.25.
468 -
469 -F0.00=0 Vector control
470 -
471 -F0.18=2.0 Acceleration time
472 -
473 -F0.19=2.0 Deceleration time
474 -
475 -F2.01=Motor rated power
476 -
477 -F2.02=Motor rated voltage
478 -
479 -F2.03=Rated motor current
480 -
481 -F2.04=Rated motor frequency
482 -
483 -F2.05=Rated motor speed
484 -
485 -F2.11=1 Static tuning
486 -
487 -F3.01=0.2 Speed loop integration time
488 -
489 -F3.07=0.005 Speed loop filter coefficient
490 -
491 -F3.09=1 Torque control
492 -
493 -F3.10=1 Torque control upper limit source
494 -
495 -F3.11=200 Torque upper limit setting
496 -
497 -F3.12=50 Torque control maximum frequency
498 -
499 -F3.14=1.2 Torque control acceleration time
500 -
501 -F3.15=1.2 Torque control deceleration time
502 -
503 -F3.16=120 Torque stiffness factor
504 -
505 -Torque control commissioning instructions:
506 -
507 -F0.18: Frequency acceleration time
508 -
509 -F0.19: Frequency deceleration time
510 -
511 -F3.14: Torque acceleration time
512 -
513 -F3.15: Torque deceleration time
514 -
515 -F3.07: Frequency low-pass filtering factor
516 -
517 -F3.24: Static friction compensation
518 -
519 -F3.25: Static friction compensation time
464 + The input terminal of the inverter has EMC screw access option.