Changes for page 4 Common function of VB
Last modified by Theodore Xu on 2025/02/27 09:58
From version 37.1
edited by Theodore Xu
on 2024/07/31 11:26
on 2024/07/31 11:26
Change comment:
There is no comment for this version
Summary
-
Page properties (4 modified, 0 added, 0 removed)
-
Attachments (0 modified, 0 added, 3 removed)
Details
- Page properties
-
- Title
-
... ... @@ -1,1 +1,1 @@ 1 - 4Common function of VB1 +Common function of VB - Parent
-
... ... @@ -1,1 +1,1 @@ 1 -VFD.WebHome 1 +VFD.3\. Demo.WebHome - Author
-
... ... @@ -1,1 +1,1 @@ 1 -XWiki. AiXia1 +XWiki.Stone - Content
-
... ... @@ -1,18 +16,3 @@ 1 -= Parameters uploading and downloading = 2 - 3 -(% class="box infomessage" %) 4 -((( 5 -**✎Note:** 6 -1.Parameter uploading and downloading is only supported between the same models. 7 -2.F7.11 shows the software version of the inverter, the parameters may differ between different versions, especially between 2.072 and versions below 2.072. 8 -))) 9 - 10 -1.Press MF.K and ↑ and wait while the keyboard displays "u~-~-~-~-", the keyboard is uploading the parameters. 11 - 12 -2.Remove the keyboard and install to other VB. Please be careful to align the pins when unplugging and plugging in the keyboard. 13 - 14 -3.Press MF.K and ↓ and wait while the keyboard display"d~-~-~-~-", the keyboard is downloading the parameters. 15 - 16 16 = **Start up** = 17 17 18 18 ~1. Keyboard start and stop, panel potentiometer speed regulation. (F5.17 adjusts the change amplitude of the panel potentiometer) ... ... @@ -55,7 +55,7 @@ 55 55 56 56 F0.07=01 57 57 58 -6. 43 +6.On some equipment, two potentiometers are required to adjust the speed, one potentiometer 0-10V controls 20HZ, and the other potentiometer controls 0-10V control 25HZ so that the spindle frequency is superimposed, and the frequency is 45HZ. 59 59 60 60 F0.03=2 61 61 ... ... @@ -81,7 +81,7 @@ 81 81 82 82 = **Acceleration time** = 83 83 84 - ~1.When the device is started, the customer feels that the startup time is too long or the startup time is too short, which parameters need to be modified? (This parameter should be fine-tuned appropriately according to the equipment load. Improper setting can easily cause fault alarms such as overcurrent).69 +1 When the device is started, the customer feels that the startup time is too long or the startup time is too short, which parameters need to be modified? (This parameter should be fine-tuned appropriately according to the equipment load. Improper setting can easily cause fault alarms such as overcurrent). 85 85 86 86 F0.18 (appropriate setting) etc. 87 87 ... ... @@ -253,6 +253,7 @@ 253 253 254 254 = **Digital input function** = 255 255 241 + 256 256 ~1. Since an external switch is needed on the device to control the emergency stop of the motor, which function parameter should be set? 257 257 258 258 F5.02=10 ... ... @@ -278,11 +278,13 @@ 278 278 279 279 = **Digital output function** = 280 280 267 + 281 281 ~1. The customer needs to use the FM open-collector output function. When the inverter fails, output a switch value to make the fault alarm lamp/fault buzzer act, so that the on-site operator knows that the inverter has a fault alarm and what to do Setup and wiring? 282 282 283 283 F6.00=1 284 284 285 285 F6.01=2 273 + 286 286 287 287 2. When the inverter runs more than 20HZ, the relay T1A and T1C terminals output a switch value to control an indicator light, so that the indicator line is connected and the indicator light is on. How to set up and wire? 288 288 ... ... @@ -316,10 +316,12 @@ 316 316 317 317 = **Display monitoring** = 318 318 307 + 319 319 ~1. Master the functions of F7.03, F7.04, and F7.05, all of which are used for display and monitoring. Please refer to page 35 of the manual for details 320 320 321 321 = **Operating mode selection** = 322 322 312 + 323 323 ~1. Master the definition of each control mode of the F0.00 parameter group. 324 324 325 325 Vector control, V/F control ... ... @@ -326,6 +326,7 @@ 326 326 327 327 = **Analog signal gain** = 328 328 319 + 329 329 ~1. The user uses the AI1 terminal function, and the device is given a voltage of 0-5V for speed regulation. Which parameter should be modified accordingly? 330 330 331 331 F0.03=2 ... ... @@ -338,8 +338,10 @@ 338 338 339 339 F5.23=2 340 340 341 -= **Parameter protection** = 332 += 333 +**Parameter protection** = 342 342 335 + 343 343 ~1. The protection parameters cannot be modified and the parameters are locked. 