Changes for page 4 Common function of VB

Last modified by Theodore Xu on 2025/02/27 09:58

From version 34.1
edited by Theodore Xu
on 2024/04/23 19:51
Change comment: There is no comment for this version
To version 17.1
edited by Mora Zhou
on 2023/11/20 14:49
Change comment: There is no comment for this version

Summary

Details

Page properties
Author
... ... @@ -1,1 +1,1 @@
1 -XWiki.AiXia
1 +XWiki.Mora
Content
... ... @@ -353,29 +353,6 @@
353 353  
354 354  F7.05
355 355  
356 -= **Constant pressure water supply** =
357 -
358 -The following example uses a current sensor to simulate a water pressure test, the sensor specification is 4-20mA current signal, the range is 16 bar. use the sensor to connect to the AI2 terminal port of the VB.
359 -Firstly please check the software version of **F7.11**, **F7.11 **is software version, if the **F7.11 **is greater than 2.064, please use A4 parameter group, A4 parameter group is special parameter for constant pressure water supply project.
360 -F0.20=1 Factory data reset
361 -A4.00=1
362 -A4.01=Set pressure
363 -A4.03=Sensor range
364 -A4.04=0
365 -
366 -If the value of F7.11 is less than or equal to 2.064, use PID parameter group F9.
367 -F0.20=1 Factory data reset
368 -F0.03=8
369 -F5.23=2
370 -F9.01=Upper limit water pressure
371 -F9.02=1 (AI2)
372 -F9.28=1
373 -F9.29=Target value
374 -F9.31=Lower limit water pressure
375 -
376 -
377 -In the parameter setting of group F9, 20mA is the maximum value of the transducer with a range of 16bar, and F9.01/F9.29/F9.31 are the setting parameters for the water pressure in the VB in percentage. For example when the inverter is required to keep the pressure at 8bar, modify F9.29=50%. F9.01 is the upper limit of water pressure setting, it is recommended to set F9.29=F9.01,of course you can set F9.01=80%,it needs to be greater than or equal to F9.29. If when the control effect of the inverter is slow or the descent time is too long, try reducing the integration time: F9.06 = 0.5 or 1.0.
378 -
379 379  = **PID function** =
380 380  
381 381  (% style="text-align:center" %)
... ... @@ -417,6 +417,10 @@
417 417  
418 418  Control operation command address: 2000H (premise F0.01=2)
419 419  
397 += **Safety and precautions** =
398 +
399 +~1. Familiar with product standard technical specifications. Please refer to the manual
400 +
420 420  = **Grounding** =
421 421  
422 422  ~1. Understand the meaning and function of the ground wire and connect it correctly.
... ... @@ -442,91 +442,20 @@
442 442  
443 443  Braking resistor
444 444  
445 -= **EMC** =
426 += **Power and current value** =
446 446  
447 - The input terminal of the inverter has EMC screw access option.
428 + ~1. Familiar with the rated current of the inverter in different power ranges, please refer to the manual
448 448  
449 -* EMC Screws Installation Role: Filter out the common mode interference signals on the input side to the ground.
450 -* Role of removing EMC screws: When the grounding of the whole equipment system is unstable, it is easy for the interference signal to enter the input terminal of the VFD, which leads to the inaccurate operation of the terminal motor, and then it is necessary to remove the EMC screws on the machine in order to solve the influence of external interference.
430 += **Braking resistor** =
451 451  
452 -(% class="box infomessage" %)
453 -(((
454 -Do not remove the EMC unless there are special circumstances.
455 -)))
432 + ~1. Familiar with the selection of braking resistor. Under what conditions do you need to install a braking resistor? How to install the braking resistor?
456 456  
457 -(% style="text-align:center" %)
458 -[[image:企业微信截图_16890580824807.png||height="394" width="284"]]
434 +Braking resistors are installed on the and PB ends of the inverter (built-in braking unit)
459 459  
460 -
436 += **Fault code and troubleshooting** =
461 461  
462 -= Torque mode control on winding project =
438 + ~1. Familiar with various fault codes and countermeasures to deal with faults.
463 463  
464 -Torque mode can only be vector control, torque control refers to the strength, that in the torque mode F0.03 is the default value, modify F0.03 for other values is invalid.
440 += **Installation guidance required by EMC** =
465 465  
466 -Debugging ideas:
467 -
468 -~1. According to the application requirements of the torque command and the upper limit of the frequency.
469 -
470 -2. Set the frequency acceleration/deceleration time F0.18/F0.19 and the torque acceleration/deceleration time F3.14/F3.15, the torque acceleration/deceleration time is less than or equal to the frequency acceleration/deceleration time.
471 -
472 -3. Start the motor and observe whether the motor can run or not, if it can't run normally, rotate the motor with external force, if it can be started, it is judged to be necessary to increase the static friction coefficient compensation.
473 -
474 -4. After the motor is running, observe the motor running state, if the motor is blocked, check whether it is shaking when it is blocked, if it is shaking, increase F3.07, generally 0.01 amplitude increment.
475 -
476 -5. When the torque command F3.10 is lower than the percentage of "no-load current / rated current", the running frequency is about: rated frequency * torque command percentage * rated current / no-load current.
477 -
478 -6. Static Friction Compensation Logic: During startup, the torque command 1 = F3.11* F3.24 /100 is passed to the performance; after a maintenance time of F3.25 seconds, it reverts to torque command 2 = F3.11; the switching of torque commands 1 /2 occurs through the torque acceleration and deceleration times F3.14 / F3.15;
479 -
480 -7. Auxiliary debugging parameters: filter coefficient F3.07 and static friction compensation F3.24/ F3.25.
481 -
482 -F0.00=0 Vector control
483 -
484 -F0.18=2.0 Acceleration time
485 -
486 -F0.19=2.0 Deceleration time
487 -
488 -F2.01=Motor rated power
489 -
490 -F2.02=Motor rated voltage
491 -
492 -F2.03=Rated motor current
493 -
494 -F2.04=Rated motor frequency
495 -
496 -F2.05=Rated motor speed
497 -
498 -F2.11=1 Static tuning
499 -
500 -F3.01=0.2 Speed loop integration time
501 -
502 -F3.07=0.005 Speed loop filter coefficient
503 -
504 -F3.09=1 Torque control
505 -
506 -F3.10=1 Torque control upper limit source
507 -
508 -F3.11=200 Torque upper limit setting
509 -
510 -F3.12=50 Torque control maximum frequency
511 -
512 -F3.14=1.2 Torque control acceleration time
513 -
514 -F3.15=1.2 Torque control deceleration time
515 -
516 -F3.16=120 Torque stiffness factor
517 -
518 -Torque control commissioning instructions:
519 -
520 -F0.18: Frequency acceleration time
521 -
522 -F0.19: Frequency deceleration time
523 -
524 -F3.14: Torque acceleration time
525 -
526 -F3.15: Torque deceleration time
527 -
528 -F3.07: Frequency low-pass filtering factor
529 -
530 -F3.24: Static friction compensation
531 -
532 -F3.25: Static friction compensation time
442 + The input terminal of the inverter has EMC screw access option.
企业微信截图_16890580824807.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.AiXia
Size
... ... @@ -1,1 +1,0 @@
1 -423.4 KB
Content