344 344 345 345 F0.21=1 ... ... @@ -348,8 +348,10 @@ 348 348 349 349 FE.00 = non-zero number 350 350 351 -= **Set running time action** = 344 += 345 +**Set running time action** = 352 352 347 + 353 353 ~1. The customer sells the machine to the user, worrying that the customer did not pay on time, set some parameters inside the inverter. After the inverter has been running for 10 hours, the inverter will automatically stop and cannot start. Wait for the user to pay before the machine can run. How to set parameters for such a function? 354 354 FE.00=Set password 355 355 ... ... @@ -359,6 +359,7 @@ 359 359 360 360 = **Display monitoring options** = 361 361 357 + 362 362 ~1. The user requires the inverter to display only the speed during operation, which parameter should be modified? 363 363 364 364 F7.03=4000 ... ... @@ -367,34 +367,10 @@ 367 367 2. The user requires the inverter to display various states during shutdown. Which parameter can be set? 368 368 369 369 F7.05 366 + 370 370 371 -= **Constant pressure water supply** = 372 - 373 -The following example uses a current sensor to simulate a water pressure test, the sensor specification is 4-20mA current signal, the range is 16 bar. use the sensor to connect to the AI2 terminal port of the VB. 374 -Firstly please check the software version of **F7.11**, **F7.11 **is software version, if the **F7.11 **is greater than 2.064, please use A4 parameter group, A4 parameter group is special parameter for constant pressure water supply project. 375 -F0.20=1 Factory data reset 376 -A4.00=1 377 -A4.01=Set pressure 378 -A4.03=Sensor range 379 -A4.04=0 380 - 381 -If the value of F7.11 is less than or equal to 2.064, use PID parameter group F9. 382 -F0.20=1 Factory data reset 383 -F0.03=8 384 -F5.23=2 385 -F9.01=Upper limit water pressure 386 -F9.02=1 (AI2) 387 -F9.28=1 388 -F9.29=Target value 389 -F9.31=Lower limit water pressure 390 - 391 - 392 -In the parameter setting of group F9, 20mA is the maximum value of the transducer with a range of 16bar, and F9.01/F9.29/F9.31 are the setting parameters for the water pressure in the VB in percentage. For example when the inverter is required to keep the pressure at 8bar, modify F9.29=50%. F9.01 is the upper limit of water pressure setting, it is recommended to set F9.29=F9.01,of course you can set F9.01=80%,it needs to be greater than or equal to F9.29. If when the control effect of the inverter is slow or the descent time is too long, try reducing the integration time: F9.06 = 0.5 or 1.0. 393 - 394 394 = **PID function** = 395 395 396 -(% style="text-align:center" %) 397 -[[image:生产流程图.png]] 398 398 399 399 ~1. To be familiar with the PID function of constant pressure water supply, the feedback signal sources are remote pressure gauges and pressure transmitters. How to wire and which parameters should be set? For example, the maximum range of the remote pressure gauge is 1Mpa, and the current user needs to set the panel 0.45 MPa kg pressure, how to set the pressure? 400 400 F0.01=0 (panel start and stop)/1 (terminal start and stop) ... ... @@ -425,6 +425,7 @@ 425 425 426 426 = **Communication function** = 427 427 400 + 428 428 ~1. Familiar with RS485 communication function, communication address, communication speed, communication format, how to set it? Familiar with the address of communication function? 429 429 Please refer to page 129 of the manual 430 430 ... ... @@ -432,13 +432,22 @@ 432 432 433 433 Control operation command address: 2000H (premise F0.01=2) 434 434 408 += 409 +**Safety and precautions** = 410 + 411 + 412 +~1. Familiar with product standard technical specifications. Please refer to the manual 413 + 435 435 = **Grounding** = 436 436 416 + 437 437 ~1. Understand the meaning and function of the ground wire and connect it correctly. 438 438 The grounding terminal E of the inverter must be well grounded, the grounding resistance should be less than 102, and the grounding wire should be thick and short. Multi-strand copper core wire of 3.5mm2 or more should be used. 439 439 440 -= **Peripheral lines** = 420 += 421 +**Peripheral lines** = 441 441 423 + 442 442 ~1. Understand the role of peripheral line equipment: 443 443 444 444 Open ... ... @@ -457,91 +457,30 @@ 457 457 458 458 Braking resistor 459 459 460 -= **EMC** = 442 += 443 +**Power and current value** = 461 461 462 - The input terminal of the inverter has EMC screw access option. 463 463 464 -* EMC Screws Installation Role: Filter out the common mode interference signals on the input side to the ground. 465 -* EMC Screw Removal Function: When the grounding of the whole equipment system is unstable, it is easy for the interference signal to enter the input terminal of the VFD, which leads to the inaccurate operation of the terminal motor, and then it is necessary to remove the EMC screws on the machine in order to solve the influence of external interference. 446 + ~1. Familiar with the rated current of the inverter in different power ranges, please refer to the manual 466 466 467 -(% class="box infomessage" %) 468 -((( 469 -Do not remove the EMC unless there are special circumstances. 470 -))) 448 += 449 +**Braking resistor** = 471 471 472 -(% style="text-align:center" %) 473 -[[image:企业微信截图_16890580824807.png||height="394" width="284"]] 474 474 475 - 452 + ~1. Familiar with the selection of braking resistor. Under what conditions do you need to install a braking resistor? How to install the braking resistor? 476 476 477 - =Torquemodecontrol onwindingproject=454 +Braking resistors are installed on the and PB ends of the inverter (built-in braking unit) 478 478 479 -Torque mode can only be vector control, torque control refers to the strength, that in the torque mode F0.03 is the default value, modify F0.03 for other values is invalid. 456 += 457 +**Fault code and troubleshooting** = 480 480 481 -Debugging ideas: 482 482 483 -~1. Accordingto theapplication requirementsofhetorquecommand and theupperlimitfthefrequency.460 + ~1. Familiar with various fault codes and countermeasures to deal with faults. 484 484 485 -2. Set the frequency acceleration/deceleration time F0.18/F0.19 and the torque acceleration/deceleration time F3.14/F3.15, the torque acceleration/deceleration time is less than or equal to the frequency acceleration/deceleration time. 462 += 463 +**Installation guidance required by EMC** = 486 486 487 -3. Start the motor and observe whether the motor can run or not, if it can't run normally, rotate the motor with external force, if it can be started, it is judged to be necessary to increase the static friction coefficient compensation. 488 488 489 - 4.After themotoris running, observethemotorrunning state,if themotoris blocked, check whetherit is shakingwhenit isblocked,if it is shaking, increaseF3.07, generally 0.01 amplitudeincrement.466 + The input terminal of the inverter has EMC screw access option. 490 490 491 -5. When the torque command F3.10 is lower than the percentage of "no-load current / rated current", the running frequency is about: rated frequency * torque command percentage * rated current / no-load current. 492 - 493 -6. Static Friction Compensation Logic: During startup, the torque command 1 = F3.11* F3.24 /100 is passed to the performance; after a maintenance time of F3.25 seconds, it reverts to torque command 2 = F3.11; the switching of torque commands 1 /2 occurs through the torque acceleration and deceleration times F3.14 / F3.15; 494 - 495 -7. Auxiliary debugging parameters: filter coefficient F3.07 and static friction compensation F3.24/ F3.25. 496 - 497 -F0.00=0 Vector control 498 - 499 -F0.18=2.0 Acceleration time 500 - 501 -F0.19=2.0 Deceleration time 502 - 503 -F2.01=Motor rated power 504 - 505 -F2.02=Motor rated voltage 506 - 507 -F2.03=Rated motor current 508 - 509 -F2.04=Rated motor frequency 510 - 511 -F2.05=Rated motor speed 512 - 513 -F2.11=1 Static tuning 514 - 515 -F3.01=0.2 Speed loop integration time 516 - 517 -F3.07=0.005 Speed loop filter coefficient 518 - 519 -F3.09=1 Torque control 520 - 521 -F3.10=1 Torque control upper limit source 522 - 523 -F3.11=200 Torque upper limit setting 524 - 525 -F3.12=50 Torque control maximum frequency 526 - 527 -F3.14=1.2 Torque control acceleration time 528 - 529 -F3.15=1.2 Torque control deceleration time 530 - 531 -F3.16=120 Torque stiffness factor 532 - 533 -Torque control commissioning instructions: 534 - 535 -F0.18: Frequency acceleration time 536 - 537 -F0.19: Frequency deceleration time 538 - 539 -F3.14: Torque acceleration time 540 - 541 -F3.15: Torque deceleration time 542 - 543 -F3.07: Frequency low-pass filtering factor 544 - 545 -F3.24: Static friction compensation 546 - 547 -F3.25: Static friction compensation time 468 +
- PID原理图.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.AiXia - Size
-
... ... @@ -1,1 +1,0 @@ 1 -53.5 KB - Content
- 企业微信截图_16890580824807.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.AiXia - Size
-
... ... @@ -1,1 +1,0 @@ 1 -423.4 KB - Content
- 生产流程图.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.AiXia - Size
-
... ... @@ -1,1 +1,0 @@ 1 -1.0 MB - Content